Isolated Footing 1
2.25 ft
2.75 ft
Elevation
X 6.5 ft
2.5 ft
1 ft
13 ft
Plan
Input Values
Footing Geomtery
Column Dimensions
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 2 of 10
Pedestal
Include Pedestal : No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : N/A
Design Parameters
Soil Properties
Global Settings
Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)
Top Reinforcement Factor : 1.000
------------------------------------------------------
Design Calculations
Footing Size
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 3 of 10
Load Combinations
Applied Loads
Before consideration of self weight and load safety factor table
Note: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacity.
Pressures at 4 Corners
Please note that pressures values displayed in tables below are calculated after dividing by soil bearing factor
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 4 of 10
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the pressure
will be redistributed to remaining corners.
Pressure at
Pressure at top Pressure at top bottom right Pressure at
Load Case / left corner right corner corner bottom left corner
Combination (kip/ft2) (kip/ft2) (kip/ft2) (kip/ft2)
Stability Check
OTM
2.25 ft
. Sliding Force
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 5 of 10
Shear Calculation
X 6.5 ft
Z
1.1665 ft
Plan
Total Footing Depth, D = 2.750ft
Calculated Effective Depth, d = D - Ccover - 1 * db = 2.333 ft
For rectangular column, = Bcol / Dcol = 2.500
Punching shear strength, Vc = 0.75 X minimum of (Vc1, Vc2, Vc3) = 937.147 kip
0.75 X Vc > Vu hence, OK
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 6 of 10
X 6.5 ft
Z 3.708 ft
3.708 ft
Plan
From ACI Cl.11.2.1.1, Vc = = 542.647 kip
Check that 0.75 X Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the X axis.
X 6.5 ft
2.875 ft 2.875 ft
Plan
From ACI Cl.11.2.1.1, Vc = = 562.379 kip
Check that 0.75 X Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the Z axis.
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 7 of 10
14 - #8
Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
Note: The minimum reinforcement is the sum of the reinforcement provided at top and bottom.
Bars parallel to X Direction are placed at bottom
Effective Depth d = 2.375 ft
Factor from ACI Cl.10.2.7.3 =
= 0.850
Warning:Calculated spacing is more than maximum spacing considering cracking condition. Modify spacing manually if
cracking consideration is necessary.
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 8 of 10
#8 @ 12in o.c.
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Total reinforcement area, As_total = Nbar X (Area of one bar) = 11.060 in2
d= D - Ccover - 0.5 X (dia. of one bar) = 2.375 ft
14 - #8
Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in ksi
Note: The minimum reinforcement is the sum of the reinforcement provided at top and bottom.
Bars parallel to X Direction are placed at bottom
Effective Depth d = = 2.292 ft
Factor from ACI Cl.10.2.7.3 =
= 0.850
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 9 of 10
Warning:Calculated spacing is more than maximum spacing considering cracking condition. Modify spacing manually if
cracking consideration is necessary.
#8 @ 12in o.c.
Because the number of bars is rounded up, make sure new reinforcement ratio < max
Total reinforcement area, As_total = Nbar X (Area of one bar) = 11.060 in2
d= D - Ccover - 1.5 X (dia. of one bar) = 2.292 ft
file:///C:/ProgramData/Bentley/Engineering/STAAD%20Foundation%20Advanced/Repo... 06/03/2017
Page 10 of 10
6.5 ft 6.5 ft