ELECTRICAL
TESTER The industrys recognised information tool
How to diagnose
faulty cables, even
if youve tried
everything!
frequency testing of cables is not commonly
Friedrich Enkert used.
Europe/CIS Sales Director
An alternative is dc testing, using an insulation
test set that typically operates at 1 or 5 kV.
While power cables sometimes fail soon after
Such test sets are small, convenient and
being put into service into service e.g. caused by
inexpensive, and when they are used to carry
bad workmanship, failure is usually associated
out tests of suitable duration, typically a
with ageing of the insulation in a cable that
minute, this is a particularly useful form of
has been in service for a long period and with
testing as it is non-destructive and provides a
the associated cable joints. The fact that many
first-line insight into the condition of the cable
of these cables are underground present real
insulation.
challenges to identify, locate and repair.
It has to be said however, that
dc testing at these modest voltages,
Megger acquires SebaKMT while it provides a guide to the
In June 2012, Megger acquired SebaKMT, the world presence or absence of serious
leader in cable test equipment to add to its existing faults, it is less useful in providing
expertise. While Megger launched the first dc insulation information about general degradation
resistance tester in the 19th century and also has a and ageing of insulation. In addition,
range of earth ground testers and TDRs, it was a this form of testing does not model
predecessor company to SebaKMT that brought out the the cables normal working conditions
first cable fault location equipment in the early 1950s. and does not, therefore, replicate
A main aim of the acquisition is to offer customers a the stress distribution in the insulation
better range of solutions than either company could when the cable is operating at
do on its own. Clearly, sharing the technologies of the power frequency.
two companies will provide significant benefits for the
future. Detection of insulation failures at
higher voltages may require high-
voltage tests, often at two or three
Diagnostic testing times the working voltage of the cable. There Trouble with trees? VLF could be the answer.
Its clear that there is a need for diagnostic is however a serious concern that high-voltage
testing that will provide reliable information dc testing can unnecessarily damage the cable
about the insulation condition of a cable and under test. In particular, polarisation of the These problems and concerns led to the Types of very low frequency (VLF) test
its susceptibility to failure. In theory, such insulation may course flashovers later when development of yet another approach to cable sets
testing would best be carried out at power the cable is going back to service testing the use of ac at very low frequency Commercially available VLF cable test sets can
frequency in order to replicate, as accurately The water tree problem, a problem many (VLF). Commonly, the frequency used is be divided into two categories: those that use
as possible, the normal working conditions of of the early cable types 0.1 Hz. At such a low frequency, the capacitive a test waveform that is sinusoidal, and those
the cable. Water trees start as minute inclusions of water reactance of even a long cable is relatively that use a cosine-rectangular waveform. The
vapour within the insulation at the production low, so the charging current is manageable advantage usually claimed for testing with
In practice, however, this approach is
or installation phase, and grow into tree-like even for a conveniently small test set. sinusoidal technology is that it lends itself
problematic. Cables present a highly capacitive
structures. Water trees in themselves do not to being combined with other insulation
load to the test set, which means that if
cause immediate cable failure, but the danger Because the test is carried out with alternating evaluation techniques, such as tan delta
testing is carried out at power frequency, a
is that a water tree may continue to develop current, the cable is not subject to a unipolar measurement and partial discharge (PD)
large amount of reactive power is required to
until the field stress in the remaining insulation applied voltage for long periods, so no polari- diagnostics.
charge the cable. To meet this requirement, a
is to high and an electrical tree is started. This sation will take place and the cable will not be
test set necessarily has to be physically large,
can lead to electrical leakage and failure of the damaged after putting back into operation. continue on page 2
heavy and expensive. For this reason, power
cable insulation.
Useful transients
milliseconds. This in turn produces two waves ways to decouple and analyse these transients
Applying a sudden change in current also travelling in opposite directions. These waves including range-dependant arc reflection,
known as a transient can be useful in testing are reflected back at the cable ends so that differential arc reflection and impulse current
Allen Joyce cables. Using an impulse generator (thumper) they then travel toward each other again in the emission. With the right TDR (time domain
HV and Cable Fault Location Product Manager and arc reflection filter, several methods of high direction of the cable fault. The waves are reflectometer) equipment, you will be able to
voltage fault prelocation are possible. If you unable to pass the fault because of the short identify breakdowns hundreds of kilometres
trigger a breakdown at the cable fault, you can circuit, so they are reflected back again as with away.
create a low-resistance short circuit for a few the arc reflection method. There are various
To request a licence to use an article in Electrical Tester, Ideally, the instrument data sheet should
please email ElectricalTester@Megger.com, with a brief include a figure for noise immunity expressed
outline of the reasons for your request. in milliamps, as this is definitive and easy to
All trademarks used herein are the property of their respective
interpret. If, for example using DC insulation
owners. The use of any trademark in this text does not imply resistance tester, the noise current rejection
trademark ownership rights in such trademarks, nor does use quoted is 2 mA, this means that the instrument
of such trademarks imply any affiliation with or endorsement
of Electrical Tester by such owners.
will give reliable and accurate results provided
A printed newsletter is not as interactive as its email
that the noise current induced in the test circuit
equivalent so to help you find items quickly on www. at is 2 mA or less.
megger.com, we have underlined key search words in blue.
Note from the Editor For general use, instruments with a noise
Time for your say. immunity of 2 mA will prove satisfactory in
We have introduced a Questions and Answers section and most cases, although it is worth noting that
would like your input. If you have any questions or stories
that you think we could use, then please email electrical- Testers with high noise immunity performance can be enhanced with the latest HV DC insulation testers now offer
tester@megger.com shielded test leads 3 mA noise immunity, and cost no more than
Views expressed in Electrical Tester are not necessarily the their less capable predecessors.
views of Megger.
For instruments that will be regularly used
The word Megger is a registered trademark
As used in the electrical and electronics obtained may be inaccurate or may fluctuate in substations and similarly demanding
Editor Nick Hilditch. sectors, the term noise is something of a erratically. environments, even higher noise immunity is
T +44 (0)1304 502232 misnomer after all, you cant hear it! desirable. Megger has responded to this need
E nick.hilditch@megger.com Electrical noise, which is more properly This can be a particular problem when by producing high noise immunity versions of
www.megger.com called electromagnetic interference or EMI, carrying out high voltage insulation testing in its latest HV DC insulation testers, which it
can be just as problematic as its acoustic environments like electrical substations, where offers in its S1 range. These units offer a 4 mA
Megger Limited
Archcliffe Road Dover Kent CT17 9EN
counterpart. If for example, significant levels high levels of EMI are frequently present. noise immunity rating, which is one of the
T +44 (0)1304 502100 of EMI are present when measurements are Instrument manufacturers are, of course, highest ratings currently available in this class
E electricaltester@megger.com being made on electrical systems, the readings aware of this and they make efforts to design instrument.
www.megger.com
Sharing protective relay know-how 44%, at which point the power supply on one
of our own harmonic recorders failed. Then
Kathleen Wolf-Davis
region. The scheme incorporates 12 optical
Product Marketing Specialist
CTs, 8 merging units, 6 digital relays, 2 GPS
IRIG B clocks, 2 managed Ethernet switches
At Georgia Techs 66th Annual Protective and 2 digital recorders for sampled values.
Relaying Conference, which was held in
Atlanta in April as part of the universitys The project, run by Instituto de Investigaciones
Power System Conferences series, Meggers Elctricas (CFEs research arm), included the
James Ariza presented a headline paper, active participation of Alstom, Arteche, ABB,
Lessons Learned From First Multivendor SEL, GE, Megger, Omicron and Universidad
400 kV Transmission Line Protection Scheme Politecnica de Chiapas. The participants faced
Using Optical CTs and IEC 61850-9-2 Process a number of challenges, including no previous
Bus Protection Relays, to a packed project references with multivendor optical
conference session. Ariza wrote the paper in CTs and sample values; a risk of testing on a
conjunction with Carlos Melendez and Nicolas real line instead of in the lab; issues with testing
Juarez at Comisin Federal de Electricidad procedures and lack of testing options for
(CFE), the Mexican state-owned electric optical CTs, relays, merging units and Ethernet
utility, and Rodolfo Colon at Instituto de switches; varying procedures and standards.
Investigaciones Elctricas (IIE).
The paper explained how these challenges
The paper examined a multi-vendor transmission were addressed and how success was
protection scheme for a 400 kV line using ultimately achieved. With the success of this
optical current transformers (CTs) and sample scheme, CFE plans to expand the project,
values. The CTs and connecting system were Here is what a 44% harmonic looks like. Note the peak voltage that the diodes in the television
James noted in his presentation, which was
power supply had to deal with no wonder they went pop with such regularity.
installed inside a CFE substation to protect enthusiastically received by the audience,
the 150-mile line linking the Manuel Moreno and which prompted lively discussion at its
Torres and El Juile substations in the southern conclusion.
Transformer manufacturers, test laboratories, The absolute current and voltage levels are Unlike conventional
power utilities and many others have a regular measured with an accuracy of 0.5%. bridges, there is no
requirement to accurately measure capacitance A disadvantage of traditional bridge methods balancing to perform,
and dissipation factor at high voltages. These is that they can only measure and compare and all calculations are
tests are performed as part of the quality control capacitive or inductive currents in-phase. The automatic.
procedure when new materials are investigated, new technique in CDAX605 can measure
for final test of instrument transformers and 0-360 phase and can therefore compare In achieving
for general testing of electrical insulation and signals that are phase-shifted. As an example, convenience, the new
equipment. for ratio measurements it is possible to use instruments make no
a standard capacitor to measure the HV test sacrifices in the areas of
The approach traditionally adopted for carrying voltage and reference resistor on the LV versatility or accuracy.
out tests of this type is to use a capacitance side of the transformer. This is a significant The instruments can
bridge in conjunction with a separate standard advantage since calibrated standard capacitors accommodate all
capacitor and test voltage source. In earlier are typically only available in the 100 pF standard test
times Schering bridges were used for loss to 10000 pF range which may give a very configurations,
measurements and later-on automatic balancing low test current for high ratio devices like including UST-R, UST-B,
bridges. While this method is satisfactory, capacitive coupled voltage transformers UST-RB, GST-GND,
at least in some applications, it can be time (CCVT). GSTg-R, GSTg-B and
consuming and it has limitations. GSTg-RB, with three
Like traditional bridges, these novel measurement inputs,
Alternatives to the traditional bridge for instruments are designed for use with an and they offer a wide
capacitance and dissipation factor measurement external voltage source and reference measurement range,
are now becoming available and these capacitor. This means that most prospective typically covering
innovative instruments, of which the new users will already have the necessary capacitance from 0 to
Megger CDAX605 is a leading example, additional equipment needed to form a 100 F and dissipation
offer important benefits. The new design for complete dissipation factor and capacitance factor from 0 to 10, as
dissipation factor and capacitance measurement measurement system. And more importantly, well as phase angle
also compares the test specimen against a this approach makes the instruments measurement from 0 to CDAX605 can measure phase shifted signals
standard capacitor but it does not need bridge particularly versatile users are free to select 360. Measurement accuracy
balancing. voltage sources and standard capacitors equals that of the best bridges.
or resistors to meet their own specific With the new instruments, HV measurements
Instead, the current signals from the standard requirements. Designed to be used with an external PC, of capacitance and dissipation factor can now
capacitor and test specimen are simultaneously the instruments are supplied with soft-ware be quickly and conveniently performed.
measured and capacitance and dissipation In addition, they work with almost any value that provides a convenient and intuitive user
factor are calculated. With the use of of reference capacitor or resistor value, and interface and has integrated data logging The instruments deliver results that are at least
sophisticated internal calibration procedures, offer an automatic testing process that always facilities. The CDAX605 also supports LabView as accurate as those obtained with a traditional
accuracy down to 0.005% is reached for give direct readings of capacitance, dissipation and C# communication interfaces that further bridge, and they are much more versatile.
dissipation factor/phase angle and 0.03% for factor, inductance and ratio. enhance its versatility.
capacitance measurements. They are, you might say a bridge to the future!
themselves nothing new but in recent times, in line with IEC 62271-100, and for measuring It has only been possible here to mention a
there has been a growing feeling that the the coil current in each phase separately. It few of the features that are now available in
available models while perfectly adequately is worth noting that many older instruments mid-range circuit breaker test sets. There are
specified when they were first introduced no measure only the total current for all three many others including, for example, provision
longer measure up to the increasingly complex phases. Unfortunately, this measurement is for connecting transducers so that CB motion
requirements of todays circuit breaker users. essentially worthless. can be measured directly and facilities for
easily adding vibration monitoring and analysis
This gap in the market has now been Another important feature for the new functions.
addressed with a new generation of circuit mid-range CB test sets is provision for
breaker analysers that offer enhanced comprehensive first-trip testing with the aid If you are thinking about buying new circuit
functionality at prices substantially less than of accessory clamp-on CTs, whether the breaker test equipment in the near future, or if
those of the high-end instruments. Lets breaker has a single operating mechanism youre finding that your existing CB test kit no
examine what these groundbreaking mid- common to all three phases, or a separate longer really meets your requirements, it will
range instruments have to offer. operating mechanism for each phase. These be well worth your while to take a look at the
invaluable facilities make it possible to analyse data sheets for the new generation mid-range
Since safety is always of paramount the coil current signature, which is the most instruments, of which the products in Meggers
importance, a key feature is support for important part of the first-trip test. They also new range are excellent examples.
DualGround testing. This allows tests to be allow the contact opening time of a CB to be
performed with both sides of the breaker measured, together with the synchronisation
The TM1700 provides reliable and accurate grounded, which ensures that dangerous of the opening times for the three phases,
test results voltages from adjacent equipment can never without taking it out of service.
be induced into the breaker under test.
Careful attention has also been given to the
HV circuit breakers are the key safety Another important feature of these instruments user interface, with the best of currently
components in every power transmission is active interference suppression, which available instruments incorporating colour
and distribution system. No one can afford to minimises the effect of capacitively coupled touch screen displays, and software wizards
take a chance on whether they will operate interference current in the test object, making that take much of the complexity out of tasks
correctly when called upon to do so testing it possible to make accurate measurements, like the production of custom test templates.
is essential. But when it comes to buying including measurements of PIR values, even in The screens can also show test results
circuit breaker test equipment, what are the electrically noisy environments. graphically making them much easier to
options? interpret, a process that is further aided by the
Advances have also been made in the provision of magnify and compare functions
There are low-end instruments that offer functionality of the control units of these for the traces displayed.
excellent value for money in simple instruments allowing independent control
applications, and there are high-end pulse generation for each phase, which makes Comprehensive help is also offered, including
instruments that offer superb performance it possible to simulate the sequence of a one- on-screen display of the connection diagrams
and versatility but are undeniably a major phase ground fault. that show exactly how the test leads need to
investment. So what about the middle ground? The control units also make provision for be connected for the test chosen.
Mid-range circuit breaker analysers are, in automatically measuring the control voltage,
Schneider Electric was showing iPads configured It may seem to be an almost insignificant
DELTA4000 so that they could be used to monitor the contribution in so vast a plan, but Megger
DELTA4000 is a light weight and rugged 12 kV AC complete electricity supply network of a small test and measurement equipment is ideal for
use in these new systems. And the company
WWW.MEGGER.COM/FREETIME
insulation diagnostic system which provides accurate town, while Siemens was presenting high-
and repeatable Tan Delta / Power factor measurements voltage switchgear and power transformers couldnt find a better marketing executive
in demanding and extreme conditions. New test designed to fit into the base of wind turbine anywhere in the world than Angela Merkel!
techniques include intelligent temperature correction towers.
to eliminate inaccurate correction tables and automatic
For Megger, the Energiewende offers literally
voltage dependence detection to identify insulation Technologies for tomorrows energy supply electrifying prospects in Germany. At Hanover
problems which need investigation. were seen everywhere at the fair, and it was Fair, it was possible to take a look at this
very apparent that this is likely to be an brave new world in colour and in 3D!
For your free Megger guide to transformer energy supply scenario, led by Germanys Overall, it was a place where Megger, with its
testing, visit www.megger.com/freetime
Energiewende, that doesnt depend on world-leading innovations, was very much at
nuclear power or on power from fossil fuel home among its peers.
sources.
MEGGER_Delta4000_Skiing_A5.indd 1 31/05/2012 17:12
Q&A
Q: Why is temperature compensation needed,
This time we are looking at some of the questions that are most frequently asked about and what is the best approach to providing
insulation power factor/dissipation factor (tan ) testing. The answers given here are necessarily this compensation?
short, but much more detailed information can be found in the publication DELTA 4000 Reference A: The test results are most useful when
Manual Applications Guide which is available as a free download from the Megger website. compared either with the results from
previous tests, or with manufacturers data.
However, the results are influenced by
temperature, which means that comparisons
basis present the result as the tangent of the deterioration of insulation due to ageing and
are only valid for tests carried out at the same
dielectric loss angle that is, tan . The power temperature; contamination of insulation by
temperature. The ideal approach would be to
factor and tan tests are essentially the same, water, carbon deposits, dirty oil and other
standardise on a specific test temperature
Q: What is tan testing and how is it different and good instruments will display either tan chemicals; and severe current leakage through
20 C is usually suggested but in practice
from insulation power factor testing? or power factor. It is worth noting that, for cracks and over insulator surfaces.
this is often not possible, and compensation
A: When an ac voltage is applied to a test small values of , tan is almost equal to cos
must be used. In the past, this has usually
object, the phase difference between the , so in many cases, the two tests will deliver Q: What is voltage dependence in tan /
meant using compensation tables, but these
voltage and resulting current, in degrees, is the same numerical result. power factor testing, and why is it important?
are at best averages, and their use is not
the phase angle, and is usually designated A: With an ideal insulator, tan /power factor
conducive to accuracy. Test sets are now
(phi). The cosine of this angle (cos ) is the Q: Why is tan /power factor testing useful? would remain the same for a wide range of
available, however, that provide automatic
power factor, and this is what is measured in A: With modern test equipment, these tests are test voltages. With old or deteriorated insulation,
intelligent temperature compensation (ITC),
an insulation power factor test. For perfect relatively easy to carry out and they provide however, the results vary as the voltage varies.
by making use of the fact that a tan /power
insulation, would be exactly 90, and cos dependable information about the condition When such voltage dependence is detected, it
factor measurement made at a certain temperature
would be 0. In reality, no insulator is per- of insulation. As insulation problems are one is advisable to carry out additional tests, such
and frequency corresponds to the same
fect so is less than 90 and cos is greater of the most common causes of failure in as tip-up tests, to more accurately assess the
measurement made at a different temperature
than zero. The value of cos is an indicator electrical equipment, this information is an insulation condition. The latest tan /power
and frequency. ITC provides much more
of insulation condition. It is also possible to invaluable aid for preventative maintenance. factor test sets automatically detect voltage
accurate and dependable results than using
work with the dielectric loss angle, , which is Examples of the conditions that can be detected dependence, and trigger an alarm to alert the
compensation tables.
equal to (90 - ). Test sets that work on this with tan /power factor testing are chemical user that further testing is recommended.
and the The origin of this story was a chance conversation with a neighbour and fellow
Dover UK resident, Alex Elliott.
weather
Jeff Jowett
Applications Engineer
Part 3
advantage, and can backfire by freezing solid
around the probe and making it near impossible
NEVER GO WITHOUT YOUR
The first two parts of this article examined
various weather-related factors that influence
ground resistance testing, including moisture,
to remove. But once an adequate setup is
accomplished, Brooks advises, testing under
snow is just as reliable as at any other time.
Where snow actually can afford an advantage
AVO!
temperature and the influence of freezing. In is when it falls early in the season, before the
this final part, we look at the importance of first major frost. Snow may then thermally As the accompanying photograph
know-how in ground testing, why a well- insulate the ground and limit frost penetration of a youthful Alex Elliott shows, the
planned test regime may require working in to more workable depths, say 6-8 inches. If one thing you always wanted to be
adverse weather conditions, and the criteria snow has been plowed or drifted away, frost sure you had with you when you
that affect the selection of test equipment for penetrates deeper and test results may be made a service call in the late 1930s
use in such conditions. rendered less consistent. Testing under snow was your trusty Avometer! Alex, who
can actually be more reliable. Just shovel recently sent this photograph to
Knowledge is the most effective tool for all away an area large enough to drive the test Electrical Tester, was just 14 when it
types of field work, and it becomes that much rods. was taken in 1938, and was working
more valuable in applications where variables for Wycombe Electrical Supplies in
are as large and uncontrollable as they are in The final consideration is that of the test High Wycombe, Buckinghamshire,
ground testing. Assess the site and recent instrumentation itself. No one is likely to want England.
conditions in order to make an educated to perform a ground test in a driving rain,
decision as to where test results may fall on and lightning conditions, even if miles away, He recalls that the company was the
the min/max cycle, then proceed accordingly. are to be avoided because of the risk to the main distributor in the area for the
At the least, arrangements should be made operator. Dangerous voltages developing on prestigious HMV and Marconiphone
to retest at a suspected worst time. If a the power lines can be transmitted through
ranges of radios and that for servicing
maintenance schedule is to be established, the grounding system and will appear at the
these, an Avometer was literally
be judicious about the interval. For most terminals of a tester if a test is in progress.
indispensible. In fact, the HMV and
electrical maintenance, a regular schedule, But aside from these extreme circumstances,
Marconiphone service sheets of the
for instance annually or semi-annually, is the ground testing can be performed on moist
era not only specified that an
order of the day. But be careful not to apply or rainy days, or the sudden appearance of a
Avometer should be used for testing,
this practice to ground maintenance. Testing at shower need not send the operator scurrying.
The determining factor here is the IP rating of but even detailed which of the
regular intervals will result in readings being
the instrument. This rating should be available meters ranges was to be used for
taken under the same general weather conditions
in the instruments specifications and is each individual test!
year in and year out. If these are optimal
times of year, a false sense of security can commonly referred to as Ingress Protection. IP Alex Elliott with his AVO Model 8
ratings were established by the International Alex also recalls that the owner of Wycombe
develop. Instead, test at irregular intervals, like
5, 7, or 11 months, so that all times of year Electrotechnical Commission (IEC) in Stand- Electrical Supplies saw great possibilities for
and all weather conditions will be evaluated. ard #529, and provide a means of evaluating television, which was very much in its infancy BBC television transmitter at Alexandra Palace
A worst case will be recognized and if the effectiveness of an instruments casework at the time. however, reception was somewhat hit and
necessary the grid can be expanded or in keeping out dirt and moisture. The IP miss.
improved so that there will be no unpleasant rating consists of two numbers and in both He had a Baird mechanical receiver with a
surprises. cases, the higher the better. The first number rotating scanning disc, with which he received In any event, it wasnt poor reception that
indicates how well the instrument is sealed the pioneering BBC TV broadcasts that started spoiled the plans of Wycombe Electrical
Testing around the calendar may result in the against particle invasion, with 6 being dust in August 1932. These broadcasts used just Supplies to profit from television, but the
disagreeable necessity of working in snow. tight. Quarries and mines are particularly bad 30 scanning lines per picture a far cry from coming of the Second World War. BBC
When you have to put food on the table in environments in this regard, while a steady the 1080 lines of a modern HD receiver but television broadcasts were terminated
the wintertime, you have to think of these wind in a dusty environment can also pose a nevertheless created huge interest because of abruptly on 1st September 1939, ostensibly so
things, says Burt Brooks of Power Quality hazard to the instrument. The second number their novelty. that aircraft could not use the signals from
& Ground Testing LLC. It may seem counter- refers to moisture ingress, with 8 the highest Alexandra Palace transmitter as a direction
intuitive, but in frigid climes, snow can rating, continuous immersion. Since ground In 1935, the BBC ceased broadcasts on the finding aid.
provide an advantage. First, the test rods must tests are not performed under water, this Baird 30-line standard, replacing them in 1936
be driven through the frost layer. The ground would be overkill. But note the IP rating and by high definition broadcasts that alternated The last programme transmitted was a Mickey
tester must establish a minimum amount of obtain an instrument that is adequate to the between the new Baird 240-line standard and Mouse cartoon, and when the BBC television
current through the soil in order to meet its rigors of the field. the Marconi-EMI 405-line standard in black- service resumed on 7th June 1946, this same
measurement parameters and to sense the and-white only, of course! cartoon was also the first programme to be
voltage drop across the measured resistance. Armed with knowledge and a good instrument,
transmitted. Who said that repeats were a
Modern testers include indicators that will the skilled technician will be a match for any- With a keen eye for future profits from modern phenomenon? By this time, Alex had
warn the operator if these parameters are not thing the weather can deal. selling and maintaining television equipment, a new career in precision engineering, but he
being met. Additional measures must then be Alexs employer set up a showroom for still has happy memories of the days when
taken, such as driving deeper rods, to bring Sources of information:
demonstrating HMV televisions that worked the only instruments needed for electronic
the test setup within specifications. Pouring A Simple Guide to Earth Testing and Getting Down
with this new service. Since High Wycombe servicing were a signal generator and, of
hot water provides only a marginal temporary to Earth both published by Megger.
was outside the official service area for the course, that indispensible Avometer.
Power Quality & Ground Testing LLC, Newton, MA