FUNCTIONAL SPECIFICATION FOR SALES GAS


FILTRATION SYSTEM
12/28/16
NO. DATE
REV

DISCIPLINE
ENGINEER
VTN
ISSUED FOR 90 % REVIEW
12/16
DATE:
PROJECT
ENGINEER
MGB
12/16
DECEMBER 2016
DATE:
CERTIFIED
ADF

DATE:
CONSTRUCTION
AGENCY PREPARED BY:

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:

A. Al-Saihati, A. Fattani & O. Al-Othman Consulting Engineering Co.


BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 1


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
TABLE OF CONTENTS
ADF
ENGG CERT

1 INTRODUCTION................................................................................................................4
MGB

1.2 Sales Gas Filtration System .................................................................................................. 4


1.3 Definitions .............................................................................................................................. 4
1.4 Conflicts and Deviations ........................................................................................................ 5

2 REFERENCES...................................................................................................................5
ISSUED FOR 90% REVIEW

2.1 Drawings & Documents ......................................................................................................... 5


DESCRIPTION

2.2 Saudi Aramco Engineering Standards................................................................................... 5


2.3 Saudi Aramco Material System Specifications ...................................................................... 7
2.4 Saudi Aramco Engineering Procedures................................................................................. 8
2.5 Saudi Aramco General Instructions ....................................................................................... 8
2.6 Saudi Aramco Inspection Requirements ............................................................................... 9
2.1 Saudi Aramco Standard and Library Drawings ..................................................................... 9
JO/EWO

2.2 Saudi Aramco Forms ........................................................................................................... 10


2.3 Industry Codes and Standards ............................................................................................ 10
12/28/16
DATE

3 OPERATION & CONTROL REQUIREMENTS ................................................................13


NO.
REV

3.1 Control Philosophy ............................................................................................................... 13


DISCIPLINE
ENGINEER
VTN 4 SCOPE OF WORK ..........................................................................................................11
12/16
DATE:
PROJECT
ENGINEER 5 DESIGN REQUIREMENTS ..............................................................................................14
MGB
12/16
DATE: 5.1 Process Design .................................................................................................................... 14
CERTIFIED
ADF 5.2 Filter System Operation and Maintenance Requirements ................................................... 16
DATE: 5.3 Material Selection ................................................................................................................ 17
CONSTRUCTION
AGENCY 5.4 Mechanical Design............................................................................................................... 17

DATE:
5.5 Nozzles & Manways ............................................................................................................. 18
OPERATIONS
5.6 Piping ................................................................................................................................... 19
5.7 Instrumentation .................................................................................................................... 20
DATE:
5.8 Electrical .............................................................................................................................. 21
CONTROL NUMBER
VERIFICATION

5.9 Fire Proofing/Fire Protection ................................................................................................ 22


EDSD

5.10 Ladders, Cages, Platforms and Vehicle Barriers ................................................................. 22


DATE:
BY:

5.11 Structural .............................................................................................................................. 22


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

5.12 Fabrication ........................................................................................................................... 23


OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

6 INSPECTION AND TESTING ..........................................................................................24

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 2


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
6.1 Pressure Testing .................................................................................................................. 24

7 GUARANTEE & PERFORMANCE TEST ........................................................................24


ADF
ENGG CERT
MGB

8 TRAINING ........................................................................................................................24

9 DATA REQUIREMENT ....................................................................................................25

10 PREPARATION FOR SHIPMENT ...................................................................................27


ISSUED FOR 90% REVIEW
DESCRIPTION

11 FIELD ERECTION ...........................................................................................................27

12 SPARE PARTS DATA PACKAGE ..................................................................................28

13 NOZZLE LOADS .............................................................................................................28

14 APPENDIX-A ...................................................................................................................29
JO/EWO

15 APPENDIX-B ...................................................................................................................30
12/28/16
NO. DATE
REV

DISCIPLINE
ENGINEER
VTN
12/16
DATE:
PROJECT
ENGINEER
MGB
12/16
DATE:
CERTIFIED
ADF

DATE:
CONSTRUCTION
AGENCY

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 3


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1 INTRODUCTION

This specification covers the minimum technical requirements for the design, engineering,
ADF
ENGG CERT

material procurement, fabrication, inspection, transportation, site erection, testing,


MGB

commissioning and performance guarantee of a Sales Gas Filtration System (SGFS) for the
new Cement Plant of Yamama Cement Company Ltd. This filtration system shall be installed
in the Yamama Gas Metering Station.

1.1 Yamama Gas Metering Station Facilities


ISSUED FOR 90% REVIEW

Yamama Gas Metering Station is composed of 20 main supply pipeline from Saudi
Aramco, EIV, Filtration System, Metering System, Gas Heating and Pressure Reducing
DESCRIPTION

Stations. The Filtration System shall be designed to remove particles greater than 1
micron from the sales gas stream.

1.2 Sales Gas Filtration System

The Yamama sales gas filtration facilities are required to remove the black powder from
sales gas delivered to YNP.

The Filtration System shall be designed as FILTER-SEPARATOR type. It is suggested


JO/EWO

that the VENDORs design shall utilize a two-stage filtration system: The first stage can be
cyclonic to remove particles eight (8) microns and larger and the second stage can be
cartridge filtration to remove particles one (1) micron and larger. The frequency of
12/28/16
DATE

cartridge filter change shall be minimum six (6) months under design conditions. The
filtration system shall be designed considering the Process design parameters given in,
NO.
REV

Table T1 to T5 of section 5.1, and shall consist of two 100% capacity gas filtration units;
A

DISCIPLINE one operating and one standby.


ENGINEER
VTN

DATE:
12/16 The SGFS shall be equipped with a PLC system that shall be utilized to control and switch
PROJECT
ENGINEER
the filtration units as operating/ standby.
MGB

DATE:
12/16 These filters shall be located in Yamama Gas Metering Station. New sales gas filtration
CERTIFIED system shall be supplied by an approved Saudi Aramco Vendor. The Vendor shall be
ADF
responsible for the design, engineering, material procurement, fabrication, inspection,
DATE: transportation, site erection, testing & commissioning and performance guarantee of the
CONSTRUCTION
AGENCY
gas filtration system.

DATE: 1.3 Definitions


OPERATIONS
For the purpose of this specification, the following definitions are used:
DATE:
CONTROL NUMBER


VERIFICATION

SGFS shall mean Sales Gas filtration system


EDSD

Include(s) means includes but not limited to.


DATE:
BY:

Company means a Yamama Cement Company.


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

CONTRACTOR means LSTK contractor who is executing the project on a Lump


(DCC) NO. _____________________

Sum Turn Key basis.

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 4


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
VENDOR means the company responsible for the design, fabrication, installation,
and testing of the new gas filtration system for which this specification is
applicable.
ADF
ENGG CERT
MGB

1.4 Conflicts and Deviations

1.4.1 If any inconsistency or conflict exists between this specification, and other project
or SAUDI ARAMCO Engineering Standards, SAUDI ARAMCO Material System
Specifications, industry standards or drawings, the inconsistency shall be brought
ISSUED FOR 90% REVIEW

to the attention of COMPANY Representative for resolution at the time of


submitting a quotation. The deviations and/or clarifications shall be clearly and
DESCRIPTION

specifically stated in the quotation under a separate heading of Deviations and


Clarifications with the comprehensive reasons and supporting information. The
implied or hidden deviations shall not be acceptable. The deviations that sacrifice
the safety or reliability of the equipment shall not be acceptable.

1.4.2 If CONTRACTOR fails to submit Deviations and Clarifications to the COMPANY


with his proposal (including any deviations and clarifications from VENDOR),
CONTRACTORs bid shall be regarded as No deviations or clarifications to this
specification.
JO/EWO

1.4.3 CONTRACTOR may propose alternative equipment from SAUDI ARAMCO


qualified and approved VENDORS, which shall meet the performance
12/28/16
DATE

requirements of this specification without sacrificing safety, reliability or


maintainability. However, even in such case, CONTRACTOR shall furnish the gas
NO.
REV

filtration equipment according to this specification as the base proposal.


A

DISCIPLINE
ENGINEER
VTN
12/16
DATE:
PROJECT
2 REFERENCES
ENGINEER
MGB
12/16
The following Drawings, SAUDI ARAMCO Engineering Standards (SAES), SAUDI ARAMCO
DATE: Materials System Specification (SAMSS), Industry Codes and Standards referenced below
CERTIFIED
ADF shall form part of this specification:
DATE:
CONSTRUCTION
2.1 Drawings & Documents
AGENCY

DATE:
OPERATIONS
SK-A-YCC-002 Sht. 001 Piping and Instrument Diagram
SK-A-YCC-002 Sht. 002 Piping and Instrument Diagram
DATE:
CONTROL NUMBER
VERIFICATION

2.2 Saudi Aramco Engineering Standards


EDSD

SAES-A-004 General Requirements for Pressure Testing


DATE:
BY:

SAES-A-007 Hydrostatic Testing Fluids and Lay-Up Procedures


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

SAES-A-112 Meteorological and Seismic Design Data


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 5


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SAES-A-202 Saudi Aramco Engineering Drawing Preparation
ADF
ENGG CERT

SAES-A-204 Preparation of Structural Calculations


MGB

SAES-B-006 Fireproofing for Plants

SAES-B-019 Portable Mobile and Special Fixed Firefighting Equipment

SAES-B-054 Access, Egress, and Materials Handling for Plant Facilities


ISSUED FOR 90% REVIEW
DESCRIPTION

SAES-B-067 Safety Identification and Safety Colors

SAES-B-068 Electrical Area Classification

SAES-D-001 Design Criteria for Pressure Vessels

SAES-H-001 Coating Selection and Application Requirements for Industrial Plants


and Equipment
SAES-H-101 Approved Saudi Aramco Data Sheets - Paints and Coatings
JO/EWO

SAES-H-101V Approved Saudi Aramco Data Sheets - Paints and Coatings


12/28/16
DATE

SAES-J-001 Instrumentation Index


NO.
REV

DISCIPLINE SAES-J-002 List of Inspectable Instruments


ENGINEER
VTN

DATE:
12/16
SAES-J-003 Instrumentation - Basic Design Criteria
PROJECT
ENGINEER
MGB
SAES-J-004 Instrumentation Symbols and Identification
12/16
DATE:
CERTIFIED
ADF SAES-J-005 Instrumentation Drawings and Forms
DATE:
CONSTRUCTION SAES-J-200 Pressure
AGENCY

DATE: SAES-J-300 Level


OPERATIONS

SAES-J-600 Pressure Relief Devices


DATE:
CONTROL NUMBER

SAES-J-902 Electrical Systems for Instrumentation


VERIFICATION
EDSD

SAES-L-105 Piping Line Classes


DATE:
BY:

SAES-L-108 Selection of Valves


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

SAES-L-150 Pressure Testing of Plant Piping and Pipelines


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 6


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
SAES-M-001 Structural Design Criteria for Non-Building Structures
ADF
ENGG CERT

SAES-Q-005 Concrete Foundations


MGB

SAES-Q-007 Foundations and Supporting Structures for Heavy Machinery

SAES-Q-010 Cement Based, Non-Shrink Grout for Structural and Equipment


Grouting
SAES-P-100 Basic Power System Design Criteria
ISSUED FOR 90% REVIEW
DESCRIPTION

SAES-P-101 Regulated Vendors List for Electrical Equipment

SAES-P-111 Grounding

SAES-P-104 Wiring Methods and Materials

SAES-P-123 Lighting

SAES-W-010 Welding Requirements for Pressure Vessels


JO/EWO

SAES-W-011 Welding Requirements for On-Plot Piping


12/28/16
DATE

SAES-W-012 Welding Requirements for Pipelines


NO.
REV

DISCIPLINE 2.3 Saudi Aramco Material System Specifications


ENGINEER
VTN

DATE:
12/16 32-SAMSS-004 Manufacture of Pressure Vessels
PROJECT
ENGINEER
MGB 09-SAMSS-069 Qualification Requirements for Epoxy Coatings for Atmospheric
DATE:
12/16 Service
CERTIFIED
ADF
04-SAMSS-050 Gate Valves, Through Conduit Type, API SPEC 6D
DATE:
CONSTRUCTION
04-SAMSS-051 Ball Valves, API SPEC 6D
AGENCY

DATE:
09-SAMSS-071 Qualification Requirements for Inorganic Zinc Primer (APCS-17A)
OPERATIONS and (APCS-17B)
12-SAMSS-007 Fabrication of Structural and Miscellaneous Steel
DATE:
CONTROL NUMBER

12-SAMSS-008 Erection of Structural and Miscellaneous Steel


VERIFICATION
EDSD

16-SAMSS-518 Low Voltage Panelboards


DATE:
BY:

34-SAMSS-718 Electric Motor Operated Valve Actuators


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

34-SAMSS-830 Programmable Logic Controller


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 7


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
34-SAMSS-831 Instrumentation for Packaged Units
ADF
ENGG CERT

01-SAMSS-010 Fabricated Steel Piping


MGB

02-SAMSS-011 Forged Steel and Alloy Flanges

02-SAMSS-005 Butt Welding Pipe Fittings

34-SAMSS-611 Safety Relief Valves Conventional and Balanced Types


ISSUED FOR 90% REVIEW
DESCRIPTION

34-SAMSS-913 Instrumentation and Thermocouple Cable

04-SAMSS-035 General Requirements for Valves

04-SAMSS-048 Valve Inspection and Testing Requirements

2.4 Saudi Aramco Engineering Procedures


JO/EWO

SAEP-35 Valves Handling, Hauling, Receipt Tests and Storage

SAEP-121 Operating Instructions for New Facilities


12/28/16
DATE

SAEP-122 Project Records


NO.
REV

DISCIPLINE
ENGINEER
VTN
SAEP-302 Instructions for Obtaining a Waiver of a Mandatory Saudi Aramco
12/16 Engineering Requirement
DATE:
PROJECT SAEP-334 Retrieval, Certification and Submittal of Saudi Aramco Engineering and
ENGINEER
MGB Vendor Drawings
DATE:
12/16 SAEP-349 Advanced Process Control (APC) Systems
CERTIFIED
ADF
SAEP-358 Management of Technologically Enhanced Naturally Occurring
DATE:
Radioactive Material (NORM)
CONSTRUCTION
AGENCY
SAEP-3101 Equipment and Spare Parts Data Requirements for Contractor
Procured Equipment
DATE:
OPERATIONS
2.5 Saudi Aramco General Instructions
DATE:
G.I. 2.100 Work Permit System
CONTROL NUMBER
VERIFICATION
EDSD

G.I. 2.710 Mechanical Completion


DATE:

G.I. 7.028 Crane lifts


BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

G.I. 430.001 Waste Management


OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 8


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
2.6 Saudi Aramco Inspection Requirements

175-321900 Inspection and Testing Requirements - Pressure Vessel


ADF
ENGG CERT

175-091900 Inspection Requirements for Coatings, Shop Applied.


MGB

175-340200 Instrumentation for package units

175-341000 Inspection Requirements for Actuators


ISSUED FOR 90% REVIEW

175-043600 Inspection Requirements for Valves


DESCRIPTION

175-060100 Inspection & testing requirement Gaskets

175-320300 Inspection & testing requirement Positive Materials Identifications

175-340200 Inspection & testing requirement Instrumentation for package


units
175-120100 Inspection & testing requirement Steel Structures

175-173700 Inspection & testing requirement Auxiliary Electrical Systems


JO/EWO

175-013100 Inspection & testing requirement Pipes


12/28/16
DATE

175-347600 Inspection Requirements for Valves Instrumentation and


Thermocouple Extension Cable
NO.
REV

175-341900 Inspection Requirements for Valves (Safety Relief)


DISCIPLINE
ENGINEER
VTN 175-022501 Inspection Requirements for Flanges
12/16
DATE:
PROJECT
ENGINEER
175-026100 Inspection Requirements for Fittings
MGB

DATE:
12/16 175-043600 Inspection Requirements for Valves
CERTIFIED
ADF
2.1 Saudi Aramco Standard and Library Drawings
DATE:
CONSTRUCTION
AGENCY
AA-036322 Anchor Bolt Details

DATE:
AB-036386 Hardness Testing for Welding Procedure Qualifications
OPERATIONS
AE-036451 Pre-heat Levels for Welding Carbon Steel
DATE:
DD-950003 Manway Cover Detail for Pressure Vessel and Column
CONTROL NUMBER
VERIFICATION
EDSD

DD-950053 Field Mounting Details for Instruments


DATE:
BY:

AC-036045 Details: Vents, Drains and Sample Connections


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

AD-036673 W.N. and Blind Flanges Large Size Class 600# R.F.
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 9


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AD-036981 Tolerances for Pressure Vessel

AC-036915 Fireproofing for Column & Vessel Skirts


ADF
ENGG CERT

AC-036963 Davits Assembly, Side Mounting On Pressure Vessels


MGB

2.2 Saudi Aramco Forms

NMR-7907 Nonmaterial Requirements for Instrumentation (General)


ISSUED FOR 90% REVIEW

NMR-7919-1 Nonmaterial Requirements for Pressure Vessel


DESCRIPTION

NMR-7927 Nonmaterial Requirement for Fabricated Structural Steel

2.3 Industry Codes and Standards

2.3.1 American Petroleum Society


API RP 520 Part-I Sizing, Selection and Installation of Pressure Relieving Devices
in Refineries
JO/EWO

API 6D Pipeline Valves


12/28/16
DATE

API 5L Specification for Line Pipe


NO.
REV

2.3.2 American Society for Mechanical Engineers (ASME)


DISCIPLINE
ENGINEER
VTN ASME B31.8 Gas Transmission & Distribution Piping Systems
12/16
DATE:
PROJECT
ENGINEER
ASME B31.3 Process Piping
MGB

DATE:
12/16 ASME Sec. V Non-Destructive Examination
CERTIFIED
ADF
ASME Sec. VIII Division 1 Boiler & Pressure Vessel Code
DATE:
CONSTRUCTION
AGENCY
ASME 16.5 Pipe Flanges and Flange Fittings

DATE:
ASME 16.47 Large Diameter Steel Flanges
OPERATIONS
ASME SA-20 Specification for General Requirements for Steel Plates for Pressure
DATE:
Vessels
CONTROL NUMBER
VERIFICATION
EDSD

ASME SA-388 Ultrasonic Examinations for Heavy Steel Forgings


DATE:

ASME SA-435 Straight Beams Ultrasonic Examination for Steel Plates


BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

ASME Sec-II Material Specifications Part A, B and D


OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

ASME Sec IIC Specification for Welding Rods, Electrodes and Filler Metals

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 10


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
ASME B16.20 Metallic Gaskets for Pipe Flanges, Ring-Joint, Spiral-Wound and

Jacketed
ADF
ENGG CERT

2.3.3 American Society of Civil Engineers (ASCE)


MGB

ASCE 7 Minimum Design Loads for Buildings and Other structures

ASCE 40262 Wind Loads and Anchor Bolt Design for Petrochemical Facilities
ISSUED FOR 90% REVIEW

2.3.4 American Concrete Institute (ACI)


DESCRIPTION

ACI 318 Building Code Requirements for Structural Concrete

2.3.5 American Institute of Steel Companies (AISC)

Manual of Steel Construction Allowable Stress design

2.3.6 Process Industry Practices (PIP)

PIP-STF05501 Fixed Ladders and Cages


JO/EWO

PIP-STF05520 Details for Pipe Railing for Walking and Working Surfaces
12/28/16
DATE

PIP-STF05530 Grating Fabrication Details


PIP-STF05511 Fixed Industrial Stairs
NO.
REV

2.3.7 Welding Research Council (WRC)


DISCIPLINE
ENGINEER
VTN WRC Bulletin 107 Local Stresses in Spherical and Cylindrical Shells Due to
DATE:
12/16 External Loadings
PROJECT WRC Bulletin 297 Welding Research Council Bulletin
ENGINEER
MGB
12/16 3 SCOPE OF WORK
DATE:
CERTIFIED
ADF
3.1 VENDOR shall be responsible for the complete detail design of the SGFS. Vendor shall
DATE: procure material, fabricate, inspect, transport, erect on site, and test the SGFS.
CONSTRUCTION
AGENCY
VENDOR shall assist CONTRACTOR in supervising fabrication and installation on site,
shall conduct the PLC FAT and system SAT performance testing and provide
DATE:
commissioning assistance, commission and provide a performance guarantee of the
OPERATIONS SGFS that meets the requirements of this Functional Specification. The SGFS shall
include, but not limited to, cyclonic and filter element vessels, interconnecting piping,
DATE:
valves, instrumentation, junction boxes (instrument/ electrical), XXX-PLC-XXXX
(Filtration System PLC), HMI, structural supports, and other accessories.
CONTROL NUMBER
VERIFICATION
EDSD

3.2 After CONTRACTOR issues a contract to VENDOR for this portion of the work,
VENDOR shall immediately arrange to take on-stream samples of the black powder in
DATE:
BY:

the gas stream of EWRGD-1 pipeline at the take-off point for the design of the filtration
system. CONTRACTOR is advised that Saudi Aramco shall be taking on-stream black
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

powder measurements at the tie-in location (i.e, at the new scraper launcher area
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

located approximately @ KM 41 from the East West Pipeline Pump Station-3) and at
(DCC) NO. _____________________

the outlet of the new filtration system (located at the YNP Fuel Connection Facilities

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 11


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
area). The data (black powder loading and particle size distribution from these two
locations will be used to verify the design basis. The samples shall be analyzed by
VENDOR for particle size distribution for solids loading to confirm the design of SGFS
ADF
ENGG CERT

is adequate for the filter life of 6 months between filter changes (if the exercise has
MGB

already been done for the Aramco Filtration System design the same is to be
considered for this Yamama Filtration System design also).

3.3 VENDOR shall design, provide materials, fabricate and install the gas filtration system
that shall include, but not limited to, the following:
ISSUED FOR 90% REVIEW

3.3.1 Two (2) 100% capacity filtration streams (one operational and another standby).
The filtration process shall consist of two stages connected in series.
DESCRIPTION

3.3.1.1 cyclonic filtration vessel to remove particle sizes 8 microns and larger
3.3.1.2 cartridge filtration vessel to remove particles sizes 1 micron and larger

3.3.2 The new filtration vessels shall be complete with nozzles, manholes with davits,
bolts, gaskets, blinds, internals, cleats, lifting lugs, supports and other accessories.

3.3.3 Interconnecting piping (including filter inlet and outlet header and piping connecting
JO/EWO

the headers to the filters), valves, instruments, access and task lighting, structural
supports, access platforms, ladders, crossovers and accessories required for the
complete filtration systems. VENDOR and CONTRACTOR shall provide the plot
12/28/16
DATE

plan requirements for the layout and vessel sizes of the SGFS proposed by
VENDOR.
NO.
REV

DISCIPLINE
ENGINEER
VTN
3.3.4 The filter elements shall be removable type on a fixed tube sheet.
12/16
DATE:
PROJECT
ENGINEER
3.4 VENDOR shall submit a complete design package including, calculations, drawings and
MGB specifications for all parts of the filtration units including process & utilities, piping,
DATE:
12/16 mechanical, electrical, instrumentation, and civil/ structural details.
CERTIFIED
ADF
3.5 VENDORs proposed design shall consider ease of fabrication, transportation to site,
DATE: erection on site, operation and maintenance especially black powder removal from
CONSTRUCTION
AGENCY
cyclones and removal and installation of filtration cartridges.

DATE: 3.6 VENDOR shall provide control and monitoring philosophy, logic diagrams, ILD, ISS,
OPERATIONS SIS, PFD, and P&ID drawings and all design documents per SAEP-334 which are
required to implement the filtration system control and monitoring from XXX-PLC-XXXX
DATE: as well as monitoring and control as mentioned under section 3.1. VENDOR shall
conduct site verification to support the control and monitoring philosophy of the filtration
CONTROL NUMBER
VERIFICATION

system and, as minimum, to utilize XXX-PLC-XXXX (Filtration System PLC) and its
EDSD

connectivity with YNP CCR.


DATE:
BY:

3.7 VENDOR shall prepare and submit the Operation and Maintenance Manuals for
REVISIONCERTIFICATION

VENDORs design in accordance with SAEP-121. The Operations and Maintenance


APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

Manuals shall include the procedure of unloading, removal, storing and transporting of
A

black powder to an approved disposal site.


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 12


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4 OPERATION & CONTROL REQUIREMENTS

4.1 Control Philosophy


ADF
ENGG CERT
MGB

The SGFS shall be designed for unattended operation when filtering the sales gas in
automatic mode and manned operation after switching from inline to offline for cleaning &
maintenance. YNP CCR shall receive status and alarm data from the SGFS XXX-PLC-
XXXX (Filtration System PLC) installed in Metering Building. YNP CCR shall have high
Filter DP monitoring facility and control & monitoring facilities of the MOVs via data sent
from the filtration system XXX-PLC-XXXX.
ISSUED FOR 90% REVIEW

YNP CCR shall also receive the following main information from SGFS:
DESCRIPTION

The filtration system is bypassed: the sales gas is no longer filtered

Number of filtration units which are available

A filtration unit is off stream and requires maintenance

Discrepant inlet/outlet/outlet bypass valve on any of the filter train


JO/EWO

The control system shall manage the switch over from the active to the standby
filtration unit or to the SGFS bypass valve to ensure continuity of the gas flow to the YNP
12/28/16
DATE

Pressure Reducing Station-1. However, all switch over can be done manually also.
NO.
REV

No condition other than a switchover condition shall affect the active filtration unit while in
DISCIPLINE
ENGINEER
operation. In addition to high differential pressure across the filter and high level of powder
VTN in the bottom of the filter vessel, another switch over condition shall be the loss of control
DATE:
12/16
(loss of limit switch signal) of the inlet or outlet MOV on the active filtration unit or
PROJECT
ENGINEER activation of manual switchover.
MGB

DATE:
12/16 The HMI located inside the Local Control Building, shall display live information on the
CERTIFIED status of the SGFS and its main components, a journal of alarms, and historical trends for
ADF
the main parameters.
DATE:
CONSTRUCTION
AGENCY When a filtration unit has been removed from the stream for maintenance, this unit cannot
be placed on standby ready for use until the required maintenance is complete and the
DATE: operator confirms it is available from the HMI.
OPERATIONS

The SGFS can also be controlled either in Semi-Automatic or in Manual mode by the
DATE: Operations team. The Semi-Automatic mode is used for initial pressurization of each filter
train before they are put in Automatic mode and for the maintenance operations on one
CONTROL NUMBER
VERIFICATION

filter train whilst the other train is onstream and keeps being controlled by the PLC in
EDSD

automatic mode. Maintenance operations carried out in Semi-Automatic mode are


controlled through a series of interlocks, confirmations and commands by the operator on
DATE:
BY:

HMI that will follow the logic imposed by the PLC. Any discrepancy will result in an alarm
REVISIONCERTIFICATION

and will either abort or suspend the ongoing sequence.


APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

In addition, the filter system shall have a soft emergency trip button located on the filter
(DCC) NO. _____________________

system safe location Human Machine Interface (HMI) panel which Loss Prevention

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 13


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Department of Saudi Aramco considers to comply with the requirements of SAES-B-058
for shutting down and isolating the sales gas filter systems. VENDOR shall participate in
HAZOP study to determine if it is recommended to automatically depressurize the filter
ADF
ENGG CERT

vessels in the event the trip button is activated. Required conditions to put one filtration
MGB

unit on-stream shall be:


Pressure inside the filter vessels is equal to the pressure inside the pipeline (this is
accomplished by having an open by-pass valve around the closed filter outlet
valve).

All motor operated valves (MOV) are in closed position except the filter outlet MOV
ISSUED FOR 90% REVIEW

bypass valve.
DESCRIPTION

Only one filtration unit can be put online at one time.

When one filtration unit is on-stream, the second filtration unit will be assigned the
stand by status. The status of each filtration unit is shown on the HMI.

Maintenance operations shall be carried out manually. Manual mode shall be possible
either from HMI under the control of XXX-PLC-XXXX (Filtration System PLC) or by
switching an MOV to local mode from the local control panel located on the MOV actuator.
JO/EWO

From the HMI the operator shall be able to actuate one MOV at a time.
12/28/16
DATE

5 DESIGN REQUIREMENTS
NO.
REV

DISCIPLINE
ENGINEER
Design requirements of the SGFS shall include the process and mechanical design of the
VTN complete filtration system.
12/16
DATE:
PROJECT
ENGINEER
5.1 Process Design
MGB a. The proposed Sales Gas Filtration System design (cyclone in series with cartridge
DATE:
12/16 filters) shall be based on the process conditions specified below.
CERTIFIED
ADF
b. Table T1 below provides sales gas compositions while Tables T2, T3, T4 & T5
DATE: provide process parameters and design conditions.
CONSTRUCTION
AGENCY
Table T1: Sales Gas Composition (Volume %)
DATE:
OPERATIONS Butane
Molecular
Methane Ethane Propane & Nitrogen HHV
Weight
DATE: others
CONTROL NUMBER

89.14 3.38 0.58 0.30 6.60 988


VERIFICATION

17.61
mol % mol % mol % mol % mol % BTU/SCF
EDSD

Table T2: Particle Loading


DATE:
BY:

Filter Loading Bulk Density


Particle Distribution
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

Grams per MMSCF Grams/cm


THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

By vendor By vendor By vendor


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 14


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Table T3: Black Powder Properties

Composition Hardness
ADF
ENGG CERT

By vendor By vendor
MGB

Table T4: Sales Gas Flow Condition at Aramco tie-in point

Design Pressure (PSIG): 1012


Normal operating Pressure at Aramco tie-in point
600-960
(PSIG)
ISSUED FOR 90% REVIEW

Design Temp (F): 150


DESCRIPTION

Operating Temp (F): 90-130


Viscosity 0.012 cP (Note 1)

Table T5: Design Conditions:


The filtration system shall be designed as per the parameters given below.
Filtration System Tag Number: XXX-U-XXXX
Cyclone separator vessels XXX-D-XXX A/B
Filters XXX-D-XXX A/B
JO/EWO

ASME Section VIII D1 or D2,


Vessel Code:
(Latest), 32-SAMSS-004
Piping Code ASME B31.3
12/28/16
DATE

Design Pressure, psig 1012


Design Temp (F): 150
NO.
REV

Normal inlet pressure, psig 500-860 (see note 2)


DISCIPLINE
ENGINEER Operating Temperature Range, F (90 to 130)
VTN
Design Flow Rate (MMSCFD): 140
12/16
DATE: Normal Flow Rate (MMSCFD) 80
PROJECT
ENGINEER Minimum Flow Rate (MMSCFD) 10
MGB
12/16
Inlet/Outlet Flange Size: 20/20 600#
DATE: 0F (Vendor to confirm based on De-
CERTIFIED
ADF Minimum Design Metal Temp, (MDMT) F pressurization minimum
Temperature)
DATE:
Maximum Pressure Drop across Filter
CONSTRUCTION
25
AGENCY
assembly, psi
Maximum particles size at filter outlet 1.0 microns
DATE:
OPERATIONS
Corrosion Allowance, mm 1.6 mm
Joint Efficiency Factor (E) 1
Radiography 100%
DATE:
Post Weld Heat Treatment As per Code
CONTROL NUMBER
VERIFICATION

As per ASME Sec VIII SAES-A-004 &


Hydrostatic Test Pressure, Psig
EDSD

SAES-A-007
Impact at MDMT As per ASME Sec VIII
DATE:
BY:

No. of Cartridges: By vendor Note 3


SAES-H-101 APCS 1B Color Code A
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

External Coating/painting and as per 32-SAMSS-004 & SAES-


OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

D-001
(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 15


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Notes:
1. Vendor to calculate the operating viscosity based on gas composition and
ADF
ENGG CERT

process parameters.
MGB

2. The pressure at the filter inlet is considered based on conservative pressure


drops of 100 psig across the upstream metering, filtration skids and 20 KM
pipeline.
3. VENDOR shall size the vessels and specify the number and size of internal
ISSUED FOR 90% REVIEW

cartridges that meets the design objectives. Vendor to furnish the pressure drop
DESCRIPTION

at which the duty/ standby filter change-over will be effected as per his design.
4. Cartridge sizes shall be standardized for interchangeability, minimum inventory
and spare parts management.
5. Tag number is temporary. Final number will be assigned during review of
VENDOR drawings.
JO/EWO

5.2 Filter System Operation and Maintenance Requirements


12/28/16
DATE

VENDORs design of the SGFS shall incorporate the operating and maintenance
requirements below:
NO.
REV

DISCIPLINE
ENGINEER
a) The processes of filter replacement and black powder removal shall be quick, easy
VTN and safe.
12/16
DATE:
PROJECT
ENGINEER
b) Maintenance frequency shall be as long as possible. However, the minimum filter
MGB cartridge life shall be 6 months for replacing with new ones. VENDOR shall provide
DATE:
12/16 estimates for cartridge filter life based upon measured "Black Powder" loading levels
CERTIFIED determined during sampling of both normal flow conditions and during pipeline
ADF
scraping operations. VENDOR shall develop an algorithm and program into XXX-
DATE: PLC-000X (Filtration System PLC) to calculate remaining filter life based on actual
CONSTRUCTION
AGENCY
black powder loading conditions to date for a specific set of filters.

DATE: c) The SGFS shall provide for change-over of filter vessels based on conditions
OPERATIONS stipulated in paragraph 3.1 above. Replacement of filter cartridges and the removal
of black powder from vessels shall be performed manually.
DATE:
d) The instrumentation, event sequencing and change-over of filters will be monitored
CONTROL NUMBER
VERIFICATION

remotely by YNP CCR via Filtration System PLC XXX-PLC-XXXX.


EDSD

e) It is planned to use vacuum trucks for normal black powder removal from the cyclone
DATE:
BY:

portion of the filter vessels.


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

f) Water spray of black powder, nitrogen or air purge (during powder removal by
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

vacuum truck and during filter replacement) shall take place to ensure zero (0) LEL
(DCC) NO. _____________________

conditions. VENDOR shall supply all required attachments and connections inside

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 16


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
and outside the filter vessels to easily perform these tasks. provide connection on
vent to flare line (sales gas depressurization) to check HC/O2 content using a
portable O2 HC device All interface points shall be at the filtration system edge with
ADF
ENGG CERT

safe access and clearance for utility tankers and vehicles. The amount, flow rate and
MGB

operating conditions of air and Nitrogen shall be specified by VENDOR. Water


composition, pressure and flow rate shall also be defined by VENDOR.

a) Hydrocarbon sensors shall be supplied on the blowdown line to ensure proper


inserting of the vessels prior to maintenance. VENDOR shall specify the design basis
for the hydrocarbon sensors.
ISSUED FOR 90% REVIEW

b) Independent utility lines will be supplied for each filter vessel and shall be terminated
DESCRIPTION

close to filtration system by CONTRACTOR (i.e. utilities for each vessel shall not
have a common header system serving both headers). VENDOR shall specify the
quantities of nitrogen, air and water and pressure required for complete filter
replacement and black powder removal processes.

c) Standby filtration unit shall be kept at line pressure with sales gas to ensure they are
ready for change-over.

d) The changeover to active filter will be initiated by XXX-PLC-XXXX (Filtration System


JO/EWO

PLC) & HMI SGFS. Signal exchange table between HMI and PLC for interfacing with
YNP CCR for the controls & monitoring as mentioned under section 3.1 shall be
provided by VENDOR, after receipt of pre-alarms status of black powder high level
12/28/16
DATE

and/or high filter differential pressure from XXX-PLC-XXXX (Filtration System PLC).
NO.
REV

e) The PLC controller, back-up operator interface HMI, HMI server, local control panel
DISCIPLINE
ENGINEER will be housed in a Metering Building fully equipped with DC and AC power systems
VTN
and UPS with 8 hours battery back-up.
12/16
DATE:
PROJECT
ENGINEER 5.3 Material Selection
MGB
12/16
DATE: Metallic materials required for filters, piping and structural steels on the system shall be in
CERTIFIED
ADF
accordance with the applicable data sheets and SA material specifications

DATE: Materials shall be determined based on service, MDMT and LODMAT


CONSTRUCTION
AGENCY
External attachments welded directly to vessel components including stiffener, insulation
DATE: support and brackets shall have the same nominal chemical composition as the pressure
OPERATIONS
component.

DATE: 5.4 Mechanical Design


CONTROL NUMBER
VERIFICATION

VENDORs design of the SGFS shall incorporate the following:


EDSD

DATE:

a) The filter vessels shall be designed, fabricated, tested and inspected in accordance
BY:

with SAUDI ARAMCO Materials System Specification 32-SAMSS-004 and ASME


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

Boiler and Pressure Vessel Code Section VIII Division I or Division II and this
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

Functional Specification.
(DCC) NO. _____________________

b) The preferred design will be based on ease of fabrication, transportation to site,


FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 17


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
installation, operation and maintenance.

c) The cyclone portion shall be supplied with a collection chamber to allow discharge of
ADF
ENGG CERT

the separated and accumulated black powder particles. The cyclone portion shall be
designed with required valves and instruments for quick, safe and easy removal of
MGB

the accumulated black powder into a vacuum tanker.

d) The filtration portion shall be equipped with a fixed tube sheet mounted with high
capacity removable filter media cartridges with graded pore structure depth to trap
contaminant particles 1 micron and larger. Waste volume shall be minimized by
ISSUED FOR 90% REVIEW

using fully disposable media. Metallic parts shall be permanent (not disposable). The
contaminant loading downstream of filter system shall not exceed 1 micron particles.
DESCRIPTION

The filter media shall be 1 micron absolute rated.

e) Provision shall be made for water soaking of the black powder inside the vessels.
The nozzles shall be positioned such that they shall soak particles to avoid exposure
of Black Powder to air (cyclone sump and filter elements).

f) All vent valves on the vessels and interconnecting piping shall be connected to a
common header and routed to the filtration system limit. MOV vent valves shall be
equipped with safety interlocks to prevent valves from opening while there is
JO/EWO

pressure inside the vessel.

g) The filter elements shall be removable type in case of maintenance.


12/28/16
DATE

h) The period between filter cartridge changes due to clogging must be as long as
practically possible but shall not be less than six (6) months. The filter elements shall
NO.
REV

DISCIPLINE be designed with a minimum 2 year service life if the maximum differential design
ENGINEER
VTN pressure is not reached.
12/16
DATE:
PROJECT i) VENDOR shall design lifting attachments. VENDOR shall also provide detailed
ENGINEER
MGB
transportation, lifting and on site erection procedures. VENDOR shall provide data
12/16 sheets, process and mechanical design calculations for review and approval.
DATE:
CERTIFIED
VENDOR design calculations shall prove structural integrity of the vessel and its
ADF supports.
DATE: 5.5 Nozzles & Manways
CONSTRUCTION
AGENCY
a) Adequate maintenance access shall be provided for filter system layout to ensure
access to vessel internal parts, valves, relief valves, gauges etc.
DATE:
OPERATIONS
b) The vessels shall be provided with circular manways to facilitate inspection,
maintenance, and installation and removal of the vessel internals. The manways
DATE:
shall be fabricated per ASME Section VIII D1 and 32-SAMSS-004.
CONTROL NUMBER
VERIFICATION

c) Manways shall be accessible from the decks or platforms.


EDSD

DATE:

d) Manways and inspection openings shall be Blind Flange with Davit type. All
BY:

removable internals shall be able to pass through the manway. VENDOR shall
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

design the filter replacement operation where confined space entries into the vessels
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

would not be required.


(DCC) NO. _____________________

e) Minimum clear ways width of walking surfaces and access/egress of personnel for
FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 18


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
operation/maintenance purposes need to be as per SAES-B-054, section 4
requirements.
ADF
ENGG CERT

f) All nozzles shall be flanged. Threaded, socket welded, seal welded connections shall
not be used.
MGB

g) Nozzles and manways shall be attached by welding completely through the total
thickness of the shell/ head including any reinforcement.

h) Nozzles shall be designed in accordance with the requirements of ASME Section


ISSUED FOR 90% REVIEW

VIII, Div I or Div II and 32-SAMSS-004.


DESCRIPTION

i) Flanges shall be weld neck RFSF per ASME B16.5 for flanges up to 24 NPS and
ASME B16.47A for flanges above 24 NPS. Flanges larger than 26 shall comply
with SAUDI ARAMCO Standard drawing AD-036673, sheet 1, rev 16.

j) All flange bolt holes shall straddle vessel centerlines.

k) Inlet and outlet valves to the SGFS shall be designed with spectacle blinds.
5.6 Piping
JO/EWO

a) All interconnecting piping shall be designed in accordance with 01-SAMSS-010,


ASME B31.3 and Piping specification SAES-L-105 (Line Class 6CS1P) and other
applicable SAUDI ARAMCO Standards.
12/28/16
DATE

b) All pipe, pipe fittings and valve materials shall be suitable for sales gas service.
NO.
REV

DISCIPLINE
c) All valves shall be in accordance with SAES-L-108 and applicable 04-SAMSS. The
ENGINEER
VTN
sizes of valves shall be specified by VENDOR based on final filtration system piping
12/16 sizes.
DATE:
PROJECT
ENGINEER d) Trim for all Valves upstream of cyclone shall be of AISI 410 Stainless Steel.
MGB
12/16
DATE: e) Utility piping shall be sloped back towards the filtration system edge interface points.
CERTIFIED
ADF If sloping is not possible drain connections shall be supplied.
DATE:
CONSTRUCTION
f) The minimum drain size for the cyclone filter vessel shall be 8-inch. Single drain full
AGENCY bore ball valve shall be provided in the cyclone filter drain line.
DATE:
g) Installation of drain, vent, or sample connection valves shall be in accordance with
OPERATIONS
Standard Drawing AC-036045.

DATE: h) All vent lines on inlet piping, outlet piping and vessels shall be connected to the
CONTROL NUMBER

system blowdown line.


VERIFICATION
EDSD

i) Inlet and outlet piping shall be properly supported including the flanged connection
DATE:

between inlet piping and outlet piping connected to the filter vessels to prevent
BY:

binding of the flange connections for spectacle blinds when the filter vessels are out
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

of service.
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

j) Vendor shall consider in his design the external forces and moments at inlet and

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 19


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
outlet flanges as given in ATTACHMENT- I.
ADF
ENGG CERT

5.7 Instrumentation
MGB

a) VENDOR shall provide the SGFS with complete instrumentation devices required to
operate the online and standby filter vessels manually including:

Air Pressure at Filter Inlet


Nitrogen Pressure at Utility Header
ISSUED FOR 90% REVIEW

Utility Water Pressure at Utility Header


DESCRIPTION

Sales Gas Pressure at Filter Inlet


Sales Gas Outlet Header Pressure
Differential Pressure across Filter Elements
Black Powder Level in Sump of the Cyclone Vessel
Cyclone Vessel Sump High Level
Cyclone Vessel Sump High-High Level
JO/EWO

Pressure Relief Valve for each Vessel


12/28/16
DATE

b) All MOVs and instruments shall be provided with signal cabling up to and including
instrument explosion proof junction boxes. VENDOR shall provide power cables and
NO.
REV

DISCIPLINE
conduits to the MOVs and will terminate them at the edge of filtration system .
ENGINEER
VTN
12/16
c) The instrumentation devices will be monitored / controlled from a dedicated PLC/HMI
DATE:
PROJECT
server to be located in the new Local Control Building. All significant filtration system
ENGINEER data points shall be transmitted back to YNP CCR for remote monitoring of filter
MGB
12/16
status, DPI across filter and control of MOVs (refer section 3.1). The point of
DATE:
interface to YNP CCR is through the Engineering Workstation Server to be provided
CERTIFIED
ADF by Sales Gas Metering Vendor and to be installed in the same Local Control
Building. Hardware or software and system configuration required to communicate
DATE:
CONSTRUCTION XXX-PLC-XXXX (Filtration System PLC) with Engineering Workstation Server and
AGENCY
YNP CCR shall be vendor scope. Vendor shall also update the Engineering
Workstation to provide Graphic Displays for SGFS.
DATE:
OPERATIONS
d) Signals that will be sent to YNP CCR shall include:
DATE:
Status of control mode (local or remote)
CONTROL NUMBER
VERIFICATION

Status of each filter vessel and position and control of the MOVs
EDSD

DATE:

Pressure drop across the on-stream filter vessel


BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,

Pressure inside each filter vessel


THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

Level of black powder in each filter vessel (cyclone portion)

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 20


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
On-stream duration since the last time that black powder was drained for each
filter vessel
ADF
ENGG CERT

On-stream duration since the last filter element was replaced for each filter
MGB

vessel (by the PLC)

Predicted remaining on-stream duration until the next black powder drain for
each filter vessel (by the PLC)

Predicted remaining on-stream duration until next filter element replacement for
ISSUED FOR 90% REVIEW

each filter vessel (by the PLC)


DESCRIPTION

e) VENDOR shall supply the HMI as part of filtration system for operation and
maintenance use during maintenance, filter replacement, cleaning and sequencing.
HMI shall be with 20-inch color touch screen display.

f) HMI Graphics

MOVs shall show green when open, red when closed and yellow when traveling.

Process lines shall be color coded GREEN when open and flowing and RED when
JO/EWO

closed and not flowing.

The color of water lines shall be BLUE, air lines WHITE and NITROGEN lines
12/28/16
DATE

CYAN or PURPLE.
NO.
REV

Each vessel, MOV, and instrument shall be shown with their specific tag number
A

DISCIPLINE
ENGINEER
VTN
5.8 Electrical
12/16
DATE:
PROJECT
The VENDOR shall provide and install electrical distribution system for the filtration
ENGINEER system and associated works that includes, but not limited to:
MGB
12/16
DATE:
CERTIFIED
ADF Power for the various equipment and appurtenances will be provided at 480VAC, 60
Hz, 3 PH or 230VAC, 60 Hz, 1 PH.
DATE:
CONSTRUCTION
AGENCY

Vendor shall provide the following but not limited to the following:
DATE:
OPERATIONS
Grounding for, equipment, steel platforms as per SAES-P-111.

DATE: Task lightings and power receptacles.


CONTROL NUMBER
VERIFICATION

All electrical installation work shall be carried out in compliance with the latest
EDSD

National Electrical Code (NEC) and applicable Saudi Aramco Engineering


DATE:

Standards SAES-P-104, SAES-P-111 and SAES-P-123.


BY:
REVISIONCERTIFICATION


APPROVAL/CERTIFICATION REQUIREMENTS,

Filtration System lighting fixtures shall operate on 230VAC, 60 Hz, 1 PH.


THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

Vendor shall provide suitable termination cabinets in the filtration system for
terminating power required for MOVs instruments, equipment and appurtenances.
FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 21


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
The VENDOR shall provide and install required power cables, conduits, cable
glands and other accessories for the various filtration system instruments,
ADF
ENGG CERT

equipment and appurtenances up to termination junction boxes.


MGB

All electrical materials used with in the filtration system shall suitable for area
classification Class 1 Zone 2 T3.

5.9 Fire Proofing/Fire Protection


ISSUED FOR 90% REVIEW

Filter vessels are designated as Fire Hazardous equipment. Fire proofing shall meet the
requirements of SAES-B-006. Accordingly, VENDOR shall furnish fire hazardous
DESCRIPTION

classification drawing(s) for the SGFS as per SAES-B-006 requirements.

CONTRACTOR shall submit a fire protection plan in accordance with SAES-B-019


showing the location and types of fire extinguishers to be provided for final approval by
the Chief Fire Prevention Engineer or his representative. As a minimum CONTRACTOR,
shall provide two (2) two-wheeled, cart-type dry chemical, 68 kg size extinguishers; one
located at each end of the filter system. In addition, CONTRACTOR, shall provide hand-
type portable extinguishers which shall be mounted in easily accessible locations at
grade and on first level operating decks near access stairs.
JO/EWO

5.10 Ladders, Cages, Platforms and Vehicle Barriers


12/28/16
DATE

a) The ladders, cages, platforms and stairs shall meet the requirements of SAES-B-
054, PIP-STF05501, PIP-STF05511, PIP-STF05520 and PIP-STF05530.
NO.
REV

DISCIPLINE
b) The minimum width of clear area on platforms shall be 760mm, except for the
ENGINEER
VTN
unobstructed width of platforms in front of manways which shall not be less than
12/16 900mm.
DATE:
PROJECT
ENGINEER c) Platforms and stairs shall be made of galvanized steel bar grating. The galvanized
MGB
12/16
steel bar grating shall have a non-slip design.
DATE:
CERTIFIED
ADF d) Vehicle barriers shall be provided at the corners of the filter system structure, in front
of the SGFS utility connections and the corners of the outside shelter for HMI-2 and
DATE:
CONSTRUCTION
other areas designated by Loss Prevention Department.
AGENCY
5.11 Structural
DATE:
a) The gas filtering system structural steelworks shall be designed in accordance with
OPERATIONS
SAES-M-001, Structural Design Criteria for Non Building structures and 12-SAMSS-
007, Fabrication of Structural & Miscellaneous steel.
DATE:
CONTROL NUMBER

b) The filtration system framework shall be designed for all applicable loads/load
VERIFICATION

combinations as outlined in SAES-M-001. In addition, the framework shall be


EDSD

designed to withstand the additional stresses induced during shipment, installation,


DATE:

and hydrostatic testing with the vessels full of water without imposing undue
BY:

distortion and strain to the piping/valves/instruments supported there upon.


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

c) Seismic loads shall be as per ASCE-7 and SAES-A-112


(DCC) NO. _____________________

d) Wind loads shall be as per SAES-A-112, ASCE-7, ASCE 40262 and SABP-M-006.

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 22


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Wind load on steel structure shall be for open frame structures.

e) Suitable lifting lugs shall be provided on the vessels. VENDOR shall design the base
ADF
ENGG CERT

framework for actual weight of installed instruments/equipment. The framework and


lifting lugs shall also withstand loads/ stresses during erection/installation of the
MGB

system. VENDOR shall show the location of center of gravity on the framework for
total lifted weight of the system on the project design drawings. VENDOR shall
provide location of anchor points and loading detail for design of the foundation.

f) VENDOR shall submit all calculations to Company Representative for approval.


ISSUED FOR 90% REVIEW

g) Anchor bolts shall be designed and installed as per 12-SAMSS-007, SAES-M-001,


DESCRIPTION

SAES-Q-005 and appendix D of ACI 318-2008. Anchor bolt type and details shall
conform to SAUDI ARAMCO Standard Drawing AB-036322 Sht. 001. All anchor bolt
patterns to be located within a minimum tolerance of 1.5mm (1/16) both directions
within each pattern.

h) VENDOR shall supervise the detail design of the foundation for the filtration system
based on support reactions for all possible load combinations as outlined in SAES-
M-001 including, but not limited to, when filter vessels are full of water during
hydrostatic testing, when filters are empty and when they are full of black powder.
JO/EWO

i) Lifting eyes shall be provided to ease turning spectacle blinds.


12/28/16
DATE

j) Hot dip galvanizing Coating is required as per 12-SAMSS-007


5.12 Fabrication
NO.
REV

DISCIPLINE
ENGINEER
VTN
a) Vendor shall comply fabrication requirements and PWHT in accordance with Saudi
12/16 Aramco standard 32-SAMSS-004. Welding requirements shall comply Saudi Aramco
DATE:
PROJECT
Engineering standard SAES-W-010, SAES-W-011 and SAES-W-012
ENGINEER
MGB
12/16
b) Fabrication shall not begin until the Contractor has received written approval from
DATE:
CERTIFIED
Company Representative of the detailed design and drawings, the Inspection and
ADF Test Plan (ITP) and WPS, PQR weld map, weld description sheet.
DATE:
CONSTRUCTION
c) All cold formed heads and toriconical transition sections shall be stress-relieved or
AGENCY
normalized before attachment to the shell.
DATE:
OPERATIONS
d) Hot-formed vessel sections shall be normalized and the normalizing treatment shall
be performed separately and not as part of the hot-forming process.
DATE: e) The qualification of welding procedures and qualification of welders and welding
CONTROL NUMBER

operators shall be in accordance with the applicable Code. Certified welding


VERIFICATION

procedures, complete with qualification test records, shall be submitted for review
EDSD

and approval by SAUDI ARAMCO Consulting Services Department (CSD) prior to


DATE:

fabrication as per requirements of SAES-W-010 clause 7.0 for WPS, PQR, weld map
BY:

and weld description sheet.


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

f) Fabrication tolerances shall be in accordance with ASME Code and PIP VEFV1100.
(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 23


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
6 INSPECTION AND TESTING

6.1 Pressure Testing


ADF
ENGG CERT

a) After fabrication of the vessels and piping are completed and the vessel stress-
MGB

relieved, hydrostatic test shall be conducted in accordance with the requirements of


ASME Section VIII Division I and 32-SAMSS-004, para 16.3 for the vessels, ASME
B31.3 for piping. The hydrostatic test pressure shall be based on the maximum
allowable working pressure.
ISSUED FOR 90% REVIEW

b) General requirements for hydrostatic testing shall be in accordance with SAES-A-004


and SAES-A-007
DESCRIPTION

c) The minimum test water temperature and metal temperature shall be 17C.

d) After the final hydrostatic test, vessels shall be immediately drained, dried completely
and then sealed for internal corrosion protection.

VENDOR shall prepare the procedure for the Factory Acceptance Test (FAT) and Site
Acceptance Test (SAT) for the PLC (including control panel and local and remote HMIs), PLC
JO/EWO

software which shall be approved by Yamama Cement Company at least 30 days prior to the
schedule FAT or SAT dates. VENDOR shall clearly state his plan for performing Factory
Acceptance Test (FAT) and Site Acceptance Test (SAT) in his technical proposal his.
12/28/16
DATE

7 GUARANTEE & PERFORMANCE TEST


NO.
REV

DISCIPLINE
ENGINEER
a) VENDOR shall guarantee the complete gas filtration system and accessories meet the
VTN
requirements of this specification.
12/16
DATE:
PROJECT
ENGINEER b) VENDOR shall conduct Site Acceptance Test (SAT) on completion of the commissioning
MGB of each system to prove the performance of the filtration system meets the requirements of
DATE:
12/16
this specification. VENDOR shall sample black powder upstream and downstream of each
CERTIFIED filter system for a period of one (1) month to ensure that VENDORs design meets the
ADF
performance criteria and projected filter life of 6 months before replacement.
DATE:
CONSTRUCTION
AGENCY
8 TRAINING
DATE:
OPERATIONS
Vendor shall prepare material and perform site training for an estimate 30 operations and
maintenance personnel.
DATE:
Training shall consists of reviewing the P&ID and logic diagrams, operation of the filter system
CONTROL NUMBER
VERIFICATION

(including explanation of HMI parameters, trends, alarms, modes of operation, etc),


maintenance requirements for the filter system (including steps for draining and filter element
EDSD

replacement, special tools required, spare parts requirements, troubleshooting, individual


DATE:

instrument preventative maintenance schedules, etc), and PLC special training for Proponent
BY:

controls engineers including PLC software architecture, logic, troubleshooting.


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 24


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
8.1 SURFACE PREPARATION AND PAINTING

8.1.1 Surface Preparation


ADF
ENGG CERT

Sharp edges including all welds, weld spatters and other projections anywhere on
MGB

the surface shall be ground smooth. Edges shall be with 1/8 minimum radius.

The surface preparation shall be as per SAES-H-100 and SAES-H-101.

8.1.2 Painting
ISSUED FOR 90% REVIEW

Painting and coating requirements for Vessels shall be in accordance with


DESCRIPTION

SAES-H-101, APCS-1A. The painting & coating requirements for piping,


support structures, electrical equipment, instruments etc. shall be in accordance
with SAES-H-100, SAES-H-101, and SAES-H-101V.

Safety identification and colors shall comply with SAES-B-067. The water, steam,
air, and nitrogen lines shall be marked and color-coded as specified in SAES-L-
310.

8.2 NAMEPLATES AND STAMPINGS


JO/EWO

ASME name plate stamping and other requirements for Vessels shall comply with
12/28/16
DATE

Saudi Aramco standard 32-SAMSS-004, section 17.

Vendor shall provide SS tags (showing Purchasers tag numbers) and name
NO.
REV

DISCIPLINE
plates attached to each piece of equipment including boxes, instruments and
ENGINEER
VTN
mechanical components as specified. All instruments shall have SS tags with full device
12/16
tag number engraved and affixed to the device.
DATE:
PROJECT
ENGINEER
MGB
9 DATA REQUIREMENT
12/16
DATE:
CERTIFIED 9.1.1 All documents required in SAUDI ARAMCO Non-Material Requirements (NMR)
ADF
forms and all documents and drawings listed below shall be provided for review
DATE: and approval by Yamama Cement Company.
CONSTRUCTION
AGENCY
9.1.2 CONTRACTOR and VENDOR shall be responsible for submittal of complete
DATE: documentation required for design, engineering, material procurement, fabrication,
OPERATIONS installation and testing of the filtration system which may require deliverables not
limited to the list below. All CAD drawings shall be in Autocad Format using SAUDI
DATE: ARAMCO drawing border frame including, but not limited to:
CONTROL NUMBER
VERIFICATION

9.1.3 Estimated filter system maintenance costs for one year assuming 1 draining and 1
EDSD

filter element replacement each filter unit (i.e. maintenance costs assuming both
filter units require draining and filter replacement over a one year period). Vendor
DATE:
BY:

shall provide details of the cost estimate broken down into labor description and
numbers, equipment description and numbers, number of days to drain each
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE

vessel, number of days to replace filter elements per vessel, quantity of


A

consumables (Nitrogen & water), and spare parts used (gaskets, filter elements)
(DCC) NO. _____________________

(with Technical Proposal & Detail Design)

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 25


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
9.1.4 P&ID (with Technical Proposal & Detail Design)

9.1.5 System Layout Drawing (with Technical Proposal & Detail Design)
ADF
ENGG CERT

9.1.6 System General Arrangement (with Technical Proposal & Detail Design)
MGB

9.1.7 Footprint drawing (with Technical Proposal & Detail Design)

9.1.8 Piping Isometrics (with Detail Design)


ISSUED FOR 90% REVIEW

9.1.9 Vessel Outline Drawing (with Technical Proposal & Detail Design)
DESCRIPTION

9.1.10 Vessel internals detail including filter clusters (with Technical Proposal & Detail
Design)

9.1.11 Filter Specification (with Technical Proposal & Detail Design)

9.1.12 Line Designation Table (with Detail Design)

9.1.13 Safety Instruction Sheets (with Detail Design)

9.1.14 Vessel Calculations (basic with Technical Proposal & Detail Design)
JO/EWO

9.1.15 Fire Risk Assessment (with Detail Design)


12/28/16
DATE

9.1.16 Electrical Area Classification (with Detail Design)


NO.
REV

9.1.17 Valve Schedule (with Detail Design)


DISCIPLINE
ENGINEER
VTN
9.1.18 Valve Data Sheets (with Detail Design)
12/16
DATE:
PROJECT
ENGINEER 9.1.19 Complete BOM (with Detail Design)
MGB
12/16
DATE: 9.1.20 Maintenance Procedure (with Detail Design)
CERTIFIED
ADF
9.1.21 Operating Procedure (with Detail Design)
DATE:
CONSTRUCTION
AGENCY 9.1.22 HAZOP reports (with Detail Design)

DATE: 9.1.23 Individual Equipment Specifications (with Detail Design)


OPERATIONS

9.1.24 Structural calculations, which include base plate, anchor bolt size and numbers.
DATE: Calculations shall be submitted as hard copy and searchable pdf file. Electronic file
of structural analysis software shall be submitted (with Detail Design)
CONTROL NUMBER
VERIFICATION
EDSD

9.1.25 Connections details and calculations (with Detail Design)


DATE:
BY:

9.1.26 Structural frame drawings (with Detail Design)


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

9.1.27 Platform drawings (with Detail Design)


OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

9.1.28 Support reactions as indicated in section 6.9 (with Detail Design)

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 26


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
9.1.29 For instrumentation design, should be per SAES-J-005, SAES-A-202, SAEP-334
(with Detail Design)
ADF
ENGG CERT

9.1.30 For electrical Design, should be per SAES-A-202, SAEP-334 and all basic
electrical design drawings and documents. (with Detail Design)
MGB

9.1.31 Filtration System layout drawing, piping plans and elevations, pipe stress analysis,
ASME pressure vessel calculations, quality plan, ITP and ladders& platform
drawings.
10 PREPARATION FOR SHIPMENT
ISSUED FOR 90% REVIEW
DESCRIPTION

Shipping preparation and packing requirements for filters and process piping shall comply with
32-SAMMS-004, section 19.
All Carbon Steel unmachined surfaces shall be painted and all machined surfaces coated with
a suitable rust preventative coating before shipment. No internal/ external painting or rust
preventative coating should be used on the stainless steel parts.
Spare parts and parts shipped loose shall be tagged with the vendors part numbers or item
numbers for easy identification.
The vendor shall protect his equipment during transportation, handling and storage against
outdoor conditions. Vendor shall provide and install all necessary bracing, supports, saddles
etc. to protect vessels from damage during loading, shipment and unloading. Preservatives for
JO/EWO

corrosion protection shall be used. The vendor shall clearly indicate on the shipping cases or
other packages the required storage conditions.
Vendor shall include along with the shipment of GOODS, signed release form (by COMPANY
12/28/16
DATE

authorized inspector).
NO.
REV

DISCIPLINE
ENGINEER 11 FIELD ERECTION
VTN
12/16
DATE:
PROJECT a) All components, including valves etc, shall be fit up preassembled (where possible) in
ENGINEER
MGB
the shop before shipping. The components may be disassembled for shipment by the
12/16 vendor. If disassembly is required, all components shall be labeled or marked by the
DATE:
CERTIFIED vendor for ease of reassembly on site. Vendor shall list these components and provide
ADF complete erection drawings which denote the piece number and location of each
DATE:
piece or section. The erection instructions shall be a clear step by step procedure
CONSTRUCTION reflecting the order of priority the pieces must be put together. The system shall be
AGENCY
provided in minimum number of (flanged) sections possible to minimize field welding.
DATE:
OPERATIONS b) Vendor shall design filtration system so that minimum site work and welding is
required. Vendor shall identify the site activities upfront in the project and provide field
execution plan for review and approval.
DATE:
CONTROL NUMBER
VERIFICATION

c) All components (including pipes, structural etc) of the package and auxiliaries will
EDSD

come with final paint (as required by Saudi Aramco standards and site conditions).
Field painting shall be limited to touch-up only, where damaged during transportation
DATE:

or erection.
BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

d) Vendor shall obtain all necessary permits per OWNERs site requirements including,
OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

but not limited to:


(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 27


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
All necessary hot and cold work permits required for the work
Confined space entry permits.
ADF
ENGG CERT

e) Vendor shall be responsible for the mechanical completeness and turn over of the unit
MGB

in full compliance with the Standards, Codes, and Specifications listed in this
document.

12 SPARE PARTS DATA PACKAGE


ISSUED FOR 90% REVIEW

During detail design, CONTRACTOR and VENDOR shall recommend a complete original
Spare Parts Data Package (SPDP) in accordance with SAUDI ARAMCO Engineering
DESCRIPTION

Procedure SAEP-3102.

13 NOZZLE LOADS

Allowable nozzle loads of flanges shall be as per APPENDIX-B


JO/EWO
12/28/16
NO. DATE
REV

DISCIPLINE
ENGINEER
VTN
12/16
DATE:
PROJECT
ENGINEER
MGB
12/16
DATE:
CERTIFIED
ADF

DATE:
CONSTRUCTION
AGENCY

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 28


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
14 APPENDIX-A
ADF
ENGG CERT
MGB

APPENDIX-A DEVIATION LIST

The VENDOR shall state in the following list all deviations to this document and Referenced
Standards, Specifications, Forms, Drawings and Codes. If no exception is taken to a specific
ISSUED FOR 90% REVIEW

document, then the VENDOR is deemed by the COMPANY to be in full compliance with that
Document
DESCRIPTION

DETAILED DEVIATION / EXCEPTION LIST


Exception / Document Reference / VENDOR Exception / Deviation
Deviation Paragraph
Number
JO/EWO
12/28/16
NO. DATE
REV

DISCIPLINE
ENGINEER
VTN
12/16
DATE:
PROJECT
ENGINEER
MGB
12/16
DATE:
CERTIFIED
ADF

DATE:
CONSTRUCTION
AGENCY

DATE:
OPERATIONS

DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 29


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021
OF A
RIYADH SAUDI ARABIA JO: 30
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
15 APPENDIX-B
ADF
ENGG CERT

APPENDIX-B NOZZLE LOADS


MGB

Nozzle ASME Radial Circum. Long. Circum. Long. Torsional


NPS B16.5 Force Shear Shear Moment Moment Moment
(in.) Rating (kgf) (kg f) (kgf) (kgf-m) (kgf-m) (kgf-m)
2 150# 275 275 275 26 26 26
ISSUED FOR 90% REVIEW

300# 325 325 325 26 26 26


600# 370 370 370 34 34 34
DESCRIPTION

3 150# 370 370 370 60 60 60


300# 430 430 430 60 60 60
600# 490 490 490 80 80 80
4 150# 490 490 490 110 110 110
300# 575 575 575 110 110 110
600# 655 655 655 150 150 150
6 150# 735 735 735 295 295 295
300# 860 860 860 350 350 350
600# 1080 1080 1080 420 420 420
JO/EWO

8 150# 980 980 980 550 550 550


300# 1145 1145 1145 580 580 580
600# 1310 1310 1310 675 675 675
12/28/16
DATE

10 150# 1230 1230 1230 920 920 920


300# 1430 1430 1430 1215 1215 1215
NO.
REV

600# 1635 1635 1635 1405 1405 1405


DISCIPLINE
ENGINEER
12 150# 1475 1475 1475 1265 1265 1265
VTN 300# 1720 1720 1720 1360 1360 1360
12/16 2150 2150
DATE: 600# 1960 1960 1960 2150
PROJECT
ENGINEER
14 150# 1720 1720 1720 1435 1435 1435
MGB 300# 2000 2000 2000 1650 1650 1650
DATE:
12/16 600# 2650 2650 2650 2640 2640 2640
CERTIFIED 16 150# 1960 1960 1960 1755 1755 1755
ADF
300# 2290 2290 2290 2285 2285 2285
DATE: 600# 2780 2780 2780 2595 2595 2595
CONSTRUCTION
AGENCY 18 150# 2200 2200 2200 2070 2070 2070
300# 2575 2575 2575 3000 3000 3000
DATE: 600# 3480 3480 3480 4700 4700 4700
OPERATIONS 20 150# 2450 2450 2450 2355 2355 2355
300# 2860 2860 2860 3610 3610 3610
DATE: 600# 3780 3780 3780 5860 5860 5860
CONTROL NUMBER

24 150# 2940 2940 2940 2800 2800 2800


VERIFICATION

300# 3435 3435 3435 4940 4940 4940


EDSD

600# 4025 4025 4025 8180 8180 8180


DATE:
BY:

***** END OF SPECIFICATION *****


REVISIONCERTIFICATION

APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


A

(DCC) NO. _____________________

FUNCTIONAL SPECIFICATION DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO.
REVISION

YAMAMA GAS METERING STATION- FILTRATION SYSTEM DOC 30


FUEL SUPPLY TO YAMAMA NEW PLANT XXX A SK-A-YCC-021