Beruflich Dokumente
Kultur Dokumente
A three-phase equivalent circuit diagram of the Therefore, the fundamental positive sequence
proposed DSTATCOM topology is shown in Fig. 1. It is components of three-phase voltages are extracted to generate
realized using a three-phase four-wire two-level neutral- reference lter currents (if2a, if2b, and if2c) based on the
point-clamped VSI. The proposed scheme connects an LCL instantaneous symmetrical component theory. These currents
filter at the front end of the VSI, which is followed by a are given as follows:
series capacitor Cse. Introduction of the LCL filter
significantly reduces the size of the passive component and
improves the reference tracking performance. Addition of the
series capacitor reduces the dc-link voltage and, therefore, the * * vta1
power rating of the VSI. i f2a i1a i sa i1a (P1avg Ploss )
1
Here, R1 and L1 represent the resistance and
inductance respectively at the VSI side; R2 and L2 represent
the resistance and inductance respectively at the load side; * * vtb1
and C is the filter capacitance forming the LCL filter part in i f2b i1b i sb i1b (P1avg Ploss )
all three phases. A damping resistance Rd is used in series 1
with C to damp out resonance and to provide passive
damping to the overall system. VSI and filter currents are if1a
and if2a, respectively, in phase-A similar for other phases. In
* * vtc1
addition, voltages across and currents through the shunt i f2c i1c i sc i1c (P1avg Ploss ) (1)
branch of the LCL filter in phase-A are given by vsha and isha, 1
respectively, and similarly for the other two phases. The
voltages maintained across the dc-link capacitors are Vdc1 =
Vdc2 = Vdcref. The DSTATCOM, source, and loads are Where vta1 , vtb1 and v tc1 are fundamental positive sequence
connected to a common point called the point of common voltages at the respective phase load terminal, and
coupling (PCC). Loads used here have both linear and 1 (vta 1 ) 2 (vtb 1 ) 2 (vtc1 ) 2 .The terms P1avg and Ploss
nonlinear elements, which may be balanced or unbalanced. In
represent the average load power and the total losses in the
VSI, respectively. The average load power is calculated using procedure to design the filter parameters is given here in
a moving average filter for better performance during detail.
transients and can have a window width of half-cycle or full
cycle depending upon the odd or odd and even harmonics, 1) Reference DC-Link Voltage V dcref : The voltage across
respectively, present in the load currents. At any arbitrary
time t1, it is computed as follows: the dc capacitor is a source of energy and is selected to
achieve good tracking performance. Here, the use of a series
t1 capacitor and a small filter inductor has enabled a significant
1 reduction in the dc-link voltage. In present case, a dc-link
P1avg (vta i1a vtb i1b vtc i1c )dt
T t1 T voltage of 110 V is chosen, which is found to provide
(2) satisfactory compensation.
The total losses in the VSI are computed using a 2) Design of LCL Filter Parameters: While designing
proportionalintegral (PI) controller at the positive zero suitable values of LCL filter components, constraints such as
crossing of phase-a voltage. It helps in maintaining the dc- cost of inductor, resonance frequency fres, choice of damping
link voltage at a reference value 2V dcref by drawing a set of resistor Rd, and attenuation at switching frequency fsw should
be considered. Consider only L1 of the passive filter, as
balanced currents from the source and is given as shown in Fig. 3, is used. The value of inductance L1 is chosen
from a tradeoff, which provides a reasonably high switching
Ploss K p e vdc K i e vdcdt frequency and a sufficient rate of change of the filter current,
(3) such that the VSI currents follow the reference currents. At
any point of time, the following equation represents the
Where K p , K i and evdc 2Vdcref (v dc1 v dc 2 ) are the inductor dynamics:
proportional gain, integral gain, and voltage error of the PI
controller, respectively. The current error eabc is obtained by di fi
subtracting the actual filter currents from the reference filter L1 vt R1i fi Vdcref
currents. The error is regulated around a predefined hysteresis dt (4)
band h using the hysteresis current controller (HCC), and
IGBT switching pulses are generated. For further analysis, R1 can be neglected. The inductor is
designed to provide good tracking performance at maximum
switching frequency, which is achieved at zero supply
voltage in the HCC. Taking these into consideration,
inductance L1 is given by
Vdcref Vdcref
L1
(2h a )(2f max ) 4h a f max
(5)
A more generalized expression can be written as (LCL filter L1 6.5mH, L2 1mH, Rd 15,
based)
Vinv1 Vt1 R1 R2 0.05,C=10F
I 1 max 1 pf12min
X f 12 X se1
(17)
VSI Vdcref 110 V, Cdc=3000F,
Where I1 max Vt1 / Z1 min , and pf1min is the minimum load parameters
(proposed
power factor given by R R1min / z1min . Hence, X se1 will be topology) L1 1.5mH, L2 0.6mH, Rd 15,
Vinv1 Vt1
X se1 X f12 R1 R2 0.05,C=10F,C C se
2
I 1max 1 pf1min =50F
(18)
3. Defuzzificaion
RC type Rl=50,C1=1000F A plant requires non fuzzy values to control, so
nonlinear defuzzification is used. The output of FLC controls the
load switch in the inverter. To control these parameters they are
sensed and compared with the reference values. To obtain
this the membership functions of fuzzy controller are shown
in fig (4).
RL type Rl=50,L1=200mH
nonlinear The set of FC rules are derived from
load
u=-[ E + (1-)*C] (16)
(c)
In Fig. 8(a) the three-phase source current Fig. 8: Simulation results for the proposed topology. (a)
waveforms are shown, which are balanced, sinusoidal, and Source currents. (b) PCC voltages. (c) Filter currents. (d)
have negligible switching ripple compared with the Voltages across the dc link.
traditional topology. In addition, neutral current is nearly
zero. Fig. 8(b) shows the three-phase compensated PCC In Fig. 9 the source currents are sinusoidal with a
voltages with reduced switching harmonics. Additionally, negligible harmonic component, although load currents are
source currents are in phase with their respective phase highly distorted. The PCC voltages are also balanced and
voltages. The filter currents, as shown in Fig. 8(c) have sinusoidal with a small ripple component. This confirms that
smaller ripples as compared with that of the traditional the reduced dc-link voltage is sufficient to compensate the
topology. The voltages across each capacitor and the total dc- RC-type nonlinear load using fuzzy controller.
link voltage are shown in Fig. 8(d).
Fig. 10: Damping rms current. (a)With the LCL filter. (b)
Proposed topology.