Summary

CFM as
System TR per ACH Deh CFM
1 33.5 9061 2643
2 29.9 1260 16800
3 4.9 1224 2200
4 29.6 1093 16700
5 3.2 1203 1213
6 3.1 594 1500
7 3.1 594 1500
8 3.1 594 1500
9 12.8 6800 6800
10 2.4 929 849
11 2.1 700 850
12 4.3 707 2200
13 1.3 687 353
14 3.1 690 1450
15 1.2 560 416
16 7.4 1710 3300
17 1.3 963 248
18 4.5 656 2300
19 4.5 656 2300
20 4.5 656 2300
21 2.3 1257 656
22 1.3 584 446
23 12.5 7175 3289
24 1.4 290 700
JOB : Cameroon
HEAT LOAD CALCULATIONS
SPACE : AHU 01 DATE 04/12/17
TIME 08:57
ENGR Rajesh
DESIGN DATA
AREA: = 2652
HT.OF THE AREA: = 8.2
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF FRESH AIR CHANGE REQUIRED = 2.5 GRAND TOTAL HEAT 33.5
Cfm VENTILATION = 906 DEHUMIDIFIED AIR Cfm 2643
a BLEED -
Cfm/PERSON = 10
NO.OF PEOPLE = 3 NO OF AIR CHANGRES/HR 25 d
b Cfm VENTILATION = 30 AHU CFM AS PER ACH 9061 e
c Cfm VENTILATION IN CAL. = 3000.0 BLOWER PRESSURE IN INCHES 5 f

D.B. W.B. %RH


OUTSIDE 90 85 90 196
INSIDE 75 50 65.0
DIFF. 15 - - 131.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
3000 131 0.12 0.68 32069
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 3* 205 615
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 32684
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 1634
S-E 0 12 0.56 0 ROOM LATENT HEAT 34318
S-W 0 85 0.56 0
SKY LIGHT 0 16 0.56 0 ROOM TOTAL HEAT 112183
SOLAR & TRANSMISSION GAIN
NORTH 0 4 0.34 0 OUTSIDE AIR HEAT
SOUTH 135 16 0.34 734
EAST 0 18 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 107 12 0.34 437 SENS 3000 15 0.88 1.08 42768
N-E 0 10 0.34 0 LAT 3000 131 0.88 0.68 235171
N-W 0 6 0.34 0
S-E 0 18 0.34 0 SUB TOTAL 277939
S-W 0 14 0.34 0 TOTAL 390122
ROOF 0 35 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 11704

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 33.5 401826


AGLS 0 15 1.13 0
PART 135 10 0.4 1 540
CEIL 2652 10 0.4 0 10608 SENSIBLE HEAT FACTOR 0.69
FLOR 0 10 0.4 0 0 SELECTED A.D.P. 44
DEHUMIDIFIED RISE 27.28
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 2643
3000 15 0.12 1.08 5832 TONS AS PER Cfm 6.6

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 3 * 245 735 GRAND TOTAL HEAT(BTU/HR/SQFT.) 151.52
APPL. 1000 * 3.4 1 3400 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 29.36
LIGHTS 3978 * 3.4 1 13525 SQFT/PERSON 884.00
TONS PER SQFT 0.00249
SUB TOTAL 35811 CFM PER SQFT 0.997
LEAK LOSS +SAFETY FACTOR=12.5% 5372 TONS/PERSON 11.16
BLOWER MOTOR GAIN 36682 DEHUMIDIFIED CFM/TON 78.93
ROOM SENSIBLE HEAT 77865 AREA PER TON 79.20
JOB : Cameroon
HEAT LOAD CALCULATIONS
SPACE : AHU -02 DATE 04/12/17
TIME 08:57
ENGR Rajesh
DESIGN DATA
AREA: = 368
HT.OF THE AREA: = 8.2
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF FRESH AIR CHANGE REQUIRED = 2.5 GRAND TOTAL HEAT 29.9
Cfm VENTILATION = 126 DEHUMIDIFIED AIR Cfm 16773
a BLEED -
Cfm/PERSON = 10
NO.OF PEOPLE = 3 NO OF AIR CHANGRES/HR 25 d
b Cfm VENTILATION = 30 AHU CFM AS PER ACH 16800 e
c Cfm VENTILATION IN CAL. = 126.0 BLOWER PRESSURE IN INCHES 5 f

D.B. W.B. %RH GR/LB


OUTSIDE 90 85 90 196
INSIDE 75 50 65.0
DIFF. 15 - - 131.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
126 131 0.12 0.68 1347
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 3* 205 615
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 1962
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 98
S-E 0 12 0.56 0 ROOM LATENT HEAT 2060
S-W 0 85 0.56 0
SKY LIGHT 0 16 0.56 0 ROOM TOTAL HEAT 336831
SOLAR & TRANSMISSION GAIN
NORTH 0 4 0.34 0 OUTSIDE AIR HEAT
SOUTH 183 16 0.34 996
EAST 0 18 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 12 0.34 0 SENS 126 15 0.88 1.08 1796
N-E 0 10 0.34 0 LAT 126 131 0.88 0.68 9877
N-W 0 6 0.34 0
S-E 0 18 0.34 0 SUB TOTAL 11673
S-W 0 14 0.34 0 TOTAL 348505
ROOF 0 35 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 10455

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 29.9 358960


AGLS 0 15 1.13 0
PART 135 10 0.4 1 540
CEIL 368 10 0.4 0 1472 SENSIBLE HEAT FACTOR 0.99
FLOR 10 0.4 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 18.48
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 16773
126 15 0.12 1.08 245 TONS AS PER Cfm 41.9

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 3 * 245 735 GRAND TOTAL HEAT(BTU/HR/SQFT.) 975.43
APPL. 66500 * 3.4 1 226100 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 909.70
LIGHTS 552 * 3.4 1 1877 SQFT/PERSON 122.67
TONS PER SQFT 0.11395
SUB TOTAL 231964 CFM PER SQFT 45.580
LEAK LOSS +SAFETY FACTOR=12.5% 34795 TONS/PERSON 9.97
BLOWER MOTOR GAIN 68012 DEHUMIDIFIED CFM/TON 560.74
ROOM SENSIBLE HEAT 334771 AREA PER TON 12.30
JOB : Cameroon
HEAT LOAD CALCULATIONS
SPACE : AHU -03 DATE 04/12/17
TIME 08:57
ENGR Rajesh
DESIGN DATA
AREA: = 224
HT.OF THE AREA: = 13.12
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF FRESH AIR CHANGE REQUIRED = 2.5 GRAND TOTAL HEAT 4.9
Cfm VENTILATION = 122 DEHUMIDIFIED AIR Cfm 2179
a BLEED -
Cfm/PERSON = 10
NO.OF PEOPLE = 4 NO OF AIR CHANGRES/HR 25 d
b Cfm VENTILATION = 40 AHU CFM AS PER ACH 2200 e
c Cfm VENTILATION IN CAL. = 122.0 BLOWER PRESSURE IN INCHES 5 f

D.B. W.B. %RH GR/LB


OUTSIDE 90 85 90 196
INSIDE 75 50 64.0
DIFF. 15 - - 132.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
122 132 0.12 0.68 1314
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 4* 205 820
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 2134
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 107
S-E 0 12 0.56 0 ROOM LATENT HEAT 2241
S-W 0 85 0.56 0
SKY LIGHT 0 16 0.56 0 ROOM TOTAL HEAT 45726
SOLAR & TRANSMISSION GAIN
NORTH 0 4 0.34 0 OUTSIDE AIR HEAT
SOUTH 178 16 0.34 968
EAST 0 18 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 12 0.34 0 SENS 122 15 0.88 1.08 1739
N-E 0 10 0.34 0 LAT 122 132 0.88 0.68 9637
N-W 0 6 0.34 0
S-E 0 18 0.34 0 SUB TOTAL 11376
S-W 0 14 0.34 0 TOTAL 57102
ROOF 0 35 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 1713

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 4.9 58815


AGLS 0 15 1.13 0
PART 0 10 0.4 0
CEIL 224 10 0.4 0 896 SENSIBLE HEAT FACTOR 0.95
FLOR 0 10 0.4 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 18.48
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 2179
122 15 0.12 1.08 237 TONS AS PER Cfm 5.4

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 5 * 245 1225 GRAND TOTAL HEAT(BTU/HR/SQFT.) 262.57
APPL. 4000 * 3.4 1 13600 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 194.13
LIGHTS 336 * 3.4 1 1142 SQFT/PERSON 56.00
12000 TONS PER SQFT 0.02432
SUB TOTAL 30069 CFM PER SQFT 9.727
LEAK LOSS +SAFETY FACTOR=12.5% 4510 TONS/PERSON 1.23
BLOWER MOTOR GAIN 8906 DEHUMIDIFIED CFM/TON 444.54
ROOM SENSIBLE HEAT 43486 AREA PER TON 45.70