7371 m^2

Fire nd

Although the amount of water used in a year for firefighting is small, the rate of
use is large. The Insurance Services Office uses the formula;

F18 C A 0.5

L
Where: F = needed fire flow day
C = coefficient for construction factor
A = floor area excluding basement of the building m2

The fire flow must be maintained for a minimum of 4 hours. Most


communities will require a duration of 10 hours. In order to determine the
maximum water demand during a fire flow, the fire flow must be added to the
maximum daily consumption.

*add to methodology:
Fire Demand
Fire flow The rate of water flow needed to control a fire (AWWA, 20008)
Coefficient for construction factor tabulated coefficients (Table 1-4) related to the
type of construction (ISO, 1998)
Class of Construction Description C
1 Frame 1.5
2 Joisted Masonry 1.0
3 Noncombustible 0.8
4 Masonry, noncombustible 0.8
5 Modified Fire Resistive 0.6
6 Fire Resistive 0.6