1 ABSTRACT
It has long been known that comparing the partial discharge results obtained from a single machine is a valuable
tool enabling companies to observe the gradual deterioration of a machine stator winding and thus plan
appropriate maintenance for the machine [1]. In 1998, at the annual Iris Rotating Machines Conference
(IRMC), a paper was presented that compared thousands of partial discharge (PD) test results to establish the
criteria for comparing results from different machines and the expected PD levels [2]. At subsequent annual Iris
conferences, using similar analytical procedures, papers were presented that supported and expanded upon the
previous criteria [4 - 16].
In the past few decades, continuous monitors of PD in rotating machines have become quite common. To ensure
that PD magnitude can be trended over time with data collected under the same operating conditions; these
monitors have the ability to also track the voltage, load, winding temperature, hydrogen pressure, etc. In spite of
these controls, the PD trend activity is often still very variable. One of the root causes of the unexplained
variation was eventually determined to be humidity, moisture content, dew point or related phenomena
associated with the atmosphere in which the machine operates. This paper examines this effect on the PD
database rather than individual machines.
Calibration of on-line PD test results is impractical [3]; therefore, only results obtained using the same method
of data collection and noise separation techniques are compared. For this paper, all the data were obtained with
a PDA-IV, TGA, Trac or Guard test instrument. Data collected through 2011 was used; and, as in past papers, it
is standardized for frequency bandwidth and pruned to include only the most recent full-load-hot (FLH) results
collected for each sensor on operating machines. All questionable data, or data from off-line testing or unusual
machine conditions was excluded, leaving over 16,700 statistically independent new results. The Appendix
presents the statistical summary of the latest data to enable Trac, Guard, TGA and PDA-IV test users to compare
on a gross level their test results to those of similar machines.
2 INTRODUCTION
2.1 PD - A COMPARISON TEST
Partial discharges (PD) are small electrical sparks that occur when voids exist within or on the surface of high
voltage insulation of stator windings in motors and generators. These PD pulses can occur because of the
manufacturing/installation processes, thermal deterioration, winding contamination or stator bar movement
during operation. As the insulation degrades, the number and magnitude of PD pulses will increase. Although
the magnitude of the PD pulses cannot be directly related to the remaining life of the winding, the doubling of
PD pulse magnitudes approximately every 6 months indicates rapid deterioration is occurring. If the rate of PD
pulse activity increases rapidly, or the PD levels are high compared to other similar machines, this is an
indicator that visual inspections and/or other testing methods are needed to confirm the insulation condition [4].
Furthermore, if the PD magnitudes by the same test method from several identical windings are compared, the
windings exhibiting higher PD activity are generally closer to failure [1].
PD Progress Report 1 of 13
IRMC 2012
PD levels appear to be influenced by the quality of design, manufacturing, and installation, and not
solely operating hours or operating condition [6, 7,10, 13, 14, 16]
Not as significant are:
Type of insulation system [6, 9, 12]
Machine type [2,5,6,11]
Winding type [2,5,6,11]
Differences in operating loads and temperatures could also affect the results, but these were dependent on the
condition of the stator winding and therefore, would only be applicable when comparing the PD results obtained
from a single machine, not when comparing results from different machines.
3 COLLECTION OF DATA
3.1 PD TEST METHOD
During normal machine operation, an instrument called the PDA-IV or TGA is temporarily connected to the
previously installed sensors in each phase. The sensor blocks the power frequency voltage, and passes the high
frequency voltage pulse accompanying partial discharge. To avoid any confusion with electrical noise from
power tool operation, corona from the switchgear, RF sources, etc., the PDA-IV or TGA separates PD from
system noise on the bases of time-of-arrival and pulse characteristics, and measures the number, magnitude and
ac phase position of the PD pulses.
Once these criteria were applied, about 16,700 statistically independent test results were analyzed.
PD Progress Report 2 of 13
IRMC 2012
The following tables show the breakdown of the
results that were retained once non-FLH and repeat Percentage of Tests
tests were discarded. by Machine Type
1
Fluctuations from previous years due to a large influence from one or more manufacturers
2
Fluctuations from previous years due to a large influence from one or more manufacturers
PD Progress Report 3 of 13
IRMC 2012
off-line tests and/or a visual inspection would be prudent. Continuous PD monitors should have their alarm
levels set to the 90% level.
4 HUMIDITY EFFECT
Environmental conditions may have a very noticeable impact, especially if the surface contamination becomes
partly conductive when damp, so it should be recorded from one test to the next. It is appreciated that at times it
may be very difficult to duplicate test conditions, particularly temperatures; however, the emphasis should
always be on trying to achieve as uniform conditions as possible. This means taking tests when units are hot and
the temperature has stabilized, while accurately recording both the operating and ambient conditions.
Perhaps the most influential, yet unpredictable, impacts of ambient conditions to PD are the effects of variances
in ambient humidity on air-cooled machines. Humidity can cause the electrical breakdown stress of the air to
decrease, and therefore cause an increase in surface PD. On the other hand, humidity can also impact the
electrical tracking of surface PD, and therefore cause a decrease in PD. Thus, in some circumstances, the PD
may go up (direct effect), while in others it would go down (inverse effect) with increases in relative humidity.
In some circumstances, the humidity effect has been known to cause the PD to fluctuate by as much as 300%.
Since each scenario is different, it is extremely important the ambient humidity be recorded at test time so trends
can be properly evaluated and decisions are not made about upward trends that occur because of humidity
effects and not changes in winding condition. Present experience indicates humidity only affects surface
activity.
0 0
PD Progress Report 4 of 13
IRMC 2012
4.1.2 Hydrogen-Cooled Machines with 80pF Couplers
0 0
be detected on hydrogen-cooled machines, the
problem is outside of the hydrogen-environment
from PD sources within the air environment.
PD Progress Report 5 of 13
IRMC 2012
4.2.2 Case Study 2 (Contamination)
A 4.1 kV cooling water motor in a nuclear power plant was equipped with a continuous PD monitor employing
80pF capacitive sensors. At the same time, a portable relative humidity indicator monitored the humidity of the
air in the motor environment. Figure 2 shows that over a 48 h period there is an excellent inverse effect between
the PD activity, expressed by Qm and NQN (IEEE Std 1434-2000), and relative humidity. That is as the relative
humidity increases from 32% to 54%, the peak PD magnitude (Qm) drops from 200 mV to 100 mV, over a 5 h
period.
Analysis of the data revealed that the PD was occurring in the end-winding area between phase A and B, since
the PD was phase shifted +30 in A phase and -30" in B phase from the normal phase position in the ac voltage
cycle for PD occurring in the stator slot [19. ]. Since the endwinding area of machines is specifically designed to
be away from ground planes, PD that occurs due to contamination in the endwinding is normally phase-to-phase
voltage dependent and will be 30 phase shifted from the classic positions of 45 and 225 . The direction of the
shift is dependent on the location of the contamination and the voltages of the affected coils and is therefore
unpredictable. Though there may be some effect of temperature or load changes on PD activity from
contamination, it is difficult to predict the expected results. However, environmental conditions such as
humidity may have a very noticeable effect, especially if the surface contamination becomes partly conductive
when damp.
In a later visual inspection of the winding by plant staff, the end-windings of this vertical motor were found to be
soaked in oil from an upper bearing oil leak. In addition, a heavy layer of dead insects covered the end-winding.
Such contamination is conductive and known to produce electrical tracking in the endwindings of coils
connected to the phase terminals. Thus for this motor it appears that lower humidity causes the end-winding
electrical tracking to accelerate. [18.
PD Progress Report 6 of 13
IRMC 2012
4.2.3 Case Study 3 (Multiple effects)
A 21kV air-cooled steam turbine
generator with bus couplers has been
periodically tested for PD activity over
the past year. Though the levels are
relatively low compared to the Iris
database, it is apparent that there are
some fluctuations that appear to track
the relative humidity values. Note that
most of the Qm levels are directly
correlated; whereas, the C-Qm+ is
inversely correlated between the PD
levels and the relative humidity levels.
[m V ]
[m V ]
B ip o la r M a c h in e P D B ip o la r M a c h in e P D B ip o la r M a c h in e P D
1 to 3 .1 6 p p s 3 .1 6 to 1 0 p p s 1 0 to 3 1 .6 p p s 3 1 .6 to 1 0 0 p p s 1 to 3 .1 6 p p s 3 .1 6 to 1 0 p p s 1 0 to 3 1 .6 p p s 3 1 .6 to 1 0 0 p p s 1 to 3 .1 6 p p s 3 .1 6 to 1 0 p p s 1 0 to 3 1 .6 p p s 3 1 .6 to 1 0 0 p p s
1 0 0 to 3 1 6 p p s 3 1 6 to 1 0 0 0 p p s > 1000 pps S ubset8 1 0 0 to 3 1 6 p p s 3 1 6 to 1 0 0 0 p p s > 1000 pps S ubset8 1 0 0 to 3 1 6 p p s 3 1 6 to 1 0 0 0 p p s > 1000 pps S ubset8
M a g n itu d e
M a g n itu d e
M a g n itu d e
75 75 75 75 75 75
50 50 50 50 50 50
25 25 25 25 25 25
0 0 0 0 0 0
-25 -25 -25 -25
P u ls e
P u ls e
-25 -25
P u ls e
-50 -50 -50 -50
-50 -50
-75 -75 -75 -75
-75 -75
0 45 90 135 180 225 270 315 360 0 45 90 135 180 225 270 315 360
P h a s e A n g l e [d e g ] P h a s e A n g l e [d e g ] 0 45 90 135 180 225 270 315 360
P h a s e A n g l e [d e g ]
PD Progress Report 7 of 13
IRMC 2012
4.2.5 Case Study 5 (Voltage Stress Coatings)
A 13.8kV air-cooled turbine generator
with bus couplers has been periodically
tested for PD activity over the past year.
Though the levels are relatively low
compared to the Iris database, it is
apparent that there are some
fluctuations that appear to track the
relative humidity values. At present,
the PD levels on B-phase are low and
inversely track with humidity.
B ip o la r M a c h in e P D
Though not as prevalent with Case Study 3, there is a
1 to 3 .1 6 p p s 3 .1 6 to 1 0 p p s 1 0 to 3 1 .6 p p s 3 1 .6 to 1 0 0 p p s
noticeable hook in the negative PD clusters for B-phase.
1 0 0 to 3 1 6 p p s 3 1 6 to 1 0 0 0 p p s > 1000 pps Su b s e t 8
This combined with the clusters of PD near 90/270
M a g n itu d e
150 150
100 100 suggests and the inverse humidity dependence suggests that
50 50 this may be the onset of early deterioration of the voltage
0 0 stress coatings or perhaps phase-to-phase contamination
-50 -50 either within the winding or perhaps at the machines
P u ls e
B-phase (clusters/hook)
5 CONCLUSION
Based on the database analysis, it is unusual to find situations where the PD directly or inversely tracks with the
relative humidity. This is likely due to two issues: one, the fact that there is minimal variability of humidity
within the machine housing, and two, the majority of machines probably have PD activity that is within the slot
section of the winding. Therefore, if humidity dependence is noted, then it is highly recommended that the
investigation begin at the machines terminals and then proceed into the machine housing. This is especially the
case when PD sensors for hydrogen-cooled windings are installed outside of the hydrogen environment at the
terminals, and where only PD sources at the terminals would be impacted by humidity changes. Results that
track with humidity are from surface PD activity, such as would occur with deterioration of voltage stress
coatings, contamination or insufficient spacing between high voltage components.
Though it is always recommended that you trend the results for one machine over time and thus monitor the rate
of degradation of the stator winding, it is also possible to compare results from similar machines. If the test
instrument is a TGA, PDA-IV, Trac or Guard and the sensors are either 80pF capacitors, or stator slot couplers,
then the tables contained within the appendix can be used to ascertain whether a machine warrants further tests
and inspections or is operating within reasonable limits. Red flags should only be raised if the PD levels on a
specific machine are doubling over a six-month interval, or if they are above the 90 th percentile and steadily
rising. In all cases, raising the red flag means increasing the frequency of PD testing to determine the rate of
deterioration and when possible, conduct specialized tests, inspections and repairs as required. PD is a symptom
of a failure mechanism; action should be based on the severity of the failure mechanism detected by the PD, not
the PD results. PD levels exceeding threshold alarms are warnings for further investigation to determine the
cause of the high PD; however, be aware that PD levels can fluctuate with ambient and operating conditions.
PD Progress Report 8 of 13
IRMC 2012
Maintenance should be based on the cause of the PD, not the overall levels. Continuous PD monitors should
have their alarm levels set to the 90% level.
The time of winding failure is normally the result of a deteriorated winding being subjected to an extreme stress
such as a lightning strike, out-of-phase synchronization, excessive starts, or system imbalance. As these are
unpredictable, it is impossible to forecast when a failure will occur. However, by monitoring the PD
characteristics of a stator winding, it is often possible to determine which machines are more susceptible to
failure, and therefore which require maintenance.
6 REFERENCES
1. J.F. Lyles, T.E. Goodeve, and G.C. Stone, Using Diagnostic Technology for Identifying Generator
Winding Maintenance Needs, Hydro Review Magazine, June 1993, pp. 59-67.
2. V. Warren, How Much PD is Too Much PD? Proc. Iris Rotating Machine Conference, Dallas, TX,
March 1998.
3. IEEE 1434-2000 IEEE Guide to the Measurement of Partial Discharges in Rotating Machinery.
4. V. Warren, G.C. Stone, Recent Developments in Diagnostic Testing of Stator Windings, IEEE Electrical
Insulation Magazine, September 1998.
5. V. Warren, Further Analysis of PD Test Results Proc. Iris Rotating Machine Conference, Scottsdale, AZ,
March 1999.
6. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, New
Orleans, LA, June 2000.
7. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference,
Washington, D.C., June 2001.
8. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, San
Antonio, TX, June 2002.
9. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference,
Santa Monica, CA, June 2003.
10. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, New
Orleans, LA, June 2004.
11. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference,
Scottsdale, AZ, June 2005.
12. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference,
Toronto, ON, June 2006.
13. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, San
Antonio, TX, June 2007.
14. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, Long
Beach, CA, June 2008.
15. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, New
Orleans, LA, June 2009.
16. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference,
Orlando, FL, June 2010.
17. V. Warren, Partial Discharge Testing A Progress Report Proc. Iris Rotating Machine Conference, San
Antonio, TX, June 2011.
18. M. Fenger and G. Stone, Investigations into the Effect of Humidity on Stator Winding Partial Discharges,
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 12, No. 2; April 2005, pp. 341-365.
19. V. Warren, G. C. Stone and M. Fenger, "Advancements in Partial Discharge Analysis to Diagnose Stator
Winding Problems", IEEE Intcrn. Sympos. Electr. Insul., pp. 497-500, 2000.
PD Progress Report 9 of 13
IRMC 2012
7 APPENDIX DATA ANALYSIS OF RESULTS THRU 2009
The following summarizes the analysis of the PD levels, given by Qm number, for all data collected with Iris
equipment up to the end of the year 2011 with over 272,000 results. Since it has been well established that it is
ambiguous to compare PD results obtained using different types of sensors [3], data analysis requires separation
of the database based on sensor type. The two basic types of sensors used in the data collection are: 80pF
capacitors (cable-type and epoxy-mica type) and stator slot couplers (SSC). Furthermore, data will be
separated based on gas cooling pressure and operating voltages.
7.1.1 Capacitors (air-cooled machines)
The most widely employed sensors are the 80pF couplers used on motors, hydro-generators, and small turbine
generators. There are two methods of sensor installation for the capacitive couplers, the directional (TGA) and
the differential (PDA) methods.
As shown here, the majority, 75%, of the results obtained with the directional mode installation (BUS) of
capacitive couplers are below 172mV for machines rated less than 12kV, 239mV for machines rated 13-15kV,
151mV for 16-18kV 184mV for those >19kV.
Additionally, there is at least a doubling of the Qm levels between the 75% and the 90%. There are a few
machines with PD much higher than the 90th percentile with Qm levels >220-500mV. These machines are
suspected to have significant deterioration.
3
Fluctuations from previous years due to a large influence from one or more manufacturers
PD Progress Report 10 of 13
IRMC 2012
differential (PDA) results, though there are some minor variances, there is little significant difference between
the statistical summaries for windings rated less than 19kV. Thus, it is safe to say that for a 13.8kV winding,
regardless of installation type, the PD levels should be less than ~240mV and those machines with PD higher
than 500mV need further investigation.
Capacitors (gas-cooled)
Since the occurrence of PD is extremely dependent on the electrical breakdown point of the gas medium, PD
results from air-cooled machines are typically higher than machines cooled with either hydrogen or pressure
carbon dioxide. Therefore, it is not advisable to compare the results from machines using different gas
mediums. Since most hydro-generators (PDA installations) are air-cooled, all of the tests for gas-cooled
machines with capacitors were obtained using a TGA instrument and directional sensor installation. Most of the
hydrogen-cooled machines have high rated loads and frequently suffer from problems with the core iron arcing.
PD or noise activity at the machine terminals, outside the hydrogen environment, can make stator winding
insulation condition difficult to interpret. As a result, stator slot couplers (SSC) are the recommended sensors in
these applications to avoid misdiagnosis resulting from the capacitive sensor detecting core-iron problems in
addition to stator winding problems.
Qm values for non air-cooled machines with directional capacitive couplers (TGA)
Rated V 13-15kV 16-18kV > 19kV
.
H2 (psig) 11-20 21-30 31-50 11-20 21-30 31-50 >50 21-30 31-50 >50
Avg 163 87 138 148 222 103 56 105 60 125
4
25% 35 18 18 57 31 25 9 43 20 9
50% 84 42 43 116 60 50 22 94 45 29
4 4
75% 172 91 95 188 182 110 38 172 77 87
4 4 4
90% 363 173 277 313 891 249 102 217 132 255
4 4 4 4
95% 556 370 648 441 966 423 309 246 159 732
As expected, the PD results for gas-cooled machines are much lower than for the air-cooled machines. This is
especially observable at higher pressures, where 75% of the tests for all operating voltages operated above
31psig are below 110mV and 90% generally below ~250mV, less than half of that observed on the air-cooled
machines (TGA). At the lower operating pressures the PD levels are much higher, with a few machines having
extremely high PD of Qm levels >600mV, which would require more tests and investigation
7.1.2 Stator Slot Couplers (SSC) (gas-cooled)
Qm values for non air-cooled machines with SSC sensors- Slot PD
Rated V 13-15kV 16-18kV 19-22kV 23-26kV
H2 (psi) 11-20 21-30 31-50 11-30 31-50 > 50 11-30 31-50 >50 31-50 >50
4
Fluctuations from previous years due to a low number of samples
PD Progress Report 11 of 13
IRMC 2012
Avg 25 21 13 14 12 7 35 19 10 14 7
25% 1 0 0 0 0 0 1 0 0 0 0
50% 10 1 9 2 3 0 7 8 3 7 3
75% 25 13 19 15 14 6 20 22 11 165 7
5
90% 47 63 31 45 37 15 83 50 22 29 18
5
95% 49 92 50 78 53 22 198 67 37 41 29
The preferred sensor for turbine generators rated higher than 100MVA is a stator slot coupler (SSC). The
sensor is placed within the slot of the highest voltage bar either directly beneath the wedge or between the top
and bottom bars in the slot. There is little difference in the results obtained from the two installations [2].
Since these machines are operating in a hydrogen environment, the overall slot PD is quite low. It should be
observed that though the majority of the machines have slot Qm values less than ~30mV, there are a few with
levels higher than 60-200mV. These should be subjected to further tests and inspections. The SSC is a high
frequency antenna that will detect the pulses and through pulse analysis, the TGA is capable of discriminating
between pulses originating in the high voltage insulation and those from core-iron arcing or external sources.
Furthermore, the SSC/TGA test setup can identify whether the PD originates in the slot portion of the bar or in
the endwinding area [15].
7.1.2.1 Qm values for non air-cooled machines with SSC sensors- Endwinding PD
Rated V 13-15kV 16-18kV 19-22kV 23-26kV
H2 (psi) 11-20 21-30 31-50 11-30 31-50 > 50 11-30 31-50 >50 31-50 >50
Avg 4 3 4 5 2 5 3 4 6 4 5
25% 0 0 0 0 0 0 0 0 0 0 0
50% 0 0 0 0 0 0 0 0 0 0 0
75% 3 0 6 2 0 2 1 3 5 1 0
5
90% 14 9 12 14 8 15 9 12 13 11 4
5 5 5
95% 27 19 18 22 14 35 25 19 26 12 22
The endwinding PD results are slightly lower than the slot PD results, with 90% of all the tests less than ~15mV.
There are, however, a few machines with Qm levels higher than 25mV, and these machines require additional
attention.
PD Progress Report 12 of 13
IRMC 2012
It is not surprising that the PD levels for the air-cooled machines with SSCs are generally higher than the gas-
cooled ones. The majority of these machines have slot Qm levels less than ~30mV, but there are a few with
extraordinarily high PD, >90mV, that would require further investigation.
PD Progress Report 13 of 13