Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Series EC-11 & EC-14 11.2 and 14.0 K-factor


Extended Coverage (Light and Ordinary Hazard)
Upright, Pendent, and Recessed Pendent Sprinklers
Corrosion resistant coatings, where
General applicable, are utilized to extend the
life of copper alloy sprinklers beyond
Description that which would otherwise be ob-
tained when exposed to corrosive at-
The Tyco Series EC-11 and EC-14 mospheres. Although corrosion resis-
Extended Coverage Upright and Pen- tant coated sprinklers have passed the
dent Sprinklers are decorative glass standard corrosion tests of the appli-
bulb sprinklers designed for use in cable approval agencies, the testing is
light or ordinary hazard occupancies. not representative of all possible cor-
They are intended for use in automatic rosive atmospheres. Consequently, it
sprinkler systems designed in accord- is recommended that the end user be
ance with standard installation rules consulted with respect to the suitability
(e.g., NFPA 13) for a maximum cover- of these corrosion resistant coatings
age area of 400 ft2 (37,2 m2), as com- for any given corrosive environment.
pared to the maximum coverage area The effects of ambient temperature,
of 130 ft2 (12,1 m2) for standard cover- concentration of chemicals, and
age sprinklers used in ordinary haz- gas/chemical velocity, should be con-
ard occupancies or 225 ft2 (20,6 m2) sidered, as a minimum, along with the
for standard coverage sprinklers used corrosive nature of the chemical to
in light hazard occupancies. which the sprinklers will be exposed.
The Series EC-11 and EC-14 Sprin-
klers feature a UL and C-UL Listing WARNINGS
that permits their use with unob- The Series EC-11 and EC-14 Ex-
structed or non-combustible ob- tended Coverage Sprinklers described
structed ceiling construction as de- herein must be installed and main-
fined and permitted by NFPA 13, as tained in compliance with this docu-
well as a specific application listing for ment, as well as with the applicable
use under concrete tees. standards of the National Fire Protec-
tion Association, in addition to the
The Series EC-11 and EC-14 Ex- standards of any other authorities hav-
tended Coverage Sprinklers have ing jurisdiction. Failure to do so may
been fire tested to compare their per- impair the performance of these de-
formance to that of standard coverage vices.
spray sprinklers. These tests have
shown that the protection provided is The owner is responsible for maintain- Model/Sprinkler
equal to or more effective than stand-
ard coverage spray sprinklers.
ing their fire protection system and de-
vices in proper operating condition. Identification
The installing contractor or sprinkler
manufacturer should be contacted Number
with any questions. TY5137 - Upright, 11.2K
IMPORTANT TY5237 - Pendent, 11.2K
Always refer to Technical Data TY6137 - Upright, 14.0K
Sheet TFP700 for the INSTALLER TY6237 - Pendent,14.0K
WARNING that provides cautions
with respect to handling and instal- TY5137 is a redesignation for C5137,
lation of sprinkler systems and com- G1894, and S2510.
ponents. Improper handling and in- TY5237 is a redesignation for C5237,
stallation can permanently damage G1893, and S2511.
a sprinkler system or its compo-
nents and cause the sprinkler to fail TY6137 is a redesignation for C6137,
to operate in a fire situation or cause G1896, and S2610.
it to operate prematurely. TY6237 is a redesignation for C6237,
G1895, and S2611.

Page 1 of 8 DECEMBER, 2007 TFP220


< 1 > Close

Page 2 of 8 TFP220

WRENCH 3/4" ** ESCUTCHEON PLATE


FLAT NPT SEATING SURFACE 1
1- Frame
2- Button
3- Sealing Assembly
4- Bulb
2
5- Compression Screw
6- Deflector*
2-7/16" 3
(61,9 mm)
* Temperature rating is UPRIGHT &
indicated on deflector
PENDENT 1-11/16" 4
(42,7 mm)
** Pipe thread
connections per ISO
7/1 can be provided
5
on special request.

6*
1/2" (12,7 mm)
NOMINAL MAKE-IN
CROSS
UPRIGHT PENDENT SECTION

FIGURE 1
SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT
14.0 K-FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT

SPRINKLER FINISH (See Note 5)


HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE* LEAD
LIQUID BRASS PLATED POLYESTER COATED

135F/57C Orange
UPRIGHT 1, 2, 3**, 4
155F/68C Red
LIGHT K=11.2 (TY5137)
PENDENT 175F/79C Yellow
K=11.2 (TY5237) 1, 2, 4 1, 2, 4
200F/93C Green
Refer to Table B for K=14.0 (TY6237)
UL and C-UL 286F/141C Blue
Sensitivity Rating 135F/57C Orange
and REC. PENDENT 1, 2, 3, 4
Refer to Table C for 155F/68C Red
K=11.2 (TY5237) N/A
FM K=14.0 (TY6237) 175F/79C Yellow
Sensitivity Rating With Style 30 1, 2, 4
200F/93C Green
Escutcheon
286F/141C Blue
UPRIGHT 135F/57C Orange
K=11.2 (TY5137) 1, 2, 3, 4
155F/68C Red
ORDINARY K=14.0 (TY6137) 1, 2, 3, 4
and 175F/79C Yellow
Refer to Table B for PENDENT 1, 2, 4
200F/93C Green
UL and C-UL K=11.2 (TY5237)
Sensitivity Rating K=14.0 (TY6237) 286F/141C Blue
and REC. PENDENT 135F/57C Orange
Refer to Table C for K=11.2 (TY5237)
FM 155F/68C Red
K=14.0 (TY6237) 1, 2, 4 N/A
Sensitivity Rating With Style 40 175F/79C Yellow
Escutcheon
200F/93C Green
NOTES:
1.Listed by Underwriters Laboratories, Inc. (UL).
2.Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the City of New York under MEA 177-03-E.
5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers.
*Frame and Deflector only. Listings and approvals apply to color (Special Order).
** Pendent Only.
N/A: Not Available
TABLE A, LABORATORY LISTINGS AND APPROVALS
< 1 > Close

TFP220 Page 3 of 8

LIGHT HAZARD ORDINARY HAZARD

135F 155F 175F 200F 286F 135F 155F 175F 200F 286F

AREA STYLE

14 x 14 Up. or Pend. QR QR QR QR SR
14 x 14 Style 30 Recessed QR QR QR QR N/A
14 x 14 Style 40 Recessed QR QR QR QR N/A

16 x 16 Up. or Pend. QR* QR* QR* QR* QR* SR SR SR SR SR


16 x 16 Style 30 Recessed QR* QR* QR* QR* QR* SR SR SR SR N/A
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A

18 x 18 Up. or Pend. QR* QR* QR* QR* QR* SR SR SR SR SR


18 x 18 Style 30 Recessed QR* QR* QR* QR* QR* SR SR SR SR N/A
18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A

20 x 20 Up. or Pend. QR* QR* QR* SR* SR* SR SR SR SR SR


20 x 20 Style 30 Recessed QR* SR* QR* SR* SR* SR SR SR SR N/A
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A

QR: Quick Response


SR: Standard Response
N/A: Not Applicable
* Does not apply to Upright K = 14.0
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS
(SEE TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS)

LIGHT HAZARD ORDINARY HAZARD

135F 155F 175F 200F 286F 135F 155F 175F 200F 286F

AREA STYLE

14 x 14 Up. or Pend. SR SR SR SR SR
14 x 14 Style 30 Recessed N/A N/A N/A N/A N/A
14 x 14 Style 40 Recessed N/A N/A N/A N/A N/A

16 x 16 Up. or Pend. QR* QR* N/A N/A N/A SR SR SR SR SR


16 x 16 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

18 x 18 Up. or Pend. QR* QR* N/A N/A N/A SR SR SR SR SR


18 x 18 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A
18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

20 x 20 Up. or Pend. QR* QR* N/A N/A N/A SR SR SR SR SR


20 x 20 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

QR: Quick Response


SR: Standard Response
N/A: Not Applicable
* Pendent Only
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS
(SEE FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
< 1 > Close

Page 4 of 8 TFP220

Sprinklers, to prevent cold solder-


Technical Operation ing, is 8 feet (2,4 m) for upright sprin-
klers and 9 feet (2,7 m) for pendent
Data The glass bulb contains a fluid which
expands when exposed to heat. When
sprinklers.
Approvals the rated temperature is reached, the 5. The Series EC-11 and EC-14 Sprin-
The Series EC-11 and EC-14 Ex- fluid expands sufficiently to shatter the klers are to be installed in accord-
tended Coverage Upright, Pendent, glass bulb, which then allows the ance with all other requirements of
and Recessed Pendent Sprinklers are sprinkler to activate and flow water. NFPA 13 for extended coverage up-
UL and C-UL Listed. (Refer to Table A right and pendent sprinklers. For ex-
for complete sprinkler approval infor- ample: obstructions to sprinkler dis-
mation including corrosion resistant Design charge, obstructions to sprinkler
status. The approvals apply to the pattern development, obstructions
service conditions indicated in the De- Criteria to prevent sprinkler discharge from
sign Criteria section.) reaching hazard, clearance to stor-
The Tyco Series EC-11 and EC-14 age, etc.
The Series EC-11 and EC-14 Ex- Extended Coverage Sprinklers must
tended Coverage Upright and Pendent only be installed in accordance with
Sprinklers are FM Approved. (Refer to UL and C-UL Specific Application
the applicable UL and C-UL Listing or Listing Requirements For
Table A for complete sprinkler ap- FM Approval requirements as indi-
proval information including corrosion Installation Under Concrete Tees
cated below. Only the Style 30 or 40 The Series EC-11 and EC-14 Ex-
resistant status. The approvals apply Recessed Escutcheon is to be used for
to the service conditions indicated in tended Coverage Upright and Pendent
recessed installation, as applicable Sprinklers (TY5137, TY5237, TY6137
the Design Criteria section.) (Ref. Table A, B, and C). & TY6237) have a UL and C-UL Spe-
The Style 60 Two-Piece Flush Es- UL and C-UL Listing cific Application Listing for use under
cutcheon (Ref. Figure 4) is UL Listed Requirements concrete tees when installed as fol-
and FM Approved for use with the Se- lows:
ries EC-11 and EC-14 Pendent Sprin- 1. The Series EC-11 and EC-14 Sprin-
klers. klers may be used for the coverage 1. The stems of the concrete tee con-
Maximum Working Pressure areas shown in Table D, based on struction must spaced at less than
175 psi (12,1 bar) maintaining the minimum specified 7.5 feet (2,3 m) on center but more
flow rate as a function of coverage than 3 feet (0,9 m) on center. The
Pipe Thread Connection area and hazard group for all of the depth of the concrete tees must not
3/4 inch NPT sprinklers in the design area. exceed 30 inches (762 mm). The
Discharge Coefficients maximum permitted concrete tee
K = 11.2 GPM/psi1/2 2. The Series EC-11 and EC-14 Sprin- length is 32 feet (9,8 m); however,
(161,3 LPM/bar1/2) klers are permitted to be used with where the concrete tee length ex-
K = 14.0 GPM/psi1/2 unobstructed or non-combustible ceeds 32 feet (9,8 m), non-combus-
(201,6 LPM/bar1/2) obstructed ceiling construction as tible baffles, equal in height to the
defined and permitted by NFPA 13. depth of the tees, can be installed so
Temperature Ratings For example: that the space between the tees
135F/57C to 286F/141C does not exceed 32 feet (9,8 m) in
Finish Unobstructed, combustible or non- length.
Sprinkler: Refer to Table A combustible, ceiling construction
Recessed or Flush Escutcheon: White with a deflector to ceiling/roof deck 2. The sprinkler deflectors are to be
Coated, Chrome Plated, and Brass distance of 1 to 12 inches (25 to 300 located in a horizontal plane at or
Plated mm). above 1 inch (25,4 mm) below the
bottom of the concrete tee stems.
Physical Characteristics Obstructed, non-combustible, ceil-
Frame . . . . . . . . . . . . . Bronze ing construction with a deflector lo- 3. When the sprinkler deflectors are
Button . . . . . . . . . . . . . Bronze cation below structural members of located higher than a horizontal
Sealing Assembly . . . . . . . . . . 1 to 6 inches (25 to 150 mm) and a plane 1 inch (25l,4 mm) beneath the
. . . . . Beryllium Nickel w/Teflon maximum deflector to ceiling/roof bottom of the concrete tee stems,
Bulb . . . . . . . . Glass (3 mm dia.) deck distance of 22 inches (550 the obstruction to sprinkler dis-
mm). charge criteria requirements of
Compression Screw . . . . . . . . .
. . . . . . . . . . . . . . . . Bronze NFPA 13 for extended coverage up-
3. The Series EC-11 and EC-14 Sprin- right sprinklers applies.
Deflector . . . . . . . . . . . . Brass
klers having been specifically tested
and listed for non-combustible ob- FM Approval
Patents structed construction are permitted Requirements
U.S.A. Patent Numbers 5,366,022; to be used within trusses or bar joists The Series EC-11 and EC-14 Ex-
5,579,846; 5,584,344; 5,609,211; having non-combustible web mem- tended Coverage Sprinklers are to be
5,862,994; and 5,865,256. bers greater than 1 inch (25.4 mm) installed in accordance with the appli-
when applying the 4 times obstruc- cable Factory Mutual Loss Prevention
tion criteria rule defined under Ob- Data Sheet for limited use in buildings
structions to Sprinkler Discharge of specific roof construction and for the
Pattern Development. protection of certain specific ordinary
hazard (non-storage and/or non-flam-
4. The minimum allowable spacing be- mable or combustible liquid) occupan-
tween the Series EC-11 and EC-14 cies. Information provided in the FM
< 1 > Close

TFP220 Page 5 of 8

Loss Prevention Data Sheets relate to,


but are not limited to, hydraulic design,
2-7/8" DIA. ceiling slope and obstructions, mini-
1/21/8" (73,0 mm) 1/2" (12,7 mm) mum and maximum allowable spac-
(12,73,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) ing, and deflector-to ceiling distance.
FACE OF (57,2 mm)
These criteria may differ from UL
SPRINKLER 1/8"
and/or NFPA criteria, therefore the de-
FITTING (3,2 mm)
signer should review and become fa-
miliar with Factory Mutual require-
ments before proceeding with design.

MOUNTING
Installation
SURFACE MOUNTING
PLATE The Series EC-11 and EC-14 Sprin-
CLOSURE
klers must be installed in accordance
with the following instructions:
1-3/8" (34,9 mm)
NOTES
1-1/8" (28,6 mm) Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
FIGURE 2 held horizontally, a small air bubble
should be present. The diameter of the
SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
air bubble is approximately 1/16 inch
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT (1,6 mm) for the 135F/57C to 3/32
STYLE 30 RECESSED ESCUTCHEON inch (2,4 mm) for the 286F/141C
temperature ratings.
A 3/4 inch NPT sprinkler joint should
be obtained with a minimum to maxi-
mum torque of 10 to 20 ft.lbs. (13,4 to
26,8 Nm). Higher levels of torque may
distort the sprinkler inlet with conse-
2-7/8" DIA.
(73,0 mm)
quent leakage or impairment of the
5/81/4" 3/4" (19,1 mm)
sprinkler.
(15,96,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) Do not attempt to compensate for in-
FACE OF sufficient adjustment in an Escutcheon
SPRINKLER 1/8"
(3,2 mm) Plate by under- or over-tightening the
FITTING
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position,
MOUNTING MOUNTING and upright sprinklers must be in-
SURFACE PLATE stalled in the upright position.
CLOSURE Step 2. After installing the Style 30, 40,
1-3/8" (34,9 mm) or 60 mounting plate (or other escutch-
7/8" (22,2 mm) eon, as applicable) over the sprinkler
pipe threads and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
FIGURE 3 sprinkler fitting.
SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY Step 3. Wrench tighten upright or pen-
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT dent sprinklers using only the W-Type
STYLE 40 RECESSED ESCUTCHEON 3 (End A) Sprinkler Wrench. When in-
stalling the pendent sprinkler with
Style 30, 40, or 60 Escutcheon,
wrench tighten the sprinkler using only
the W-Type 22 Sprinkler Wrench. The
wrench recess of the applicable sprin-
kler wrench (Ref. Figure 5 and 6) is to
be applied to the sprinkler wrench flats
(Ref. Figure 1).
< 1 > Close

Page 6 of 8 TFP220

"FITTING SIDE"
2-7/8" DIA.
(73,0 mm) TOWARDS SPRINKLER
INTERNAL FITTING
2-1/4" DIA.
DIMENSIONS OF
(57,2 mm)
STYLE 60 ESCUTCHEON
ACCOMMODATE
CLASS 150 MALLEABLE
FACE OF IRON REDUCING
SPRINKLER FITTING: SPRINKLER FITTING
3/8" (9,5 mm) ABOVE WRENCH
TO 1/8" (3,2 mm) BELOW MOUNTING
MOUNTING SURFACE SURFACE RECESS
1/8"
(3,2 mm) (END "A")

ESCUTCHEON PLATE FIGURE 5


SEATING SURFACE: W-TYPE 3 SPRINKLER
CLOSURE
1/4" (6,4 mm) ABOVE WRENCH
2-5/16" (58,7 mm)
TO 1/2" (12,7 mm) BELOW 3/4" NPT
MOUNTING SURFACE; MOUNTING 1-13/16" (46,0 mm)
3/4" (19,1 mm) TOTAL PLATE WRENCH
ADJUSTMENT RECESS

FIGURE 4
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY
WITH 3/4 INCH TOTAL ADJUSTMENT
STYLE 60 TWO-PIECE FLUSH ESCUTCHEON

2 1

twist/slippage, or the like, must be re-


Care and placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
WRENCH

Maintenance liquid from its bulb. (Ref. Installation


FIGURE 6
HEX

Section).
The Tyco Series EC-11 and EC-14 W-TYPE 22 RECESSED
Sprinklers must be maintained and Frequent visual inspections are rec- SPRINKLER WRENCH
serviced in accordance with the follow- ommended to be initially performed for
ing instructions: corrosion resistant coated sprinklers,
after the installation has been com-
NOTE pleted, to verify the integrity of the cor-
ance with local requirements and/or
Before closing a fire protection system rosion resistant coating. Thereafter,
national codes.
main control valve for maintenance annual inspections per NFPA 25
work on the fire protection system that should suffice; however, instead of in-
it controls, permission to shut down the specting from the floor level, a random
affected fire protection systems must sampling of close-up visual inspec-
be obtained from the proper authori- tions should be made, so as to better
ties and all personnel who may be determine the exact sprinkler condi-
affected by this action must be notified. tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
Sprinklers that are found to be leaking present.
or exhibiting visible signs of corrosion
must be replaced. The owner is responsible for the in-
spection, testing, and maintenance of
Automatic sprinklers must never be their fire protection system and de-
painted, plated, coated, or otherwise vices in compliance with this docu-
altered after leaving the factory. Modi- ment, as well as with the applicable
fied sprinklers must be replaced. standards of the National Fire Protec-
Sprinklers that have been exposed to tion Association (e.g., NFPA 25), in
corrosive products of combustion, but addition to the standards of any other
have not operated, should be replaced authorities having jurisdiction. The in-
if they cannot be completely cleaned stalling contractor or sprinkler manu-
by wiping the sprinkler with a cloth or facturer should be contacted relative
by brushing it with a soft bristle brush. to any questions.
Care must be exercised to avoid dam- Automatic sprinkler systems should be
age to the sprinklers - before, during, inspected, tested, and maintained by a
and after installation. Sprinklers dam- qualified Inspection Service in accord-
aged by dropping, striking, wrench
< 1 > Close

TFP220 Page 7 of 8

GROUP I GROUP II
LIGHT HAZARD ORDINARY HAZARD ORDINARY HAZARD
0.10 GPM/FT2 0.15 GPM/FT2 0.20 GPM/FT2

DESCRIPTION AREA GPM PSI GPM PSI GPM PSI

TY5137 (K=11.2) UPRIGHT 14 x 14 30 7.2 39 12.1


16 x 16 30 7.2 39 12.1 51 20.7
18 x 18 33 8.7 49 19.1 65 33.7
20 x 20 40 12.8 60 28.7 80 51.0

TY5237 (K=11.2) PENDENT 14 x 14 30 7.2 39 12.1


16 x 16 30 7.2 39 12.1 51 20.7
18 x 18 33 8.7 49 19.1 65 33.7
20 x 20 40 12.8 60 28.7 80 51.0

TY6137 (K=14.0) UPRIGHT 14 x 14 N/A N/A


16 x 16 N/A N/A 39 7.8 51 13.3
18 x 18 N/A N/A 49 12.3 65 21.6
20 x 20 N/A N/A 60 18.4 80 32.7

TY6237 (K=14.0) PENDENT 14 x 14


16 x 16 37 7.0 39 7.8 51 13.3
18 x 18 37 7.0 49 12.3 65 21.6
20 x 20 40 8.2 60 18.4 80 32.7
1 ft. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3.785 lpm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/min

TABLE D
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS

sprinkler system design errors or inac-


Limited curate or incomplete information sup-
plied by Buyer or Buyers repre-
Warranty sentatives.
Products manufactured by Tyco Fire & In no event shall TFBP be liable, in
Building Products (TFBP) are war- contract, tort, strict liability or under
ranted solely to the original Buyer for any other legal theory, for incidental,
ten (10) years against defects in mate- indirect, special or consequential dam-
rial and workmanship when paid for ages, including but not limited to labor
and properly installed and maintained charges, regardless of whether TFBP
under normal use and service. This was informed about the possibility of
warranty will expire ten (10) years such damages, and in no event shall
from date of shipment by TFBP. No TFBPs liability exceed an amount
warranty is given for products or com- equal to the sales price.
ponents manufactured by companies The foregoing warranty is made in lieu
not affiliated by ownership with TFBP of any and all other warranties, ex-
or for products and components which press or implied, including warranties
have been subject to misuse, improper of merchantability and fitness for a par-
installation, corrosion, or which have ticular purpose.
not been installed, maintained, modi-
fied or repaired in accordance with ap- This limited warranty sets forth the ex-
plicable Standards of the National Fire clusive remedy for claims based on
Protection Association, and/or the failure of or defect in products, materi-
standards of any other Authorities als or components, whether the claim
Having Jurisdiction. Materials found is made in contract, tort, strict liability
by TFBP to be defective shall be either or any other legal theory.
repaired or replaced, at TFBPs sole This warranty will apply to the full ex-
option. TFBP neither assumes, nor tent permitted by law. The invalidity, in
authorizes any person to assume for it, whole or part, of any portion of this
any other obligation in connection with warranty will not affect the remainder.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
< 1 Close

Page 8 of 8 TFP220

Ordering P/N 51 - AAA - B -CCC

Procedure AAA = 893 (for TY5237


When placing an order, indicate the full K11.2 Pendent)
product name. Please specify the AAA = 894 (for TY5137
Sprinkler Identification Number (SIN), K11.2 Upright)
quantity, and temperature rating. Re- AAA = 895 (for TY6237
fer to the Price List for complete listing
K14.0 Pendent)
of Part Numbers.
AAA = 896 (for TY6137
Contact your local distributor for avail- K14.0 Upright)
ability.

Sprinkler Assemblies with NPT B = 1 (for Natural Brass)


Thread Connections: B = 3 (for White [RAL9010])*
Specify: (specify SIN), (specify K-Fac- B = 4 (for White Polyester)
tor), (specify temperature rating), B = 7 (for Lead Coated
(specify Pendent or Upright) Extended
B = 9 (for Chrome Plated)
Coverage Sprinkler with (specify fin-
ish), P/N (specify - from Table E,
where applicable). CCC = 135 (for 135F/57C)
CCC = 155 (for 155F/68C)
Recessed Escutcheon, Two-Piece : CCC = 175 (for 175F/79C)
Specify: Style (30 or 40) Two-Piece
Recessed Escutcheon with (specify CCC = 200 (for 200F/93C)
material or finish*), P/N (specify).
*Eastern Hemisphere sales only.
*Refer to Technical Data Sheet
TFP770. TABLE E
PART NUMBERS FOR
Flush Escutcheon, Two-Piece : EC-11 AND EC-14 SPRINKLERS
Specify: Style 60 Two-Piece Flush Es-
cutcheon with (specify finish*), P/N
(specify).

*Refer to Technical Data Sheet


TFP778.

Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprin-
kler Wrench, P/N 56-665-7-001

2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446