Refrigerant Piping Design

Design Guideline Summary

Device Connection Limitations


A single-zone four-way ceiling cassette system consists of one outdoor unit and one indoor unit. One of the most critical elements of a
single-zone four-way ceiling cassette system is the refrigerant piping. The table below lists pipe length limits that must be followed in the
design of a single-zone four-way ceiling cassette refrigerant pipe system:
Ceiling-Concealed Duct (High Static) System Engineering Manual

Table 34: Single-Zone Four-Way Ceiling Cassette Refrigerant Piping System Limitations.
System Model Name LC187HV, LC247HV LC367HV, LC427HV

Pipe Length Longest total equivalent piping length 164 feet 246 feet
(ELF = Equivalent Length of Pipe) Distance between fittings and indoor or outdoor units 20 inches 20 inches
Elevation If outdoor unit is above indoor unit 98 feet 98 feet
(All Elevation Limitations are
Measured in Actual Feet) If outdoor unit is below indoor unit 98 feet 98 feet

DFS System Layout


Figure 34: Typical LC187HV and LC247HV System Layout.
Unit = Feet
Max Length = A
Max Elevation = B Outdoor unit
Indoor unit

164 164
A
A
98

B
B
98

Indoor unit

Outdoor unit
Figure 35: Typical LC347HV and LC427HV System Layout.
Unit = Feet
Max Length = A
Max Elevation = B Outdoor unit
Indoor unit

246 246
A
A
98

B
B
98

Indoor unit
Outdoor unit

Due to our policy of continuous product innovation, some specifications may change without notification.
54 | Duct (High Static) LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.