Sie sind auf Seite 1von 14

SACMAG DE MEXICO, S.A. DE C.V.

NUEVA YORK No 310


COL. NAPOLES
MEXICO, D.F. C.P. 03800
(55) 5687 3666

Job Name : prueba


Building :
Location :
System :
Contract :
Data File : prueba AREA 1.wxfprueba Area .WXF

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
SACMAG DE MEXICO, S.A. DE C.V. Page 1
prueba Date

Pump Data: Demand:


P1 - Pump Churn Pressure : 139.7 D1 - Elevation : 9.935
P2 - Pump Rated Pressure : 127 D2 - System Flow : 296.423
P2 - Pump Rated Flow : 2000 D2 - System Pressure : 45.298
P3 - Pump Pressure @ Max Flow : 82.55 Hose ( Demand ) : _______
P3 - Pump Max Flow : 3000 D3 - System Demand : 296.423
Safety Margin : 94.401

150
P1
140

130 P2

P 120

R 110

E 100

S 90 P3
S 80

U 70

R 60

E 50 D2

40

30

20

10 D1

300 600 900 1200 1500 1800 2100 2400 2700


FLOW ( N ^ 1.85 )

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Diagram
SACMAG DE MEXICO, S.A. DE C.V. Page 2
prueba Date

23.8
EQ01
DP01

23.2 71.4 121.4 147.9 147.9 147.9 147.9 296.4 291 282.3 273.5 270.3 270.2 273.6 281 296.4
35 36 37 38 39 40 41 42 43 44 45 46 47 48 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 BOR
TOR
47.2 96 147.9 147.9 147.9 147.9 147.9 296.4 286.7 277.6 271.5 269.4 271.6 276.2 296.4

296.4 296.4
TOR 31 32 PUMP
296.4

0.6 0.6 48.3 96.8 148.5 148.5 148.5 148.5 148.5


35 34 33 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0.6 24.4 72.3 122 148.5 148.5 148.5 148.5

5.4 9.7 18.9 24.9 27 24.9 20.2 10 4.6 10


17 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 30
5.4 14.2 22.9 26.1 26.3 22.8 15.4 4.6 4.6 15.4
| 291| 5.4
| 4.3|
18 50

| 286.7
| 9.7
| 4.5|
19 51

| 282.3
| 14.2
| 4.7|
20 52

| 277.6
| 4.1 4.1
21 68 69 53
4.1
| 273.5 | 22.9
| 2 2 |
22 70 71 54
2
| 271.5 | 24.9
| 1.3 1.3|
23 72 73 55
1.3
| 270.3
| 0.8
24 56

0.7
57 25

| 26.3
| 1.4 1.4
58 74 75 26
1.4
| 24.9
| 2.1
59 27

| 22.8| 273.6

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Diagram
SACMAG DE MEXICO, S.A. DE C.V. Page 3
prueba Date

| 2.6|
60 28

| 20.2
| 4.8
61 76 29
4.8
| 15.4
| 5.4
62 67
|
| 10 | 10
| 5.4
63 66

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
SACMAG DE MEXICO, S.A. DE C.V. Page 4
prueba Date

Fitting Legend
Abbrev. Name 1 1 1 2 2 3 3 4 5 6 8 10 12 14 16 18 20 24

E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61


T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121

Units Summary

Diameter Units Inches


Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch

Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
SACMAG DE MEXICO, S.A. DE C.V. Page 5
prueba Date

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

DP01 21.94 8 8.85 na 23.8 0.2 119 7.0


EQ01 22.94 9.49 na
35 22.94 K = K @ EQ01 9.49 na 23.8
36 22.94 K = K @ EQ01 9.66 na 24.0
37 22.94 K = K @ EQ01 9.8 na 24.18
38 22.94 K = K @ EQ01 10.14 na 24.6
39 22.94 K = K @ EQ01 10.81 na 25.39
40 22.94 K = K @ EQ01 11.82 na 26.56
41 22.94 13.29 na
42 22.94 14.76 na
43 22.94 16.43 na
44 22.94 18.06 na
45 22.94 19.74 na
46 22.94 21.34 na
47 22.94 22.5 na
48 22.94 32.92 na
15 22.94 32.98 na
16 22.94 33.13 na
17 22.94 33.43 na
18 22.94 33.47 na
19 22.94 33.49 na
20 22.94 33.52 na
21 22.94 33.54 na
22 22.94 33.66 na
23 22.94 33.69 na
24 22.94 33.71 na
25 22.94 33.74 na
26 22.94 33.76 na
27 22.94 33.78 na
28 22.94 33.81 na
29 22.94 33.93 na
30 22.94 34.0 na
BOR 22.94 34.29 na
TOR 23.02 34.36 na
31 1.02 44.69 na
32 1.02 44.72 na
PUMP 0.0 45.3 na
34 22.94 9.49 na
33 22.94 9.49 na
1 22.94 K = K @ EQ01 9.49 na 23.8
2 22.94 K = K @ EQ01 9.54 na 23.85
3 22.94 K = K @ EQ01 9.68 na 24.03
4 22.94 K = K @ EQ01 10.04 na 24.47
5 22.94 K = K @ EQ01 10.71 na 25.27
6 22.94 K = K @ EQ01 11.74 na 26.46
7 22.94 13.22 na
8 22.94 14.69 na
9 22.94 16.38 na
10 22.94 18.08 na
11 22.94 19.71 na
12 22.94 21.32 na
13 22.94 22.49 na
14 22.94 23.19 na
49 22.94 33.69 na
50 22.94 33.69 na
51 22.94 33.69 na
52 22.94 33.69 na
53 22.94 33.7 na
54 22.94 33.7 na
55 22.94 33.71 na
56 22.94 33.72 na
57 22.94 33.73 na

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Summary - Standard
SACMAG DE MEXICO, S.A. DE C.V. Page 6
prueba Date

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

58 22.94 33.74 na
59 22.94 33.74 na
60 22.94 33.75 na
61 22.94 33.76 na
62 22.94 33.76 na
63 22.94 33.76 na
64 22.94 33.76 na
65 22.94 34.0 na
66 22.94 34.0 na
67 22.94 34.0 na
68 22.94 33.59 na
69 22.94 33.6 na
70 22.94 33.68 na
71 22.94 33.68 na
72 22.94 33.7 na
73 22.94 33.7 na
74 22.94 33.75 na
75 22.94 33.75 na
76 22.94 33.93 na

The maximum velocity is 13.04 and it occurs in the pipe between nodes 6 and 7

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
SACMAG DE MEXICO, S.A. DE C.V. Page 7
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

DP01 23.80 1.049 1T 5.0 1.000 8.851 K Factor = 8.00


to 120.0 0.0 5.000 -0.433
EQ01 23.8 0.1795 0.0 6.000 1.077 Vel = 8.84
0.0
23.80 9.495 K Factor = 7.72
35 23.19 2.157 2T 24.613 7.300 9.495 K Factor @ node EQ01
to 120.0 0.0 24.613 0.0
36 23.19 0.0051 0.0 31.913 0.163 Vel = 2.04
36 24.01 2.157 0.0 7.300 9.658 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
37 47.2 0.0190 0.0 7.300 0.139 Vel = 4.14
37 24.17 2.157 0.0 8.520 9.797 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
38 71.37 0.0408 0.0 8.520 0.348 Vel = 6.27
38 24.60 2.157 0.0 9.330 10.145 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
39 95.97 0.0708 0.0 9.330 0.661 Vel = 8.43
39 25.39 2.157 0.0 9.330 10.806 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
40 121.36 0.1092 0.0 9.330 1.019 Vel = 10.66
40 26.56 2.157 0.0 9.330 11.825 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
41 147.92 0.1574 0.0 9.330 1.469 Vel = 12.99
41 0.0 2.157 0.0 9.290 13.294
to 120.0 0.0 0.0 0.0
42 147.92 0.1576 0.0 9.290 1.464 Vel = 12.99
42 0.0 2.157 0.0 10.630 14.758
to 120.0 0.0 0.0 0.0
43 147.92 0.1576 0.0 10.630 1.675 Vel = 12.99
43 0.0 2.157 0.0 10.350 16.433
to 120.0 0.0 0.0 0.0
44 147.92 0.1575 0.0 10.350 1.630 Vel = 12.99
44 0.0 2.157 0.0 10.670 18.063
to 120.0 0.0 0.0 0.0
45 147.92 0.1575 0.0 10.670 1.681 Vel = 12.99
45 0.0 2.157 0.0 10.120 19.744
to 120.0 0.0 0.0 0.0
46 147.92 0.1575 0.0 10.120 1.594 Vel = 12.99
46 0.0 2.157 0.0 7.410 21.338
to 120.0 0.0 0.0 0.0
47 147.92 0.1575 0.0 7.410 1.167 Vel = 12.99
47 0.0 2.157 1T 12.307 53.820 22.505
to 120.0 0.0 12.307 0.0
48 147.92 0.1575 0.0 66.127 10.417 Vel = 12.99
48 0.0 4.26 0.0 10.550 32.922
to 120.0 0.0 0.0 0.0
15 147.92 0.0058 0.0 10.550 0.061 Vel = 3.33
15 148.50 4.26 0.0 7.100 32.983
to 120.0 0.0 0.0 0.0
16 296.42 0.0207 0.0 7.100 0.147 Vel = 6.67

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 8
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

16 0.0 6.357 2E 35.205 67.100 33.130


to 120.0 0.0 35.205 0.0
17 296.42 0.0030 0.0 102.305 0.302 Vel = 3.00
17 -5.40 6.357 0.0 12.770 33.432
to 120.0 0.0 0.0 0.0
18 291.02 0.0028 0.0 12.770 0.036 Vel = 2.94
18 -4.29 6.357 0.0 7.130 33.468
to 120.0 0.0 0.0 0.0
19 286.73 0.0028 0.0 7.130 0.020 Vel = 2.90
19 -4.47 6.357 0.0 9.960 33.488
to 120.0 0.0 0.0 0.0
20 282.26 0.0027 0.0 9.960 0.027 Vel = 2.85
20 -4.70 6.357 0.0 9.950 33.515
to 120.0 0.0 0.0 0.0
21 277.56 0.0026 0.0 9.950 0.026 Vel = 2.81
21 -4.06 6.357 2E 35.205 12.090 33.541
to 120.0 0.0 35.205 0.0
22 273.5 0.0025 0.0 47.295 0.120 Vel = 2.76
22 -1.96 6.357 0.0 12.950 33.661
to 120.0 0.0 0.0 0.0
23 271.54 0.0025 0.0 12.950 0.033 Vel = 2.74
23 -1.26 6.357 0.0 6.970 33.694
to 120.0 0.0 0.0 0.0
24 270.28 0.0024 0.0 6.970 0.017 Vel = 2.73
24 -0.84 6.357 0.0 9.960 33.711
to 120.0 0.0 0.0 0.0
25 269.44 0.0025 0.0 9.960 0.025 Vel = 2.72
25 0.72 6.357 0.0 9.940 33.736
to 120.0 0.0 0.0 0.0
26 270.16 0.0024 0.0 9.940 0.024 Vel = 2.73
26 1.40 6.357 0.0 9.970 33.760
to 120.0 0.0 0.0 0.0
27 271.56 0.0025 0.0 9.970 0.025 Vel = 2.75
27 2.07 6.357 0.0 9.960 33.785
to 120.0 0.0 0.0 0.0
28 273.63 0.0026 0.0 9.960 0.026 Vel = 2.77
28 2.56 6.357 2E 35.205 10.880 33.811
to 120.0 0.0 35.205 0.0
29 276.19 0.0026 0.0 46.085 0.119 Vel = 2.79
29 4.81 6.357 1E 17.603 8.390 33.930
to 120.0 0.0 17.603 0.0
30 281.0 0.0027 0.0 25.993 0.069 Vel = 2.84
30 15.42 6.357 2E 35.205 61.860 33.999
to 120.0 0.0 35.205 0.0
BOR 296.42 0.0030 0.0 97.065 0.287 Vel = 3.00
BOR 0.0 6.357 1T 37.72 0.080 34.286
to 120.0 0.0 37.720 -0.035
TOR 296.42 0.0030 0.0 37.800 0.112 Vel = 3.00

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 9
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

TOR 0.0 6.357 5E 88.014 144.430 34.363


to 120.0 1T 37.72 125.734 9.528
31 296.42 0.0030 0.0 270.164 0.797 Vel = 3.00
31 0.0 8.249 1T 41.108 3.630 44.688
to 120.0 0.0 41.108 0.0
32 296.42 0.0008 0.0 44.738 0.037 Vel = 1.78
32 0.0 10.42 11E 292.823 201.050 44.725
to 120.0 0.0 292.823 0.442
PUMP 296.42 0.0003 0.0 493.873 0.131 Vel = 1.12
0.0
296.42 45.298 K Factor = 44.04
System Demand Pressure 45.298
Safety Margin 94.401
Continuation Pressure 139.699
35 0.61 2.157 1T 12.307 0.580 9.495
to 120.0 0.0 12.307 0.0
34 0.61 0.0 0.0 12.887 0.0 Vel = 0.05
34 0.0 4.26 0.0 10.540 9.495
to 120.0 0.0 0.0 0.0
33 0.61 0.0 0.0 10.540 0.0 Vel = 0.01
33 0.0 2.157 1T 12.307 0.580 9.495
to 120.0 0.0 12.307 0.0
1 0.61 0.0 0.0 12.887 0.0 Vel = 0.05
1 23.80 2.157 0.0 7.300 9.495 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
2 24.41 0.0056 0.0 7.300 0.041 Vel = 2.14
2 23.85 2.157 0.0 7.300 9.536 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
3 48.26 0.0199 0.0 7.300 0.145 Vel = 4.24
3 24.03 2.157 0.0 8.520 9.681 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
4 72.29 0.0419 0.0 8.520 0.357 Vel = 6.35
4 24.47 2.157 0.0 9.330 10.038 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
5 96.76 0.0718 0.0 9.330 0.670 Vel = 8.50
5 25.28 2.157 0.0 9.330 10.708 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
6 122.04 0.1104 0.0 9.330 1.030 Vel = 10.71
6 26.46 2.157 0.0 9.330 11.738 K Factor @ node EQ01
to 120.0 0.0 0.0 0.0
7 148.5 0.1586 0.0 9.330 1.480 Vel = 13.04
7 0.0 2.157 0.0 9.290 13.218
to 120.0 0.0 0.0 0.0
8 148.5 0.1587 0.0 9.290 1.474 Vel = 13.04
8 0.0 2.157 0.0 10.630 14.692
to 120.0 0.0 0.0 0.0
9 148.5 0.1587 0.0 10.630 1.687 Vel = 13.04
9 0.0 2.157 0.0 10.690 16.379
to 120.0 0.0 0.0 0.0
10 148.5 0.1587 0.0 10.690 1.696 Vel = 13.04

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 10
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

10 0.0 2.157 0.0 10.300 18.075


to 120.0 0.0 0.0 0.0
11 148.5 0.1586 0.0 10.300 1.634 Vel = 13.04
11 0.0 2.157 0.0 10.120 19.709
to 120.0 0.0 0.0 0.0
12 148.5 0.1587 0.0 10.120 1.606 Vel = 13.04
12 0.0 2.157 0.0 7.410 21.315
to 120.0 0.0 0.0 0.0
13 148.5 0.1587 0.0 7.410 1.176 Vel = 13.04
13 0.0 2.157 0.0 4.430 22.491
to 120.0 0.0 0.0 0.0
14 148.5 0.1587 0.0 4.430 0.703 Vel = 13.04
14 0.0 2.157 1T 12.307 49.390 23.194
to 120.0 0.0 12.307 0.0
15 148.5 0.1587 0.0 61.697 9.789 Vel = 13.04
0.0
148.50 32.983 K Factor = 25.86
17 5.40 1.442 2T 14.864 82.050 33.432
to 120.0 2E 7.432 22.296 0.0
49 5.4 0.0025 0.0 104.346 0.256 Vel = 1.06
49 0.0 3.26 0.0 6.560 33.688
to 120.0 0.0 0.0 0.0
50 5.4 0.0 0.0 6.560 0.0 Vel = 0.21
50 4.29 3.26 0.0 5.940 33.688
to 120.0 0.0 0.0 0.0
51 9.69 0.0002 0.0 5.940 0.001 Vel = 0.37
51 4.47 3.26 0.0 13.970 33.689
to 120.0 0.0 0.0 0.0
52 14.16 0.0002 0.0 13.970 0.003 Vel = 0.54
52 4.70 3.26 0.0 9.960 33.692
to 120.0 0.0 0.0 0.0
53 18.86 0.0005 0.0 9.960 0.005 Vel = 0.72
53 4.06 3.26 0.0 9.960 33.697
to 120.0 0.0 0.0 0.0
54 22.92 0.0007 0.0 9.960 0.007 Vel = 0.88
54 1.96 3.26 0.0 11.600 33.704
to 120.0 0.0 0.0 0.0
55 24.88 0.0008 0.0 11.600 0.009 Vel = 0.96
55 1.27 3.26 0.0 8.310 33.713
to 120.0 0.0 0.0 0.0
56 26.15 0.0008 0.0 8.310 0.007 Vel = 1.01
56 0.83 3.26 0.0 9.960 33.720
to 120.0 0.0 0.0 0.0
57 26.98 0.0009 0.0 9.960 0.009 Vel = 1.04
57 -0.72 3.26 0.0 9.950 33.729
to 120.0 0.0 0.0 0.0
58 26.26 0.0009 0.0 9.950 0.009 Vel = 1.01
58 -1.39 3.26 0.0 9.960 33.738
to 120.0 0.0 0.0 0.0
59 24.87 0.0007 0.0 9.960 0.007 Vel = 0.96

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 11
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

59 -2.08 3.26 0.0 9.960 33.745


to 120.0 0.0 0.0 0.0
60 22.79 0.0007 0.0 9.960 0.007 Vel = 0.88
60 -2.56 3.26 0.0 9.960 33.752
to 120.0 0.0 0.0 0.0
61 20.23 0.0005 0.0 9.960 0.005 Vel = 0.78
61 -4.81 3.26 0.0 9.960 33.757
to 120.0 0.0 0.0 0.0
62 15.42 0.0003 0.0 9.960 0.003 Vel = 0.59
62 -5.43 3.26 0.0 9.960 33.760
to 120.0 0.0 0.0 0.0
63 9.99 0.0002 0.0 9.960 0.002 Vel = 0.38
63 -5.40 3.26 0.0 2.520 33.762
to 120.0 0.0 0.0 0.0
64 4.59 0.0 0.0 2.520 0.0 Vel = 0.18
64 0.0 1.442 3T 22.296 95.770 33.762
to 120.0 3E 11.148 33.444 0.0
65 4.59 0.0018 0.0 129.214 0.234 Vel = 0.90
65 0.0 4.26 0.0 2.420 33.996
to 120.0 0.0 0.0 0.0
66 4.59 0.0 0.0 2.420 0.0 Vel = 0.10
66 5.40 4.26 0.0 9.950 33.996
to 120.0 0.0 0.0 0.0
67 9.99 0.0001 0.0 9.950 0.001 Vel = 0.22
67 5.43 4.26 1T 26.334 2.500 33.997
to 120.0 0.0 26.334 0.0
30 15.42 0.0001 0.0 28.834 0.002 Vel = 0.35
0.0
15.42 33.999 K Factor = 2.64
18 4.29 1.442 2T 14.864 92.460 33.468
to 120.0 8E 29.728 44.592 0.0
50 4.29 0.0016 0.0 137.052 0.220 Vel = 0.84
0.0
4.29 33.688 K Factor = 0.74
19 4.47 1.442 2T 14.864 86.330 33.488
to 120.0 4E 14.864 29.728 0.0
51 4.47 0.0017 0.0 116.058 0.201 Vel = 0.88
0.0
4.47 33.689 K Factor = 0.77
20 4.70 1.442 2T 14.864 78.660 33.515
to 120.0 0.0 14.864 0.0
52 4.7 0.0019 0.0 93.524 0.177 Vel = 0.92
0.0
4.70 33.692 K Factor = 0.81
21 4.06 1.442 1T 7.432 22.150 33.541
to 120.0 2E 7.432 14.864 0.0
68 4.06 0.0014 0.0 37.014 0.053 Vel = 0.80

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 12
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

68 0.0 1.682 1E 4.95 7.640 33.594


to 120.0 0.0 4.950 0.0
69 4.06 0.0007 0.0 12.590 0.009 Vel = 0.59
69 0.0 1.442 1E 3.716 53.950 33.603
to 120.0 1T 7.432 11.148 0.0
53 4.06 0.0014 0.0 65.098 0.094 Vel = 0.80
0.0
4.06 33.697 K Factor = 0.70
22 1.96 1.442 1T 7.432 42.160 33.661
to 120.0 2E 7.432 14.864 0.0
70 1.96 0.0004 0.0 57.024 0.022 Vel = 0.39
70 0.0 1.682 0.0 1.510 33.683
to 120.0 0.0 0.0 0.0
71 1.96 0.0 0.0 1.510 0.0 Vel = 0.28
71 0.0 1.442 2E 7.432 40.830 33.683
to 120.0 1T 7.432 14.864 0.0
54 1.96 0.0004 0.0 55.694 0.021 Vel = 0.39
0.0
1.96 33.704 K Factor = 0.34
23 1.27 1.442 1T 7.432 5.250 33.694
to 120.0 2E 7.432 14.864 0.0
72 1.27 0.0001 0.0 20.114 0.003 Vel = 0.25
72 0.0 1.682 0.0 0.890 33.697
to 120.0 0.0 0.0 0.0
73 1.27 0.0 0.0 0.890 0.0 Vel = 0.18
73 0.0 1.442 2E 7.432 79.290 33.697
to 120.0 1T 7.432 14.864 0.0
55 1.27 0.0002 0.0 94.154 0.016 Vel = 0.25
0.0
1.27 33.713 K Factor = 0.22
24 0.83 1.442 2T 14.864 86.280 33.711
to 120.0 4E 14.864 29.728 0.0
56 0.83 0.0001 0.0 116.008 0.009 Vel = 0.16
0.0
0.83 33.720 K Factor = 0.14
57 0.72 1.442 2T 14.864 84.110 33.729
to 120.0 4E 14.864 29.728 0.0
25 0.72 0.0001 0.0 113.838 0.007 Vel = 0.14
0.0
0.72 33.736 K Factor = 0.12
58 1.40 1.442 1T 7.432 42.390 33.738
to 120.0 4E 14.864 22.296 0.0
74 1.4 0.0002 0.0 64.686 0.013 Vel = 0.28
74 0.0 1.682 0.0 1.440 33.751
to 120.0 0.0 0.0 0.0
75 1.4 0.0 0.0 1.440 0.0 Vel = 0.20
75 0.0 1.442 1T 7.432 40.310 33.751
to 120.0 0.0 7.432 0.0
26 1.4 0.0002 0.0 47.742 0.009 Vel = 0.28

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SACMAG DE MEXICO, S.A. DE C.V. Page 13
prueba Date

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
1.40 33.760 K Factor = 0.24
59 2.08 1.442 2T 14.864 80.790 33.745
to 120.0 0.0 14.864 0.0
27 2.08 0.0004 0.0 95.654 0.040 Vel = 0.41
0.0
2.08 33.785 K Factor = 0.36
60 2.56 1.442 2T 14.864 80.790 33.752
to 120.0 0.0 14.864 0.0
28 2.56 0.0006 0.0 95.654 0.059 Vel = 0.50
0.0
2.56 33.811 K Factor = 0.44
61 4.82 1.442 1T 7.432 77.640 33.757
to 120.0 0.0 7.432 0.0
76 4.82 0.0020 0.0 85.072 0.169 Vel = 0.95
76 0.0 2.157 1T 12.307 2.220 33.926
to 120.0 0.0 12.307 0.0
29 4.82 0.0003 0.0 14.527 0.004 Vel = 0.42
0.0
4.82 33.930 K Factor = 0.83
62 5.42 1.442 2T 14.864 80.790 33.760
to 120.0 0.0 14.864 0.0
67 5.42 0.0025 0.0 95.654 0.237 Vel = 1.06
0.0
5.42 33.997 K Factor = 0.93
63 5.40 1.442 2T 14.864 80.790 33.762
to 120.0 0.0 14.864 0.0
66 5.4 0.0024 0.0 95.654 0.234 Vel = 1.06
0.0
5.40 33.996 K Factor = 0.93

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

Das könnte Ihnen auch gefallen