Reference : HVSYS16-IT-029-CR-2-1
*****
New Assiut Add-on
Combined Cycle Power Plant
10083A
*****
CALCULATION NOTE
SHORT CIRCUIT CALCULATIONS
*****
1x1200 mm Copper XLPE Cu/Lead
Socit anonyme Directoire et Conseil de Surveillance au capital de 136 800 000 Euros
Sige Social : 23, avenue Aristide Briand BP 801 Paron 89108 Sens Cedex - R.C.S. SENS B 095 750 311 - APE 748 D
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
SUMMARY
2
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
1. GENERAL DESCRIPTION
This project consist to cover the engineering, design, manufacture, testing, supply,
installation and commissioning of 220 kV underground XLPE according Technical
Specification for 220 KV XLPE Cable System from Main Transformer to 220 KV GIS
Switchyard, 10083A-9-3PS-EZS0-00011, Rev. 1. Some modifications regarding drawing
10083A-09-ER-0000-00002 Rev. 0 are taken into account.
The purpose of this connection is to supply as required on the Material Requisition mainly 2
separate circuits of 220kV 1x1200 mm CU (minimal cross section required) XLPE cables, 6
XLPE/Air termination and 6 XLPE/gas terminations.
According the Technical Specifications, the earthing system will be a single point bonding,
which means to have sheath voltages limiters at one end.
Overhead connections from MT air bushing to HV Surge arrester and XLPE/Air Termination
is included.
The proposed cables have been verified for the following main electrical, laying,
environmental and operating data, according the technical specifications.
According 220kv Switchyard diagram line diagram, power required is about 381 MVA
(1000 A permanent current rating).
3
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
3. DESCRIPTION OF CIRCUITS
Two New STG main transformers (MTs) to the two new 220 kV GIS
Cable length (approximate) m See enclosed Fig N1
Number of circuits - 2
Terminations Units Type
6 TES 245/123 (XLPE/air)
6 EGS 245 (XLPE/gas)
Sheath bonding arrangement - Single point bonding
3200 m
4
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
4. CABLES DESIGN
5
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
The final temperature of a current carrying component (f), is calculated with the following
formula in accordance with IEC 60949 standards:
f i exp
I 2 t
K 2 S 2
Where:
According to IEC 61443 standards Short-circuit temperature limits of electric cables with
rated voltages above 30 kV (Um = 36 kV), the assumed maximum permissible final
temperatures "f" are set to 250 C, 210 C, respectively for HV cable copper conductor and
the HV cable lead alloy sheath and 250 C for Cu wire screen and copper earthing cable
conductor (ECC), XLPE insulated and PVC sheathed.
Pre-existing steady-state temperature conditions among the cable components (conductor, lead
alloy sheath and ECC cable) are relevant to 1000 A rating current.
The calculations have been carried out for both the three-phase symmetrical and the single-
phase short-circuit currents.
As far as the single-phase fault is concerned, the short circuit current is taken by the
composite metallic screen in case of internal fault and it is assumed to be taken completely
from the ECC (300 mm size) in case of fault external to the cables.
6
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
5.1 CALCULATION
i 90 (C)
234.5 (K)
t 1 (s)
I 172920 (A)
K 226 (As/mm)
S 1200 (mm)
f 250 (C)
The composite screen is composed of one layer of n 85 copper wires 1.53 mm (total
area 156 mm2) surrounded by a lead alloy sheath having a nominal thickness of 3.0 mm,
applied on a diameter of about 103.2 mm (total cross section 1000 mm2).
80
i (C)
Cu/Pb
234.5/230 (K)
t 1 (s)
I 45170 (A)
K 226/41 (As/mm)
S 156/1000 (mm)
f 250/210 (C)
7
Project: NEW ASSIUT ADD-ON CCPP / 10083A
Client: PESCO / ORASCOM
Country : CAIRO - EGYPT
Ref.: HVSYS16-IT-029-CR-2-1
220kV Underground Cables Date: 12th of July, 2016
i 50 (1) (C)
234.5 (K)
t 1 (s)
I 50180 (A)
K 226 (As/mm)
S 300 (mm)
f 250 (C)
6. CONCLUSIONS
For every short circuit conditions, all the calculated maximum allowable short circuit currents
are higher than the required ones.
Consequently, the component temperature is inside the safety margins stated in item 5.
7. CALCULATION REPORTS