Fig:ATYPICALLAYOUTOFANUCLEARMEDICINELABORATORYFORDIAGNOSTICSTUDIES(INVIVO)IMAGING)TOTALAREA=

150160SQ.M.

Note:Allthewalls/partitionsoftheNuclearMedicinelaboratoryshouldbemadeof9brickor6concrete.FumeHoodtobe
installed;ifrequired
DecontaminationRoomisoptional.Theactivetoiletmaybeusedforpersonneldecontaminationbyprovidingashowerand
washbasin.


Fig:ATYPICALLAYOUTFORAPETCTFACILITY.TOTALAREA=150160SQ.M.
Note: All the walls /partitions of the PET facility should be made of concrete only, the thickness of which will depend on the
requiredworkload.
DecontaminationRoomisoptional.Theactivetoiletmaybeusedforpersonneldecontaminationbyprovidingashowerand
washbasin.
FacilitiesusingGe68/Ga68generatorwillrequireaHotLabof12sq.m.area.
RadioactivewastestorageroomforPETfacilityisoptional.However,analternativeplacehastobeidentifiedintheHotLab
forstorageofdecayedGe68/Ga68generators.



Fig:ATYPICALLAYOUTFORNUCLEARMEDICINEFACILITYHAVINGBOTHGAMMACAMERAAND
PETCTINSTALLATION
Note:Allthewalls/partitionsoftheNuclearMedicinelaboratoryshouldbemadeof9brickor6concreteonlybutthewallsofthe
PETshouldbemadeofconcreteonly,thethicknessofwhichwilldependontheworkload.
DecontaminationRoomisoptional.Theactivetoiletmaybeusedforpersonneldecontaminationbyprovidingashowerand
washbasin.
FacilitiesusingGe68/Ga68generatorwillrequireaHotLabof12sq.m.area.
RadioactivewastestorageroomforPETfacilityisoptional.However,analternativeplacehastobeidentifiedintheHotLab
forstorageofdecayedGe68/Ga68generators.

Fig:ATYPICALLAYOUTPLANFORA2BEDDEDISOLATIONWARDFORHOSPITALISATIONOFPATIENTSTREATED
WITHLARGEDOSEOFI131.
Note:Allthewalls/partitionsofthefacilityshouldbemadeofconcreteonly,thethicknessofwhichwilldependontheareaof
theroom,positionofthebedandtheoccupanciesallaround.Theductinglineofthefumehoodshouldbeshownintheplan
DecontaminationRoomisoptional.Theactivetoiletmaybeusedforpersonneldecontaminationbyprovidingashowerand
washbasin.Also,theplumbingandductinglinefromtheisolationwardtothedelaytankistobeshownclearly.


Fig:DUALDELAYTANKSYSTEMFORCOLLECTIONANDSAFEDISPOSAL
OFRADIOACTIVEWASTEFROMISOLATIONWARD

Note:Thecapacityofthedelaytankforasinglepatientis3000litres
each.