Sie sind auf Seite 1von 2

DATE :

PROJECT :
COMPUTED BY :

LIQUEFIED PETROLEUM TANK CALCULATIONS

LOCATION ALL FLOORS TOTAL BTU/HR USE FACTOR HR CONSUMPTION BTU

MAIN LABORATORY 0 0 10500 1.00 2 0

SMALL LABORATORY 0 0 5000 1.00 1 0

MAIN KITCHEN 1 1 65000 1.00 6 390000

SMALL KITCHRN 0 0 12000 1.00 2 0

PANTRY 0 0 9000 1.00 1 0

390000

TANK SIZE 0.9142 M3 TOTAL BTU/HR 65000

DESIGN DATA* VALUE UNIT


LPG HEATING VALUE 21560 BTU/IB
SPECIFIC VOLUME 8 FT3/IB
TANK RESERVE 45 DAYS
MAX LIQUIED VOL. 70 %

* 2005 ASHRAE FUNDAMENTALS- F18 Page ( 18-3,4 )


LPG PIPE SIZE CALCULATORS

SPACE BTU/HR CFH NO OF POINT IN LINE TOTAL CFH

MAIN LABORATORY 10500 4.0 0 0


SMALL LABORATORY 5000 1.9 0 0
MAIN KITCHEN 65000 24.8 1 25
SMALL KITCHRN 12000 4.6 0 0
PANTRY 9000 3.4 0 0

GROSS TOTAL CFH 25

25 FT3/HR 0.75 INCH

Das könnte Ihnen auch gefallen