Beruflich Dokumente
Kultur Dokumente
4R-98
This report gives general information regarding the evaluation of corrosion CONTENTS
damage in structures reinforced with unbonded single strand post-tension- Chapter 1Introduction, p. 423.4R-2
ing tendons. Historical development of those parts of the building code 1.1General
dealing with durability and corrosion protection is explained. Evolution of 1.2Background
the types and components of unbonded tendons is described. Specific
aspects of corrosion in unbonded single strand tendons are described, and
1.3Scope
common problems in structures reinforced with these tendons are discussed. 1.4Limitations
Methods are presented for repairing, replacing, and supplementing tendons.
Chapter 2Review of code requirements and
Keywords: allowable stresses; anchorage; carbonation; concrete con- changes, p. 423.4R-3
struction; corrosion; corrosion protection; cover; durability; embrittle- 2.1General
ment; external post-tensioning; grease; inspection; post-tensioned 2.2Cover requirements for unbonded tendons
concrete; pre-stressed concrete; repair; sheathing; single strand tendons; 2.3Allowable tensile stresses in concrete
surveys; tendons; tests; unbonded post-tensioning.
2.4Protection of unbonded tendons
ACI Committee Reports, Guides, Standard Practices, and
Chapter 3Unbonded tendons, p. 423.4R-5
Commentaries are intended for guidance in planning, design- 3.1Evolution of unbonded tendons
ing, executing, and inspecting construction. This document 3.2Sheathing problems
is intended for the use of individuals who are competent 3.3Detailing practices
to evaluate the significance and limitations of its content 3.4Storage, handling, and construction problems
and recommendations and who will accept responsibility 3.5Deterioration mechanisms
for the application of the material it contains. The American 3.6Performance record
Concrete Institute disclaims any and all responsibility for the
stated principles. The Institute shall not be liable for any loss
or damage arising therefrom.
Reference to this document shall not be made in contract
ACI 423.4R-98 became effective February 23, 1998.
documents. If items found in this document are desired by Copyright 1998, American Concrete Institute.
the Architect/Engineer to be a part of the contract docu- All rights reserved including rights of reproduction and use in any form or by any
means, including the making of copies by any photo process, or by electronic or
ments, they shall be restated in mandatory language for in- mechanical device, printed, written, or oral, or recording for sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device, unless permission in
corporation by the Architect/Engineer. writing is obtained from the copyright proprietors.
423.4R-1
423.4R-2 MANUAL OF CONCRETE PRACTICE
Chapter 4Evaluating corrosion damage, p. the prestressing steel where corrosion has been initiated. The
423.4R-10 tendons usually require separate evaluation and repair.
4.1General
4.2Condition surveys of concrete 1.2Background
4.3Condition surveys of tendons Commercially viable unbonded post-tensioning systems
4.4Nondestructive testing were introduced to North America in the 1950s. At that time
4.5Exploratory concrete removal there were no accepted standards for design nor material
4.6Exposing tendons specifications for prestressing steels, and guidance came in
4.7Strand removal the form of tentative recommendations from a joint commit-
4.8Other testing and investigative procedures tee of the American Concrete Institute (ACI) and the Amer-
ican Society of Civil Engineers (ASCE), from the
Chapter 5Repair schemes and methods, p. Prestressed Concrete Institute (PCI), or from the Bureau of
423.4R-14 Public Roads, United States Department of Commerce. Un-
5.1General bonded tendons in the early systems used bundles of wires or
5.2Existing tendon repair strands, sometimes inaccurately called cables, of various
5.3Strand replacement diameters, and protected by grease and paper sheathing that
5.4Tendon replacement were sometimes applied by hand.1,2
5.5External post-tensioning The use of unbonded tendons became more common dur-
5.6Continuous acoustic monitoring ing the late 1950s and early 1960s as progress was made in
5.7External non-prestressed reinforcement or support establishing design and materials standards. Acceptance of
5.8Total demolition and replacement the concept was regional at first, and was largely the result of
sales efforts and design tutoring by tendon suppliers. The use
Chapter 6Summary, p. 423.4R-18 of post-tensioning increased rapidly during the late 1960s
and 1970s as the advantages of the system were demonstrat-
Chapter 7References, p. 423.4R-18 ed. For many types of structures, these advantages included
7.1Recommended references shorter construction time, reduced structural depth, in-
7.2Cited references creased stiffness, and savings in overall cost. In addition to
their use in enclosed buildings, unbonded post-tensioning
systems were used in parking structures and slabs on grade,
CHAPTER 1INTRODUCTION and bonded post-tensioning was used on water tanks, bridg-
1.1General es, dams, and soil tie-back systems. Unbonded multiwire and
This report is intended to provide historical and general in- multistrand tendons have been used extensively in nuclear
formation on the evaluation of known or suspected corrosion power structures.
problems in unbonded single strand tendons, and to describe Incidents of corrosion of unbonded single strand tendons
typical repair methods currently in use. It has been prepared began to surface during the 1970s. It had been believed by
to describe the state of knowledge as perceived by the com- some that corrosion protection would be provided by the
mittee. It is not a standard or recommended practice. Exper- grease during shipping, handling and installation, and by the
tise in design, construction, evaluation, and repair of concrete thereafter. However, the early greases often did not
structures utilizing single strand unbonded tendons is strong- provide the corrosion-inhibiting characteristics that are re-
ly recommended for a team undertaking evaluation and re- quired in the current Post-Tensioning Institute (PTI) Speci-
pair of corrosion problems. fications for Unbonded Single Strand Tendons. In the early
There have been corrosion problems with other types of 1980s, PTI recognized the structural implications of corro-
pre- and post-tensioning systems.1 However, certain aspects sion and began to implement measures to increase the dura-
of corrosion of unbonded single strand tendons are unique. bility of unbonded post-tensioning systems. In 1985, PTI
The causes and effects of corrosion of unbonded single published the first performance standard for single strand
strand tendons are, in several respects, different from those tendons.3 Relying on experience and practice in the nuclear
of bonded conventional reinforcing or other post-tensioning industry using corrosion-inhibiting hydrophobic grease,
systems. Thus, the methods for evaluating and repairing cor- similar performance standards for grease were incorporated.
rosion of single strand tendons are also different in some re- In the 1989 edition of ACI 318, Building Code Require-
spects. For example, since the tendons are largely isolated ments for Reinforced Concrete, changes were made to in-
from the surrounding concrete, they may not be affected by corporate measures that related the required protection of the
deleterious materials such as chlorides and moisture in the tendons and the quality of the concrete to the environmental
concrete. However, they also are not passivated by the sur- conditions that could promote corrosion of the post-tension-
rounding concrete, and can corrode if water gains access to the ing. Structures built prior to the adoption of these new stan-
inside of the sheathing or anchorage and the grease protection dards, especially those in aggressive environments, are more
is inadequate. Measures taken to repair and protect the sur- likely to experience corrosion of the post-tensioning system
rounding concrete may not repair or reduce deterioration of than those designed and built since.
SINGLE STRAND TENDONS 423.4R-3
Tendons that are broken, or are known to be damaged by concrete quality in providing adequate corrosion protection
corrosion, can be repaired or supplemented by any of several to the non-prestressed, bonded reinforcement.
methods. The more difficult task is to determine the extent of In 1958, ACI-ASCE Joint Committee 323 published
corrosion damage and the degree to which tendon repairs are Tentative Recommendations for Prestressed Concrete and
needed. This report is intended to provide guidance in the addressed the protection of prestressing steel in three areas
evaluation of suspected or known corrosion problems and to of recommended practice: concrete cover, allowable tensile
describe repair methods currently in use. stresses, and, for unbonded systems, protection of the strand
or wire with grease and a sheathing material. Since 1958,
1.3Scope provisions for prestressed concrete have included require-
This report includes a review of the following: ments for corrosion protection. The grease and sheathing
Codes and code changes affecting unbonded post-ten- were viewed, by most, primarily as a lubricant and bond
sioning tendons; breaker, and secondarily as a corrosion deterrent during
Past and present corrosion protection systems and how shipping, handling, and placing. Long-term corrosion pro-
those systems have changed to enhance corrosion pro- tection was viewed by some as being provided by the un-
tection; cracked concrete cover.
Types of corrosion damage found in prestressing steel; In 1963, prestressed concrete was first included in ACI
Methods for evaluating structures which are suspected 318 with provisions for concrete cover, allowable tensile
of, or known to have, corrosion damage in the post-ten- stresses, and strand protection. These items have been mod-
sioning system; and ified from time to time, but the substantive change came in
Basic repair options currently in use. 1989 when durability was emphasized in ACI 318.
content, maximum water-cement ratio (or minimum steel be increased for prestressed members exposed to earth,
strength of lightweight concrete), maximum chloride- weather or corrosive environments. Concrete protection for
ion in concrete, and cement type. Additionally, for cor- reinforcement required a 50 percent increase in cover for
rosion protection, a minimum concrete cover for rein- members exposed to weather, earth, or corrosive environ-
forcement of 2 in. (50 mm) for walls and slabs and 2 ments and with a tensile stress greater than 6 fc psi
in. (60 mm) for other members is recommended. For (0.5 fc MPa). The 1995 Code retains the allowable tensile
precast concrete manufactured under plant control con- stresses as outlined in the 1977 Code.
ditions, a minimum cover of 1 and 2 in. (40 and 50
mm), respectively, is recommended. 2.4Protection of unbonded tendons
This discussion is important as it calls the designers atten- The protection of unbonded prestressing strands was ini-
tion to the importance of air content, maximum water-ce- tially described by ACI-ASCE Committee 323 to consist of
ment ratio, maximum chloride-ion content, and cement type a grease- or asphalt-impregnated material enclosed in a
when designing for corrosion protection. sheath. Specification and approval of the method of protec-
Finally, a distinction between plant-cast members and oth- tion was left to the engineer. In ACI 318-63, Section 2620 in-
er prestressed concrete members was made in the 1971 Code dicated that unbonded steel shall be permanently protected
with the addition of distinct cover requirements for plant- from corrosion. However, no specific information was pro-
cast members. vided relative to the sheath material and the required corro-
sion protection. As noted previously, concrete cover was
2.3Allowable tensile stresses in concrete sometimes interpreted as providing the permanent protection
In aggressive environments, designing to minimize cracking from corrosion.
was used to improve durability by reducing ingress of corrosive The 1971 Code included a section entitled Corrosion Pro-
elements. Though a properly greased tendon in an intact sheath- tection for Unbonded Tendons. It stipulated that unbonded
ing may not be affected at first by a crack in the surrounding tendons shall be completely coated with suitable material to
concrete, corrosion of nearby conventional reinforcing can ensure corrosion protection. This section also required that
cause spalling which may expose the tendon to physical dam- wrapping should be continuous over the entire unbonded
age which may then lead to corrosion of the strand. zone of tendons in order to prevent bonding with surround-
For consideration of long-term durability and corrosion ing concrete and loss of the coating material during concrete
protection, the maximum allowable tensile stresses in the placement.
concrete at service loads, after allowance for all prestress In 1972, the Post-Tensioning Institute (PTI) published its
losses, are of most interest. The initial recommendations pre- first edition of the Post-Tensioning Manual, which includ-
sented in 1958 by ACI-ASCE Committee 323 limited allow- ed a specification for post-tensioning materials. Subsequent-
able tensile stresses in pretensioned members to 6 fc psi ly, this specification was revised and published as a guide
(0.5 fc MPa) where not exposed to weather or corrosive specification in the second and third editions of the Manual
environments. In post-tensioned members not exposed to (1976 and 1981, respectively). In 1985 PTI published Spec-
weather or corrosive environments, tensile stresses were lim- ification for Unbonded Single Strand Tendons, the first de-
ited to 3 fc psi (0.25 fc MPa). No mention was made of tailed specification to be based on experience. ACI 318
allowable stresses in unbonded systems. referenced this document in 1989 under Corrosion Protec-
In ACI 318-63, allowable tensile stresses in concrete were tion for Unbonded Prestressing Tendons.
limited to 6 fc psi (0.5 fc MPa) for members not exp o sed Significant new provisions of the 1985 PTI specification
to freezin g tem p eratu re o r to a co rro siv e en v iro n m en t, p ro v id ed are discussed below.
th e m em b ers co n tain ed b o n d ed rein fo rcem en t (p restressed o r Definition of exposure conditions: The 1985 specifica-
n o n -p restressed ) to co n tro l crack in g . F o r all o th er m em b ers, n o tions addressed tendons in normal (non-corrosive)
ten sile stresses at serv ice lo ad lev els w ere allo w ed . environments, and tendons in aggressive (corrosive)
The 1971 Code, Prestressed ConcretePermissible environments. Normal environments were defined as
Stresses, required that tensile stresses in concrete be limited those present in nearly all enclosed buildings with dry
to 6 fc psi (0.5 fc MPa) for most members, but allowed interiors, and exposed structures in areas with very little
up to 12 fc psi (1.0 fc MPa) in tension in the concrete or no snow. Aggressive environments were defined as
provided computations were made using the cracked trans- those that would expose the structure to direct or indi-
formed section and a bi-linear moment-deflection relation- rect applications of deicer chemicals, seawater, brack-
ship to confirm that long-term deflection of the member ish water, or spray from these sources.
satisfied Strength and Serviceability RequirementsCon- Anchorages and couplings: Anchorages were required
trol of Deflections. In addition, the allowable tension limits to have watertight connection to the sheathing and a
could be exceeded provided that experimental and analytical watertight closing of the wedge cavity. Couplings were
work could show that performance would not be impaired. required to be protectively coated the same as the
In the 1977 Code, for an allowable tensile stress up to strand, since they become part of the strand.
12 fc psi (1.0 fc MPa), a provision was added requiring Sheathing: Sheathing material thickness was specified
that the concrete cover for prestressed and non-prestressed according to exposure, and was given as 0.025 in. (0.6
SINGLE STRAND TENDONS 423.4R-5
mm) for normal environment and 0.030 in. (0.8 mm) encapsulation of tendons to be used in aggressive envi-
for aggressive environment. The inside diameter of the ronments was specified with the same watertightness
finished sheathing was required to be at least 0.010 in. requirements given for anchorages. A statement was
(0.3 mm) greater than the diameter of the strand. added that calls for the designer to specify the amount
Corrosion-preventive coating: (Hereafter, the term of unsheathed strand permitted at the anchorages for
grease will be used to describe the corrosion-protec- tendons exposed to normal environments.
tive coating, defined in the PTI specification as ...an Corrosion-inhibiting coating (formerly Corrosion-pre-
organic coating with appropriate polar, moisture-dis- ventive coating) (commonly referred to as grease): All
placing, and corrosion-preventive additives.) The min- tendons are to use grease that meets the ASTM B117
imum weight of grease coverage of the strand was Rust Grade 7 criteria after 1000 hr. (The shorter test
given, as was a list of test requirements for the grease time previously permitted for tendons to be used in nor-
itself. The corrosion protection performance was based mal environments was dropped.)
on ASTM B-117 for the time until Rust Grade 7 devel- Installation requirements: The minimum cover require-
oped and was set as 720 hr minimum for normal envi- ment for anchorages was added and was specified to be
ronment and 1000 hr for aggressive environment. at least 1.50 in. (40 mm) for normal environments and 2
PTI reissued this specification in 1993 after substantial re- in. (50 mm) for aggressive environments.
visions were made to all chapters. Major changes are sum- Tendon finishing: Permissible length of strand projec-
marized below: tion from the face of the wedges was reduced. The pre-
Definition of exposure conditions: The terms used in vious projection allowed was 0.75 in. (20 mm)
previous specifications normal (non-corrosive) and minimum and 1.25 in. (30 mm) maximum; the revised
aggressive (corrosive), were changed to normal projection limits are 0.50 in. (12 mm) minimum and
and aggressive. The definitions of normal and aggres- 0.75 in. (20 mm) maximum.
sive remained similar to the 1985 specification except
that exposed structures in areas with very little or no CHAPTER 3UNBONDED TENDONS
snow were no longer mentioned as being in a normal 3.1Evolution of unbonded tendons
environment. The designer was advised to evaluate the The first building structures to use unbonded tendons in
conditions carefully to determine if the environment in North America were lift slabs built during the mid-1950s.4
which a structure is located is considered aggressive in The early, unbonded tendons were greased and helically
any way. wrapped with paper. They used high-strength wires, general-
Definition of exposure conditions: A stipulation was ly 0.25 in. (6 mm) diameter, with an ultimate strength of 240
added that stressing pockets not maintained in a dry ksi (1650 MPa), with button-head type anchorages, as shown
condition after construction should be considered by Fig. 3.1. This system had large cumbersome anchorages,
exposed to an aggressive environment. large trumpet transitions and a fixed distance between but-
Prestressing steel: Protection requirements were added tons at each end of the tendon. Systems also evolved during
for packaging and identification. A criterion was added this period that used single and multiple strands.
that limited surface rust to pits no more than 0.002 in. In the early 1960s the convenience of placing unbonded
(0.05 mm) diameter or length. (This type of rust can be single strand tendons was realized and the number of suppli-
removed with fine steel wool and might not be felt with ers increased. The marketplace found the competitiveness of
the fingernail.) this system favorable, and the use of unbonded single strand
Anchorages and couplers (formerly Couplings): tendons increased significantly. Anchorage hardware varied
Static test criteria were clarified and linked to ACI 318, considerably and included high-strength spirals, barrels, or
and dynamic test requirements were added. Design cri- castings with wedges, and fittings that were swedged (me-
teria were added for bearing stresses on concrete. A chanically attached) to the prestressing steel. The anchor that
stipulation was added that required anchorages prevailed was a casting that contained a recess to house a
intended for use in aggressive environments to be fully two-piece wedge for use with a single strand. This is current-
protected against corrosion. Encapsulation of the ly the predominant system and represents about 60 percent
anchorage, the connection of the sheathing to the of all post-tensioning tonnage.5
anchorage encapsulation, and the seal of the wedge By the late 1960s, plastic began replacing paper sheathing.
cavity were required to sustain a hydrostatic water pres- Three different processes have been used (Fig. 3.2 and 3.3):
sure of 1.25 psi (0.0086 MPa) for 24 hr. 1. The strand is covered by preformed push-through plastic
Sheathing: The thinner sheathing previously allowed for tubes; 2. The strand is wrapped longitudinally with a
tendons to be exposed to normal environments was heat-sealed strip; and (most recently) 3. The greased strand
removed; the minimum thickness of sheathing was spec- is covered by molten plastic that is continuously extruded
ified as 0.040 in. (1.0 mm) for both environments. The around it.6 Thickness and composition of the sheathing ma-
size of the annular space between the outside of the terial were left to the supplier and were not uniform in the in-
strand and the inside of the sheathing was increased from dustry. The first effort to regulate these items was by the PTI
0.010 in. (0.3 mm) to 0.030 in. (0.8 mm). Complete in their 1985 specification.
423.4R-6 MANUAL OF CONCRETE PRACTICE
Fig 3.1(a) Live end anchorage assembly for button-headed wire post-tensioning system;
(b) intermediate anchorage assembly with threaded coupler rod; and (c) dead end anchor-
age assembly; dimensions A and B were usually 4 and 6 in. (100 and 150 mm),
respectively, for a typical 7-wire slab tendon (reprinted from Reference 1).
Initially, there were no corrosion protection standards for of grease to be applied to the prestressing steel. Deterioration
the grease (except in the nuclear industry, refer to ACI 359- of the grease was not expected, but as problems became
74, Code for Concrete Reactor Vessels and Containments), known they were addressed by the PTI in their recommended
so the tendon manufacturers used the grease of their choice. specifications.
Corrosion-resisting properties of the grease were not speci-
3.2Sheathing problems
fied, nor were there standards for the uniformity and amount The push-through system required that the sheathing be
sufficiently oversized to allow the greased strand to be in-
serted without too much difficulty. This resulted in a tendon
with many air voids inside the sheathing and allowed infil-
tration of water during storage, shipping, and installation,
and in service.
With the heat-sealed system, the sheathing was provided
in rolls of flat plastic tape that was usually 20 to 40 mils (0.5
to 1.0 mm) thick. During tendon fabrication, the strand
would be taken from the pack and passed through a grease
extrusion head. The tape was then folded over the greased
strand and the lapped seam welded shut with a flame. This
method also formed a slightly oversized sheathing that could
have air voids. The seam weld was interrupted every time
there was a pause in the process, and sometimes the sealed
seam pulled apart during handling or installation. This sys-
tem is frequently found to have gaps from one cause or an-
other that expose the greased strand to contact with the
concrete.
Seamless extruded sheathing first appeared in the early
1970s.7 The extruded sheathing minimized the problems ex-
perienced with the push-through and heat-sealed systems by
providing a snug, seamless sheathing around the greased
strand.
3.3Detailing practices
Fig. 3.2Evolution of corrosion protection for unbonded sin- Certain details that were initially considered acceptable
gle strand tendons for buildings (reprinted from Reference 2). are insufficient to provide the degree of durability required
SINGLE STRAND TENDONS 423.4R-7
Fig 3.4Potential defects in corrosion protection at unbonded single strand tendon live
end anchorage.
423.4R-8 MANUAL OF CONCRETE PRACTICE
have been found to suffer from brittle failure. The primary can damage the corrosion protection provided by the grease
problem has been either corrosion of the wedges or the mi- and sheathing.
gration of water down the tendon in the void between the Typical problem areas have included:
wires or around the outside edge of the strand. Corrosion Tearing and/or cutting of the sheathing by wire or metal
failures of the strand have occurred in the unsheathed length bands that hold the tendons in coils for shipping;
in front of the anchor, at low points in the profile where water Tearing and/or cutting of the sheathing by unpadded
collects, and at points where sheathing was damaged and slings used to lift the bundles of tendons from the truck
permitted direct access of corrosive materials. to the storage area, and from the storage area to the
At intermediate anchorages, features of both dead- and formwork where they are to be placed;
live-end anchorages are found. The sheathing may not be ad- Unprotected storage, such as leaving the tendons in
equately sealed to the anchorage on the first pour side. direct contact with the ground, leaving them exposed to
Strand and anchorages may be in direct contact with con- snow or rain, or placing them where they will be dam-
crete on the second pour side of the anchorage. Water aged by construction traffic;
could gain access to the tendon during shipping, storage, and Rough handling during placement of tendons in form-
installation, or after construction has been completed. Prob- work, causing splits and tears in the sheathing;
lems have developed at the intermediate anchorages when Incomplete repair of damage to tendon sheathing;
the construction joint over the anchorages was not sealed to Leaving the unsealed tendon ends exposed to the
prevent leaking of water (sometimes containing chlorides) weather, either before concrete placement or after
through the construction joint in elements exposed to the stressing;
weather, such as in parking structures and balconies. Signif- Inadequate cover over the cut-off strand tail at live-end
icant chloride contamination of concrete has occurred as a stressing pockets;
result of leakage through unsealed construction joints. Inadequate concrete cover to protect the tendon at high
Corrosion of the upper surface of the anchorage castings, and low points of drape, and at the anchorages;
and of backer bars, can cause corrosion-induced spalling at Voids inside sleeves or trumpets, where water may col-
an early age. Such spalls then act as small reservoirs for wa- lect;
ter, further accelerating the deterioration process. Corrosion Improper grouting of the stressing pockets; and
of the backer bars, bearing plates or anchorages, and on Using grout material that contains chlorides or other
occasion the strand, is promoted by this frequent supply of chemicals that will accelerate corrosion of the strand.
water and oxygen adjacent to the joint. With the earlier bear- Some current encapsulation systems used in aggressive
ing plate and intermediate barrel anchorage hardware, the environments incorporate oversize sleeves or trumpets to as-
bearing plate was occasionally located outside the bulk- sist in sealing the tendon at the transition from the sheathing
head of the slab, meaning that the construction joint would to the anchorage. Since these systems rely on friction rather
be located directly over the plate and allow water to come than on a mechanical connection between the anchor and the
into contact with strand end anchorage. sleeve, these sleeves have been seen to work loose and pull
away from the anchorage prior to or during concrete place-
The designers choice of locations for anchorages has
ment. Final inspection with reattachment as necessary has
sometimes led to corrosion problems. Locating anchorages
been required to achieve the intent of the PTI 1985 and 1993
in gutter lines or expansion joints of parking structures or at
Specification for Unbonded Single Strand Tendons for
exposed edges of slabs in commercial and residential build-
protection of unbonded tendons.
ings (i.e., balconies) has resulted in water infiltration into an-
Damage to the protective grease and sheathing or exposure
chorage areas and caused corrosion failures of the strand.
to moisture during these periods of the construction could
Without special waterproofing, construction joints at beam-
adversely affect the future performance of the post-tension-
column connections have, on occasion, allowed water to en-
ing, but neither responsibility for protection nor specific
ter tendon sheathing through the anchorages in joints in col-
measures for achieving protection were defined in an indus-
umns. These joints are seldom sealed, even though they are try-wide specification or procedure. These issues are now
frequently in the drainage flow path, and can be exposed to partially addressed in Field Procedures Manual, 2nd edi-
rain and melting snow. Water running down the face of a col- tion. As of 1997, the PTI Specification for Unbonded Sin-
umn can gain access to the tendon anchorage if consolidation gle Strand Tendon is being reviewed, rewritten, and
of the concrete at the construction joint is poor. Honey- incorporated through a standardization process by ACI/
combed, permeable concrete, ponding areas, leaking con- ASCE Committee 423, Prestressed Concrete. Concerns re-
struction joints, misplaced conduits, and other construction garding shipping and handling are being considered.
defects can all contribute to water access to tendons.
3.5Deterioration mechanisms
3.4Storage, handling, and construction problems In most cases, the corrosion mechanism requires that wa-
Though the tendon sheathing is fairly tough, the wear and ter and oxygen be present. If a corrosion-inhibiting grease
tear to which it is sometimes subjected during shipping, stor- completely covers the strand, and the grease is not affected
age, handling, and concrete placement can be severe. These by water, corrosion generally will not occur. There is always
SINGLE STRAND TENDONS 423.4R-9
Fig 4.1Loops of failed tendons that burst through top of Fig. 4.2Failed tendons protruding from ceiling. Location
slab. Note kinks in individual wires of upper tendon; some- of break in tendon is remote from location of protruding
times these are the only portion to burst through the con- loops.
crete cover.
defects, eliminate the causes of deterioration where practical,
There are no recorded incidents of sudden collapse of slow continued deterioration, and determine requirements
structures using unbonded tendons while the structure is in for monitoring and future maintenance.
service. Demolition of these structures has shown that they
possess greater reserve of strength than is shown by struc- 4.2Condition surveys of concrete
tures that are not post-tensioned. One characteristic of struc- Many references in Chapter 7 provide specific information
tures that use unbonded tendons is their propensity to develop about the generally accepted methods for evaluation of con-
significant catenary action even while the main parts of the slabs crete structures. Typical procedures are reviewed here.
and beams are being pulverized or broken away.11,12 While The evaluation should include a careful and well-docu-
there is no guarantee against a sudden partial collapse, it is mented inspection to identify deterioration and distress, and
likely that a post-tensioned structure will continue to perform to identify their causes. If available, the original design
in a ductile manner even when a significant number of the drawings and shop drawings should be reviewed to identify
tendons have failed. problems that might be attributed to the design, detailing, or
material selection. The drawings should be compared with
CHAPTER 4EVALUATING CORROSION DAMAGE the findings of the condition survey to assess the in-service
4.1General performance and determine whether suspected problems are
Almost any structure can have its useful life extended by local or might be widespread. It is normal for the as-built
the use of appropriate maintenance procedures and suitable conditions to differ from the drawings to some degree. Refer
repairs, whether the structure is of post-tensioned concrete or to ACI 364.1R, Guide for Evaluation of Concrete Struc-
of some other material. The cost of repairs can usually be es- tures Prior to Rehabilitation, and ACI 437, Strength Eval-
timated to a reasonable degree of accuracy and a judgment uation of Existing Concrete Structures, for additional
made as to the feasibility of that investment. For concrete guidelines.
structures that do not use unbonded tendons, damage caused A crack survey is useful since cracks can be caused by
by corrosion is estimated by examination of rust-stained or structural distress, insufficient cover to reinforcing bars or
spalled areas. It is assumed, based on spot checking and on tendons, incipient delaminations due to corrosion of rein-
past performance of similar conditions, that the reinforce- forcement or embedded conduit, or restrained shrinkage.
ment is serviceable in areas where the concrete is not stained, Notes should be made to document the width and length of
spalled, or delaminated. That same logic applies to evalua- the cracks, as well as the presence of leakage, efflorescence,
tion of deterioration of bonded reinforcing bars in structures and rust stains.
using unbonded tendons, but it is of less help in evaluating A survey should be performed to locate delaminations in
the tendons themselves. slabs and other structural members, using methods that are
An appropriate evaluation of the condition of the structure appropriate to the conditions. The delamination survey can
should be performed to minimize the risk of overlooking be used to estimate the extent and distribution of corrosion
something significant. Ultimately, decisions will have to be damage in the reinforcing system.
made about the types of repairs to be made and the need to Typical materials testing to be performed may include:
augment the reinforcing system. These decisions are gener- Chloride-ion content testing to determine the depth and
ally based on an engineering evaluation of the data collected, intensity of chloride penetration, and to estimate the
and should be made by an experienced investigator who un- chloride content of the original concrete. Chloride con-
derstands that all latent deficiencies have probably not been tamination can promote corrosion of portions of the
identified. As in any repair, the objective is to fix the obvious post-tensioning system in contact with concrete as well
SINGLE STRAND TENDONS 423.4R-11
as conventional reinforcing and hardware whose corro- distance from midspan toward the supports.
sion may damage the concrete protection of the post- An unintended reversal in the curvature of the tendons
tensioning. at any point in the beam can cause splitting of the beam
Evaluation of depth of carbonation into the concrete. due to local internal tension in the concrete around the
This reaction decreases the pH of the concrete, thus reversal, produced when the tendons are tensioned.
making corrosion more likely in the presence of mois- These cracks can form without affecting the condition
ture and oxygen. of the post-tensioning tendons but can be a warning of a
Obtaining measurements of concrete cover over ten- potential blowout.
dons and reinforcing steel and, if appropriate, correlat- Cracks in the area of beam-column connections may be
ing these measurements with the chloride due to structural action, to a deficiency of reinforce-
contamination profiles or depth of carbonation. ment intended to control bursting stresses in the tendon
Copper-copper sulfate half-cell testing to determine anchorage zone, to restrained shrinkage, or to a combi-
whether corrosion activity is presently occurring in the nation of these effects. Water that enters these cracks
reinforcing system. (These tests may not provide mean- has easy access to the ends of the tendons and can cause
ingful information on tendons because of the lack of further deterioration.13
electrical continuity but may indicate likelihood of cor- Stains on the surface of the concrete can also provide ex-
rosion activity on anchorage hardware and reinforcing ternal evidence of possible internal distress due to corrosion
where electrical continuity of steel and contact with of the post-tensioning system. Grease stains on the soffits of
concrete are present.) slabs, especially at low points of tendon profiles, can be an
Extracting concrete cores for compressive strength test- indication of unrepaired damage to the tendon sheath as well
ing and for petrographic examination to include air void as shallow concrete cover over the tendons. Such grease
system analysis. (Tendons should be located before cor- staining may be accompanied by water stains or evidence of
ing begins.) leaching, indicating water infiltration into the slab tendons.
Rust staining in the vicinity may be the result of corrosion of
4.3Condition surveys of tendons the post-tensioning steel or perhaps only the supporting bol-
It is possible to obtain some information about the likely sters. A compromise in the corrosion protection of the post-
condition of the post-tensioning system by means of the vi- tensioning is indicated and would warrant further testing and
sual inspection. The visual inspection can help to identify exploratory concrete removal, as discussed in Section 4.5.
specific external evidence of possible internal distress. The Visual inspection of exposed end anchorage grout pockets
visual inspection can also help identify whether there is a should be performed, especially where exposure to moisture
pattern to the distress, and may point to the possible extent of is evident, and correlated with any signs of distress such as
a problem. described above. Evidence of shrinkage, cracking, debond-
Cracking of concrete in post-tensioned structures can be ing, freeze-thaw damage or rust staining coming from the
the result of problems with the post-tensioning system, but grout pocket may indicate a potential breach in corrosion
all cracks should be evaluated for their impact on future du- protection of the anchorage and post-tensioning tendon.
rability. Following are some examples of cracking patterns that The most obvious external evidence of corrosion damage
may provide information about the post-tensioning system: is the presence of loops of strand sticking out of the structure
Cracks that are vertical in beams, and cracks that are (Fig. 4.1 and 4.2). Such loops result when the strand breaks
perpendicular to the direction of span in slabs, may and the elastic energy is released suddenly. The strands
indicate a loss of post-tensioning force. A structural typically will erupt from the slab at high points or low points
analysis taking into account possible losses of post-ten- in the tendon profile where concrete cover may be shallow,
sioning precompression due to built-in restraint can but occasionally only a single wire will burst through the sur-
provide an indication of whether such cracking could face of the concrete. Loops formed by this phenomenon can
be anticipated. If a large discrepancy is found between be anywhere from 1 in. (25 mm) to 2 ft (600 mm) high. Rath-
the calculated service load stresses and the actual er than bursting from the structure at some point midway be-
observed extent of cracking, then a loss of post-tension- tween anchorages, the tendon may also protrude out of the
ing may be indicated. structure a distance of several inches or several feet.
Longitudinal cracks in beams, either on the sides or Strand breakage can occur without visible disturbance to
across the bottom in line with the tendons, may be an the concrete, so the absence of strand loops or projections is
indication of water infiltration into the tendons. As the not to be taken as an absence of broken tendons. Most post-
sheathing fills with water and freezes during winter tensioned structures use higher strength concrete (with high-
months in colder climates, expansion due to formation er cracking strength) and/or may incorporate (perhaps unin-
of ice can cause splitting of the concrete cover over the tentionally) a significant degree of restraint or redundancy
tendons. (i.e., below grade construction or two-way slab construc-
Leaking or leaching of moisture through the cracks is tion), so it is possible to have as many as 50 percent of the
an indication of water infiltration. Cracking due to tendons broken in a beam or in an area of slab without obvi-
water infiltration may follow the tendons a considerable ous distress.
423.4R-12 MANUAL OF CONCRETE PRACTICE
The location at which the tendon or wire has erupted out anchorage, or where on the strand), or whether wires or
of the structure is usually some distance away from the loca- the entire strand are broken.
tion of actual failure. Exploratory concrete removals com- Ultrasonic pulse velocity (ASTM C 597) is useful in
bined with the removal of the broken tendon will be required determining certain properties of concrete, but it has
to identify the location, nature, and the possible causes of the not proven to be adaptable to determining the integrity
failure. of tendons.
The visual review of the structure can serve to determine Half-cell potential (ASTM C 876) can be used to deter-
the distribution of such eruptions in the structure, which can mine the presence of corrosion activity in bonded rein-
then be correlated to detailing problems and inadequate cor- forcing bars and in anchors and strands that are in
rosion protection to help determine the possible appropriate contact with concrete. Half-cell testing does not reli-
repair and protection measures. It may be useful to attempt ably locate corrosion along the length of a tendon since
to determine the distribution of such eruptions over time as the grease and sheathing will electrically insulate the
well to see if any trends are apparent in the frequency of ten- strand. This method is redundant where visible evi-
don failures with the passage of time. Unfortunately, delay- dence of corrosion is present.
ing repairs to monitor tendon failures may permit Pachometer devices will locate greased and sheathed
acceleration in the rate of deterioration. Usually it is better to tendons as well as bonded reinforcement. They are use-
begin repairs as soon as a reasonable condition study has ful in estimating the thickness of concrete cover over
been completed rather than to wait for months or years to anchorages and along strands, and the thickness of
gather more information. In a few cases, the rate of corrosion grout protection of strand stubs at stressing pockets.
activity has been observed to increase over time, indicating Pachometer readings for anchorages and stubs as well
that the rate of tendon failures could increase with time. as along strands may require calibration by comparing
against actual physical measurements of concrete cover
4.4Nondestructive testing thickness.
Currently there are no dependable nondestructive testing Vacuum testing of grouted stressing pockets can assess
methods for evaluating the existing condition of tendons in- the quality of the grout and its bond to the sides of the
side a structure. The main shortcomings of present test meth- block-out.2 Such testing can help quantify the effective-
ods include inability to provide information about severity or ness of the grout plug in preventing water from infiltrating
location of pitting, gross section loss, location of pre-existing the post-tensioning tendon.
cracks or breaks, or breaks and section loss of individual Impact-echo testing can be used to supplement a
wires in a strand. Several common procedures are reviewed delamination survey to more accurately determine the
below with comments about their limitations for application delaminated areas. It can also be used to determine
to unbonded tendons. crack depths, voids, and honeycombing. Impact-echo
X-ray techniques are often used to locate embedded provides no information regarding the strand condition.
reinforcing in concrete, usually for a very limited area
due to their expense. X-ray cannot be used to obtain 4.5Exploratory concrete removal
information about pitting, breaks, or loss of cross sec- Usually it is necessary to chip into the concrete to inspect
tion of individual wires. The images obtained are fuzzy the strand, grease, sheathing and anchorages, and to assess
and do not lend themselves to fine interpretation. Also, the extent of corrosion activity of the bonded reinforcement.
other reinforcement can shield the tendon being This procedure is slow and is limited to parts of the struc-
checked. It is usually impractical to use this method ture that are accessible. For example, anchorages for beam
along the length of a tendon to find strand breaks. tendons are frequently embedded in columns and are not
Radar (ASTM D 4748) can also be used to locate readily exposed. Occupied structures present special prob-
embedded reinforcing in concrete. Radar has the same lems since concrete removal is noisy and dirty. The number
limitations as X-ray but is more adaptable to scanning of inspection opportunities may be small compared to the to-
large areas to locate reinforcement, including tendons. tal number and lineal footage of tendons in a structure, so the
Acoustic emission (not to be confused with Continuous information obtained may not be statistically meaningful.
Acoustic Monitoring discussed in Section 5.6) is a Exploratory concrete removal can be used to calibrate or
technique for locating corrosion based on detection of confirm results from nondestructive tests.
high-frequency sounds emitted at sites of active corro- Repair of concrete removals should restore grease, sheath-
sion, and has been used successfully on steel structures ing and concrete protection. Refer to ACI 546, Guide to Re-
such as storage tanks. For detection of corrosion dam- pair of Concrete.
age in post-tensioning, acoustic emission is an experi-
mental procedure from which has come no correlation 4.6Exposing tendons
between test results and the condition of tendons. With Exposing parts of tendons is most convenient where con-
acoustic emission testing, it is not possible to determine crete cover is shallowest, such as at low points or high points
the nature of the corrosion damage (surface attack ver- in the tendon profile. In most structures, it is preferable to ex-
sus pitting), the location of the damage (strand versus pose the strand at low points in the profile for several reasons:
SINGLE STRAND TENDONS 423.4R-13
first, removal of the upper surface often will be more disrup- Exploratory concrete removals undertaken in the area of
tive to the use of the building; second, the upper surface is intermediate anchorages are useful, particularly where leak-
often more exposed to sources of water or other aggressive age has occurred through construction joints. The stressing
agents, and achieving good quality and timely repairs to re- side of the joint is the side that can be exposed without com-
establish protection may be difficult at the time exploratory promising the integrity of the tendon; the concrete on the
work is being performed, or it may be desirable to leave the other side is under compression and should not be disturbed.
test areas open for some period for repeated viewing; and Exploratory concrete removals should not be started with-
third, if water is present in the tendons, it tends to collect at out a detailed plan of action. A specification should be pre-
low points in the profile and is more likely to be detected pared that outlines safety precautions and acceptable
there, especially for loosely sheathed strand. Care must be procedures for demolition, encapsulation repairs, and con-
taken in all cases not to damage the tendons since they are crete patching. Individuals performing the chipping must be
usually fully stressed. educated about tendons so that they understand what they are
It must be kept in mind that an unblemished, greasy strand looking for and the consequences of breaking a strand. They
uncovered in a convenient area can be seriously corroded a should use slow, careful means of concrete removal, and use
few feet away without showing distress. Once broken, the tools that are appropriate to the task. Refer to ACI 546.1R,
tendon has lost its structural value for its entire length, so it Guide to Repair. As previously discussed, broken strands
is important to take as many observations as possible and to can erupt vertically through the top or bottom surfaces of the
locate them in the areas of suspected corrosion. Engineering concrete, or horizontally through the anchors.
judgment must be applied to estimate the current condition
and future performance of the structure. 4.7Strand removal
As previously discussed, grease stains or water stains on Strands can be removed for inspection, but it is unusual to
the soffit of the slabs and beams can help identify locations cut a live tendon for this purpose. It is more common to ex-
where exploratory removals may be desirable. Locations that tract part of a strand that is known to be broken, usually one
appear to be free from distress should also be examined to that has erupted from the concrete. It is usually possible to
provide a more representative picture of the general condi- remove the strand between the eruption and the break, but
tion of the tendons. considerable effort is sometimes required. Laying the strand
Exposing selected tendons for a length of at least 12 in. piece on the deck is a simple way to find the location of the
(300 mm), for as much of their circumference as practical, break. Once removed, the strand can be examined to deter-
can provide the following information: mine the condition of the grease, the frequency and severity
The type of sheathing (paper-wrapped, push-through, of corrosion, and the type of failure of the wires.
heat-sealed or extruded), its tightness to the strand, and Signs of corrosion are sometimes subtle and look more
its thickness; like stains than rust, so it is important that the strand be ex-
Unrepaired damage to the sheathing; amined closely by someone experienced in this type of eval-
uation. The failed end of a strand can be submitted to a
Water within the sheathing;
metallurgical testing laboratory for an analysis of the broken
The condition of the grease; wires. Microscopic examination of the external and internal
Corrosion on the strand; wires of the strand can be performed to look for cracking,
Verification of stand size; and pitting, and corrosion.
Loose strand or wire indicating prestress loss. Chemical residue present on the wires at the failure loca-
Loose strand or wire is commonly checked by means of tion can sometimes be identified and related to the failure.
pry bars or screwdrivers. If the strand can be displaced any Testing of physical and mechanical properties of the strand
significant amount with a pry bar, it is likely there is little or can be performed on strand taken some distance from the
no tension remaining in the strand. This testing is subjective, break to determine tensile strength, elongation, and bend
since the length of strand exposed affects the amount of dis- testing.
placement which can be obtained. The screw driver penetra-
tion test can be used to identify loose or broken wires. The 4.8Other testing and investigative procedures
inspector attempts to drive a standard (flat blade) screwdriv- Lift-off testing (pulling the strand loose from an anchor to
er between the wires of the strand at an inspection port. Pen- measure its effective force) can be used to check tension in
etration of the screwdriver indicates little or no force in the the strands, but is difficult to do with single strand tendons in
wire(s). If sufficient length of the strand is exposed, the test a completed structure. Since the strand has been cut close to
can be performed between each of the six outer wires, thus the wedges, special tools are required to grip the strand stub
identifying individual wire breaks. The test is also subjective sufficiently to pull on the strand and loosen the wedges. Cor-
and will not necessarily detect all wire breaks, especially if rosion increases the locking force of the wedges and weak-
they are at some distance from the inspection location. Inter- ens the stub, making the process difficult to execute.
mediate anchorages and bonding of the tendon by build-up Welding an extension onto the strand is not feasible because
of corrosion product may maintain sufficient force in the ten- of the likelihood of permanently damaging the anchorage
don to mask strand or wire breaks. and the strand. When barrel anchorages have been used, it
423.4R-14 MANUAL OF CONCRETE PRACTICE
may be possible to clamp onto the barrel and perform a lift- maintain adequate precompression or ultimate strength.
off of the tendon in this manner. However, care should be Where the type and condition of the strand and sheathing
taken since barrels are generally heat-treated, making them permit, it is possible to replace the old strand with one of the
hard, difficult to grip, and non-weldable. same diameter. If analysis indicates that a reduction in load
Lift-off tests will not provide any information about the carrying capacity below code limits, and especially below
amount or distribution of corrosion on the strand, nor will service load levels, has occurred, then evacuating or shoring
they give an indication of the loss of ultimate strength. It will the affected portions of the structure may be required in ad-
only provide knowledge that the strand had the ability to sus- vance of repairs.
tain the force held by the jack after the wedges came loose. When tendon corrosion has progressed to the point where
Typically, lift-off tests do not exceed the tension originally the strength of any part of a structure has been reduced to an
used to set the wedges. Sometime the strand will break just unacceptable level, repairs should be considered to correct
after the wedges come loose, indicating that strength was lost the deficiency. The type of repair will depend on the extent
before the test. The logical next step is to pull the strand out (or assumed extent) of the corrosion damage and the result-
of the sheathing for inspection. ing loss of strength. If the damage is known to be minor, and
An alternative to lift-off testing is to check for tension in its location is easily identified, the remedy may consist of
the strand using equipment that analyzes the vibration char- simply repairing and protecting the existing tendons. Most
acteristics of the strand under tension. This equipment is probably a variety of conditions will be encountered, some
adapted from that used to check tendons in cable-stayed of which might require the removal and replacement of en-
bridges and in similar applications. tire tendons. Engineering assessment of the proposed repair
A portion of the strand is exposed, typically about 2 ft (600 methods and sequence is needed to determine how the repair
mm), and the ends of the exposed length are chocked to pro- process may further affect the integrity of the structure.
vide node points. An accelerometer is attached to the ex- When the actual or assumed extent of damage makes lo-
posed strand and the strand excited by means of tapping. The calized repairs impractical, the structure may need to be
vibration is transmitted from the accelerometer to computing strengthened with an externally applied structural system
equipment to determine the tension in the strand as a func- consisting of post-tensioned tendons, structural steel sec-
tion of the frequency of vibration. As with lift-off testing, tions, or concrete members. External post-tensioning sys-
checking tension in this manner does not provide detailed in- tems have been designed to completely replace the original
formation about corrosion on the strand. tendons in some structures. These various approaches are
Load testing of slabs and beams in accordance with ACI discussed in the following sections. When external strength-
318 under Strength Evaluation of Existing Structures pro- ening is not feasible, partial or complete demolition and re-
vides no detailed information about the condition of the in- placement may be necessary.
dividual tendons. A significant number of tendons could
have failed without being detected by a load test. The period 5.2Existing tendon repair
of time subsequent to the testing for which the test results are Visible evidence of tendon corrosion, such as that which
valid is subject to a great deal of uncertainty, and ACI 318 may be seen on exposed tendon anchorages where the stress-
provides no guidance for estimating the remaining service ing pocket has not been grouted, should be repaired as quick-
life. Also, load testing is expensive and disruptive. There- ly as possible. The exposed part of the anchorage should be
fore, although a load test can confirm that the tested part of cleaned by abrasive blasting or equivalent, coated with a
the structure has adequate strength at the time of the test, this rust-preventive paint or other corrosion protection, and the
method has limitations when applied to structures with sus- stressing pocket properly filled in accordance with PTI
pected or known corrosion damage to unbonded tendons. Specification for Unbonded Single Strand Tendons.
In a structure where tendon corrosion has been diagnosed,
CHAPTER 5REPAIR SCHEMES AND METHODS appropriate means of stopping or slowing the rate of corro-
5.1General sion in the existing tendons should be applied. Eliminating
Prior to launching a repair effort of any kind, it is prudent water intrusion is of primary importance, so concrete repairs
to determine the causes of corrosion damage and possible should be made and cracks should be sealed. Random cracks
preventative measures which may be taken. Incorporating can be routed and sealed, but consideration should be given
measures that address causes of deterioration can make a re- to the application of a waterproofing membrane, possibly in-
pair program more effective for extending the useful life of corporating a wearing surface as appropriate, if extensive
the structure. Whether the need for tendon repair is critical cracking is present or if there is widespread deficiency of
should be assessed by analyzing the structure to determine if protective concrete cover throughout the structure or a por-
sufficient reserve capacity exists to adequately support the tion of the structure. Refer to ACI 224.1R, Causes, Evalua-
design loads after a few tendons are lost. In some cases it tion and Repair of Cracks in Concrete Structures.
might not be necessary to replace every broken or damaged
tendon, or it might be reasonable to use smaller diameter 5.3Strand replacement
strand to replace the strands that were removed. The smaller When a strand has been inadvertently cut or damaged, or
diameter tendon may be of a higher strength if required to when corrosion damage is known or believed to be localized,
SINGLE STRAND TENDONS 423.4R-15
11. Freyermuth, C. L., Structural Integrity of Buildings Constructed Zones of Post-Tensioned Beams, Cracking in Prestressed Concrete
with Unbonded Tendons, Concrete International, Mar. 1989. Structures, SP-113, American Concrete Institute, Farmington Hills,
12. Suarez, M. G., and Schupack, M., Evaluation of the Performance of Mich., 1989.
Single Strand Unbonded Tendons in the Collapse of the LAmbiance Plaza 14. Elliott, J. F., Monitoring Prestressed Structures, Civil Engineering, Jul.
Lift Slab Building, Post-Tensioning Institute Project Report, Phoenix, 1996.
Ariz., April 1988. 15. Chacos, G., Demolishing a Post-Tensioned Parking Garage, Con-
13. Nawy, E. G., Stresses, Strains, and Bursting Cracks in Anchorage crete International, V. 13, No. 10, Oct. 1991, pp. 44-46.