Customer Service/Sales:

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385

Series TY-L 5.6 and 8.0 K-factor


Upright and Pendent Intermediate Level Sprinklers
Standard Response
standards of the National Fire Protec-
General tion Association, in addition to the
standards of any other authorities hav-
Description ing jurisdiction. Failure to do so may
impair the performance of these de-
The Series TY-L, 5.6 and 8.0 K-factor vices.
Upright and Pendent Intermediate
Level Sprinklers described in this data The owner is responsible for maintain-
sheet are automatic sprinklers of the ing their fire protection system and de-
standard response solder type. They vices in proper operating condition.
are standard spray sprinklers in- The installing contractor or sprinkler
tended for use in fire sprinkler systems manufacturer should be contacted
designed in accordance with the with any questions.
standard installation rules recognized
by the applicable Listing or Approval
agency (e.g., UL Listing is based on
NFPA requirements). Both the Pen- Model/Sprinkler
dent and Upright Sprinklers produce a
hemispherical water distribution pat- Identification
tern below the deflector.
Intermediate Level Sprinklers are pri- Numbers
marily designed for use in rack storage TY3113 - Upright 5.6K, 1/2"NPT
sprinkler systems where their ther- TY3211 - Pendent 5.6K, 1/2"NPT
mally sensitive elements must be TY4113 - Upright 8.0K, 3/4"NPT
shielded from the water spray of higher TY4211 - Pendent 8.0K, 3/4"NPT
elevation sprinklers that could operate
earlier during a fire. Intermediate Level TY3113 is a redesignation for S1809
Sprinklers are also used in other appli- and G3253.
cations such as beneath open gridded TY3211 is a redesignation for S1801
catwalks. and G3112.
TY4113 is a redesignation for S1822
and G3153.
WARNINGS
The Series TY-L Sprinklers described TY4211 is a redesignation for S1811
Technical
herein must be installed and main-
tained in compliance with this docu-
and G3102. Data
ment, as well as with the applicable Approvals
UL and C-UL Listed.
FM Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the INSTALLER
WARNING that provides cautions Maximum Working Pressure
with respect to handling and instal- 175 psi (12,1 bar)
lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
stallation can permanently damage K = 8.0 GPM/psi1/2 (115,2 LPM/bar 1/2)
a sprinkler system or its compo-
nents and cause the sprinkler to fail Temperature Ratings
to operate in a fire situation or cause Refer to Table A
it to operate prematurely. Finishes
Natural Brass

Page 1 of 6 JANUARY, 2005 TFP350


Page 2 of 6 TFP350

3" (76,2 mm) DIA.

1/2" NPT

2-11/16" FACTORY
(68,3 mm) ASSEMBLED
UPRIGHT 7/16"
7/16" SHIELD MODEL S5 (11,1 mm)
(11,1 mm)
PENDENT NOMINAL
NOMINAL
WRENCH SHIELD MAKE-IN
MAKE-IN
FLANGES WITH 2-5/8"
O-RINGS (66,7 mm)
WRENCH
AREA
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)

* Temperature rating is indicated on the deflector or shield.


** Pipe thread connections per ISO 7/1 can be provided on special request.

FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY3113) AND PENDENT (TY3211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT

3" (76,2 mm) DIA.

3/4" NPT

2-3/4" FACTORY
(69,9 mm) ASSEMBLED
UPRIGHT 1/2"
1/2" (12,7 mm)
SHIELD MODEL S5
(12,7 mm) NOMINAL
NOMINAL PENDENT
SHIELD MAKE-IN
MAKE-IN WRENCH
FLANGES WITH 2-11/16"
O-RINGS (68,3 mm)
WRENCH
AREA
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)

* Temperature rating is indicated on the deflector or shield.


** Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY4113) AND PENDENT (TY4211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT
TFP350 Page 3 of 6

SPRINKLER FINISH
K = 5.6, UPRIGHT TY3113 K = 8.0, UPRIGHT TY4113
K = 5.6, PENDENT TY3211 K = 8.0, PENDENT TY4211

TEMP. FRAME NATURAL NATURAL


RATING COLOR BRASS BRASS
CODE
165F/74C Unpainted
1, 2, 3
212F/100C White
280F/138C Blue

NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
TABLE A
LABORATORY LISTINGS AND APPROVALS

Physical Characteristics
Frame . . . . . . . . . . . . . . Brass Design
Sealing Button . . Bronze w/Teflon
Ejection Spring . . . . Stainless Steel Criteria WRENCH
Fusible Element . . . Solder, Copper RECESS
. . . . . . . . . . . . Stainless Steel The Series TY-L Pendent and Upright
Strut . . . . . . . . . . . . . . Monel Intermediate Level Sprinklers are in-
Hook . . . . . . . . . Bronze/Monel tended for fire protection systems de-
Deflector . . . . . . . . . . . Bronze signed in accordance with the stand-
Shield . . . . . . . . . . . . . . Brass ard installation rules recognized by the
DuPont Registered Trademark applicable Listing or Approval agency
(e.g., UL Listing is based on the re-
quirements of NFPA 13, and FM Ap-
proval is based on the requirements of FIGURE 3
Operation FMs Loss Prevention Data Sheets). W-TYPE 9 SPRINKLER
WRENCH
A copper tube sealed by two stainless
steel balls holds a fusible alloy. When Installation
the rated temperature is reached, the plied to the pipe threads, hand tighten
alloy melts, the balls are forced toward The Series TL-B Sprinklers must be the sprinkler into the sprinkler fitting.
each other releasing the tension installed in accordance with the follow-
mechanism, allowing the sprinkler to ing instructions: Step 2. Tighten the sprinkler into the
operate. sprinkler fitting using only the W-Type
NOTE 9 Sprinkler Wrench (Ref. Figure 3).
A leak tight 1/2 inch NPT sprinkler joint With reference to Figure 1 or 2, the
should be obtained with a torque of 7 W-Type 9 Sprinkler Wrench is to be
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- applied to the wrenching area.
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with Pendent Sprinklers
1/2 NPT connections. A leak tight 3/4 The Series TY-L Intermediate Level
inch NPT sprinkler joint should be ob- Pendent Sprinklers must be installed
tained with a torque of 10 to 20 ft.lbs. in accordance with the following in-
(13,4 to 26,8 Nm). A maximum of 30 structions.
ft.lbs. (40,7 Nm) of torque is to be used Step 1. Roll one of the two required
to install sprinklers with 3/4 NPT con- O-Rings over the sprinkler threads un-
nections. Higher levels of torque may til it seats against the sprinkler wrench-
distort the sprinkler inlet and cause ing area flange as shown in Figure 1 or
leakage or impairment of the sprinkler. 2, as applicable.
Upright Sprinklers Step 2. Install the Shield over the
The Series TY-L Intermediate Level sprinkler threads, and then roll the sec-
Upright Sprinklers must be installed in ond O-Ring over the sprinkler threads
accordance with the following instruc- until it is seated firmly against the
tions. Shield.
Step 1. With pipe thread sealant ap- Step 3. With pipe thread sealant ap-
Page 4 of 6 TFP350

plied, hand tighten the sprinkler into


the sprinkler fitting. Limited
Step 4. Tighten the sprinkler into the
sprinkler fitting using only the W-Type Warranty
9 Sprinkler Wrench (Ref. Figure 3). The Products manufactured by Tyco Fire
wrench is to be applied to the sprinkler Products are warranted solely to the
wrenching area shown in Figure 1 or 2, original Buyer for ten (10) years
as applicable. against defects in material and work-
When installed correctly, the O-Rings manship when paid for and properly
will be slightly compressed and the installed and maintained under normal
Shield will be held firmly in place. use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
Care and ranty is given for products or
components manufactured by compa-
Maintenance nies not affiliated by ownership with
Tyco Fire Products or for products and
The Series TY-L Sprinklers must be components which have been subject
maintained and serviced in accord- to misuse, improper installation, corro-
ance with the following instructions: sion, or which have not been installed,
maintained, modified or repaired in ac-
NOTES cordance with applicable Standards of
Before closing a fire protection system the National Fire Protection Associa-
main control valve for maintenance tion, and/or the standards of any other
work on the fire protection system that Authorities Having Jurisdiction. Mate-
it controls, permission to shut down the rials found by Tyco Fire Products to be
affected fire protection system must be defective shall be either repaired or
obtained from the proper authorities replaced, at Tyco Fire Products sole
and all personnel who may be affected option. Tyco Fire Products neither as-
by this action must be notified. sumes, nor authorizes any person to
Sprinklers that are found to be leaking assume for it, any other obligation in
or exhibiting visible signs of corrosion connection with the sale of products or
must be replaced. parts of products. Tyco Fire Products
shall not be responsible for sprinkler
Automatic sprinklers must never be system design errors or inaccurate or
painted, plated, coated or otherwise incomplete information supplied by
altered after leaving the factory. Modi- Buyer or Buyers representatives.
fied or over-heated sprinklers must be
replaced. IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
Care must be exercised to avoid dam- TRACT, TORT, STRICT LIABILITY OR
age to the sprinklers - before, during, UNDER ANY OTHER LEGAL THE-
and after installation. Sprinklers dam- ORY, FOR INCIDENTAL, INDIRECT,
aged by dropping, striking, wrench SPECIAL OR CONSEQUENTIAL
twist/slippage, or the like, must be re- DAMAGES, INCLUDING BUT NOT
placed. LIMITED TO LABOR CHARGES, RE-
The owner is responsible for the in- GARDLESS OF WHETHER TYCO
spection, testing, and maintenance of FIRE PRODUCTS WAS INFORMED
their fire protection system and de- ABOUT THE POSSIBILITY OF SUCH
vices in compliance with this docu- DAMAGES, AND IN NO EVENT
ment, as well as with the applicable SHALL TYCO FIRE PRODUCTS LI-
standards of the National Fire Protec- ABILITY EXCEED AN AMOUNT
tion Association (e.g., NFPA 25), in EQUAL TO THE SALES PRICE.
addition to the standards of any other THE FOREGOING WARRANTY IS
authorities having jurisdiction. The in- MADE IN LIEU OF ANY AND ALL
stalling contractor or sprinkler manu- OTHER WARRANTIES EXPRESS OR
facturer should be contacted relative to IMPLIED, INCLUDING WARRANTIES
any questions. OF MERCHANTABILITY AND FIT-
It is recommended that automatic NESS FOR A PARTICULAR PUR-
sprinkler systems be inspected, POSE.
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
TFP350 Page 5 of 6

P/N 53 XXX X XXX


TEMPERATURE
RATING
SPRINKLER
MODEL/SIN 165 165F/74C

253 5.6K UPRIGHT (1/2"NPT) TY3113 1 NATURAL BRASS 212 212F/100C

153 8.0K UPRIGHT (3/4"NPT) TY4113 280 280F/138C

TABLE B
PART NUMBER SELECTION
SERIES TY-L UPRIGHT INTERMEDIATE LEVEL SPRINKLERS
(UPRIGHT SHIELD INCLUDED WITH SPRINKLER)

P/N 53 XXX X XXX


TEMPERATURE
RATING
SPRINKLER
MODEL/SIN 165 165F/74C

112 5.6K PENDENT (1/2"NPT) TY3211 1 NATURAL BRASS 212 212F/100C

102 8.0K PENDENT (3/4"NPT) TY4211 280 280F/138C

TABLE C
PART NUMBER SELECTION
SERIES TY-L PENDENT SPRINKLERS
(MODEL S2 PENDENT SHIELD & O-RING MUST BE SEPARATELY ORDERED)

Pendent Sprinkler Assemblies with


Ordering (Shield Ordered Separately) and
NPT Thread Connections:
Procedure Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
When placing an order, indicate the full (specify temperature rating), Series
product name. Refer to the Price List TY-L Pendent Sprinkler with natural
for complete listing of Part Numbers. brass finish), P/N (specify from Table
Contact your local distributor for avail- C)
ability.
Model S5 Pendent Shield Package:
Upright Sprinkler Assemblies with Specify: S5 Pendent Shield Package
Shield and NPT Thread (one shield / two o-rings) for use with
Connections: (specify 1/2" NPT or 3/4" NPT) Series
Specify: (Specify Model/SIN), Stand- TY-L Pendent Sprinklers, P/N (spec-
ard Response, (specify K-factor), ify).
(specify temperature rating), Series 1/2" NPT S5
TY-L Upright Intermediate Level Sprin- Pendent Shield
kler with natural brass finish, P/N Package . . . . . . . . . . . . . . P/N 56-015-6-802
(specify from Table B). 3/4" NPT S5
Pendent Shield
Package . . . . . . . . . . . . . . P/N 56-015-6-803

Sprinkler Wrench:
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849.
Page 6 of 6 TFP350

TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446