Sie sind auf Seite 1von 2

Siemens Proposal 2016-0174 February 16, 2016

Item 1
Type No JFR
Standards (1999) C57.15
Voltage kV 19.92
BIL KV 150
Frequency HZ 60
Amps 335
Regulation +/- 10%, 32 steps, Yes
Sealed tank design Yes
Cooling ONAN
Non-PCB Oil Type II ASTM D-3487 Yes
Lightning Arresters No
Color ANSI-70, Gray Yes
Factory routine tests only to ANSI Yes
Siemens Control Panel MJ Yes
Comm. Module No

Features of the JFR Units:


Meet or exceeds ANSI, IEEE and NEMA standards.
Automatic pressure relief valve.
Line Terminals.
Laser-scribed anodized aluminum nameplates.
Lifting lugs.
Mounting provisions for lightning arresters.
External MOV bypass arrester.
Position Indicator with VARI-AMP feature.
An oil drain valve and sampling device.
Upper filter press connection.
Control cabinet.
Control panel with PDS quick disconnect plug.

The following tests per ANSI C57.15 are performed:


1) Resistance measurements of all windings
2) Ratio tests on all tap connections.
3) Polarity test.
4) No load loss at rated voltage and frequency.
5) Excitation current at rated voltage and frequency.
6) Impedance and load loss at rated current and frequency.
7) Applied potential for 60 seconds.
8) Induced potential.
9) Insulation power factor test.
10) Megger test.
11) Impulse test.

Page 3 of 7
Siemens Proposal 2016-0174 February 16, 2016

Optional Equipment for Siemens Voltage Regulators


Optional Modifications (at additional cost)

1) Lightning arresters
2) Nameplates in different language or metric units
3) Bird guards
4) Control heater
5) Cooling Fans
6) Special ground pads/Connectors
7) Special Drain Valves
8) Auxiliary Potential Transformers
9) Auxiliary Current Transformers
10) Special Ultra-Creep Bushings
11) Special Current Transformers

Documentation (with delivery) will include:

Our Standard Documentation will be provided.

Page 4 of 7