Beruflich Dokumente
Kultur Dokumente
CHE504
1. Switch on the main power supply to the Plant at the front of the panel.
WHENEVER ANY ANNUNCIATOR IS ACTIVATED, PRESS THE ACKNOWLEDGE
(RED) BUTTON TO SILENCE THE BUZZER. RATIONALISE THE CAUSE OF THE
ALARM CONDITION.
2. Switch the DP Selector Switch to the equalizing (vertical or 0) position.
3. The manual valve at the external water supply inlet to T1 should always be opened.
4. Fill tank T1 and T2 with water to their maximum level.
5. At tank T1, shut fully the discharge valve (HV) but open fully its by-pass valve (BVH). Start
the HW pump PH for the water recirculate around its tank T1, via only BVH. The suction valve
of pump PH must remain open at all times.
6. Switch ON the heaters from the front of the panel and allow the water in tank T1 to be heated to
its maximum temperature 70C (see TIC5).
7. Check that all the CW pumps (PC1, PC2) by-pass valves (BVC1, BVC2) and discharged valves
(CV1, CV2) are opened. All suction valves for pumps PC1, PC2 and PH must remain open at
all times.
8. Make sure CW pumps PC1 and PC2 are off. Note that the HW pump PH is still recirculating
HW around its tank T1 via its by-pass valve (BVH), but its discharge valve (HV) is still fully
shut.
9. Quickly check the various manual valves as follows:-
The manual by-pass valves around the control valves TSV3A and TSV3B should be always
shut but their adjacent manual valves should be always opened.
The bottom manual drain valves of tank T1 and T2 are always shut.
10. For details of the Experiments to be conducted, please refer to the Plant Experiment Manual of
MODEL HE12.
Exp/HE 1
Universiti Teknologi MARA
CHE504
AIM OF EXPERIMENTS:
To evaluate and study the performance of the Shell and Tube Heat Exchanger at various
operating conditions.
A) DESCRIPTION OF EQUIPMENT
The major equipment are as follows :-
i. The hot water tank T1 must be filled with water up to its maximum level - the level of
its overflow drain pipe (D).
iii. Pump PH circulates the hot water (heating medium) HW into the tube-side of the
Heat Exchanger and then returns it to tank T1. The pump should always be started
only when the water level in tank T1 is near its maximum level and its by-pass valve
(BVH) fully opened.
iv. The flowrate of HW to the Heat Exchanger can be manually regulated at the by-pass
valve (BVH) with the discharge valve (HV) fully opened.
Exp/HE 2
1 T
Universiti Teknologi MARA
CHE504
ii. The maximum cold water level in each tank is defined by its overflow drain pipe D.
External ambient water supply is permanently available to tank T2 and this inflow is
controlled by a mechanical float and valve to ensure that its level will be maintained at
its maximum level.
iii. CW heated at the shell-side of the Heat Exchanger returns to tank T2, so that the CW
in T2 becomes warm. Excess water in T2 overflows into the drain (D).
iv. There are two similar CW pumps PC1 and PC2 pumping CW to the shell-side of the
Heat Exchanger from T2, via their respective manual discharge valves CV1, CV2.
Both pumps are operated simultaneously. When only one CW pump is operated for
pumping CW into the Heat Exchanger, the other CW pump is operated as a back-
mixing pump with its manual discharge valve fully shut but its by-pass valve fully
opened. This is the usual mode of operation, with PC2 acting as the back-mixing
pump, and its discharge valve (CV2) fully shut but its by-pass valve (BVC2) fully
opened.
By manually regulating the by-pass valve BVC1, the flowrate of the CW from pump
PC1 to the Heat Exchanger can be varied. Note that both the pump suction valves for
PC1 and PC2 must remain always opened.
Exp/HE 3
2
Universiti Teknologi MARA
CHE504
IV. INSTRUMENTATION
i. Flowrates, USGPM
The flowrates of CW and HW can be read from the panel-mounted digital Flow
Indicators, FI(C)* and FI(H)* respectively. These flowrates are transmitted from their
respective flowmeters FT(C) and FT(H).
The pumps should always be started with their respective by-pass valves fully open.
The flowrate required is then set by regulating its by-pass valve, with the pump
discharge valve remaining fully open. All pumps suction valves must remain fully
opened.
ii. Temperatures, oC
Temperature rise in CW due to heating at the Heat Exchanger is read from the
difference between the CW outlet (TI4*, T2) and inlet (TI3*, T1) temperatures.
Similarly, the temperature drop in HW is read from the difference between the HW
inlet (TI1*, t1) and outlet (TI2*, t2) temperatures.
The four temperatures are measured using Resistance Temperature Detector (RTD)
elements which are tagged as TE1, TE2, TE3 and TE4. Their temperatures are
displayed at the digital Temperature Indicators TI1*, TI2*, TI3* and TI4* respectively,
all mounted at the panel. TI3* is tagged TI3(T1)/TIC3* denoting that TI3 also
has ON/OFF control (TIC3) capabilities.
Exp/HE 4
Universiti Teknologi MARA
CHE504
By taking a few Sets of readings consecutively for each RUN, the best Set of
readings can be selected to represent the RUN. The criterion for selection is
the Heat Balance test where Heat gain QC converges best to equal Heat lost
QH.
There is a pressure gauge PG-C to measure the CW pressure at the inlet to the Shell-
side of the Heat Exchanger.
There is a pressure gauge PG-H to measure the HW pressure at the inlet to the Tube-
side of the Heat Exchanger.
Further note that the various pressure drop tapping points are not installed directly
inside the Heat Exchanger inlet/outlet ports, to avoid excessive turbulence. Note
therefore that each measured pressure drop is due to the Heat Exchanger PLUS those
of its inlet expansion and short pipe length AND outlet contraction and short pipe
length. The short pipe lengths include pipe elbows and Tees which also contribute to
pressure drop. The actual pressure drop due to the Heat Exchanger (Shell and Tube
sides) should be less than those indicated by these measurements i.e.
Actual DP(Tube) = Measured DP(Tube) at DPI* - DP due to the HW
piping between its tapping points and the HE
inlet/outlet HW ports, which can be calculated (see
Appendix section, CORRECTION TO THE
MEASURED DP(TUBE) AND DP(SHELL).
Actual DP(Shell) = Measured DP(Shell) at DPI* - DP due to the CW
piping between its tapping points and the HE
inlet/outlet CW ports, which can be calculated (see
Appendix section, CORRECTION TO THE
MEASURED DP(TUBE) AND DP(SHELL).
Exp/HE 5
Universiti Teknologi MARA
CHE504
B) PREPARATION PROCEDURES
i. Fill tanks T1 and T2 with water to their maximum level, defined by their overflow drain
pipes D.
ii. At tank T1, shut fully the discharge valve (HV) but open fully its by-pass valve (BVH).
Start the HW pump PH for the water to recirculate around its tank T1, via only BVH. The
suction valve of pump PH must remain open at all times.
Switch ON the heaters at the front of the panel and allow the water in tank T1 to be
heated to its maximum temperature 70C /158F (see TIC5), which will take about 20
minutes. Whilst waiting, proceed to (iii) below. The ON/OFF temperature controller
TIC5 will automatically switch OFF the heaters in tank T1 when the heated water
temperature exceeds its preset High Limit (say 70C), and switch them ON again when the
temperature drops below, say 0.5 C of its preset High Limit (i.e. below 69.5C).
b) Check that the external water supply to tank T2 is always available but is automatically
shut by the mechanical float-level valve at high level in tank T2.
Test the water availability by pushing down the float - water must flow into tank T2
via the float-level valve to confirm water availability.
c) Make sure the CW pumps PC1 and PC2 are off. Note that the HW pump PH is still
recirculating HW around its tank T1 via its by-pass valve (BVH), but its discharge valve
(HV) is still fully shut.
d) Switch ON only one CW pump, say PC1 whose suction is from tank T2. Its by-pass
valve BVC1 is still fully opened.
Do not operate PC2. Shut CV2 fully.
Note the CW recirculation from PC1 back into tank T2 via mainly its by-pass valve
BVC1 and also the Heat Exchanger return solenoid valve TSV3A.
e) Practise manipulating the by-pass valve (BVC1) to set various flowrates of CW into the
Heat Exchanger from PC1 as follows:
The manual discharge valve CV1 should remain fully opened.
With BVC1 fully opened, note the CW flowrate {FC at FI(C*)}, pressure
(PG-C) and Shell-side pressure drop (at DPI*). To read DP (Shell), select the
signal to DPI* using the DP Selector Switch provided at the panel, to the DP
(Shell) position and wait till the reading at DPI* is almost steady.
Exp/HE 6
Universiti Teknologi MARA
CHE504
Manually adjust BVC1 until FC at FI(C*) reads almost 10 USGPM. Note also
DP(Shell) and PG-C.
Shut fully the by-pass valve (BVC1) and note the increase in FC, PG-C and DP
(Shell). Note the CW temperatures at the Heat Exchanger inlet (T1 at TI3*) and
outlet (T2 at TI4*).
Note the Heat Exchanger pressure drop increases with flowrates.
f) Switch ON pump PC2 whose suction is from tank T2. Open fully its manual discharge
valve CV2 and by-pass valve (BVC2). Note the CW flowrate {FC at FI(C*)}, pressure
(PG-C) and Shell-side pressure drop (at DPI*).
Gradually shut only BCV2 until the CW flowrate FC is about 20 USGPM.
Note FC, PG-C and DP(Shell) which increase with the flowrate FC.
g) Open fully BVC2 but shut fully CV2 so that pump PC2 now operates only as a back-
mixing pump for tank T2. Note the drop in FC, PG-C and DP (Shell).
Only pump PC1 is now pumping through the Heat Exchanger. Shut BVC1 fully for
maximum flow from PC1 through the Heat Exchanger.
The temperature of HW in tank T1 will drop due to heat being transferred to the
'metal' body of the Heat Exchanger, even if there is no CW flow in the Heat
Exchanger. Note the HW temperatures at the Heat Exchanger inlet (t1 at TI1*) and
outlet (t2 at TI2*).
WHENEVER THE ANNUNCIATOR TAH3 IS ACTIVATED, PRESS THE
RED ACKNOWLEDGE BUTTON TO SILENCE THE BUZZER.
c) Stop the HW pump PH and note the drop in FH, PG-H and DP (Tube).
Switch the DP Selector Switch to the equalising (vertical or 0) position.
Note that heat from HW is now 'stored' in the Heat Exchanger tubes.
Switch OFF the heaters.
b) Please refer to TABLE 1. Three (3) Sets of readings are taken for every RUN.
Each Set of temperature readings consists of four readings to be taken
simultaneously: CW
temperatures - inlet T1 at TI3* and outlet T2 at TI4*,
HW temperatures inlet t1 at TI1* and outlet t2 at TI2*.
Each set of flowrate readings consists of two readings:
CW flowrate (FC at FI(C)*),
HW flowrate (FH at FI(H)*).
Each set of Heat Exchanger inlet gauge pressure readings consists of two
readings:
PG-C of CW at the CW pipeline, inlet to the Shell side of the Heat Exchanger.
PG-H of HW at the HW pipeline, inlet to the Tube side of the Heat Exchanger.
c) Note that the HW temperature in tank T1 drops (note TIC5) when the heater
input is inadequate to meet with the heat (QC) removed by CW. Hence the
second and third Sets of temperature readings may be taken at decreasing heat
load, but the water temperature at tank T1 must be at least 60 C.
d) Concentrate on taking the three (3) Sets of temperature, flowrate and pressure
drop readings. The pressure drop readings DP (Shell) and DP (Tube) are taken at
the panel-mount DPI*, using the DP signal Selector Switch provided. Note that
the pressure drop depends on the flowrate and not on the temperature.
e) Repeat the above procedure for other RUNS (II, III, etc) at the following CW
and HW recommended nominal flowrates. It is NOT necessary to operate at
exactly the recommended nominal flowrates. A deviation of 5% is acceptable.
Below is a summary list of the recommended nominal flowrates.
RUN CW, FC HW, FH
I 10 USGPM 25 USGPM
II 10 USGPM 20 USGPM
III 10 USGPM 15 USGPM
IV 10 USGPM 10 USGPM
V 6 USGPM 10 USGPM
Exp/HE 8
Universiti Teknologi MARA
CHE504
With a good overview of the experiment plan detailed in C1, proceed with RUN 1 as
follows :-
i) Check that all the pump suction valves (for PH, PC1, PC2) are fully opened all
the time.
Open BVC2 fully but shut CV2 fully so that PC2 shall operate as a back-mixing
pump for tank T2 in the next experiment.
Open fully both CV1 and BVC1. Only PC1 shall be used here to pump CW into the
Heat Exchanger in the next experiment.
Do not switch on any CW pumps (PC1, PC2) yet.
Shut HV fully but open BVH fully.
Start pump PH for HW to circulate around tank T1 via only BVH.
Start the heaters and note TIC5.
When the HW in tank T1 is almost 70oC/158oF (see TIC5), open HV fully.
Quickly adjust the HW flowrate to about 25 USGPM by regulating its by-pass
valve BVH.
Switch ON both the CW pumps PC1 and PC2.
Quickly adjust the CW flowrate to about 10 USGPM by regulating the by-pass valve
BVC1.
Switch the DP Selector Switch to the DP(Shell) position.
Note that the CW inlet temperature (T1) is increasing gradually. The CW outlet
temperature (T2) varies together with the HW inlet/outlet temperatures t1/t2. It
is important that all the temperature and flowrate readings be taken almost
simultaneously.
Record these readings appropriately in TABLE 1.
Also record the respective inlet pressure and pressure drop of the CW and HW
flow streams. For the pressure drop readings, DP (Shell), DP (Tube) at the
panel-mount DPI*, use the DP signal Selector Switch appropriately as
explained below.
CW : PG-C; DPI * for DP (Shell) with the DP Selector Switch at the DP
(Shell) position.
HW: PG-H; DPI* for DP (Tube) with the DP Selector Switch at the DP
(Tube) position.
Exp/HE 9
Universiti Teknologi MARA
CHE504
To take the DP readings at DPI*, wait till they are fairly steady.
Then take the DP reading at its highest reading (i.e. peak reading) just when it
starts to decrease.
b) Continue and take the second and third Sets of the above readings for RUN I
consecutively. The last Set of temperature readings should be taken when all the
temperatures are fairly steady.
iii.
Check that the HW pump PH is running with BVH fully opened but HV
fully shut.
With the heaters ON, heat till the HW in tank T1 is almost 70C/158F
(see TIC5).
Open HV fully.
Adjust the HW flowrate until FH at FI (H*) is almost at the
recommended nominal flowrate for the RUN.
Exp/HE 10
RUN
StopIall
is the
completed,
CW pumps PC1
with andsets
three PC2 of. the above readings.
Universiti Teknologi MARA
CHE504
This is done by regulating the by-pass valve BVH with HV fully opened.
(However, if the flowrate is still too high even when its by-pass valve is
fully open, gradually shut its discharge valve, HV, to get the required HW
flowrate).
Start the CW pumps PC1, PC2 with CV1/BVC1/BVC2 fully opened but
CV2 fully shut. Note FC at FI(C*).
Adjust FC to the recommended nominal flowrates for the RUN by
regulating the by-pass valve BVC1 with CV1 fully opened.
(However, if the CW flowrate (FC) from PC1 is still inadequate even when
its by-pass valve BVC1 is fully shut, use the second CW pump (PC2) by
gradually opening CV2 and simultaneously shutting BVC2 to get the
required CW flowrate).
Switch the DP Selector Switch to the DP(Shell) position.
Take the various readings for the RUN. Refer to TABLE 1 of the
appropriate RUN.
Exp/HE 11
Universiti Teknologi MARA
CHE504
TABLE 1
CW HW CW HW CW HW
CALCULATE FOLLOWING:
Temp Change, C/F T2 - T1: ____ t1 - t2 : ____
Compute ratio QC QC : QC : QC :
QH QH QH QH
Exp/HE 12
Universiti Teknologi MARA
CHE504
TABLE 1 (cont.)
CW HW CW HW CW HW
CALCULATE FOLLOWING:
Temp Change, C/F T2 - T1: ____ t1 - t2 : ____
Compute ratio QC QC : QC : QC :
QH QH QH QH
SELECT Set 1 or Set 2 or Set 1 is Set 2 is Set 3 is
Set 3, based on the best Selected/Not selected Selected/Not Selected/Not
convergence of QC and QH selected selected
i.e. QC is nearest to 1.0
QH
For Selected Set, compute
0.5 (QC + QH), BTU/HR
Exp/HE 13
Universiti Teknologi MARA
CHE504
TABLE 1 (cont.)
CW HW CW HW CW HW
CALCULATE FOLLOWING:
Temp Change, C/F T2 - T1: ____ t1 - t2 : ____
Compute ratio QC QC : QC : QC :
QH QH QH QH
Exp/HE 14
Universiti Teknologi MARA
CHE504
TABLE 1 (cont.)
CW HW CW HW CW HW
CALCULATE FOLLOWING:
Temp Change, C/F T2 - T1: ____ t1 - t2 : ____
Compute ratio QC QC : QC : QC :
QH QH QH QH
SELECT Set 1 or Set 2 or Set 1 is Set 2 is Set 3 is
Set 3, based on the best Selected/Not selected Selected/Not Selected/Not
convergence of QC and QH selected selected
i.e. QC is nearest to 1.0
QH
For Selected Set, compute
0.5 (QC + QH), BTU/HR
Exp/HE 15
Universiti Teknologi MARA
CHE504
TABLE 1 (cont.)
CW HW CW HW CW HW
CALCULATE FOLLOWING:
Temp Change, C/F T2 - T1: ____ t1 - t2 : ____
Compute ratio QC QC : QC : QC :
QH QH QH QH
SELECT Set 1 or Set 2 or Set 1 is Set 2 is Set 3 is
Set 3, based on the best Selected/Not selected Selected/Not Selected/Not
convergence of QC and QH selected selected
i.e. QC is nearest to 1.0
QH
For Selected Set, compute
0.5 (QC + QH), BTU/HR
Exp/HE 16
Universiti Teknologi MARA
CHE504
(E) CALCULATION
American Engineering Units are used here since KERN and other technical datas in the
APPENDIX are in such units.
PART I
i. Heat Load and Heat Balance
This part of the calculation is to use the datas in TABLE I to check the heat load QH and QC
( BTU ) and to select the set of values where QC is closest to QH.
hr
For HW: QH BTU = FH (lbm) x specific heat (BTU) x (t1 - t2) oF.
hr hr lbmoF
For CW: QC BTU = FC (lbm) x specific heat (BTU) x (T2 - T1) oF.
hr hr lbmoF
For each run, compare the calculated values of QH and QC and select the Set of
temperature and flowrate datas where the calculated values of QH and QC are closest
to each other. This selected Set of datas shall be used to represent the results of the
particular RUN, and be used for the following subsequent calculation.
ii. LMTD
LMTD = (t1 - T2) - (t2 - T1) , oF
ln (t1 - T2)/(t2 - T1)
The correction factor FT for 1 Shell Pass and 2 or more Tube Passes is given in *KERN
FIG18, a zeroxed copy of which is enclosed in the Appendix section.
\U BTU = Q (BTU) x 1 x 1
2 o
hr.ft . F hr A ft2 LMTD x FT, oF
Exp/HE 17
Universiti Teknologi MARA
CHE504
I.
II.
III.
IV.
V.
The U value calculated above shall be referred to as the 'dirty' overall heat transfer coefficient UD.
Exp/HE 18
Universiti Teknologi MARA
CHE504
Re(s) = De. Gs
m
where de = 4 ( 1/2 PT x 0.86 PT - 1/2 p do2 ) ins. Refer Kern equation 7.5.
4
-------------------------------------
1/2 p do
Ws = Flowrate in lbm
hr
= 0.029 ft2
Exp/HE 19
Universiti Teknologi MARA
CHE504
Re(t) = D. Gt
m
= 32 x 0.1924 ft2
2 144
= 0.02139 ft2
* It should also be shown here, at which HW flowrate is Re(t) less than 3000.
Try the calculation with HW at 3.5 USGPM.
Refer to FIG26 enclosed and note the sharp rise in friction factor for laminar flow.
Refer to FIG24 enclosed and note the sharp drop in heat transfer for laminar flow.
Exp/HE 20
Universiti Teknologi MARA
CHE504
For this part of the Calculation, the student are to calculate the 'clean' overall heat transfer
coefficient UC from the individual heat transfer coefficient ho and hi for inside and outside fluids.
The calculated results are to be tabulated in TABLE 3.
ho : BTU
hr. ft2 oF
--------------------------
Please refer to Kern Fig 28, a zeroxed copy of which is enclosed in the Appendix section, to
calculate ho, at the various Reynolds number calculated in PART II.
hi : BTU
hr. ft2 oF
--------------------------
Please refer to Kern Fig 24, a zerozed copy of which is enclosed in the Appendix section, to
calculate hi and hio, at the various Reynolds number calculated in PART II.
hio = hi x ID
OD
Exp/HE 21
Universiti Teknologi MARA
CHE504
Rd : hr. ft2. oF
BTU
---------------------------
UC = hio x ho
hio + ho
Rd = UC - UD
UC . U D
Note that UC is calculated from the Heat Exchanger heat transfer coefficients (ho, hi, hio), the
Reynolds numbers (i.e. flowrates), the flowing fluids properties and the Heat Exchanger diameters.
UD however is determined from actual heat transfer experiments at the Heat Exchanger. It is the
dirty or design heat transfer coefficient. Fouling reduces UD . Fouling may get worse with
operation, resulting in reduced heat transfer and increasing pressure drop (and loss of flow).
Exp/HE 22
Universiti Teknologi MARA
CHE504
The students are to calculate the pressure drop at the Shell-side and at the Tube-side i.e. DP(Shell),
DP(Tube). The calculated results are to be tabulated in TABLE 3.
The Calculated DP(Shell) and DP(Tube) are to be compared to the Measured DP(Shell) and
DP(Tube). Correction to the Measured DP(Shell) and DP(Tube) can be made.
The total pressure drop must include the tube side return (U-bend) pressure loss.
b) To avoid excessive turbulence and vortices at the vicinity of the differential pressure (DP)
tapping points, the tapping points should be located with adequate upstream/downstream
straight pipe runs away from turbulence and vortices. The pressure drop readings will be
noisy otherwise, especially if the flow stream has just negotiated from a change in flow area
or direction or if it is too near the pump discharge.
c) Note the location of each pair of tapping points. The DP measured by DPT (and displayed at
DPI*) is the DP of the Heat Exchanger (Shell/Tube) PLUS various pipe elbows and tees
and pipe length. These additional DP can be much more than DP(Tube) or DP(Shell) and
must be corrected (subtracted) from the Measured DP(Tube) and DP(Shell). Please refer to
the Appendix section CORRECTION TO THE MEASURED DP(TUBE) AND
DP(SHELL).
d) When there is no flow to the Heat Exchanger, the DP Selector Switch should be switched to
the equalising (vertical or 0) position. The DPI* will display almost 0 mmWG 0.5% i.e.
25 to 25 mm H2O.
Exp/HE 23
CHE504
Exp/HE
TABLE 3
RUN ACTUAL PART II: PART III: Heat Transfer Coefficient PART IV: Pressure Drop
FLOW Reynolds Number
Measured Measured
FC: Re (s) Re (t) ho hio Uc UD Rd Calculated Measured and Calculated Measured and
FH: Corrected Corrected
FC:
I. FH:
FC:
II. FH:
23
FC:
III. FH:
FC:
IV. FH:
FC:
V. FH:
NOTE:
Pressure conversion : 1 psi is 2.3088 ft H2O or 703.7 mm H2O, at 60F
Universiti Teknologi MARA
Universiti Teknologi MARA
CHE504
APPENDIX SECTION
Exp/HE 25
THERMAL
CONDUCTIVITY
SG
F/ft DENSITY DENSITY
F VISCOSITY HEAT