Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Automatic intelligent fire detectors with high reliability, used for premises and items of
property with medium and high concentration of valuable assets.
Detector series IQ8Quad features, system advantages
designed for optimal operation on System 8000 and IQ8Control fire alarm systems
with multisensor detectors for the detection of all types of fires, even under the most diffi-
cult operating conditions
detector with and without loop isolator
Different options of installation
-wiring in loop and spur combination, e.g.
-maximum number of detectors with cable lengths of up to 3500 m with installation cable
for fire detection, e.g. cables I-Y(St)Yn x 2 x 0.8 mm
-up to 127 detectors and detector zones per loop installation
-up to 32 detectors per zone
Easy commissioning
-automatic detector addressing
-fixed address assignment of detector location, even after detectors have been replaced or
added
-localization of wire breaks and short circuits on loop
-detector-LED used as alarm indicator and as an indicator for detectors in service
-adaptation to changing operating conditions
-dedicated LED for indicating operation (green LED)
-disconnection of individual detectors, detector zones and detection areas
-disconnection of individual sensors or several sensors at once within a multisensor
detector; either manually or depending on programmed time of the day
Automatic adaptation to varying environmental conditions
-compensation of changing levels of air pressure, humidity, smoke concentration
according to the double chamber principle
-electronic compensation of long-term influences like aging or pollution
Reliable detection
-constant alarm sensitivity of multisensor detector for all types of fire
-large signal to noise ratio due to the special design of the sensors and the electronics to
suppress electromagnetic interference
Reliable false alarm suppression
-high immunity against false alarms by means of timed evaluation of different sensor
criteria
-signal patterns not typical for fires are eliminated by using special filter algorithms
-automatic self-monitoring of detector electronics
-continuous loop monitoring even during short-circuits through isolating the relevant
segment
-automatic monitoring of all sensors to guarantee operational capacity and correct condi-
tion.
Increased operating reliability
-short-circuit and wire break tolerant through monitoring from both ends of the loop
-alarm decision inside detector
-fail-safe circuit activated if communication fails
Maintenance
-automatic maintenance request
-heat detector identification through a black circle on the light transmission plate
-multisensor gas detector identification through a golden loop on the circle transmission
plate
-operating time-, alarm- and fault counter in each detector
-automatic, cyclic loop check
-complete status interrogation from the control panel
-interrogation of operating data from all detectors on loop via standard service PC and
detector interface
Comprehensive range of accessories
-standard detector base and relay base
-base adapter for ceiling mounting
-dust cover for fire detector or detector base
-kit for suspended ceiling mounting
-RF base

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

1
Detector without integrated alarm devices
117 Technical Data
2
Operating voltage 8 ... 42 V DC
Alarm current w/o communication curtain approx. 18 mA
Air speed 0 ... 25.4 m/s
Storage temperature -25 C ... 75 C 3
62 Air Humidity < 95 % (non-condensing)
Type of protection IP 43 (with base + option)
Material ABS plastic
Color white, similar to RAL 9010
Fire detector with base
Weight approx. 110 g 4
Dimensions : 117 mm H: 49 mm (62 mm incl. base)

Special-colour on demand
The detectors part no. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are 5
approved in the scope of the DIBt system authorization for the operation with an Automatic Door
System.

Detector base is not supplied as standard


6
Accessories
767800 mounting bracket
805590 Standard detector base for IQ8Quad 7

q6h=
805591 Detector base with relay contact for IQ8Quad

802171 Fixed heat detector IQ8Quad


8
Approval: VdS, CNBOP, BOSEC

Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of
fires with strong heat generation. Intelligent fire detector with decentralised intelligence, 9
automatic function self-test, CPU failure mode, alarm and operating data memory, alarm
indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be 10
connected.

Technical Data
Quiescent current @ 19 V DC approx. 40 A 11
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54 - 5 A1S / -17 12
Special marking for heat detector on the light pipe: black ring.

802171.F q6h/G& Fixed heat detector IQ8Quad - France 13

Approval: CNMIS

As 802171, but with NF-Approval Mark at the backside. 14

Technical Data
Operating voltage 8 ... 42 V DC 15
Quiescent current @ 19 V DC approx. 40 A
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54 - 5 A1S, EN54-17
16
Marquage spcial pour le dtecteur de chaleur sur le diffuseur lumineux: Cercle noir.

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802177 q6nO Fixed heat detector class B IQ8Quad

Approval: VdS

As 802171, but for increased operating temperature according to EN 54-5 Class B.

Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 6 m
Application temperature -20 C ... 65 C
Detector specification EN 54-5 BS / -17

Special marking for heat detector on the light pipe: black ring.

802271 q7h? Rate-of-rise heat detector IQ8Quad

Approval: VdS, CNBOP, BOSEC



Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of
fires with rapidly rising temperatures and integrated fixed temperature function for the
detection of fires with slowly rising temperatures. Intelligent fire detector with decentral-
ised intelligence, automatic function self-test, CPU failure mode, alarm and operating data
memory, alarm indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be
connected.

Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1 / -17

Special marking for heat detector on the light pipe: black ring.

802271.F q7h/G( Rate-of-rise heat detector IQ8Quad - France

Approval: CNMIS

As 802271, but with NF-Approval Mark at the backside.

Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 40 A
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1R, EN 54-17

Marquage spcial pour le dtecteur de chaleur sur le diffuseur lumineux: Cercle noir.

803271 qAhS IQ8Quad Rate-of-rise detector without loop isolator

Approval: VdS, CNBOP



As 802271 but without loop isolator.
The detector can be operated in a standard detector group as well as independently.

Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759
license system IQ8FSA 8619 Z-6.5-1808 license
system 8000-FSA-PLus

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802371 q8hA Optical smoke detector IQ8Quad 1

Approval: VdS, CNBOP, BOSEC



Optical smoke detector to guarantee safe and early detection of fire. Intelligent fire detector 2
with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and
operating data memory, alarm indicator, soft-addressing and operating indication. The
detector is provided with an integrated isolator. A parallel detector indicator can be
connected.
3

Technical Data
Quiescent current @ 19 V DC approx. 50 A 4
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 72 C

qBhU
Detector specification EN 54-7 / -17
5
803371 IQ8Quad Optical smoke detector without loop isolator

Approval: VdS, CNBOP 6



As 802371 but without loop isolator.
The detector can be operated in a standard detector group as well as independently.
7
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m 8
Application temperature -20 C ... 72 C
Detector specification EN 54-7
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759
license system IQ8FSA 8619 Z-6.5-1808 license 9

q8jG
system 8000-FSA-PLus

802373 OT multisensor detector IQ8Quad


10
Approval: VdS

Multisensor detector with integrated optical detector and heat detector, with time-
controlled signal analysis and weighted data combination of both detector functions for 11
detecting smouldering fires and fires with extreme heat generation. Intelligent detector with
decentralised intelligence, self function test, CPU redundancy mode, automatic adaptation
to the environments, alarm and operating data storage, alarm indication and soft
12
addressing.
The loop isolator is integrated in the detector. A parallel detector indicator is additionally
attachable.
13
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m 14
Application temperature -20 C ... 50 C
Detector specification EN 54-7/-5 A2 /-17, CEA 4021

15

16

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802375 q8lM OTblue multisensor detector IQ8Quad

Approval: VdS

Multisensor with integrated optical detector and heat detector. The optical measurement
chamber is provided with a newly developed sensor technology, enabling the detection of
open fires, smouldering fires and fires with high heat generation. Especially for open fires,
the classical ionisation technology implemented in ionisation detectors is replaced by the
new detection technology. The detector is capable of identifying the TF1 and TF6 test fires
described in the EN 54-9:1982 specification.
The OTblue multisensor is an intelligent detector with time-related signal analysis, signal
correlation of the sensor data, decentralised intelligence, automatic function self-test, CPU
failure mode, automatic adaptation to environmental conditions, alarm and operating data
memory, alarm indicator and soft-addressing.
The detector is provided with an integrated isolator and a parallel detector indicator can be
connected.

Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C

q8l/G6
Detector specification EN 54-7/-5 A2 /-17, CEA 4021

802375.F OTblue multisensor IQ8Quad - France

Approval: NF-SSI

As 803275, but with NF-Approval Mark at the backside.

Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 50 A
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C
Detector specification EN 54-7/5 A2, EN54-17

802374 q8kJ O2T multisensor IQ8Quad

Approval: VdS, CNBOP, BOSEC



Multisensor detector provided with two built-in optical smoke sensors with different
scattered light angles as well as additional heat detector sensor evaluation to guarantee the
detection of different types of fire from smouldering fires to open fires with constant sens-
itivity level. Smoke sensor signal identification to ensure smoke classification and reduc-
tion of deceptive alarms caused, for instance, by water vapour or dust.
Because of its excellent detection characteristics, the detector is also able to identify the
standardized TF1 and TF6 test fires. The OT multisensor detector is also suitable for
applications with higher temperatures of up to +65 C. The detector is provided with an
integrated isolator. A parallel detector indicator can be connected.

Technical Data
Quiescent current @ 19 V DC approx. 60 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/-5 B /-17, CEA 4021

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802374.F q8k/G3 O2T multisensor IQ8Quad - France 1

Approval: NF-SSI

As 802374, but with NF-Approval Mark at the backside. 2
Technical Data
Operating voltage 8 ... 42 V DC 3
Quiescent current @ 19 V DC approx. 60 A
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/5 B, EN54-17
4

803374 qBk^ IQ8Quad O2T Intelligent detector without loop isolator


5
Approval: VdS, CNBOP

As 802374 but without Loop isolator.
The detector can be operated in a standard detector group as well as independently. 6

Technical Data
Quiescent current @ 19 V DC approx. 60 A 7
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/-5 B, CEA 4021
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759 8
license system IQ8FSA 8619 Z-6.5-1808 license

q9jI
system 8000-FSA-PLus

802473 OTG multisensor (CO) IQ8Quad 9

Approval: VdS

Multisensor detector with integrated smoke detector, heat detector and gas sensor (CO) for 10
preventive and early detection of fires ranging from smouldering fires to open fires through
combined evaluation of scattered light, temperature and gas. An alarm is actuated at
carbon monoxide (CO) concentration levels that are life-threatening for humans. The 11
detector is provided with an integrated isolator. A parallel detector indicator can be
connected.

Technical Data 12
Quiescent current @ 19 V DC approx. 65 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C 13
Detector specification EN 54-7/-5 A2 /-17, CEA 4021

In the course of installation, we recommend testing the integrated CO sensor with our CO test
gas (part no. 805583) or CO capsule (part no. 805553).
14
Programmable CO-alarm-thresholds: 10-150 ppm.

Gas sensors (CO) mainly react to the carbon monoxide arising from a fire (CO). They have,
however, also a cross sensitivity to other gases, as for example hydrogen (H2), acetylene (C2H2) 15
or nitric oxide (NO).

Special marking for gas detector on the light pipe: black ring. 16

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

O2T Detector with integrated alarm devices

Features The IQ8Quad smoke detectors with built-in alarm device incorporate up to 4 different func-
tionalities (detect, flash, sound, and/or speech) depending on the type (OT/F, OT/So, OT/
Detection
The reliable OT multisensor principle for Sp, OT/FSp) of detector.
consistent response performance at the highest
level of security against false alarms - fire detection as per EN 54-7
- integrated heat sensor as per EN 54-5
Flash lamp - optical alarm via flash lamp
Loop powered - no need for external power - acoustic alarm via sounder as per as per EN 54-3
supply - acoustic alarm speech messages
No additional short address
Automatic synchronization of various IQ8Quad Detection
alarm signaling devices
Multisensor detectors with two built-in optical smoke sensors with different scattered light
High flash energy angles as well as additional heat detector sensor evaluation for detecting everything from
Loop powered - no need for external power smouldering fires to open fires with consistent response performance. Smoke sensor
supply signal identification to ensure smoke classification and reduction of false alarms caused,
No additional short address for instance, by water vapour or dust. Each detector is provided with an integrated isolator.
Automatic synchronization of various IQ8Quad
alarm signaling devices Alarm signaling
Maximum sound level: 92 dB (A) at 1 m The alarm signaling device is activated by the control panel. No further short address
Maximum sound pressure can be set needs to be allocated. It is programmed with tools 8000 as of software version 1.05.
Multiple signal patterns can be combined to one
signal Alarm tone / speech message programming
Signal pattern and repetition rates can be set For detectors with speech message and/or alarm tone function with up to five language
20 different signal tones, incl. DIN-tone options, up to 4 signals can be programmed. Two signals are reserved for alarm signaling
and evacuation in the case of fire. Two further signals can be programmed for other events.
Speech massage with sounder Each signal can consist of up to four signal components, enabling one signal to be
Loop powered - no need for external power programmed as a DIN tone combined with subsequent speech messages in three different
supply languages.
No additional short address
Automatic synchronization of various IQ8Quad Alarm tones can be chosen from a table with various tone types. For application in schools,
alarm signaling devices a break signal to signify the breaks between class can be activated.
Maximum sound level: 92 dB (A) at 1 m Four different speech messages, each in three languages, are available:
Maximum sound pressure can be set
Multiple signal patterns can be combined to one - "An incident has been reported in the building. Please await further instructions.
signal
- "Attention please. This is an emergency. Please leave the building by the nearest avail-
Signal pattern and repetition rates can be set
able exit.
20 different signal tones, incl. DIN-tone
- "This is a fire alarm. Please leave the building immediately by the nearest available exit.
Speech messages can be played in up to 5
languages - This is a test message. No action is required.
5 alarm messages per languages are prepro-
grammed When the basic setting is selected, signals / signal components can be continuously
repeated until the signalling function is interrupted by the control panel. They can also be
programmed with a repetition rate of one to three times. Thus, the break signal in schools
can be deliberately set to only one repetition. In the same way, the total signal can be set to
continuous repetition, with the DIN tone being played only once while subsequent speech
messages are played up to three times.

Sound pressure programming


The sound level [dB (A)] can be set to eight levels, from approximately 64dB (A) to approx-
imately 92dB (A).

All the security you need in one housing with four functions detection, flasher, sounder and
speech alarm.

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

1
All IQ8Quad detectors with built-in alarm devices can only be operated on the powered loop. For
physical reasons, an increased sound level leads to a higher current consumption rate of the
alarm device, the respective load factor must be considered when calculating the maximum 2
number on the loop. Altogether up to 127 bus devices per loop can still be connected.
Please consider that an extra training is required when dealing with IQ8Quad with a built-in
alarm device. The training includes installation planning and commisioning techniques. For
further information take a look at our training brochure. Information concerning the calculation 3
can be found in the "Project Planning Support chapter.
signal 1
(evacuation) sequence 1 sequence 2 sequence 3 sequence 4
4
signal 2
(alarm) sequence 1 sequence 2 sequence 3 sequence 4

signal 3
sequence 1 sequence 2 sequence 3 sequence 4
5
(event 1)

signal 4
(event 2) sequence 1 sequence 2 sequence 3 sequence 4
6
Signals

10

11

12

13

14

15

16

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

O2T/Optical detector with integrated alarm devices

Country code Language


acc. to ISO code acc.
3166 -Alpha-2 to ISO 639-1 Evacuation 1 Evacuation 2 Alarm Test-message All-Clear

Dies ist ein Achtung, Achtung! Achtung, im Ge- Die Gefahrensituation


Feueralarm. Bitte Dies ist eine Gefahr- bude ist eine ist jetzt behoben. Wir
verlassen Sie das enmeldung. Bitte Gefahrensituation Dies ist eine entschuldigen uns
de Gebude um- verlassen Sie das gemeldet worden. Testdurchsage. fr jegliche
gehend ber die Gebude ber die Bitte bleiben Sie Unannehmlichkeiten.
Germany nchsten Flucht- nchsten ruhig, und warten
(DE) wege. Die Feuer- Ausgnge. Sie auf weitere
wehr ist alarmiert. Anweisungen.

This is a fire alarm. Attention please. An incident has This is a test The emergency is
Please leave the This is an emergen- been reported in the message. now cancelled. We
en building immedia- cy. Please leave the building. Please No action is apologize for any
tely by the nearest building by the await further required. inconvenience.
Great Britain available exit. nearest available exit. instructions.
(GB)

Ceci est une alarme Votre attention s'il Un incident est


incendie,veuillez vous plat, ceci est signal dans le L'alarme est
vacuer une alarme. Veuillez batiment. Merci de prsent annule.
immdiatement les vacuer les locaux garder votre calme Ceci est un test.
fr Veuillez nous excuser
locaux par la sortie par la sortie la plus et attendez les pour le dsagrment.
France la plus proche. proche. prochaines
(FR) instructions.

Esto es una alarma Atencin. Esto es Atencin, se ha Esto es un La emergencia ha


de incendio. una emergencia. reportado un mensaje sido cancelada.
Abandonen Por favor incidente de prueba. Pedimos disculpas
es por favor el edificio abandonen el en el edificio. No se requiere por las molestias
Spain inmediatamente edificio por la Aguarden por favor ninguna accin. causadas.
(ES) por la salida de salida de otras instrucciones.
evacuacin evacuacin
ms cercana. ms cercana.

Attenzione. Attenzione. Attenzione. Attenzione. Attenzione. Cessato


Allarme incendio. Allarme in corso. E' stato rilevato un E' in corso una allarme.La situazione
Abbandonare Vi preghiamo di allarme.Ulteriori prova di allarme. di normalit stata
it l'edificio tramite recarvi presso disposizioni vi Non richiesta ripristinata.
l'uscita di l'uscita di verranno alcuna azione.
Italy emergenza pi emergenza pi comunicate
(IT) vicina. vicina. appena possibile.

Standard speech messages of IQ8Quad detectors and IQ8Alarm

No. Description Frequency Pulse rate


1 School bell complex complex
FP 1063.1 Telecoms f 0,25 sec.
2 Alternating 800 / 970 Hz at 2 Hz
BS 5839 Pt1 0,25 sec.
t
0,5 sec.
3 BS 5839 Pt1 Alternating 800 / 970 Hz at 1 Hz f
0,5 sec.
t
0,5 sec.
4 BS 5839 Pt1 Intermittent 970 Hz at 1 Hz 0.5 sec. f 1,5 sec.
0,5 sec. t
0,5 sec.
5 BS 5839 Pt1 Intermittent 2850 Hz at 1 Hz 0.5 sec. f 1,5 sec.
0,5 sec. t
f 0,25 sec.
6 BS 5839 Pt1 Intermittent 970 Hz 1/4 sec. ON - 1 sec. OFF 1,0 sec.
t
7 BS 5839 Pt1 Continious 970 Hz f
t
10 ms
8 BS 5839 Pt1 Sweep tone 800 Hz tp 970 Hz at 7 Hz f
t
f 1,0 sec.
9 BS 5839 Pt1 Sweep tone 800 Hz to 970 Hz at 1 Hz
t

10 DIN Tone 1200 - 500 Hz at 1 Hz f 1,0 sec.


DIN 33404 Part 3 t
0,1 sec.
11 French fire sound 554 Hz / 100 ms + 440 Hz / 400 ms + 10 % f 0,4 sec.
t
f 3,5 sec. 0,5 sec.
12 NL - Slow Whoop 500 Hz - 1200 Hz at 3.5 sec. break of 0.5 sec.
t

13 US - Horn Continious 485 Hz f


t
US - Horn with Intermittent 485 Hz f 0,5 sec.
14 Temporal Pattern
1,5 sec.
(0,5 sec. ON; 0.5 sec. OFF; 3 times; 1.5 sec. OFF; Repeat) 0,5 sec.
t
US - March Alternating 485 Hz f
0,25 sec.
15 Time (0,25 sec. ON; 0.25 sec. OFF; Repeat) 0,25 sec.
t
US - Slow Sweep tone 500 Hz to 1200 Hz f 4,0 sec. 0,5 sec.
16 Whoop (4.0 sec. ON; 0.5 sec. OFF; Repeat) t
Sweep tone 600 Hz to 1200 Hz f 1,0 sec.
17 US - Siren (1,0 sec. ON, Repeat) t
Alternating 100 Hz / 800 Hz f
0,25 sec.
18 US - Hi/Lo (0.25 sec. ON; Alternate; 0.25 sec. ON; Alternate; Repeat) 0,25 sec.
t
US - NFPA Sweep tone 422 Hz to 775 Hz f
0,85 sec. 1,0 sec.
19 (upwards sweep 0.85 sec.; 3 times; 1 sec. OFF; Repeat)
Whoop t
1,0 sec.
IMO Intermittent 800 Hz (1,0 sec. ON; 1,0 sec. f
20 GA-Signal OFF: 7 times; 2.0 sec. ON: 2.0 sec. OFF; Repeat) 1,0 sec.
t

IQ8Quad detector and IQ8Alarm tone table

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

1
Detector with integrated alarm devices
117 Technical Data
Operating voltage 8 ... 42 V DC 2
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Air speed 0 ... 25.4 m/s
65 Application temperature -20 C ... 65 C
Storage temperature -25 C ... 75 C
3
Air humidity d 95% (ohne Betauung)
Type of protection IP 42
Material ABS plastic
Fire detector with base 4
Color white, similar to RAL 9010
Weight approx. 145 g
Detector specification En 54-7/5 B, CEA 4021
Dimensions : 117 mm H: 59 mm

Detector bases are not supplied as standard. 5


The 769836 demo package is available for presentations. Further data can be viewed in the
accessories section for automatic detectors. For calculating the battery capacity of fire alarm
control panels, the detector data "quiescent current @ FACP battery" can be added. 6
Special-colours on demand!

It is not possible to use the detector base with relay contact (part no. 805591).
7
Accessories
767800 mounting bracket
8
805590 Standard detector base for IQ8Quad

IQ8Control C
9

10

flash signal speech


11

12
esserbus-PLus
Loop length max. 3.5 km
13

speech
esserbus transponder 14

flash 15
sound speech

16
Application example

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802383 q8te O2T/F multisensor IQ8Quad

Approval: VdS

OT/F multisensor IQ8Quad with integrated flasher
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in flash lamp.

Technical Data
Quiescent current @ 19 V DC approx. 75 A
Quiescent current @ FACP battery approx. 400 A
Load factor 2
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red

Not suitable for application in relay base 805591!

802382 q8sb O/So optical smoke detector IQ8Quad

Approval: VdS

O/So optical smoke detector IQ8Quad with integrated sounder
Scatter smoke detector for safe and early detection of smouldering fires with light smoke
generation. Intelligent detector with decentralised intelligence, automatic function self-test,
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and
operating indication. The detector is provided with a loop isolator.

Along with smoke detection components, the detector is provided with a built-in sounder.

Technical Data
Quiescent current @ 19 V DC approx. 80 A
Load factor 2
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Detector specification EN54-7, EN 54-17

Not suitable for application in relay base 805591!

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802382.F0 q8s/G1T O/So optical smoke detector IQ8Quad - France 1

Approval: VdS

O/So optical smoke detector IQ8Quad with integrated sounder 2
Scatter smoke detector for safe and early detection of smouldering fires with light smoke
generation. Intelligent detector with decentralised intelligence, automatic function self-test,
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and 3
operating indication. The detector is provided with a loop isolator.

Along with smoke detection components, the detector is provided with a built-in sounder.
4
Technical Data
Quiescent current @ 19 V DC approx. 80 A
Load factor 2
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone 5
Detector specification EN54-7, EN 54-17

Not suitable for application in relay base 805591!


6

802384 q8uh O2T/So multisensor IQ8Quad


8
Approval: VdS

OT/So multisensor IQ8Quad with integrated sounder
In addition to smoke detection with the conventional OT multisensor technology, the 9
detector is provided with a built-in alarm signalling device. The sound level can be set to
eight different levels.

Technical Data
10
Quiescent current @ 19 V DC approx. 80 A
Quiescent current @ FACP battery approx. 450 A
Load factor 2 11
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Specification EN 54-3 acoustic signalling device

Not suitable for application in relay base 805591!


12

13

14

15

16

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802386 q8wn O2T/Sp multisensor IQ8Quad

Approval: VdS

OT/Sp multisensor IQ8Quad with integrated sounder and speech
In addition to smoke detection with conventional OT multisensor technology, the detector
is provided with a built-in voice alarm device. It can be set to eight different levels.

Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Specification EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)

Not suitable for application in relay base 805591!

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

802385 q8vk O2T/FSp multisensor IQ8Quad

Approval: VdS

OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in voice alarm device. It can be set to eight different levels.

Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red
Specification EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)

Not suitable for application in relay base 805591!

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

 www.esser-systems.com
Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802385.SV98 q8v/TW:9 O2T/FSp multisensor detector IQ8Quad with composition of other


languages
1

Approval: VdS
2

OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
As with 802385, but with an individual combination of national languages.
3
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the
appendix.

Cancellations or returns are not possible.


4

Not suitable for application in relay base 805591!


5
Programmed with an individual combination of up to 5 national languages.

802385.SV99 q8v/TW::& O2T/FSp multisensor detector IQ8Quad as customized version 8


Approval: VdS

OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech 9
As 802385, but with individual text and/or sounds. The max. recording time per device is
169 seconds.
10
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the
appendix.
Costs for the recording of customer-specific texts and/or tones can be obtained by request. 11
Cancellations or returns are not possible.
Not suitable for application in relay base 805591!

Programmed according to customer specifications. 12

13

802385.N0 O2T/FSp multisensory IQ8Quad Nordic 14

15

16

17


Automatic Detectors Series IQ8Quad (Intelligent Addressable)

802385.F0 q8vk O2T/FSp multisensor IQ8Quad

Approval: VdS

OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in voice alarm device. It can be set to eight different levels.

Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red
Detector specification EN 54-7, EN54-17
Specification acoustic signalling device EN 54-3
acoustic signalling device EN 54-3

Not suitable for application in relay base 805591!

Programmed with 5 standard national languages (DE/GB/FR/ES/IT).

 www.esser-systems.com