Transformer applications

Transformer feeder protection

Transformer feeder protection


b transformer short-circuit and overload protection
b internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
b RTD temperature monitoring (ANSI 49T).
Transformer feeder protection without voltage monitoring: Sepam T20, T24
Earth fault protection: Earth fault protection:
b primary: 50G/51G. b neutral point: 50G/51G.

DE88410

DE88411
Transformer feeder protection with voltage monitoring: Sepam T40, T50, T60
or T81
Earth fault protection:
b primary: 50G/51G.
DE60539

Note: for long feeders, the 50G/51G function may be replaced by the 67N/67NC.
Transformer applications
Transformer feeder protection

Transformer feeder protection with voltage monitoring and additional


current measurement: Sepam T81
Earth fault protection: Earth fault protection:
b primary: 50G/51G b primary: 50G/51G
b tank earth leakage: b secondary: 50G/51G.
50G/51G.

DE88032

DE88033
Note: for long feeders, the 50G/51G function may be replaced by the 67N/67NC.

Transformer feeder differential protection: Sepam T87


Transformer differential protection: 87T
Earth fault protection: Earth fault protection: Earth fault protection:
b primary: 50G/51G. b primary: 50G/51G b primary:
b secondary: v 64REF
v 64REF v 50G/51G
v 50G/51G. b secondary:
v 64REF
v 50G/51G.
DE88034

DE88035

DE88036
Transformer applications
Transformer incomer protection

Transformer incomer protection


b transformer short-circuit and overload protection
b internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
b RTD temperature monitoring (ANSI 49T).

Transformer incomer protection without voltage monitoring: Sepam T20,


T24
Earth fault protection: Earth fault protection:
b secondary: 50G/51G. b neutral point: 50G/51G.

DE88413

DE88414
Transformer incomer protection with voltage monitoring: Sepam T40, T50,
T60 or T81
Earth fault protection: Earth fault protection:
b secondary: 50G/51G. b secondary:
v 64REF
v 50G/51G.
DE60540

DE60541
Transformer applications
Transformer incomer protection

Transformer incomer differential protection: Sepam T87


Transformer differential protection: 87T
Earth fault protection: Earth fault protection: Earth fault protection: Earth fault protection: Earth fault protection:
b primary: 50G/51G b primary: 50G/51G b primary: 50G/51G b primary: b primary:
b secondary: 50G/51G. b secondary: b secondary: v 64REF v 64REF
v 64REF v 64REF v 50G/51G v 50G/51G
v 50G/51G. v 50G/51G. b secondary: 50G/51G. b secondary:
v 64REF
v 50G/51G.
DE88041

DE88042

DE88043

DE88044

DE88045
Protection of 2 non-coupled transformer incomers: Sepam T60 or T81
b automatic source transfer (ATS)
b synchro-check (ANSI 25).
DE60542
Transformer applications
Transformer incomer protection

Parallel transformer incomer protection: Sepam T42, T52, T62 or T82


b transformer directional phase overcurrent protection: 67
b transformer secondary earth fault protection: 50G/51G, 59N.

DE60543

b transformer directional phase overcurrent protection: 67


b transformer secondary earth fault protection: 67N/67NC, 64REF
b with synchro-check (ANSI 25).
DE60544

Parallel incomer differential protection: Sepam T87


b transformer differential protection: 87T
b directional transformer protection: 67
b transformer secondary earth fault protection: 50G/51G, 67N/67NC 64REF.
DE88049