Sie sind auf Seite 1von 35

A B C D E F G H

1
VENSON ELECTRIC PRIVATE LIMITED 1
No. 331, 4TH PHASE, 9TH CROSS, PEENYA IND. AREA
BENGALURU - 560 058, PH-080-28361208, 28360223
Email : info@vensonelectric.com
Web : www.vensonelectric.com

2 2

PANEL NAME : C & R PANEL FOR 132KV LINE INCOMER


PROJECT NAME : 132/11kV SUBSTATION AT ETHIOPIA AFRICA
CUSTOMER : KANORIA AFRICA TEXTILES
3 CONTRACTOR : SREX POWER PVT LTD. 3

LOI NO. : -
PO NO. : 006/X-293/2014-15,DATED 22.08.2014
JOB NO. : C15031
4 4

DRAWING NO. : C15031B


CONTROL VOLTAGE : 125V DC
REVISION : 2
5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL COVER SHEET BENGALURU PAGE : 1
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

TABLE OF CONTENTS
PAGE PAGE
1 SL. NO. PAGE DESCRIPTION SHEET REV. NO SL. NO. PAGE DESCRIPTION SHEET REV. NO 1

1 COVER SHEET 1 0 34 TERMINAL DIAGRAM 34 2


2 TABLE OF CONTENTS 2 0 35 TERMINAL DIAGRAM 35 2
3 GENERAL ARRANGEMENT 3 2
4 SHEET LEFT BLANK 4 0
5 LEGEND DETAILS 5 0
6 GENERAL NOTES 6 0
7 BILL OF MATERIALS 7 2
2 8 BILL OF MATERIALS 8 2
2
9 BILL OF MATERIALS 9 2
10 GENERAL SYMBOLS 10 0
11 POWER CIRCUIT 11 1
12 DC DISTRIBUTION CIRCUIT 12 1
13 AC DISTRIBUTION CIRCUIT 13 0
14 METERING CIRCUIT 14 0
15 INDICATION CIRCUIT 15 0
3 3
16 INDICATION CIRCUIT 16 0
17 ANNUNCIATOR CIRCUIT 17 0
18 MAIN PROTECTION RELAY CIRCUIT 18 0
19 MAIN PROTECTION RELAY CIRCUIT 19 1
20 MAIN PROTECTION RELAY CIRCUIT 20 1
21 MAIN PROT. RELAY AUTO RECLOSURE/DIRECT TRIP LOGIC 21 0
22 MASTER TRIP RELAY CIRCUIT - 1 22 1
23 BACKUP OC/EF RELAY CIRCUIT 23 0
4 4
24 BACKUP OC/EF RELAY CIRCUIT 24 1
25 MASTER TRIP RELAY CIRCUIT - 2 25 1
26 BREAKER SUPERVISION/CARRIER CIRCUIT 26 1
27 BREAKER CLOSING CIRCUIT 27 1
28 BREAKER TRIP CIRCUIT-1 28 0
29 BREAKER TRIP CIRCUIT-2 29 0
30 ISOLATOR CONTROL CIRCUIT 30 0

5 31 BREAKER CONTROL SWITCH 31 0


32 TERMINAL DIAGRAM 32 2 5

33 TERMINAL DIAGRAM 33 2

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL TABLE OF CONTENTS BENGALURU PAGE : 2
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

14x4 HOLES

25
2200
1 ML 1

50
VENSON
ANN.
1 5 9 13

(Typ.)
2 6 10 14

GLAND PLATE

GLAND PLATE
300
HNT 3 7 11 15 HT

REMOVABLE

REMOVABLE
4 8 12 16

700
750
A MW HZ MVAR V 70 **
132KV BUS 300 30
1775
ASS ICS-1 L5 VSS (Typ.)
S2

2 L3 1 S1 L2 4 2

25
BCS ICS-2 CSS DCSS 100 800 100
TVM
S3
1000

PB1 2 3 4 5
RP S4 FOUNDATION DETAILS
VAJHM33 P442 VAJHM33

86-1 21 86-2
LOCK ARRANGEMENT
3 3
P14D

50/51N

750
VAX31 VAX31 VAX31

95-R1 95-Y1 95-B1

VAX31 VAX31 VAX31

95-R2 95-Y2 95-B2


4 4
1000
VAA33 VAA33 VAA21
63GA COX-1
80DC-A PLAN
63GL COX-2
49T COX-3 80DC-A PROVISION FOR ML
EB EXTENSION CONTROL & RELAY PANEL FOR 132KV
LINE INCOMER
250 RTB - 1 TTB RTB - 2
RP
VENSON ELECTRIC PVT. LTD.
BANGALORE-560 058
100
CUSTOMER : KANORIA AFRICA TEXTILES

PROJECT : 132/11kV SUBSTATION AT ETHOPIA AFRICA


5 0
PO NO. : 006/X-293/2014-15,DATED 22.08.2014
100 100 25 25 5
DATED : AUX SUPPLY: 125V DC

1000 750 SL NO : DRG NO.: C15031B

ELEVATION SIDE VIEW **CUTOUT FOR INTER PANEL WIRING

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL GENERAL ARRANGEMENT BENGALURU PAGE : 3
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1

2 2

SHEET LEFT BLANK


3 3

4 4

5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL SHEET LEFT BLANK BENGALURU PAGE : 4
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1

GA LEGENDS GA LEGENDS
HNT - HOOTER FOR NON TRIP ALARM 21 - DISTANCE PROTECTION RELAY
HT - HOOTER FOR TRIP ALARM 67/67N - BACKUP O/C & E/F RELAY
ANN - ANNUNCIATOR 86 - MASTER TRIP RELAY
A - AMMETER 95-R1 - R-PH TRIP CIRCUIT-1 SUPERVISION RELAY
MW - MW METER 95-Y1 - Y-PH TRIP CIRCUIT-1 SUPERVISION RELAY
MVAr - MVAR METER 95-B1 - B-PH TRIP CIRCUIT-1 SUPERVISION RELAY
2 V - VOLT METER 95-R2 - R-PH TRIP CIRCUIT-2 SUPERVISION RELAY 2
HZ - FREQUENCY METER 95-Y2 - Y-PH TRIP CIRCUIT-2 SUPERVISION RELAY
TVM - TRI-VECTOR METER 95-B2 - B-PH TRIP CIRCUIT-2 SUPERVISION RELAY
S1 - SEMAPHORE FOR BREAKER 63GA - GAS PRESSURE LOW ALARM
S2 - SEMAPHORE FOR BUS ISOLATOR 63GL - GAS PRESSURE LOW TRIP LOCKOUT
S3 - SEMAPHORE FOR LINE ISOLATOR 49T - POLE DISCREPANCY
S4 - SEMAPHORE FOR LINE EARTH SWITCH COX-1 - CARRIER UNHEALTHY
BCS - BREAKER CONTROL SWITCH COX-2 - CARRIER RECEIVED
ICS-1 - BUS ISOLATOR CONTROL SWITCH COX-3 - DIRECT TRIP RECEIVED
ICS-2 - LINE ISOLATOR CONTROL SWITCH 80DC-A - DC SUPERVISION RELAY-1
CSS - CARRIER SELECTOR SWITCH 80DC-B - DC SUPERVISION RELAY-2
3 DCSS - DC SOURCE SELECTOR SWITCH RTB - 1 - RELAY TEST BLOCK FOR DISTANCE RELAY 3
ASS - AMMETER SELECTOR SWITCH RTB - 2 - RELAY TEST BLOCK FOR BACKUP OC/EF RELAY
VSS - VOLTMETER SELECTOR SWITCH TTB - TEST TERMINAL BLOCK FOR TVM
PB1 - LAMP TEST
PB2 - ACCEPT
PB3 - RESET
PB4 - DC FAIL TEST
PB5 - DC FAIL ACCEPT
L1 - BREAKER OPEN IGA LEGENDS
L2 - BREAKER CLOSE
L3 - BREAKER SPRING CHARGED DLS - DOOR LIMIT SWITCH FOR CUBICLE LAMP
4 L4 - BREAKER AUTO TRIP CIL - CUBICAL ILLUMINATION LAMP 4
L5 - DC FAIL SOC - MULTI PIN SOCKET WITH SWITCH
TG - TOGGLE SWITCH FOR SPACE HEATER
SH - SPACE HEATER
TH - THERMOSTAT
X - TERMINAL BLOCKS
FS - FUSES
EB - EARTH BUS
ACB - AC BELL FOR DC FAIL

5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL LEGEND DETAILS BENGALURU PAGE : 5
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

GENERAL NOTES
1. CUBICLE TYPE : SIMPLEX TYPE, DIMENSIONS ARE AS PER GA DRAWINGS
1 1
2. TOLERANCE ON DIM : 3mm

3. DEGREE OF PROTECTION : IP53 AS PER IS2147

4. THICKNESS OF MATERIAL : A. 3mm CRCA SHEET FOR LOAD BEARING MEMBERS


B. 2mm CRCA SHEET FOR NON LOAD BEARING MEMBERS

5. CABLE ENTRY : BOTTOM

6. PAINT : A. EXTERIOR : POWDER COATING SIEMENS GREY AS PER SHADE RAL 7032 NOTE: COLOUR FINISH VIZ., STRUCTURE/MATT/GLOSSY/SEMI GLOSSY TO BE CONFIRMED
2 2
B. INTERIOR : POWDER COATING EGG SHELL WHITE NOTE: INTERIOR COLOUR TO BE CONFIRMED
C. BASE FRAME : ANTICORROSIVE GLOSSY BLACK
D. COATING : ABOVE 60MICRONS
7. MIMIC : SCREEN PRINTED, 132kV BRILLIANT GREEN SHADE 221, 11kV SIGNAL RED SHADE 537(AS PER IS 5),
10mm WIDTH FOR HORIZONTAL BUS , 7mm FOR VERTICAL BUS NOTE: MIMIC COLOUR TO BE CONFIRMED

8. WIRING : FLEXIBLE STRANDED COPPER CONDUCTORS WITH PVC INSULATION, 1.1kV GRADE AS PER IS:694
AC CONTROL CIRCUIT - 2.5Sq.mm WHITE COLOUR CABLES
CT CIRCUITS - 2.5Sq.mm. R, Y, B AND GREEN COLOUR CABLES FOR PHASE IDENTIFICATION
3
DC CONTROL CKT - 2.5Sq.mm. GREY COLOUR CABLES 3
DC TRIP CKT - 2.5Sq.mm. GREY COLOUR CABLES WITH RED SLEAVE FOR POSITIVE IDENTIFICATION
IND. CKT. - 2.5Sqmm. GREY COLOUR CABLES
PT CIRCUITS - 2.5Sq.mm. R, Y, B AND GREEN COLOUR CABLES FOR PHASE IDENTIFICATION
EARTHING - 2.5Sq.mm GREEN & YELLOW COLOUR CABLE
EARTHBUS - 25x6mm COPPER
- ALL DOORS,BODY & GLAND PLATE TO BE EARTH BY BRAIDED COPPER
9. GASKET ARRANGEMENT : NEOPRENE

10. FERRULES : YELLOW/WHITE COLOUR SLEEVES WITH NUMBERS/LETTERS MARKED IN BLACK COLOR
INDIVIDUAL CT/PT/DC/AC CONTROL CIRCUIT SHALL BE DESIGINATED BY A SEPARATE ALPHABETIC LETTER,
4 AS PER IS 375 TO FACILITATE CABEL IDENTIFICATION 4

11. TERMINALS : DISCONNECTING TYPE TERMINALS ( SEREW DRIVER OPERATED) FOR INCOMING CT/PT/AC/DC CIRCUIT WITH SHROUDING
NON-DISCONNECTING TYPE TERMINALS ( NUT AND STUD TYPE) FOR CONTROL AND ANN. CIRCUIT WITH SHROUDING
30% SPARE TB WILL BE PROVIDED

12. INSCRIPTION LABEL : MAIN LABEL (FRONT & BACK ) - ALLUMINIUM/ACRYLIC WITH ENGRAVED LETTERS
APPARATUS LABEL (FRONT) - ALLUMINIUM/ACRYLIC WITH ENGRAVED LETTERS
APPARATUS LABEL (PBs & IND. LAMPs) - ALLUMINIUM/ACRYLIC WITH ENGRAVED LETTERS
APPARATUS LABEL (INTERNAL) - ALLUMINIUM/ACRYLIC WITH ENGRAVED LETTERS
-
5 IDENTIFICATION LABELS (INTERNAL) SELF ADHESIVE STICKER WITH BLACK LETTERS SCREEN PRINTED
RATING PLATE - ALUMINUM ANODISED WITH ENGRAVED (INSIDE & OUT SIDE) 5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL GENERAL NOTES BENGALURU PAGE : 6
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

BILL OF MATERIALS
1 1
SL. NO. DEVICE NAME VENSON CODE DESCRIPTION TYPE/MODEL MAKE QTY.

1 A 30106 DIGITAL AMMETER, CTR: 300/1A,CL:0.5, 4 DIGIT, LED DISPLAY,AUX SUPPLY: 220V AC,BEZEL: 96Sq mm - AE/ELCON/RISHABH 1
2 HZ 30206 DIGITAL FREQUENCY METER,4 DIGIT, LED DISPLAY ,PT RATIO : 132kV/3/100V/3,RANGE 45-55Hz, AUX. - AE/ELCON/RISHABH 1
SUPPLY: 220V AC,ACCURACY +/-0.5 HZ,BEZEL: 96Sq. mm
3 MVAR 30106 DIGITAL MVAR METER,CTR: 300/1A,PTR: 132kV/3/100V/3, RANGE: 82MVAR, CL:0.5,LED DISPLAY, AUX - AE/ELCON/RISHABH 1
SUPPLY: 220V AC,BEZEL: 96 Sq mm
4 MW 30106 DIGITAL MW METER,CTR: 300/1A,PTR: 132kV/3/100V/3, RANGE: 82MW, CL:0.5,LED DISPLAY, AUX - AE/ELCON/RISHABH 1
SUPPLY: 220V AC,BEZEL: 96 Sq mm
5 V 30206 DIGITAL VOLTMETER, PTR: 132kV/3/100V/3, CL:0.5, 4.5 DIGIT, LED DISPLAY,AUX SUPPLY: 220V - AE/ELCON/RISHABH 1
2 2
AC,BEZEL: 96Sq mm
6 21 P442 ALSTOM 1
NEUMERICAL DISTANCE PROTECTION RELAY, AUX SUPPLY:125V DC,CTR : 1A, PTR: 100V AC, 1 & 3 POLE
TRIPPING/RECLOSING WITH 16 INPUTS & 21 OUTPUTS. WITH CHECK SYNCHRONISING,RS485, IEC 61850

7 47T;63GA;63GL; 62304 AUXILARY RELAY,TYPE VAA33, 3 ELE. , 2M/2M/2M H/R CONT., H/R FLAG IND., CASE SIZE:1/2N HORZ,AUX. VAA33 ALSTOM 2
COX-1...COX-3 SUPPLY 110-125V DC
8 80DC 62303 AUXILARY RELAY,TYPE VAA21, 2 ELE.,LH UNIT: 1M+1B,RH UNIT:1M+1B,REVERSE S/R FLAG IND., AUX. VAA21 ALSTOM 1
SUPPLY 125V DC,CASE SIZE:1/2N HORZ
9 86-1;86-2 TYPE VAJHM TRIPPING RELAY 3ELE, AUX. SUPPLY 125V DC, 10M+2B,HAND RESET CONTACT WITH HAND VAJHM33 ALSTOM 2
3 RESET FLAG INDICATOR, CASE: 1-1/2D VERT. 3

10 95-B1;95-B2;95-R1; 62301 TYPE VAX31, TRIP CIRCUIT SUPERVISION RELAY, AUX. 125V DC SUPPLY FOR PRE & POST CLOSE VAX31 ALSTOM 6
95-R2;95-Y1;95-Y2 SUPERVISION, SUITABLE FOR 4 CABLE OPERATION, 2NO+1NC S/R CONT. CASE SIZE 1/2N HORZ
11 67/67N 60604 IDMT DIR/NON DIR 3 OVER CURRENT & 1 EARTH FAULT RELAY WITH HIGH SET, LBB, UV/OV,CHECK SYNC & P14D ALSTOM 1
OTHER BASE FEATURES, AUX. SUPPLY: 125V DC, 8BI, 8BO, CT SEC 1A, PT SEC. 100V AC , FLUSH
MOUNTING,RS 485 PORT AND IEC61850
12 SOC 40906 MULTI-PIN UTILITY SOCKET WITH SWITCH, 3PIN, 5/15A, 240V AC Anchor/EQU. 1
13 CIL 40904 CUBICAL ILLUMINATION,COMPACT FLOUROSCENT LAMP WITH HOLDER, 20W, 240V AC CGL/PHILIPS/EQU 1
14 BX;SX;X2...X6 80302 NON DISCONNECTING TYPE TERMINAL BLOCKS - CW/ELMEX 248
4 15 X1 80301 DISCONNECTING TYPE TERMINAL BLOCKS - CW/ELMEX 44 4
16 S1 40301 SEMAPHORE INDICATOR,AUX SUPPLY 125V DC,BAZEL SIZE : 63mm -- DAV 1
17 S2...S4 40301 SEMAPHORE INDICATOR,AUX SUPPLY 125V DC,BAZEL SIZE : 48mm -- DAV 3
18 ACB 40803 BELL, AUX. SUPPLY: 220V AC EDISON 1
19 CABLE 80101 PVC INSULATED MULTISTRAND FLEXIBLE COPPER CABLE OF SIZE-2.5Sq mm, COLOUR: - FINOLEX/LOPP 1 LOT
RED,YELLOW,BLUE,BLACK, GREEN & GREY.
20 TH 40903 THERMOSTAT 220V AC, SETTING - 35-85 C GIRISH/EQU. 1
21 DLS 40905 DOOR LIMIT SWITCH - IEC 1
22 FS1...FS41 40601 FUSE BASE 20A JAINSON/SG/INDO 41
5 23 FS1;FS2;FS11;FS12 40605 20A HRC FUSE LINK JAINSON/SG/INDO 4
24 FS3...FS6 40604 6A HRC FUSE LINK JAINSON/SG/INDO 4 5

NOTE: KINDLY CONFRIM THE ADAPTIVE CT RATIO


CONSIDERED IS 300/1A CONFIRM IF IT IS CORRECT
REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BILL OF MATERIALS BENGALURU PAGE : 7
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

BILL OF MATERIALS
1 1
SL. NO. DEVICE NAME VENSON CODE DESCRIPTION TYPE/MODEL MAKE QTY.

25 FS7;FS8;FS15;FS16; 40608 10A HRC FUSE LINK JAINSON/SG/INDO 5


FS41
26 FS9;FS10;FS13;FS14; 40605 16A HRC FUSE LINK JAINSON/SG/INDO 7
FS17...FS19
27 FS21;FS23; 40606 4A HRC FUSE LINK JAINSON/SG/INDO 10
FS29...FS31;FS33;
FS35...FS37;FS39
28 FS25...FS27 40607 2A HRC FUSE LINK JAINSON/SG/INDO 3
2 2
29 RTB-1;RTB-2 40402 RELAY TEST BLOCK,WITH TEST PLUG & 3 TRIP BYPASS CONTACT JVS 2
30 TTB 40401 TEST TERMINAL BLOCK,TYPE -3PH,4W, 10A JVS 1
31 HNT;HT 40801 MULTITONE ELECTRONIC HOOTER,96Sqm, AUX. SUPPLY: 125V DC JVS/SECO 2
32 L1 40102 INDICATING LAMP FOR CB OPEN, TYPE - LED,22.5,AUX. SUPPLY:125V DC/220V AC, GREEN - JVS/SECO 1
33 L2 40101 INDICATING LAMP FOR CB CLOSE, TYPE - LED,22.5,AUX. SUPPLY:125V DC/220V AC, RED - JVS/SECO 1
34 L3 40107 INDICATING LAMP FOR CB AUTO TRIP, TYPE - LED,22.5,AUX. SUPPLY:125V DC, WHITE - JVS/SECO 1
35 L4 40103 INDICATING LAMP FOR CB SPRING CHARGED, TYPE - LED,22.5,AUX. SUPPLY:125V DC/220V AC, BLUE JVS/SECO 1
36 L5 40106 INDICATING LAMP FOR DC SUPPLY FAIL, TYPE - LED,22.5,AUX. SUPPLY:220V AC, AMBER - JVS/SECO 1
37 PB1;PB4 40201 PUSH BUTTON ACTUATOR,22.5,GREEN JVS/SECO 2
3 3
38 PB1...PB3;PB5 40205 PUSH BUTTON N/O ELEMENT - JVS/SECO 8
39 PB2;PB5 40202 PUSH BUTTON ACTUATOR,22.5,BLUE JVS/SECO 2
40 PB3 40203 PUSH BUTTON ACTUATOR,22.5,YELLOW JVS/SECO 1
41 PB4 40205 PUSH BUTTON N/C ELEMENT - JVS/SECO 4
42 ANN 40705 ALARM ANNUNCIATOR, - MINILEC 1
16 WINDOW,AUX SUPPLY: 125V DC,
BUILTIN LAMP FOR TEST, ACCEPT,RESET
42 TVM 30804 TRIVECTOR METER,PTR : 132kV/100V/3V AC,CTR : 300/1A CL:0.2, 3PH,4W,3ELE,RS 485 PORT, WITH - SECURE/L&T 1
IMPORT & EXPORT FEATURE
4 44 43;AKT AUXILARY CONTACTOR, DIN MOUNTING TYPE, 2NO+2NC, AUX. SUPPLY: 220V AC. 3TH30 SIEMENS/EQU 2 4
45 CSS CARRIER SEECTOR SWITCH, 2 POSITION (IN,OUT) 10A,4 POLE( 2IN-2OUT POSITION),ROTARY TYPE - SWITRON/RECOM 1
46 ASS 50305 AMMETER SELECTOR SWITCH, 10A, 3 POSITION WITH OFF( R,Y,B & OFF), MAKE BEFORE BREAK TYPE - SWITRON/RECOM 1
47 BCS 50121 BREAKER CONTROL SWITCH,PISTOL GRIP HANDLE,3 POSITION,ODS MOUNTING, POLES AS PER DRAWING - SWITRON/RECOM 1
,32A,WITH SEQUENCE LOCKING(LMD)
48 DCSS DC SOURCE SELECTOR SWITCH, 32A, 220V DC, STAY PUT NON-LOCKABLE WITH PISTOL GRIP BLACK - SWITRON/RECOM 1
HANDLE POSITION (1) DC-1 (2) INDEPENDENT (3) DC-2, AS PER DRAWING
49 ICS-1;ICS-2 50103 ISOLATOR CONTROL SWITCH (OPEN,NORMAL,CLOSE), 3 POSITION SPRING RETURN TO NORMAL PISTOL - SWITRON/RECOM 2
GRIP HANDLE,25A, WAYS (2C+2O), ODS MOUNTING
5 50 VSS 50402 VOLTMETER SELECTOR SWITCH, 3 POSITION WITH OFF(RY,YB,BR,OFF),10A - SWITRON/RECOM 1
51 TG 40902 TOGGLE SWITCH 1P,10A,220V AC SWITRON/RECOM/EQU. 1 5

52 EB EARTH BUS,25x6mm COPPER WITH THREADED HOLES AT 50mm GAP VENSON 1


NOTE: KINDLY CONFRIM THE ADAPTIVE CT RATIO
CONSIDERED IS 300/1A CONFIRM IF IT IS CORRECT
REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BILL OF MATERIALS BENGALURU PAGE : 8
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

BILL OF MATERIALS
1 1
SL. NO. DEVICE NAME VENSON CODE DESCRIPTION TYPE/MODEL MAKE QTY.

53 PNL SIMPLEX TYPE ENCLOSURE, DIMENSIONS ARE AS PER GA DRAWING. VENSON 1


54 FS20;FS22;FS24;FS28; 40610 COPPER NEUTRAL LINK VENSON 8
FS32;FS34;FS38;FS40
55 SH 40901 SPACE HEATER, PLATE TYPE, 220V AC, 100W VENSON/SURYA/EQU. 1

2 2

3 3

4 4

5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BILL OF MATERIALS BENGALURU PAGE : 9
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


1 1

THREE POLE ISOLATOR SHIELDED CABLE ROTARY SWITCH WITH NO CONTACT FIXED RESISTOR

THREE POLE CIRCUIT BREAKER INDICATION LAMP SP SWITCH (GENERAL) VARIABLE RESISTOR

LIGHTING ARRESTER SPACE HEATER PUSH BUTTON, NO CONTACT CAPACITOR

2 DISCONNECTING TYPE 2
TWO PIN SOCKET PUSH BUTTON, NC CONTACT INDUCTOR
TERMINAL (CLOSE CONDITION)

DISCONNECTING TYPE
TWO PIN PLUG LIMIT SWITCH
TERMINAL (OPEN CONDITION)

NON-DISCCONNECTING TYPE
THREE PIN SOCKET AUXILARY NO CONTACT
TERMINAL

3 WAVE TRAP THREE PIN PLUG AUXILARY NC CONTACT 3

CURRENT TRANSFORMER ILLUMINATION LAMP THERMOSTAT

POTENTIAL TRANSFORMER SEMAPHORE INDICATOR AUXILARY CHANGE-OVER CONTACT

THREE PHASE TRANSFORMER THREE POSITION SWITCH CONTACTOR/RELAY


4 4

FUSE (GENERAL) TWO POSITION SWITCH TIMER RELAY

POWER EARTHING M SINGLE PHASE AC MOTOR ELECTRIC BELL


1~

RTB
SINGLE POLE MCB RELAY TEST BLOCK ELECTRIC HOOTER/BUZZER

5
5
TWO POLE MCB ROTARY SWITCH WITH NC CONTACT LED LAMP

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL GENERAL SYMBOLS BENGALURU PAGE : 10
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

C B A

LIGHTNING ARRESTOR
132kV MAIN BUS

CORE4:CL 0.2,10VA

LINE ISOLATOR
300-600/1-1-1-1A

12KV,10KA,50HZ
1 1

CORE2:CL 5P20

132KV
89LE
CORE1:CL PS

CORE3:CL PS
3150A,31.5KA/1SEC
1POLE INTERLOCK

132kV CT

WAVE TRAP
132kV,SF6 CB
BUS ISOLATO

LINE ISOLATOR
LA

132KV
89L
89B

52P
132KV

P1 P2

132kV LINE
INCOMING
/
P1
1S1 1S2 2S1 2S2 3S1 3S2 4S1 4S2
P2
/
P1 1S1 1S2 2S1 2S2 3S1 3S2 4S1 4S2 P2
/
1S1 1S2 2S1 2S2 3S1 3S2 4S1 4S2

2 2

LINE CVT
132kV/3/100V3-100V3-100V3-100V3-100V3
CORE 4: CL 3P, CORE 3: CL 3P, CORE 2: CL 0.2, CORE 1: CL 0.2,
BURDEN: 100VA BURDEN: 100VA BURDEN: 100VA BURDEN: 100VA

LK

FS

FS
FS

LK
FS

FS

FS

LK
FS

FS

FS

LK
FS

FS

FS
BUS CVT
3 132kV/3/100V/3-100V/3 3
CTJB -PTJB
INPUT FROM XMER PANEL

BX 8 BX 7
C B A
SPARE SPARE SPARE

FIELD

-X1 -X1 PANEL SCOPE


4 4
BX BX * * * -X1 * * * -X1 * * * -X1 14 13 12 11 10 9 8 7
8 7
35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15
G71 /

G11 /

G71 /

G11 /

A71 /

A51 /

A31 /

A11 /

C71 /

C51 /

C31 /

C11 /

D71 /

D51 /

D31 /

D11 /

E71 / 18.B:5
E51 / 18.B:4
E31 / 18.B:4
E11 / 18.B:3

E81 / 14.A:5
E61 / 14.A:4
E41 / 14.A:4
E21 / 14.A:4
23.B:5

23.B:5

18.B:5

18.B:5

18.A:2

18.A:2

18.A:2

18.A:1

23.B:2

23.B:2

23.B:2

23.B:1

14.A:4

14.A:3

14.A:3

14.A:3
TO BACKUP TO MAIN TO MAIN PROTECTION TO BACKUP PROTECTION TO METERING CIRCUIT TO MAIN PROTECTION TO METERING
PROTECTION PROTECTION CIRCUIT CIRCUIT CIRCUIT CIRCUIT R
5 CIRCUIT CIRCUIT

5
*NOTE:
120 120
1.CT/PT RATIO & CORE DETAILS TO BE PROVIDED
2.MARKED TB's TO BE MADE SHORTED BEFORE
120
REMOVING THE INSTRUMENT FOR SERVICE/REPAIR B Y
PHASE ROTATION

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL POWER CIRCUIT BENGALURU PAGE : 11
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

DC SUPPLY
SUPERVISION RELAY
DC FAIL TEST
DCSS 80DC VAA21
DC -PB4
1 DCDB DC-1 I DC-2 1
X1 FS1
1 J1A J1B 1 2
J1 2 1
J5
+VE
1 A 20A 9
AUX. SUPPLY GREEN
125V DC FROM A
DCDB SOURCE-1 2 J2A J2B FS2 J2
1 2
-VE
2 B 20A 10

1 1 1 1 1 1 1 1
BX FS3 FS4 FS5 FS6 FS7 FS8 FS9 FS10
6A 6A 6A 6A 10A 10A 16A 16A
2 2 2 2 2 2 2 2
1 3 C

2 2
2 4 D

L1 L2 L5 L6 K101 K102 K1 K2

L1 L2 L5 L6 K101 K102 K1 K2
15.B:1 15.B:5 17.A:1 17.A:1 18.H:1 18.H:1 27.B:1 27.B:1

TO INDICATION TO ANNUNCIATOR TO MAIN TO CLOSING &


CIRCUIT CIRCUIT PROTECTION CIRCUIT TRIPPING CIRCUIT-1
BX
3 3 5 E
3

4 6 F DC FAIL TEST

DC -PB4
DCDB
X1 FS11
3 J3A J3B 1 2
J3 2 1
J7
+VE
7 G 20A 11
AUX. SUPPLY GREEN
125V DC FROM B
DCDB SOURCE-2 4 J4A J4B FS12 J4
1 2
-VE
8 H 20A 12

1 1 1 1 1 1
4 4
FS13 FS14 FS15 FS16 FS17 FS18
16A 16A 10A 10A 16A 16A
2 2 2 2 2 2

TO ALARM 1 2 \13.C:3

TO ALARM 5 6 \13.D:3
R1 R2 K201 K202 K3 K4

R1 R2 K201 K202 K3 K4
30.A:1 30.H:1 23.G:1 23.H:1 27.F:1 27.F:1
5
TO ISOLATOR TO BACKUP TRIPPING CIRCUIT-2
5
CONTROL CIRCUIT PROTECTION CIRCUIT

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL DC DISTRIBUTION CIRCUIT BENGALURU PAGE : 12
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1

AC
AC SOURCE
X1 H1 FS19 H3
2 5 1 2 2
P
16A
AUX. SUPPLY
22V AC FROM
ACDB 6 H2 FS20 H4 11
1 2
N -DLS -TG
LK 12

BX FS23
1 2 H13 H13 / 14.A:1
5 4A
SOC
1 5
H5 H7
6
80DC-A 80DC-B
3 \12.H:1 2 \12.H:4 6 3
FS21 FS22

TO METERING CIRCUIT
4A LK
TH
H17

AC/DC CHANGE H51 H52 PE


OVER CONTACTOR H9
1 3 6
AKT -PB5 AKT A1
\13.D:4 4 BLUE 4 \13.D:4 7 43
ACCEPT AUX CONTACTOR A2

H19 H21
4 CIL SH 4
A1 x1 20W

ACB AKT L5 5 3 \15.D:1


AUX CONTACTOR 6 4 \15.D:5
A2 ABMER x2
9 7 \15.F:1 H51 H52
FS24 8 \15.F:5
1 2 H14 H14 / 14.A:1
10 15.G:1 15.G:5
TO INDICATION
LK
DC FAIL ALARM DC SUPPLY CIRCUIT CUBICAL SPACE 5/15A, POWER
BELL ACCEPT FAIL ILLUMINATION HEATER SOCKET
LAMP
1 4 \13.C:4
6 7 \13.D:4

5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL AC DISTRIBUTION CIRCUIT BENGALURU PAGE : 13
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

H13
AUX 13.E:3 / H13
SUPPLY H14
13.E:4 / H14

1 1
Ph N Ph N Ph N Ph N
TVM MW MVAR A V
AR AY AB VOLTAGE AR AY AB VOLTAGE

S1 S2 S1 S2 S1 S2 VR VY VB N S1 S2 S1 S2 S1 S2 VR VY VB S1 S2 S1 S2 S1 S2 VR VY VB
I/P I/P
D13

D14

D33

D34

D53

D54
E25

E45
E65
E85

D15

D17
D35

D37

D55

D57

D17

D19
D37

D39
D57

D59

D72
D71
E23

E43

E63

E23

E43

E63

E91
E90
2 2

-TTB 2 3 4 6 7 8 10 11 12 1 5 9 13
IS IL V1 V2

R Y B N
ASS -VSS
R Y B R Y B

D19
D39
D59
E23

E43
E63

D11 E83
11.F:4 / D11

3 3
D31
11.E:4 / D31
FROM
CT
D51
11.E:4 / D51

D71
11.E:4 / D71

4 E21 FS25 E23 4


11.H:4 / E21
2A

E41 FS26 E43


11.G:4 / E41
FROM 2A
PT E61 FS27 E63
11.G:4 / E61
2A

H14
H13
E43
E63
E81 FS28 E83
11.G:4 / E81
LK

VY VB
5
N 5
HZ Ph

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL METERING CIRCUIT BENGALURU PAGE : 14
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

L1 43 L1A L1A 43 H51


5 3 7 9
12.D:2 / L1 H51 / 13.F:4
\13.E:4 \13.E:4

1 1
X3 1 X3 5

X1 150
62
(2A)52b (2A)52a (2A)52b (2A)52b (2A)52a 88M(A)-A
61

X1 152

132kV CIRCUIT BREAKER


132kV CIRCUIT BREAKER
X1 154
2 62 2
(2B)52b (2B)52a (2B)52b (2B)52b (2B)52a 88M(B)-A
61

X1 156

X1 158
62
(2C)52b (2C)52a (2C)52b (2C)52b (2C)52a 88M(C)-A
61

X1 160

3 3
DC SUPPLY X3 2 X3 3 X3 4 X3 6 X3 7 X3 8 AC SUPPLY

L7
-BCS
H
\31.D:3 T
NAT
N
NAC
C
8

L9
-BCS
4 7 4
\31.D:3 T
L3 L5 L13 L15 L17
NAT
N
NAC
C
G
2 1

S1
L11
3 + + + +
x1
L3 L1 L2 L4
R WHITE - GREEN - RED - BLUE -
__k,__W
SPRING CHARGE
x2

5
AUTO TRIP
BREAKER

BREAKER

BREAKER

BREAKER

BREAKER
STATUS

5
CLOSE
OPEN

L2 43 6 4 L2A L2A 438 10 H52


12.D:2 / L2 H52 / 13.F:4
\13.E:4 \13.E:4

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL INDICATION CIRCUIT BENGALURU PAGE : 15
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

L1
/ L1

1 1

X3 11 X3 14 X3 17

132KV ISOLATOR EARTH SWITCH


132KV BUS SIDE ISOLATOR

132KV LINE ISOLATOR


2 89Ba 89Bb 89La 89Lb 89LEa 89LEb 2

X3 12 X3 13 X3 15 X3 16 X3 18 X3 19
3 3

DC SUPPLY

4 4
L19 L21 L23 L25 L27 L29

2 1 2 1 2 1

S2 S3 S4

3 3 3
x1 x1 x1

R R R
__k,__W x2 __k,__W x2 __k,__W x2
5
LINE ISO E/S

5
LINE ISO
BUS ISO
STATUS

STATUS

STATUS

L2
/ L2

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL INDICATION CIRCUIT BENGALURU PAGE : 16
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

12.E:2 12.E:2
L6 L5 -ANN

1
L6 L5 1
-W1 W5 W9 W13
DISTANCE MAIN RELAY CB GAS
CARRIER
PROTECTION AUTO RECLOSURE PRESSURE LOW
UNHEALTHY
+ OPERATED OPERATED ALARM

TP
HT W2 W6 W10 W14

L51 MAIN RELAY BACK UP RELAY CB GAS


DIRECT TRIP
TP DIR. OC/EF OVER CURRENT PRESSURE LOW
HOOTER FOR RECEIVED
2 TRIP OPERATED OPERATED LOCKOUT 2
HNT NT
L53
NT
HOOTER FOR
NON-TRIP
W3 W7 W11 W15
MAIN RELAY BACK UP RELAY BACK UP RELAY
CB POLE
SOTF EARTH FAULT LBB PROT.
DISCREPANCY OPTD
OPERATED OPERATED OPERATED
-PB1
TEST 4 3 L57
T
GREEN

3 -PB2 3
ACCEPT 4 3 L59
A
BLUE
W4 W8 W12 W16
SILENCE
-PB3
L61 MAIN RELAY BREAKER
RESET 4 3 MAIN RELAY
R LAMP TEST PT FUSE FAILURE TRIP CKT-1/2 SPARE
YELLOW /BACUP RELAY FAULTY
OPERATED FAULTY
ACCEPT
L63
C RESET

COM W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 W11 W12 W13 W14 W15 W16

4 L101 L103 L105 L107 L109 L111 L113 L115 L117 L119 L121 L123 L125 L127 L129 L131 L133 4

X3 23
\20.C:2

\20.C:3

\20.C:3

\20.C:4

\20.C:4

\24.F:2

\24.F:3

\18.E:2

\23.F:4

\24.F:3
\28.C:2

\28.E:2

\28.H:2

\29.C:2

\29.E:2

\29.H:2

\26.E:4

\26.F:4
\26.B:4

\26.C:4

\26.C:4
1 1 1 1 1 1 17 3

SPARE
H5 H8 H11 H14 H17 38 42 J11 3 17 19 3 29

95-R1

95-Y1

95-B1

95-R2

95-Y2

95-B2

COX-1

COX-3
2 2 2 2 2 2 18 4
63GA

47T
63GL

H6 H9 H12 H15 H18 40 44 J12 5 18 20 4 31


-21-WD

-67/67N-WD
-21-RL3

-21-RL4

-21-RL5

-21-RL6

-21-RL7

-67/67N-RL3

-67/67N-RL4

-67/67N-RL5
5
5
X3 24

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL ANNUNCIATOR CIRCUIT BENGALURU PAGE : 17
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

12.F:2 12.F:2
DISTANCE PROTN. RELAY K101 K102

-RTB-1 21 ALSTOM, P442 K101 K102


1 + 1

A11 2 1 A12 J2
11.C:4 / A11
C3 Ia -
J1
C2 NOTE:
A31 4 3 A32 CASE PB & LED TO BE ASSIGNED FOR CHECK SYNC
11.C:4 / A31 EARTHING
C6 Ib
+
FROM HV
C5
SIDE CT J18
A51 6 5 A52 -
11.B:4 / A51
C9 RS485
Ic J17
2 SCN 2
C8
A73
J16

A71 8 7 A72 C11 Im WD L117


11.B:4 / A71 WATCH DOG J11 TO ANN.,
C12 (RELAY FAIL) \17.D:5
CKT
L101
23.B:3 / E11 J12
23.B:3 / E31 RL8 K1
TO BACKUP
PROTECTION G1
23.B:4 / E51 \28.B:2
CIRCUIT
K23A
3 23.B:4 / E71 3
G2
RL9
E11 10 9 FS29 E15
11.G:4 / E11 G3
C19
\28.E:2 TO TRIP CKT-1
2A
Va
K23B
G4
RL10
FS30 G5
E31 12 11 E35 \28.G:2
11.G:4 / E31
C20 K23C
2A
LINE CVT Vb G6
4 INPUT 4
RL15 K3
F1
\29.B:2
E31 14 13 FS31 K43A
11.G:4 / E51
2A C21 F2
Vc RL16
E31 16 15 FS32
F3
11.G:4 / E71 \29.E:2 TO TRIP CKT-2
LK C22 K43B
FS33 F4
G11 18 17 G12 G13
11.B:4 / G11 RL17
5 2A C23 F5
BUS PT Vc \29.G:2
5
INPUT FS34 K43C
G71 20 19 G72 G73
11.A:4 / G71 K101 K102
C24 F6
LK 19.A:1 19.A:1

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL MAIN PROTECTION RELAY CIRCUIT BENGALURU PAGE : 18
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

18.H:5 18.H:5 DISTANCE PROTN. RELAY 19.A:5 19.A:5


K101 K102 K102 K101
CB 21 ALSTOM, P442
K101 K102 52Ra 47T K102 K101
1
-X4 -X4 K111 K127 1
BI1 BI9 2 1

1 2 D2 CB R-PH CLOSE CB POLE E2 \26.C:4


DISCREPANCY

D1 E1 -86-1-A4
8 7
52Ya \22.E:2
K113 BI2 BI10 K129
3 4 D4 CB Y-PH CLOSE E4 -86-2-A4
MTR. OPTD 8 7

\25.E:2
D3 E3
2 2
52Ba RTB-1
K115 BI3 BI11 K131
5 6 D6 CB B-PH CLOSE RTB STATUS
E6 21 22

D5 E5

COX-1 -BCS T NAT N NAC C


14 13 K117 BI4 BI12 K133 \31.D:2

\26.E:4 D8 CARRIER BCS CLOSE E8 D 4

UNHEALTHY (FOR SOTF LOGIC)

3 D7 E7 3

COX-2 -BCS T NAT N NAC C


16 15 K119 BI5 BI13 K135 \31.D:4

\26.E:4 D10 CARRIER BCS TRIP E10 P 16


(FOR AUTO RECLOSE
RECEIVED
BLOCK LOGIC)
D9 E9

COX-3 CSS IN OUT


2 1 K121 BI6 BI14 K137
\26.F:4 D12 DIRECT TRIP CARRIER ENABLED E12 1 A

RECEIVED
4 4
D11 E11

63GA -X4 -X4


14 13 K123 BI7 BI15 K139
\26.B:4 D14 CB GAS PR.,
E14 7 8
LOW ALARM

D13 E13

63GL
16 15 K125 BI8 BI16 K141
5 \26.C:4 D16 CB GAS PR.,
E16 9 10
K102 LOW TRIP L/O K102 5
D15 E15

K101 K102 K102 K101


19.H:1 19.H:1 22.A:1 22.A:1
REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL MAIN PROTECTION RELAY CIRCUIT BENGALURU PAGE : 19
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

*NOTE: INBUILT PUSH BUTTON & LED SHALL BE


DISTANCE PROTN. RELAY PROGRAMMED TO SELECT CHECK/DEAD LINE FUNCTIONAL

21 ALSTOM,P442
1 1
RL1 RL11
K103 K13A
H1 * G8
TO MASTER \22.C:2 COMMON TRIP CHECK SYNC
\27.D:2
TRIP RELAY-1(86-1) CHECK/DEAD LINE
G7
K103A K15A
H2 G9
TO CLOSING CKT
RL2 RL12
K203 K13A
H3 G11
TO MASTER \25.C:2 COMMON TRIP AUTO RECLOSE \27.E:3
TRIP RELAY-2(86-2) K203A
G10
K17
2 2
H4 G12
L103 RL3 RL13 3U13 X6
H5 G14 13
\17.B:5 DISTANCE CARRIER SEND
OPTD G13
L101 3U14 (TO PLCC PANEL CHANNEL-1)
H6 G15 14
L105 RL4 RL14 3U15
H8 G17 15
\17.B:5
DIR OC/EF DIRECT TRIP SEND
3 H7 OPTD G16 (TO PLCC PANEL CHANNEL-1) 3
3U16
H9 G18 16
TO ANNUNCIATOR L107 RL5 RL18 3U17 X6
CIRCUIT
H11 F8 17
\17.C:5
SOTF CARRIER SEND
H10 OPTD F7 (TO PLCC PANEL CHANNEL-2)
3U18
H12 F9 18
L109 RL6 RL19 3U19
H14 F11 19
4
\17.C:5
PT FUSE DIRECT TRIP SEND 4
H13 FAILURE F10 (TO PLCC PANEL CHANNEL-2)
OPTD 3U20
H15 F12 20
L111 RL7 RL20 1U1 X5
H17 F14 1U2 1
AUTO
\17.C:5
H16 RECLOSURE F13 2
OPTD 1U3
H18 F15 3
RL21 SPARE
1U4
5
F17 1U5 4 5
F16 5
1U6
F18 6

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL MAIN PROTECTION RELAY CIRCUIT BENGALURU PAGE : 20
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

DIRECT TRIP INTERNAL LOGIC

MANUAL TRIP OPTD(BCS SWITCH)


1 1
UNDER VOLTAGE OPTD
DIRECT TRIP SEND
LBB OPTD(INTERNAL DETECTION)

CARRIER ENABLED

AUTO RECLOSURE INTERNAL LOGIC


A/R BLOCK
86-1/2 OPTD
2 2

A/R DISABLED
A/R BLOCKED
CARRIER FAIL

BREAKER TROUBLE

A/R LOCKOUT

A/R LOCKOUT
3 3

MULTIPHASE FAULT
A/R LOCKOUT
AUTO RECLOSURE FAIL

A/R PICKUP
PH-GND FAULT-ZONE1
INITIATE TRIP TO FAULTY POLE-R/Y/B
4 4

PH-GND FAULT-ZONE2
A/R PICKUP
CARRIER RECEIVED

A/R INITIATE

PICKUP
A/R PICKUP DELAY-mSEC
5
A/R INITIATE 5

AGAIN FAULT DETECTED

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - MAIN PROT. RELAY AUTO RECLOSURE/DIRECT TRIP 27.OCT.2014
DETAIL BENGALURU PAGE : 21
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 LOGIC OF 35
A B C D E F G H
19.H:5 19.H:5
K101 K102
MASTER TRIP RELAY - 1
86-1 VAJHM33
K101 K102
1 K1 1

A1 1 K23A \28.B:2

RTB-1 -21-RL1 TO TRIPPING


K103A H2 H1
K103 A2 3 K23B \28.D:2
COIL-1
23 24 \20.C:1 19 4

19 19 19
A3 5 K23C \28.G:2
RTB-2 -67/67N-RL1
K103B 32 30 9 9 9
6
2 2
23 24 \24.F:1 K101
A
TO MAIN
A4 7 K129 \19.G:1
DIFF RELAY
-X4 X4 K103 8
K101 FUTURE TRIP
15 16 K3
B1 11 K43A \29.B:2

12

TO TRIPPING
3 B2 13 K43B \29.D:2 3
B COIL-2
14

B3 15 K43C \29.G:2

16
K201
TO BACKUP
B4 17 K215 \24.C:2
RELAY
18

4 K7 4
TO CLOSING
C1 21 K5A \27.C:2
INTERLOCK
22
C U9 X5
C2 23 U10 9
24 10
U11
K102 25 11 SPARE
C3 U12
10
5 26 12
U13 5
C4 27 U14 13
K101 K102 28 14
26.A:1 26.A:5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL MASTER TRIP RELAY CIRCUIT - 1 BENGALURU PAGE : 22
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

12.F:5 12.F:5
BACK UP OC/EF RELAY K201 K202

-RTB-2 67/67N ALSTOM, P14D


1 1
K201 K202
C11 2 1
C12
11.D:4 / C11
21 Ia
K201
13:+
22 AUX.
C31 4 3
C32 SUPPLY
11.D:4 / C31 K202
23 Ib
FROM
14:-
CT
C51 C52 C73 24
6 5
11.D:4 / C51
25 Ic 54
2 2
26 RS485
COM PORT 56
C71 8 7
C72 27 EF
11.C:4 / C71 SCN
28

E11 10 9
E12 FS35 E13
18.B:3 / E11
4A 17
3 Va 4 3
WD
RELAY
HEALTHY
E31 12 11
E32 FS36 E33 6
18.B:3 / E31
4A 18
Vb
L117
FROM
3
BUS PT
WD \17.D:5 TO ANNUNCIATOR
E51 E52 FS37 E53 WATCH DOG(RELAY FAIL) L101
14 13
18.B:3 / E51
4A 19 5
4 4
Vc
E71 16 15
E72 FS38 E73
18.B:3 / E71
LK 20
1

G11 18 17
G15 FS39 G17 CASE
EARTHING
11.A:4 / G11
4A 15
LINE PT INPUT V CHECK
FOR CHECK SYNC. G71 G75 G77 SYNC
20 19 FS40
11.A:4 / G71
LK 16
5
5
K201 K202
24.B:1 24.B:1

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BACKUP OC/EF RELAY CIRCUIT BENGALURU PAGE : 23
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

23.G:5 23.H:5
K201 K202

BACK UP OC/EF RELAY


1 K201 K202 67/67N ALSTOM, P14D 1
CB
52b K103
-X4 X1 29 39 40 30 X1 -X4 K211 COMMON TRIP
30

+
TO MASTER
21 40 41 22 46 RL1 \22.C:2
L1 TRIP RELAY-1(86-1)
- CB OPEN
K103B
32
-X4 52a
X1 27 37 38 28 X1 -X4 K213 COMMON TRIP
K203

+
34 TO MASTER
23 38 29 24 48 L2 RL2 \25.C:2 TRIP RELAY-2(86-2)
- CB CLOSE K203B
-86-1-B4
2 17 18 36 2

\22.E:4 K215 L113

+
OC OPTD
-86-2-B4 50 L3 38
RL3 \17.C:5
17 18 - MTR. OPTD
L101
\25.E:4 K202
40
52
L115
RTB-2 EF OPTD
K217 42
RL4 \17.D:5 TO ANNUNCIATOR

+
21 22 45 L4
- RTB STATUS
3 44 3
L131
-X4 -X4 K219 LBB INITIATED
29

+
RL5 \17.H:5
25 26 47 L5
-

31
2U25 -X5
K221
25

+
33
27 28 49 L6 RL6 SPARE
- 2U26
4 35 26 4
2U27 -BX
K223
+

LBB INITIATE
29 30 51 L7 37 11 LBB INITIATE TO
RL7 ADJACENT FEEDER
-
2U28 86-2 RELAY
39 12
K225 2U29
+

31 32 53 L8 LBB INITIATE
41 13 LBB INITIATE TO
- RL8 TRANSFORMER
2U30 86 RELAY
K202
5 43 14
55
5

K201 K202
25.A:1 25.A:1

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BACKUP OC/EF RELAY CIRCUIT BENGALURU PAGE : 24
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H
24.B:5 24.B:5
K201 K202
MASTER TRIP RELAY - 2
86-2 VAJHM33
K201 K202
1 K1 1

A1 1 K23A \28.B:2

RTB- 1 -21-RL2 TO TRIPPING


K203A H4 H3
K203 A2 3 K23B \28.D:2
COIL-1
25 26 \20.C:2 19 4

RTB- 2 -67/67N-RL2 19 19 19
K203B A3 5 K23C \28.G:2
36 34
9 9 9
2 25 26 \24.F:2 6 2
K101
A
TO MAIN
A4 7 K129 \19.G:2
DIFF RELAY
-X4 X4 K203 8
FUTURE TRIP
35 36
K3
B1 11 K43A \29.B:2
BX LBB TRIP FROM BX
12
17 ADJACENT FEEDER 18
TO TRIPPING
3 B2 13 K43B \29.D:2 3
LBB TRIP FROM B COIL-2
19 XMER 20 14

B3 15 K43C \29.G:2

16
K201
TO BACKUP
B4 17 K215 \24.C:2
RELAY
18

4 K13 4
TO CLOSING
C1 21 K13A \27.D:2
INTERLOCK
22
C U17 X5
C2 23 U18 17
24 18
U19
K102 25 19 SPARE
C3 U20
10
5 26 20
U21 5
C4 27 U22 21
28 22

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL MASTER TRIP RELAY CIRCUIT - 2 BENGALURU PAGE : 25
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

22.A:5 / K101

K101
1 1

X6 1 X6 7

MARSHALLING
BOX

2 2

CB GAS PR
CB GAS PR CB POLE

DIRECT TRIP
LOW TRIP

UNHEALTHY
LOW ALARM DICREPANCY

RECEIVED

RECEIVED
CHANNEL-1

CHANNEL-2

CHANNEL-1

CHANNEL-2

CHANNEL-1

CHANNEL-2
LOCKOUT

CARRIER

CARRIER
3 3

X6 2 3 4 X6 8 9 10

K51 K53 K55 K57 K59 K61

VAA33 6 8 10 VAA33 6 8 10
4 63GA 63GL 47T COX-1 COX-2 COX-3 4
5 7 9 5 7 9
1st ELE. 2nd ELE. 3rd ELE. 1st ELE. 2nd ELE. 3rd ELE.

K102
22.A:5 / K102
13 14 1 2 13 14 1 2
\19.B:4 \19.G:1 \19.B:3 \19.B:4
17 18 3 4 17 18 3 4
5
\17.E:5 \17.E:5 \17.G:5 \17.G:5
5
15 16 15 16
\19.B:5 \19.B:3
19 20 19 20
\17.E:5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BREAKER SUPERVISION/CARRIER CIRCUIT BENGALURU PAGE : 26
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

FROM FROM
DC SOURC 19 K9A 19
DC SOURC

12.G:2 12.G:2 95-B1 95-R2 12.G:5 12.G:5


K1 K2 \28.H:2 20 \29.C:2 20 K3 K4
1 K9 K11 1

K1 K2 19 19 K3 K4
95-Y1 95-Y2
\28.E:2 20 \29.E:2 20

K7A K11A
19 19
95-R1 95-B2
\28.C:2 20 \29.H:2 20

K7 K13
21 21

2 -86-1-C1 -86-2-C1 2
\22.E:4 22 \25.E:4 22

K5A K13A
G8
-21-RL11
\20.D:1 G9
K15A
X2 5
-BCS T
2 SX 1
FUTURE \31.D:2
3 INTERLOCK NAT G11 3
SCADA
N CLOSE -21-RL12
X2 6 NAC \20.D:2 G12
C
K5 B SX 2

FS41
10A

K15 K17
4 4

X2 1 X2 2 X2 7 X2 8 X2 3 X2 4

X1 9 X1 10 X1 33 X1 44 X1 18 X1 20
CIRCUIT BREAKER

CG MAKE
145KV,40KA,1POLE SP SPR GCB
J1 J2 K1 K3A J5 J6
K1 K2 K3 K4
52

28.A:1 28.A:1 29.A:1 29.A:1


5 +VE -VE +VE -VE
AUX. SUPPLY REMOTE AUTO AUX. SUPPLY 5
CLOSE RECLOSE
DRAWING NO:EH4-4199-12

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BREAKER CLOSING CIRCUIT BENGALURU PAGE : 27
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1
K2 K2 K2
27.A:5 / K2
FROM
DC SOURCE
K1 K1 K1
27.A:5 / K1

1 1 G1
95-R1 VAX31 3 3 G3
95-Y1 VAX31 5 5 G5
95-B1 VAX31
G2 + 4 4 G4 + G6 +
2 2
-21-RL8 X2 41 X2 43 6 6 X2 45

-86-1-A2

-86-2-A2

-21-RL9

-21-RL10
\18.E:3

\22.E:1

\25.E:1

\18.E:3

\18.E:4
-86-1-A1

-86-2-A1

-86-1-A3

-86-2-A3
\22.E:1

\25.E:1

\22.E:2

\25.E:2
18 12 12
FUTURE FUTURE FUTURE
TRIP 11 TRIP 4 TRIP 4

2 X2 42 X2 44 X2 46 2

12 OR 1 OR 1 OR

10 2 2

C C C

9 E - 17 3 E - 17 3 E - 17
3 3

K2 K2 K2
1 2 \17.F:5 1 2 \17.F:5 1 2 \17.F:5
-BCS 1 -BCS 3 -BCS 5
\31.D:2 T SX 3 3 4 \31.B:2
\31.D:2 T SX 5 3 4 \31.B:2
\31.D:2 T SX 7 13 14 \31.B:3
19 20 \27.C:2 19 20 \27.C:1 19 20 \27.C:1
NAT NAT NAT
N SCADA N SCADA N SCADA
NAC TRIP NAC TRIP NAC TRIP
C C C
A SX 4 C SX 6 E SX 8

4 4

K21A K23A K23A1 K31A K21B K23B K23B1 K31B K21C K23C K23C1 K31C

X2 11 X2 12 X2 13 X2 14 X2 15 X2 16 X2 17 X2 18 X2 19 X2 20 X2 21 X2 22
CIRCUIT BREAKER

X1 61 X1 67 X1 80 X1 63 X1 69 X1 82 X1 59 X1 65 X1 78 CG MAKE
K21A K23A K31A K21B K23B K31B K21C K23C K31C 145KV,40KA,1POLE SP SPR GCB
52

REMOTE TRIP PROTN. TRIP PRE-CLOSE REMOTE TRIP PROTN. TRIP PRE-CLOSE REMOTE TRIP PROTN. TRIP PRE-CLOSE
5 POST CLOSE SUPERVSION SUPERVSION POST CLOSE SUPERVSION
POST CLOSE
SUPERVSION SUPERVSION
SUPERVSION 5

DRAWING NO:EH4-4199-12

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BREAKER TRIP CIRCUIT-1 BENGALURU PAGE : 28
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1
K4 K4 K4
27.H:5 / K4

FROM
DC SOURCE K3 K3 K3
27.H:5 / K3

11 11 F1
95-R2 VAX31 13 13 F3
95-Y2 VAX31 15 15 F5
95-B2 VAX31
12 12 F2 + 14 14 F4 + 16 16 F6 +
X2 47 X2 49 X2 51
-86-1-B1

-86-2-B1

-21-RL15

-86-1-B2

-86-2-B2

-21-RL16

-86-1-B3

-86-2-B3

-21-RL17
\22.E:3

\25.E:3

\18.E:4

\22.E:3

\25.E:3

\18.E:5

\22.E:3

\25.E:3

\18.E:5
18 12 12
FUTURE FUTURE FUTURE
TRIP 11 TRIP 4 TRIP 4

2 X2 48 X2 50 X2 52 2

12 OR 1 OR 1 OR

10 2 2

C C C

9 E - 17 3 E - 17 3 E - 17
3 3

K4 K4 K4
1 2 \17.F:5 1 2 \17.F:5 1 2 \17.G:5
-BCS 11 -BCS 13 -BCS 15
\31.D:3 T SX 9 3 4 \31.B:3
\31.D:4 T SX 11 3 4 \31.B:3
\31.D:4 T SX 13 13 14 \31.B:4
19 20 \27.D:1 19 20 \27.D:1 19 20 \27.D:2
NAT NAT NAT
N SCADA N SCADA N SCADA
NAC TRIP NAC TRIP NAC TRIP
C C C
K SX 10 M SX 12 O SX 14

4 4

K41A K43A K43A1 K49A K41A K43B K43B1 K49B K41C K43C K43C1 K49C

X2 25 X2 26 X2 27 X2 28 X2 29 X2 30 X2 31 X2 32 X2 33 X2 34 X2 35 X2 36
CIRCUIT BREAKER

X1 65 X1 91 X1 99 X1 87 X1 93 X1 100 X1 83 X1 89 X1 98 CG MAKE
K41A K43A K49A K41B K43B K49B K41C K43C K49C 145KV,40KA,1POLE SP SPR GCB
52

REMOTE TRIP PROTN. TRIP PRE-CLOSE REMOTE TRIP PROTN. TRIP PRE-CLOSE REMOTE TRIP PROTN. TRIP PRE-CLOSE
5 POST CLOSE SUPERVSION SUPERVSION POST CLOSE SUPERVSION
POST CLOSE
SUPERVSION SUPERVSION
SUPERVSION 5

DRAWING NO:EH4-4199-12

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BREAKER TRIP CIRCUIT-2 BENGALURU PAGE : 29
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H
12.E:5 89B 12.E:5
R1 R2
BMK MAIN BUS ISOLATOR BMK
R1 TB TB R2
R1 X3 TB6 1 2 TB6 X3 R2
1 +VE -VE 1
27 1 2 28
52b-B 52b-A TB1
4
21
52b-C TB1
5
22
TB1
R7 6

29 3
-ICS-1 O N C TB1
2 R13 R9 2
7
CLOSE COMMAND
1 2 30 4
TB1
R11 8
OPEN COMMAND
3 4 31 5

SX
R15 SX FROM 16
15 SCADA
SX
17

3 3
89L
LINE ISOLATOR

X3 TB TB X3
R1 TB6 1 2 TB6 R2
+VE -VE
35 6 7 36
52b-B 52b-A TB1
4
23
52b-C 89LEb TB1
5
4 26 4
TB1
R21 6

37 8
-ICS-2 O N C TB1
R27 R23 7
CLOSE COMMAND
1 2 38 9
TB1
R25 8
OPEN COMMAND
4 3 39 10

5 SX
R29 SX FROM
19 5
SCADA
18 SX
20

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL ISOLATOR CONTROL CIRCUIT BENGALURU PAGE : 30
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

1 1

SCADA TERMINALS
-BCS
95-R1 T NAT N NAC C
SX U23 4 3 U24 SX K1 K21A TO TRIP CKT-1
23 \28.C:2 24 1 A \28.A:3
K15A K15
TO CLOSING CKT
2 B \27.D:3
95-Y1 K21B
2
SX U25 4 3 U26 SX TO TRIP CKT-1
2
3 C \28.D:3
25 \28.E:2 26 K101 K133
TO MAIN PROT. RELAY
4 D \19.F:3
K21C TO TRIP CKT-1
95-B1 5 E \28.F:3
SX U27 14 13 U28 SX
27 28 SPARE
\28.H:2 6 F
L9 L11
7 G TO INDICATION CKT
95-R2 L7 \15.C:4
SX U29 4 3 U30 SX 8 H
3 3
29 \29.C:2 30
9 I SPARE

SPARE
95-Y2 10 J
SX U31 4 3 U32 SX K3 K41A TO TRIP CKT-2
11 K \29.A:3
31 \29.E:2 32
SPARE
12 L
K41B
95-B2 TO TRIP CKT-2
SX U33 14 13 U34 SX 13 M \29.D:3

4 4
33 \29.H:2 34 14 N SPARE
K41C
TO TRIP CKT-2
15 O \29.F:3
K101 K135 TO MAIN PROT. RELAY
16 P \19.F:3

5
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL BREAKER CONTROL SWITCH BENGALURU PAGE : 31
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

TERMINAL DIAGRAM

BX SX SX
1 PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE 1

J1A K15 U29


1 \12.B:2
DC SUPPLY TO ADJ PANEL(+VE) 2 \27.E:3
FROM SCADA CLOSE TO CB 29 \31.A:3
J2A U30
2 \12.B:2
DC SUPPLY TO ADJ PANEL(-VE) 3 \28.A:3
CB TRIP COM FROM SCADA-TC-1 R 30 \31.B:3
J3A K21A U31
3 \12.B:3
DC SUPPLY TO ADJ PANEL(+VE) 4 \28.A:4
= 31 \31.A:3
J4A U32
4 \12.B:3
DC SUPPLY TO ADJ PANEL(-VE) 5 \28.D:3
CB TRIP COM FROM SCADA-TC-1 Y 32 \31.B:3
H1 K21B U33
5 \13.B:3
AC SUPPLY TO ADJ. PANEL 6 \28.D:4
= 33 \31.A:4
H2 U34
6 \13.B:3
= 7 \28.F:3
CB TRIP COM FROM SCADA-TC-1 B 34 \31.B:4
2 G11 K21C 2
7 \11.B:4
BUS CVT INPUT(R) 8 \28.F:4
= 35 SPARE TB'S
G71
8 \11.A:4
BUS CVT INPUT(N) 9 \29.A:3
CB TRIP COM FROM SCADA-TC-2 R 36 =
K41A
9 SPARE TB'S 10 \29.A:4
= 37 =

10 = 11 \29.D:3
CB TRIP COM FROM SCADA-TC-2 Y 38 =
2U27 K41A
11 \24.F:4
LBB INITIATE TO ADJACENT FEEDER 86-2 RELAY 12 \29.D:4
=
2U28
12 \24.F:4
= 13 \29.F:3
CB TRIP COM FROM SCADA-TC-2 B
2U29 K41C X1
13 \24.F:5
LBB INITIATE TO XMER 86 RELAY 14 \29.F:4
=
3 3
2U30 R15 PANEL SIDE FIELD SIDE
14 \24.F:5
= 15 \30.B:3
SCADA TO BUS ISO(89B) COMM
R9 J1A
15 SPARE TB'S 16 SCADA TO BUS ISO(89B) OPEN 1 \12.B:1
DC SUPPLY-1 TO PANEL(+VE)
\30.B:3
R11 J2A
16 = 17 SCADA TO BUS ISO(89B) CLOSE 2 \12.B:1
DC SUPPLY-2 TO PANEL(-VE)
\30.B:3
K201 R29 J3A
17 LBB TRIP FROM ADJACENT FEEDER 18 SCADA TO LINE ISO(89L) COMM 3 \12.B:3
DC SUPPLY-2 TO PANEL(+VE)
\25.B:3 \30.B:5
K203 R23 J4A
18 = 19 SCADA TO LINE ISO(89L) OPEN 4 \12.B:4
DC SUPPLY-2 TO PANEL(-VE)
\25.C:3 \30.B:5
K201 R25 H1
19 LBB TRIP FROM XMER 20 SCADA TO LINE ISO(89L) CLOSE 5 \13.B:2
AC SUPPLY TO PANEL
\25.B:3 \30.B:5
H2
20 = 21 SPARE TB'S 6 \13.B:2
=
4 \25.C:3 4
E21
21 SPARE TB'S 22 = 7 \11.H:4
PT INPUT TO METERING CKT(R)

U23 E41
22 = 23 TC-1 HEALTHY TO SCADA 8 \11.G:4
PT INPUT TO METERING CKT(Y)
\31.A:2
U24 E61
24 = 9 \11.G:4
PT INPUT TO METERING CKT(B)
\31.B:2
U25 E81
25 TC-2 HEALTHY TO SCADA 10 \11.G:4
PT INPUT TO METERING CKT(N)
\31.A:2
U26 E11
SX 26 = 11 \11.G:4
PT INPUT TO PROT. CKT(R)
\31.B:2
U27 E31
PANEL SIDE FIELD SIDE 27 12 \11.G:4
PT INPUT TO PROT. CKT(Y)
\31.A:3
K15A U28 E31
5 1 \27.E:3
FROM SCADA CLOSE TO CB
28 13 \11.G:4
PT INPUT TO PROT. CKT(B)
\31.B:3
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL TERMINAL DIAGRAM BENGALURU PAGE : 32
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

TERMINAL DIAGRAM

-X1 -X1 X2
1 PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE 1

E31 K23C
14 \11.G:4
PT INPUT TO PROT. CKT(N) 41 SPARE TB'S 20 \28.G:4
PROTN. TRIP TO CB TRIP CKT-B1
D11 K23C1
15 \11.F:4
CT INPUT TO METERING CKT(R) 42 21 \28.G:4
POST CLOSE SUP. TO CB TRIP CKT-B1
K31C
16 \11.F:4
CT SHORT LINK 43 22 \28.G:4
PRE-CLOSE SUPERVIION TO CB TRIP CKT-B1
D31
17 \11.E:4
CT INPUT TO METERING CKT(Y) 44 23 SPARE TB'S

18 \11.E:4
CT SHORT LINK 24 =
D51 K41A
19 \11.E:4
CT INPUT TO METERING CKT(B) 25 \29.A:4
MANUAL TRIP TO CB TRIP CKT-R2
2 D71 K43A 2
20 CT SHORT LINK X2 26 PROTN. TRIP TO CB TRIP CKT-R2
\11.E:4 \29.B:4
D71 PANEL SIDE FIELD SIDE K43A1
21 \11.E:4
CT INPUT TO METERING CKT(N) 27 \29.B:4
POST CLOSE SUP. TO CB TRIP CKT-R2
C11 K1 K49A
22 CT INPUT TO BCKUP PROT CKT(R) 1 \27.B:4
AUX. SUPPLY CB CLOSE & TRIP CKT-1
28 PRE-CLOSE SUPERVIION TO CB TRIP CKT-R2
\11.D:4 \29.B:4
K2 K41A
23 CT SHORT LINK 2 \27.B:4
=
29 MANUAL TRIP TO CB TRIP CKT-Y2
\11.D:4 \29.D:4
C31 K3 K43B
24 CT INPUT TO BCKUP PROT CKT(Y) 3 \27.F:4
=
30 PROTN. TRIP TO CB TRIP CKT-Y2
\11.D:4 \29.D:4
K4 K43B1
25 CT SHORT LINK 4 \27.F:4
=
31 POST CLOSE SUP. TO CB TRIP CKT-Y2
\11.D:4 \29.D:4
C51 K5A K49B
26 CT INPUT TO BCKUP PROT CKT(B) 5 \27.C:3
FUTURE INTERLOCK FOR CLOSE CKT OF CB
32 PRE-CLOSE SUPERVIION TO CB TRIP CKT-Y2
\11.D:4 \29.E:4
3 K5 3
C71 6 = K41C
27 \11.C:4
CT SHORT LINK \27.C:3 33 \29.F:4
MANUAL TRIP TO CB TRIP CKT-B2
C71 K15 K43C
28 CT INPUT TO BCKUP PROT CKT(N) 7 \27.D:4
CLOSE CMD TO BREAKER
34 PROTN. TRIP TO CB TRIP CKT-B2
\11.C:4 \29.G:4
A11 K17 K43C1
29 CT INPUT TO MAIN PROT CKT(R) 8 \27.E:4
AUTO RECLOSE CLOSE TO BREAKER
35 POST CLOSE SUP. TO CB TRIP CKT-B2
\11.C:4 \29.G:4

9 SPARE TB'S K49C


30 \11.C:4
CT SHORT LINK 36 \29.G:4
PRE-CLOSE SUPERVIION TO CB TRIP CKT-B2
A31 10 =
31 \11.C:4
CT INPUT TO MAIN PROT CKT(Y) 37 SPARE TB'S
K21A
32 CT SHORT LINK 11 \28.A:4
MANUAL TRIP TO CB TRIP CKT-R1
38
\11.C:4
A51 K23A
33 CT INPUT TO MAIN PROT CKT(B) 12 \28.B:4
PROTN. TRIP TO CB TRIP CKT-R1
39
4 \11.B:4 4
A71 K23A1
34 CT SHORT LINK 13 \28.B:4
POST CLOSE SUP. TO CB TRIP CKT-R1
40 SPARE TB'S
\11.B:4
A71 K31A
35 CT INPUT TO MAIN PROT CKT(N) 14 \28.B:4
PRE-CLOSE SUPERVIION TO CB TRIP CKT-R1
41 EXTERNAL PROTN. TRIP TO CB TRIP CKT-1
\11.B:4 \28.C:2
K21B
36 15 \28.D:4
MANUAL TRIP TO CB TRIP CKT-Y1
42 =
\28.C:2
K23B K1
37 SPARE TB'S 16 \28.D:4
PROTN. TRIP TO CB TRIP CKT-Y1
43 EXTERNAL PROTN. TRIP TO CB TRIP CKT-2
\28.E:2
K23B1
38 = 17 \28.D:4
POST CLOSE SUP. TO CB TRIP CKT-Y1
44 =
\28.E:2
K31B K1
39 = 18 \28.E:4
PRE-CLOSE SUPERVIION TO CB TRIP CKT-Y1
45 =
\28.G:2
K21C
5 40 = 19 \28.F:4
MANUAL TRIP TO CB TRIP CKT-B1
46 =
\28.G:2
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL TERMINAL DIAGRAM BENGALURU PAGE : 33
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

TERMINAL DIAGRAM

X2 X3 -X3
1 PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE 1

K3
47 \29.B:2
EXTERNAL PROTN. TRIP TO CB TRIP CKT-1 14 \16.C:1
LINE ISO. TO IND CKT(COM) 41 SPARE TB'S
L23
48 \29.B:2
= 15 \16.C:3
LINE ISO. (NC) TO IND CKT 42 =
K3 L25
49 \29.E:2
EXTERNAL PROTN. TRIP TO CB TRIP CKT-2 16 \16.C:3
LINE ISO. (NO) TO IND CKT

50 \29.E:2
= 17 \16.D:1
LINE ISO. E/S TO IND CKT(COM)
K3 L27 -X4
51 \29.G:2
= 18 \16.D:3
LINE ISO. E/S (NC) TO IND CKT
L29 PANEL SIDE FIELD SIDE
52 \29.G:2
= 19 \16.E:3
LINE ISO. E/S (NO) TO IND CKT
2 K101 2
53 SPARE TB'S 20 SPARE TB'S 1 \19.B:1
CB -Rph OPEN TO DIST. RELAY
K111
54 = 21 = 2 \19.C:1
=

55 = 22 3 \19.B:2
CB -Yph OPEN TO DIST. RELAY

L133 K113
56 = 23 SPARE WINDOW 4 \19.C:2
=
\17.H:4
L101 5 CB -Bph OPEN TO DIST. RELAY
24 \17.H:5
= \19.B:2
K115
25 SPARE TB'S 6 \19.C:2
=
K139
X3 26 7 \19.F:4
SPARE DI DIFF RELAY
3 3
PANEL SIDE FIELD SIDE R1 8 =
27 \30.D:1 \19.G:4
L1 R2 K141
1 \15.B:1
BRK CONTACT TO IND CKT(COM)
28 9 \19.F:5
=
\30.G:1
L3 R15 K101
2 \15.B:3
BRK (NO) TO IND CKT
29 10 \19.G:5
=
\30.D:2
L5 R9
3 \15.C:3
=
30 11
\30.D:2
L7 R11
4 \15.C:3
BRK NC FOR AUTO TRIP IND
31 12
\30.D:2
L1A
5 \15.E:1
BRK CONTACT TO IND CKT(COM)
32 SPARE TB'S 13 SPARE TB'S
L13
6 \15.E:3
BRK (NC) TO IND CKT
33 = 14
4 4
L15
7 \15.E:3
BRK (NO) TO IND CKT
34 = 15 \22.B:2
FUTURE TRIP
L17 R1 K103
8 \15.E:3
BRK SPRING CHR TO IND CKT
35 16 \22.C:2
=
\30.D:3

9 SPARE TB'S R2 17
36 \30.G:3

10 = R29 18 SPARE TB'S


37 \30.D:4

11 BUS SIDE ISO. TO IND CKT(COM) R23 19


\16.B:1 38 \30.D:5
L19 R25
12 \16.B:3
BUS SIDE ISO. (NC) TO IND CKT
39 20 SPARE TB'S
\30.D:5
L21
5 13 \16.B:3
BUS SIDE ISO. (NO) TO IND CKT
40 SPARE TB'S 21 \24.B:1
5

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL TERMINAL DIAGRAM BENGALURU PAGE : 34
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35
A B C D E F G H

TERMINAL DIAGRAM

-X4 -X5 X6
1 PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE PANEL SIDE FIELD SIDE 1

K211 K51
22 \24.C:1 7 SPARE TB'S 2 \26.B:3
CB GAS PR LOW ALARM
K53
23 \24.B:2 8 = 3 \26.C:3
CB GAS PR LOW TRIP LOCKOUT
K213 U9 K55
24 \24.C:2 9 \22.F:4
MTR 86-1 NC 4 \26.C:3
CB POLE DICREPANCY
U10
25 \24.B:3 10 \22.F:5
= 5 SPARE TB'S
K219 U11
26 \24.C:3 11 \22.F:5
MTR 86-1 NO 6 =
U12 K101
27 \24.B:4 12 \22.F:5
= 7 \26.E:1
COMM. SUPPLY TO CARRIER CKT
2 K221 U13 K57 2
28 \24.C:4 13 \22.F:5
= 8 \26.E:3
CARRIER UNHEALTHY CHANNEL-1/2
U14 K59
29 \24.B:4 14 \22.F:5
= 9 \26.E:3
CARRIER RECEIVED CHANNEL-1/2
K223 K61
30 \24.C:4 15 SPARE TB'S 10 \26.F:3
=
K201
31 \24.B:5 16 = 11 SPARE TB'S
K225 U17
32 \24.C:5 17 \25.F:4
MTR 86-2 NC 12 =
U18 3U13
33 SPARE TB'S 18 \25.F:5
= 13 \20.E:2
CARRIER SEND (TO PLCC PANEL CHANNEL-1)
U19 3U14
34 = 19 \25.F:5
MTR 86-2 NO 14 \20.E:3
=
3 3
U20 3U15
35 \25.B:2
FUTURE TRIP 20 \25.F:5
= 15 \20.E:3
DIRECT TRIP SEND (TO PLCC PANEL CHANNEL-1)
K203 U21 3U16
36 \25.C:2
= 21 \25.F:5
= 16 \20.E:3
=
U22 3U17
37 22 \25.F:5
= 17 \20.E:3
CARRIER SEND (TO PLCC PANEL CHANNEL-2)
3U18
38 23 SPARE TB'S 18 \20.E:4
=
3U19
24 = 19 \20.E:4
DIRECT TRIP SEND (TO PLCC PANEL CHANNEL-2)
2U25 3U20
25 \24.F:4
BACKUP RELAY SPARE O/P 20 \20.E:4
=

X5 2U26
4
26 \24.F:4
= 21 SPARE TB'S
4
PANEL SIDE FIELD SIDE 27 SPARE TB'S 22 =
1U1
1 \20.E:4
DISTANCE RELAY SPARE DO
28 = 23 =
1U2
2 \20.E:5
=
24 =
1U3
3 \20.E:5
=
1U4
4 \20.E:5
= X6
1U5
5 \20.E:5
= PANEL SIDE FIELD SIDE
1U6 K101
5 6 \20.E:5
= 1 \26.B:1
COMM. SUPPLY TO CB SUPV CKT

REV. DETAILS 1. AS PER CUSTOMER COMMENTS- 23.09.2014 2. AS PER CUSTOMER COMMENTS- 16.10.2014 3. SCALE : NTS NOTE : ALL DIMENSIONS ARE IN MM
SIGN DATE CUSTOMER KANORIA AFRICA TEXTILES DRAWING NO. REV. ISSUE
VENSON
PANEL C & R PANEL FOR 132KV LINE INCOMER 2
DRAWN GP 11.SEP.2014 CONTRACTOR SREX POWER PVT LTD. ELECTRIC
PRIVATE LTD.
C15031B
CHECKED GK 15.SEP.2014 LOI NO - 27.OCT.2014
DETAIL TERMINAL DIAGRAM BENGALURU PAGE : 35
APPROVED MR 16.SEP.2014 PO NO. 006/X-293/2014-15,DATED 22.08.2014 OF 35