Sie sind auf Seite 1von 5

WM_Spring08.qxd:WM_Summer07.

qxd 6/3/08 22:46 Page 16

SHOCK PROTECTION

16
become live under fault conditions.
The potential of the metal enclosure is
higher than that of the main earthing
terminal of the installation (and that
of Earth) because of a potential
difference created by the passage of
fault current through the impedance of
the circuit protective conductors and
the means of earthing.

Protective measures
A protective measure must consist of
provision of basic protection and

PROTECTION AGAINST provision of fault protection, which


normally are independent. For

ELECTRIC SHOCK by John Ware


example, in the case of automatic
disconnection of supply, basic
protection is provided by insulation
and barriers and enclosures while
THE FUNDAMENTAL rule of A live part is defined as: fault protection is provided by
protection against electric shock is: protective earthing, protective bonding
 live parts, such as energized A conductor or conductive part and automatic disconnection of
conductors, must not be accessible, intended to be energized in normal use, supply. Basic and fault protection are
and including a neutral conductor but, by independent.
 conductive parts which are convention, not a PEN conductor
accessible, such as metal enclosures Enhanced protective measure
of equipment or metal pipes, must Figure 1 illustrates a person coming A permitted exception is where the
not be hazardous-live into contact with live parts. protective measure is an enhanced
protective measure which provides
These two conditions must be Protection under fault conditions or both basic and fault protection. An
achieved both in normal conditions fault protection is defined as: example of an enhanced protective
(no faults on the electrical system) and measure is reinforced insulation. Basic
under single fault conditions (such as Protection against electric shock under protection and fault protection are both
a fault from a live conductor to a metal single fault conditions provided by the reinforced insulation
casing). (Refer to Regulation 410.3.2).
Fault protection provides protection
Protection under normal conditions against persons or livestock coming Recognized protective measures
Protection under normal conditions is into contact with exposed-conductive- BS 7671: 2008 recognizes the protective
achieved by basic protection, formerly parts which have become live under measures listed in Table 1 ( see page 22).
known as protection against direct single fault conditions. An exposed-
contact. Protection under single fault conductive-part is defined as: The protective measure of Automatic
conditions is achieved by fault Disconnection of Supply
protection and was previously referred Conductive part of equipment which The protective measure of automatic
to as protection against indirect contact. can be touched and which is not disconnection of supply consists of
normally live but which can become basic protection, fault protection and,
Basic protection is defined as: live when basic insulation fails for some circuits and locations,
additional protection. Basic protection
Protection against electric shock under Figure 2 illustrates how a person is provided by basic insulation of live
fault-free conditions could receive an electric shock under parts and/or by barriers or enclosures.
single fault conditions. Fault protection is provided by
Basic protection is provided to protect The person in Figure 2 is in contact (i) protective earthing,
persons or livestock coming into direct with the metal enclosure of an item of (ii) main protective equipotential
contact with live parts. Class I electrical equipment which has bonding, and

IET Wiring Matters | Spring 08 | www.theiet.org


WM_Spring08.qxd:WM_Summer07.qxd 6/3/08 23:26 Page 17

SHOCK PROTECTION
17
(iii) automatic disconnection of supply
in the case of a fault.

Protective earthing
Protective earthing requires all exposed-
conductive-parts to be connected to a
protective conductor which in turn is
connected to the main earthing terminal
and hence, via the earthing conductor to
the means of earthing.
Figure 2:
Main protective equipotential bonding Single fault
In each installation main protective Figure 1: Contact with live parts conditions

bonding conductors complying with


Chapter 54 are required to connect to
the main earthing terminal
extraneous-conductive-parts, such as
water and gas installation pipes, other
installation pipework and ducting,
central heating and air conditioning
systems and exposed metallic
structural parts of the building.

Automatic disconnection in
case of a fault
When a fault occurs, the fault current
has to be of sufficient magnitude to
operate the circuit protective device to
automatically disconnect the supply to
the faulty circuit within a prescribed
time.
A protective device such as a fuse, Figure 3: Automatic Automatic Disconnection of Supply

circuit-breaker or RCD is to be
provided and the circuit designed such required to be connected by a causing the automatic operation of the
that the device operates and protective conductor to the main disconnecting device within the time
disconnects the supply. earthing terminal of the installation specified in Table 41.1 of BS 7671.
In the event of a fault of negligible which must be connected to the Uo is the nominal a.c. rms or d.c. line
impedance between a line conductor earthed point of the power supply voltage to Earth in volts (V) which is
and an exposed-conductive-part or a system, i.e. the supply transformer. 230 V.
protective conductor, the protective The characteristics of the protective
device must disconnect the supply device and the circuit impedances are TT system
within the appropriate time stated in required to fulfil the following In a TT system, every exposed-
Table 41.1 of BS 7671 (See Table 2, requirement (Regulation 411.4.5): conductive-part is required to be
page 22). Zs x Ia Uo connected, via the main earthing
Requirements of the protective where: terminal to a common earth electrode
measure of Automatic Disconnection Zs is the impedance in ohms () the (Regulation 411.5.1 refers). The preferred
of Supply include protective earthing, fault loop comprising: protective device for fault protection is
main protective equipotential bonding  the source an RCD (Regulation 411.5.2) but where an
and automatic disconnection.  the line conductor up to the point of RCD is used, as it will be in most cases,
the fault, and overcurrent protection must nonetheless
TN systems  the protective conductor between be provided by a fuse or a circuit-
In a TN system each exposed- the point of the fault and the source. breaker, or, alternatively a combined
conductive-part of the installation is Ia is the current in amperes (A) RCD and overcurrent protective device

IET Wiring Matters | Spring 08 | www.theiet.org


WM_Spring08.qxd:WM_Summer07.qxd 6/3/08 22:47 Page 22

SHOCK PROTECTION

22
Basic protection Fault protection
Protective measure Use Fault protection provided by
provided by provided by
Automatic disconnection of supply General Insulation or barriers and Protective earthing Used in 95% of all installations.
enclosures Protective bonding Section 411 in BS 7671: 2008.
Automatic disconnection Includes FELV (411.7) and RLV (411.8)

Double or reinforced insulation General Basic insulation Supplementary insulation Section 412

Reinforced insulation
Electrical separation for the supply to General Insulation or barriers and Simple separation of the circuit Section 413
one item of current-using equipment enclosures from other circuits and Earth

Extra-low voltage (SELV and PELV). General Voltage must not exceed 50 V a.c. With SELV the circuit is separated, with
Supply from a suitable source PELV it is earthed
Separation Section 414.
Obstacles Obstacles With or without Fault protection Refer to Regulations 417.1 and 417.2
Controlled or
supervised by skilled
Placing out of reach persons Placing out of reach Refer to Regulation 417.3

Non-conducting location Installation is Insulation or barriers and The conditions of supervision Refer to Regulation 418.1
controlled or under enclosures under which the fault protective
Earth-free local equipotential the supervision of provisions of Section 418 may Refer to Regulation 418.2
bonding skilled or instructed be applied as part of the
persons so that protective measure are given in
Electrical separation for the supply to Refer to Regulation 418.3
unauthorized changes Regulation 410.3.6.
more than one item of current-using
cannot be met
equipment

Table 1: Recognized protective measures


Final circuit not Final circuit Distribution
(an RCBO) may be employed. exceeding 32 A exceeding 32 A circuit
Where an RCD is used for fault TN system 0.4 s 5s 5s
protection, the following conditions TT system 0.2 s 1s 1s
are to be fulfilled: TT system(1)
 the disconnection time must be that
0.4 s 5s 5s

(1) Where, in a TT system, disconnection is achieved by an overcurrent protective device and main
required by Table 41.1, and
 RA x In 50 V
bonding is connected to all the extraneous-conductive-parts within the installation in accordance with
Regulation 411.3.1.2, the maximum disconnection times applicable to a TN system may be used.
Where: A maximum disconnection time of 5 s applies to all circuits in a reduced low voltage system Regulation
RA is the sum of the resistances of the 411.8.3 refers). A maximum disconnection time of 5 s applies to all circuits supplying fixed equipment
used in highway power supplies (Regulation 559.10.3.3 refers).
earth electrode and the protective
conductor connecting it to the
Table 2: Extract from Table 41.1 (and others) of BS 7671: 2008 Maximum disconnection times for
exposed-conductive-parts (in ohms). a nominal a.c. rms. line voltage to Earth of 230 V
In is the rated residual operating
current of the RCD. of supply, 412 Double or reinforced special Locations (410.3.2)
insulation 413 Electrical separation and
Additional protection 414 Extra-low voltage provided by SELV The protective measure of Double or
BS 7671 recognizes this measure as or PELV; Regulation 415.1.2 refers. Reinforced Insulation
reducing the risk of electric shock in Additional protection by means of a Double or reinforced insulation is a
the event of failure of one or other of 30 mA RCD is specified as part of a protective measure in which:
the two basic protective measures protective measure for situations such as:  basic protection is provided by basic
mentioned above (insulation and  socket-outlets for use by ordinary insulation, and
barriers or enclosures) and/or failure persons for general use (411.3.3)  fault protection is provided by
of the provision for fault protection or  mobile equipment outdoors (411.3.3) supplementary insulation, or
carelessness by users.  concealed cables in walls and  both basic and fault protection are
The measure must not be used as the partitions where the installation is provided by reinforced insulation
sole means of protection and does not not intended to be under the between live parts and accessible
obviate the need to apply one of the supervision of a skilled or parts (Regulation 412.1.1).
protective measures specified in instructed person, (522.6.7) Double or reinforced insulation is
Sections 411 Automatic disconnection  circuits in circuits in certain intended to prevent the appearance of

IET Wiring Matters | Spring 08 | www.theiet.org


WM_Spring08.qxd:WM_Summer07.qxd 6/3/08 23:13 Page 23

SHOCK PROTECTION
23
a dangerous voltage on the accessible measure in which basic protection is 418.3 of BS 7671) this protective
parts of electrical equipment through provided by basic insulation of live measure is limited to the supply of one
a fault in the basic insulation. There is parts or by barriers or enclosures and item of current-using equipment
no provision for the connection of fault protection is provided by simple supplied from one unearthed source
exposed metalwork of the equipment separation of the separated circuit with simple separation.
to a protective conductor, and no from other circuits and from Earth The source of supply is an isolating
reliance upon the earthing (Regulation 413.1.1). transformer conforming to
arrangements in the fixed wiring of The two main principles underlying BS EN 61558 (which supersedes
the installation. protection by electrical separation is BS 3535), or one of the other sources
that neither the source of the supply specified in Regulation 414.3 having an
Wiring systems nor any live parts of the separated equivalent degree of separation from
Wiring systems must have a rated circuit is connected to any other any other system.
voltage of the cable(s) is not less than circuit or to Earth. Thus, in the event Protection by electrical separation
the nominal voltage of the system and at of a single fault to an exposed- requires the following conditions to be
least 300/500 V and adequate mechanical conductive-part of equipment in the met:
protection of the basic insulation must separated circuit, fault protection is  The separated circuit must be
be provided by one or more of the afforded because there is no path for supplied through a source with at
following the non-metallic sheath of the fault current to return to the source. least simple separation
cable, or non-metallic trunking or For an installation in a dwelling, the  The voltage of the separated circuit
ducting or non-metallic conduit. only likely application of the use of must not exceed 500 V
electrical separation is a shaver supply  Live parts of the separated circuit
The protective measure of unit complying with BS EN 61558-2-5 must not be connected at any point to
Electrical Separation Except under particular another circuit or to Earth or to a
Electrical separation is a protective circumstances (Refer to Regulation protective conductor

TRAINING Brought to you by the Institution of Engineering and Technology

Power your way


towards the 17th Edition
TRAIN TO THE 17TH EDITION
These new regulations come into force July 2008:
Understand the changes
Upgrade courses from the 16th Edition to the 17th Edition
17th Edition qualifications
New City & Guilds awards
Meet industry standards

To find out more about our short courses and workshops visit
www.theiet.org/wmcourses

For advice on the best course to meet your needs, call


+44 (0) 01438 767289 or email coursesreg@theiet.org

IET Wiring Matters | Spring 08 | www.theiet.org


WM_Spring08.qxd:WM_Summer07.qxd 6/3/08 23:11 Page 24

SHOCK PROTECTION

24

- 6 i * 6
- 6 -Vi -xx
* >vi >}
* >vi

"iVi
iVi `iVi

- 6
Vi}
ii

Figure 4: The principle of electrical separation Figure 5: Simple PELV system

 No exposed-conductive-part of the Extra-Low Voltage), or PELV considered insufficient to present a


separated circuit must be connected (Protective Extra-Low Voltage), hazard of electric shock (as defined) in
either to the protective conductor or Regulation 414.1.1 refers. dry situations where the person
exposed-conductive-parts of other protected has a body resistance within
circuits, or to Earth. If the exposed- SELV is defined as: normal limits. In certain locations the
conductive-parts of the separated An extra-low voltage system which is requirements of Part 7 limit the value
circuit are liable to come into contact, electrically separated from Earth and of the extra-low voltage to a value
either intentionally or fortuitously from other systems in such a way that a lower than 50 V a.c. or 120 V d.c.
with the exposed-conductive-parts of single fault cannot give rise to the risk If the nominal voltage exceeds 25 V
other circuits, protection against of electric shock a.c. or 60 V d.c., or if the equipment is
electric shock no longer depends immersed, basic protection shall be
solely on protection by electrical PELV is defined as: provided for SELV and PELV circuits
separation but on the protective An extra-low voltage system which is not by insulation in accordance with
provisions to which the latter exposed- electrically separated from Earth, but Regulation 416.1. Basic protection and
conductive-parts are subject. which otherwise satisfies all the fault protection is provided under the
requirements for SELV following conditions:
Separated circuits  The nominal voltage cannot exceed
The use of separate wiring systems is Protection by extra-low voltage the upper limit of voltage Band I, and
recommended. If separated circuits provided by SELV or PELV requires all  The supply is from a permitted
and other circuits are in the same of the following: source, and
wiring system, multi-conductor cables  Limitation of voltage in the SELV or  The requirements applicable to
without metallic covering, or insulated PELV system to the upper limit of SELV or PELV circuits listed below
conductors in insulating conduit, non- voltage Band I which is 50 V a.c. or are met. (Regulation 414.2 refers).
metallic ducting or non-metallic 120 V d.c. and
trunking shall be used, provided that  Protective separation of the SELV or If the system is supplied from a higher
the rated voltage is not less than the PELV system from all circuits other voltage by equipment which provides at
highest nominal voltage, and each than SELV and PELV circuits, and least simple separation between that
circuit is protected against overcurrent.  Basic insulation between the SELV system and the extra-low voltage system
or PELV system and other SELV or but which does not meet the requirements
The protective measure of Extra-Low PELV systems, and for a SELV and PELV source, the require-
Voltage provided by SELV or PELV  For SELV systems only, basic ments for FELV may be applicable.
Protection by extra-low voltage is a insulation between the SELV system
protective measure which consists of and Earth. For further information refer to
either of two different extra-low Guidance Note 5: Protection against
voltage systems, SELV (Separated The extra-low voltage is generally electric shock. 

IET Wiring Matters | Spring 08 | www.theiet.org

Das könnte Ihnen auch gefallen