Sie sind auf Seite 1von 3

Submittal Ref. #: 446825.

1 rev6

Split coupled vertical in line pump


Model: Series 4300-4x4x11.5-15 hp Pump (Motor supplier: Armstrong choice)

Project name: 1408-0202_Columbia U Manhattanville PH-1B


Location: 10027 Representative: SRS Enterprises Inc.
Date submitted: 10/12/2016 9:26:45 AM Phone number:
Engineer: WSP e-mail: gcalano@srs-enterprises.com
Contractor: Submitted by: Gary Calano
Application design data
Tag number: SCHWP-BG-1,2 Pipe orientation: Single
Service: Suction pressure: 0 psig
Location: Fluid: Water:
Quantity: 2 Operating temperature: 60 F
Duty flow per pump: 440 USgpm Viscosity: 31 SSU
Duty head: 75 ft Specific gravity: 1.0000
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel

Motor electrical data


Supplier: Factory Choice Insulation class: Class F Insulation
Size: 15 hp Inverter motor type: Inverter Duty
Frame number: 254TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1780 rpm
Motor Electrics: 460/3/60

INDICATE MOTOR
FULL LOAD AMPS
(FLA)
Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F


Pump casings are hydrostatically tested to 150% of maximum pump working
pressure rating.

www.armstrongfluidtechnology.com 10/12/2016, Ref. # 446825.1 rev6 Page 4 of 27


Performance curve

--- Admin Data ---


Head Series 4300 PT83-1-0 (3.23.0.1) Tag Num: SCHWP-BG-1,2
ANSI/HI 14.6.3.4 3B Service:
(ft) 4x4x11.5 @ 1780 rpm Location:
160 --- Motor Data ---
11.50 in 52 62 Motor Size: 15 hp
69 Motor Speed: 1800 rpm
140 73
76
76 --- Design Duty Point ---
77 76 Flow: 440 usgpm
120 73 Head: 75 ft
Impeller: 9.91 in
9.91 in 69
--- Performance Data ---
100 62 NPSHR: 13 ft
9.50 in Eff. @ Design: 67.10 %
BHP @ Design: 12.42 hp
80 25 hp Mtr Capability @ Rated Spd: 15.00 hp
%Mtr Safety: 20.79%
BEP @ Design Imp.:
20 hp 74.29 % @ 342.2 usgpm
60 Impeller Max BHP @ Flow:
15 hp 13.62 hp @ 513.3 usgpm
%max imp. range: 20.50 %
40 10 hp Outlet Velocity: 11.09 ft/s
7.5 hp VFD Setting: 60.0 Hz

20
System
0
0 100 200 300 400 500 600 700 800

Water:, spgr= 1.0000 Flow (usgpm)

Head PT83-1-0 (3.23.0.1) --- Admin Data ---


Series 4300 ANSI/HI 14.6.3.4 3B Tag Num: SCHW P-BG-1,2
(ft) 4x4x11.5 @ 9.91 in Service:
120 1869 rpm 53 62 20 hp Location:
68
72
1780 rpm 74 --- Motor Data ---
75 Motor Size: 15 hp
100 74
72 Motor Speed: 1800 rpm
68
--- Design Duty Point ---
80 1530 rpm Flow: 440 usgpm
62
Head: 75 ft
Impeller: 9.91 in
60
1280 rpm 15 hp --- System Intersect Data ---
1. System @ 60.0 Hz:
40 1030 rpm 10 hp 440 @ 75, 12.42 hp
2. System @ 51.6 Hz:
7.5 hp 378.4 @ 55.5, 7.91 hp
780 rpm 3. System @ 43.1 Hz:
20 316.6 @ 38.8, 4.63 hp
System
5 hp
4. System @ 34.7 Hz:
534 rpm 3 hp 254.8 @ 25.1, 2.41 hp
0 2 hp
5. System @ 26.3 Hz:
0 100 200 300 400 500 600 193 @ 14.4, 1.05 hp
6. System @ 18.0 Hz:
Water:, spgr= 1.0000 Flow (usgpm) 132.1 @ 6.7603, 0.34 hp

www.armstrongfluidtechnology.com 10/12/2016, Ref. # 446825.1 rev6 Page 5 of 27


Dimensional data (not for construction)
Side view Top view
SCHWP-BG-1,2

Weight: 665 lb
Not to scale
R = minimum lifting clearance required above motor
Units of measure : inches [millimeters]
Coupling guard and flush line (not shown) are supplied
Tolerance of 0.125 inch ( 3 mm) should be used
For certified dimensions, please contact your Armstrong representative
Pump equipped with casing drain plug and inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 ANSI-125 9 8 7.5 0.625
Outlet 4 ANSI-125 9 8 7.5 0.625
*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007


The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed
polyphase motors.

Selected options
Pump Certified Performance Curve [cc]
Casing Wear Ring - Bronze CWR

Additional equipment
Suction Guide: SG-64 (516860-023)

www.armstrongfluidtechnology.com 10/12/2016, Ref. # 446825.1 rev6 Page 6 of 27