Sie sind auf Seite 1von 3

HPS2000A-SL datasheet

Introduction
Solar power system controller controls the power to the battery and equipment supplied by solar energy, and thus
ensures that the storage battery and equipment work in a normal range of voltage and current, at the same time,
ensures solar array operate at Maximum Power Point. The controller called HPS2000A-SL, the component include
ESPS48200B (Embedded Solar Power System), HPMU (Hybrid Power Monitor Unit), Heat exchanger system and
cabinet four parts.

Functions and Features


Modularization design and supports hot-swappable online
maintenance;
Controller design used by Maximum Power Point Tracking
(MPPT) system, which efficiency reaches more than 96%;
Intelligent battery charge/discharge management ensures
system reliability and steadilyequalization ,float and full
charge, etc;
System supports smooth scalable and expandable;
System supports fault tolerance design and error proof design;
System supports operating remote monitoring management
and update;

Technical Specifications
Item Description
Type Outdoor solar controller
Cooling mode Forcible wind cooling
Dimension
600 mm x 480 mm x 700 mm
(width x depth x height)
Weight 80 kg
Cabling mode Bottom inlet and bottom outlet
Installation Ground installation
Protection IP55

www.huawei.com
HPS2000A-SL datasheet

Technical Specifications
Item Description
Working mode MPPT
Input voltage 0V150VDC
Output voltage -40VDC ~-60VDC
System efficiency >96%
Non-load power <1W
Controller capacity -48V/200A
Environment temperature () 20 +55
4000, Upper to the application temperature
Altitude
decreases by 1C per 200m
Serial port RS485/RS232
Power system failure, Wind turbine
Input failure, D.G. information, Theft-proof
Dry contact of port alarm, Low fuel level alarm, Mains failure
HPMU alarm, ATS failure alarm, EPAC input
Output Startup/stop signal of the D.G.,
Communication port
port ATS control
Input DI1: PV Stolen
port DI2,DI3: Spare
Dry contact of
DSAU02 DO1:PV Stolen Alarm and PV Fault
Output
DO2:Bus Bar Low Voltage Alarm
port
DO3:Load Fuse Break
PV input branch of
63A4(MCB)
the controller
Secondary load:
125A1(MCB), 63A1(MCB), 32A1(MCB)
Output branch
Power distribution Primary load:
20A2( MCB),16A1(MCB)
Branch of the
160A2(FUSE)
storage battery
Input of AUX. DC1(D.G):100A2

www.huawei.com
HPS2000A-SL datasheet

Technical Specifications
Item Description
Output over voltage
Output under voltage
MPPT module failure
MPPT module protected
Solar control unit communicate failure
Alarms function Solar array failure
Solar array lose
Secondary load disconnect
Primary load disconnect
Battery load disconnect
Battery over temperature
Reverse polarity
Short circuit
Input over voltage
Protection and recovery function
Battery under voltage
Battery over temperature

Differential mode: 5 kA, 8/20s;


Input
Common mode: 5 kA, 8/20 s;
Differential mode: 10 kA, 8/20 s;
Lightning protection Output
Common mode: 20 kA, 8/20 s;
Differential mode: 3 kA, 8/20s;
Signal port
Common mode: 5 kA, 8/20 s;

The information in this document may contain predictive statements including, without limitation,
statements regarding the future financial and operating results, future product portfolio, new
technology, etc. There are a number of factors that could cause actual results and developments to
differ materially from those expressed or implied in the predictive statements. Therefore, such
information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

www.huawei.com

Das könnte Ihnen auch gefallen