Sie sind auf Seite 1von 2

DSEGenset

DSE7310/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE7310 is an Auto Start The DSE7320 will also monitor the The extensive list of features TEMPERATURE
Control Module and the DSE7320 is mains (utility) supply. The modules includes enhanced event and BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
an Auto Mains (Utility) Failure include USB, RS232 and RS485 performance monitoring, remote BS EN 60068-2-2
Control Module suitable for a wide ports as well as dedicated communications, PLC functionality Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, DSENet terminals for system and dual mutual standby (DSE7310
VIBRATION
gen-set applications. expansion. only) to reduce engine wear. BS EN 60068-2-6
Ten sweeps in each of three
major axes
Monitoring an extensive number of Both modules are compatible with The modules can be easily 5 Hz to 8 Hz @ +/-7.5 mm,
engine parameters, the modules will electronic (CAN) and non-electronic configured using the DSE 8 Hz to 500 Hz @ 2 gn
display warnings, shutdown and (magnetic pick-up/alternator Configuration Suite PC software.
HUMIDITY
engine status information on the sensing) engines and offer an Selected front panel editing is also BS EN 60068-2-30
back-lit LCD screen, illuminated extensive number of flexible inputs, available. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
LEDs, remote PC and via SMS text outputs and extensive engine BS EN 60068-2-78
alerts (with external modem). protections so the system can be Cab Damp Heat Static 40 oC
easily adapted to meet the most @ 93% RH 48 Hours
demanding industry requirements. SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
COMPREHENSIVE FEATURE LIST TO SUIT A control panel with the supplied sealing gasket.

WIDE VARIETY OF GEN-SET APPLICATIONS


MODEM MODBUS PC
DSE2130
DSE2157
DSE2548 8 4 4
DSE2510/20
232 485


DSENET RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE7310/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
DSE7320 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 6

DSEGenset

DSE7310/20 SPECIFICATION

DC SUPPLY

AUTO START & AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING


8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
DSE7320 without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

DSE7310 MAXIMUM OPERATING CURRENT


340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT


160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

MAINS (UTILITY) DSE7320 ONLY


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
KEY FEATURES Reverse power (kW & kV Ar) DSENet expansion compatible 3.5 Hz to 75 Hz
4-Line back-lit LCD text display protection Heated display option available
OUTPUTS
Five key menu navigation LED and LCD alarm indication OUTPUT A (FUEL)
Front panel editing with PIN Power monitoring (kW h, kV Ar, kV KEY BENEFITS 15 A DC at supply voltage
protection A h, kV Ar h) 132 x 64 pixel ratio display for
OUTPUT B (START)
Customisable status screens Load switching (load shedding clarity 15 A DC at supply voltage
Power save mode and dummy load outputs) Real-time clock provides accurate
Support for up to three remote Automatic load transfer (DSE7320) event logging OUTPUTS C & D
8 A 250 V (Volt free)
display units Unbalanced load protection Multiple date and time scheduler
9 configurable inputs Independent Earth Fault trip Set maintenance periods can be AUXILIARY OUTPUTS E,F,G,H
8 configurable outputs True dual mutual standby with load configured to maintain optimum 2 A DC at supply voltage

Flexible sender inputs balancing timer (DSE7310 only) engine performance GENERATOR
Configurable timers and alarms USB connectivity Ethernet communications (via VOLTAGE RANGE
3 configurable maintenance Backed up real time clock DSE855 module), provides 15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
alarms Fully configurable via DSE advanced remote monitoring
Multiple date and time scheduler Configuration Suite PC software Modules can be integrated into FREQUENCY RANGE
Configurable event log (250) Configurable display languages building management systems 3.5 Hz to 75 Hz

CAN engine support Remote SCADA monitoring via (BMS) MAGNETIC PICK UP
Integral PLC editor DSE Configuration Suite PC Increased input and output VOLTAGE RANGE
Easy access diagnostic page software expansion capability via DSENet +/- 0.5 V to 70 V

CAN and Magnetic Pick-up/Alt. User selectable RS232 and RS485 Licence-free PC software FREQUENCY RANGE
sensing communications IP65 rating (with supplied gasket) 10,000 Hz (max)
Fuel usage monitor and low fuel Configurable Gencomm pages offers increased resistance to
DIMENSIONS
alarms Advanced SMS messaging water ingress OVERALL
Charge alternator failure alarm (additional external modem PLC editor allows user 240 mm x 181 mm x 42 mm
Manual speed control (on required) configurable functions to meet 9.4 x 7.1 x 1.6

compatible CAN engines) Start & stop capability via SMS specific application requirements PANEL CUT-OUT
Manual fuel pump control messaging 220 mm x 160 mm
Engine exerciser Additional display screens to help 8.7 x 6.3

Protections disabled feature with modem diagnostics MAXIMUM PANEL THICKNESS


kW & kV Ar protection Idle control for starting & stopping. 8 mm
0.3

OPERATING TEMPERATURE RANGE


RELATED MATERIALS -30C to +70C
TITLE PART NOS
DSE7310 Installation Instructions 053-028 STORAGE TEMPERATURE RANGE
-40C to +80C
DSE7320 Installation Instructions 053-029
DSE7200/7300 Quick Start Guide 057-101
DSE7200/7300 Operator Manual 057-074
DSE7200/7300 Configuration Suite PC Manual 057-077

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-051/10/11 (13) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

Das könnte Ihnen auch gefallen