Sie sind auf Seite 1von 17

This document is the property of Larsen & Toubro Limited, ECC Division - EDRC and must not be passed

on to any third person or firm not authorised by us, nor be copied/made use of in

30.03.11 A FOR APPROVAL RVS RSA AKL


DATE REV. NO. DESCRIPTION Designed Checked Approved
full or part by such person or firm without our prior permission writing

REVISIONS

LARSEN & TOUBRO LIMITED


ECC Division - EDRC

CLIENT : CONSULTANT:

RAJASTAHAN RAJYA VIDUT PRASARAN


NIGAM LIMITED

PROJECT :
Establishing of 2X160MVA, 220/132KV GIS Substation (including of IEC 61850 based automation
system) at existing 132KV Substation along with terminal bays including Equipments / materials,
Erection , Testing & Commisioning)

SUPPLIER / CONTRACTOR:

--
JOB No.
TOTAL NO. OF PAGES TITLE :
NAME SIGN DATE
DESIGNED RVS 28.03.11

CHECKED RSA 30.03.11


220/132kV Manasarovar GIS - 220V Battery sizing calculation

APPROVED AKL 30.03.11


CODE REV.
DOC. No. O 1 0 2 2 1 - E - I S - C B - D C - 0 1 0 7
A

RELEASED FOR PRELIMINARY TENDER INFORMATION P APPROVAL CONSTRUCTION


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Establishing of 2X160MVA , 220/132KV GIS Substation DOCUMENT NO


(including of IEC 61850 based automation system) at existing
PROJECT
132KV Substation along with terminal bays including
Equipments / materials, Erection , Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED APPROVED DATE


TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA AKL 30.03.11

1.0 GENERAL
1.1 The Station 220V DC Auxiliary Power supply shall consist of two Nos. 100% rated 220V DC Battery
bank and two Nos. Float cum Boost Charger

1.2 References
Technical Specification
IEEE Recommended Pratice for Sizing Lead-Acid Batteries IEEE Std 485-1997
GIS Vendor HYOSUNG

2.0 SIZING CRITERIA


Battery Sizing is based on the following criteria as per Technical Specification & IEEE Std. 485-1997

2.1 Duty Cycle


The duration of Continuous Load is considered as 3 hours as per Specification (VOLUME II PART III OF III, SECTION -IX-
a)
BATTERY SYSTEM, CLAUSE 1.1.3)

Emergency Load requirement is considered as 1 hour as per specification (VOLUME II PART III OF III, SECTION -IX-
b)
BATTERY SYSTEM, CLAUSE 1.1.3)

c) Worst contingency for assessing the Momentary Loads takes into consideration the following assumptions
for 1 minute (VOLUME II PART III OF III, SECTION -IX-BATTERY SYSTEM, CLAUSE 1.1.3)

1) Due to the fault on either 220kV or 132kV Bus, simultaneous tripping of all 220kV or 132kV breakers considered

2.2 Temperature Correction Factor: Minimum Temperature is assumed as 5C and the corresponding
Temperature correction factor is 1.19

2.3 Design Margin is 1.1 ( as per IEEE Std. 485-1997, Cl. 6.2.3)

2.4 Ageing Factor is 1.25 ( as per IEEE Std. 485-1997, Cl. 6.2.2)

Page3of17
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA , 220/132KV GIS Substation DOCUMENT NO
(including of IEC 61850 based automation system) at existing
PROJECT
132KV Substation along with terminal bays including O10221-E-IS-CB-DC-0107
Equipments / materials, Erection , Testing & Commisioning)
PREPARED CHECKED APPROVED DATE
TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA AKL 30.03.11

CALCULATION OF NUMBER OF CELLS

Design considerations:

1 System Nominal voltage = 220 Volt

2 System Maximum Voltage = 242 Volt

3 System Minimum Voltage = 198 Volt


(VOLUME II PART III OF III, SECTION -IX-
BATTERY SYSTEM, CLAUSE 1.1.3)
4 Battery nominal voltage = 2 Volt

5 End cell voltage = 1.85 Volt

6 Float charging Voltage (Max) = 2.27 Volt

7 No.of cells based on Minimum system voltage : Minimum allowable battery voltage
End Cell voltage of the cell

= 198/1.85

= 107.03 Nos. -------(1)

No.of cells based on Maximum system voltage : Maximum allowable battery voltage
Float charging voltage
= 242/2.27

= 106.61 Nos. -------(2)

From case (1) and (2)


No. of cells considered to meet voltage limits = 107 Nos.

Selecting 107 cells the final voltage limits are as follows.

Minimum System Voltage = 107*1.85 = 197.95 Volt

Maximum System Voltage = 107*2.27 = 242.89 Volt

Since the derived voltage levels are within the operating limits,107 cells considered are adequate
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS
Substation (including of IEC 61850 based DOC NO DATE
automation system) at existing 132KV
PROJECT :
Substation along with terminal bays including
Equipments / materials, Erection , Testing & O10221-E-IS-CB-DC-0107 30.03.11
Commisioning)
220/132kV Manasarovar GIS - 220V Battery PREPARED CHECKED APPROVED
TITLE :
sizing calculation RVS RSA AKL
No. of relay
Continuous Total cont.
Description /Eqpt per
Load per relay Load
feeder
132kV System:
132kV Feeder control &
A
relay panel - Type-A&B SAS - FCRA
1 Multifunction panel meter 1 10 10
2 Main-I distance/Differential protection with back up feature 1 45 45
3 Bay control unit 1 45 45
4 36 Window Annunciator 1 54 54
5 Trip Relay Supervision 2 6 12
6 Trip Circuit Supervision Relay 2 8.5 17
7 DC super vision relay 2 6 12
Total load 195

B 132kV Bus coupler control & relay panel


1 Multifunction panel meter 1 10 10
2 Directional Over Current & Earth Fault Protection 1 45 45
3 36 Window Annunciator 1 54 54
4 Bay control unit 1 45 45
5 Trip Relay Supervision 2 6 12
6 Trip Circuit Supervision Relay 2 8.5 17
7 DC super vision relay 2 6 12
Total load 195
C 220kV Transformer control panel (132kV side) SAS-TLCB
1 Multifunction panel meter 1 10 10
2 Bay Control Unit 1 45 45
3 36 Window Annunciator 1 54 54
4 Trip circuit Supervision Relay 2 8.5 17
Total load 126
D 220kV Transformer relay panel (132kV side) SAS TLRB
1 Numerical Relay for LBB Protection 1 45 45
2 DC Supervision Relay 2 6 12
3 Trip Relay Supervision 2 6 12
Total load 69
E 220kV Transformer control panel (220kV side) SAS THCB
1 Multifunction panel meter 1 10 10
2 Bay Control Unit 1 45 45
3 36 Window Annunciation 1 54 54
4 Trip circuit Supervision Relay 6 8.5 51
Total load 150
F 220kV Transformer relay panel (for HV & MV) SAS THRB
1 Differential protection Main I 1 45 45
2 Differential protection Main II 1 45 45
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS
Substation (including of IEC 61850 based DOC NO DATE
automation system) at existing 132KV
PROJECT :
Substation along with terminal bays including
Equipments / materials, Erection , Testing & O10221-E-IS-CB-DC-0107 30.03.11
Commisioning)
220/132kV Manasarovar GIS - 220V Battery PREPARED CHECKED APPROVED
TITLE :
sizing calculation RVS RSA AKL
No. of relay
Continuous Total cont.
Description /Eqpt per
Load per relay Load
feeder
3 Directional Over Current & Earth Fault Protection 2 45 90
4 Numerical Relay for LBB Protection 1 45 45
5 DC Supervision Relay 2 6 12
6 Trip Relay Supervision 2 6 12
Total load 249
G 220kV Feeder control panel SAS FCB
1 Multifunction panel meter 1 10 10
2 Bay control unit 1 45 45
3 36 way Annunciator 1 54 54
4 Trip Relay Supervision 2 6 12
5 Trip Circuit Supervision Relay 6 8.5 51
Total load 117
H 220kV Feeder relay panel SAS FRB
1 Main-I distance protection with back up feature 1 45 45
2 Line Differential Protection 1 45 45
3 Numerical Relay for LBB Protection 1 45 45
4 Back up protection with auto reclose 1 11 11
5 Trip Relay Supervision 2 6 12
6 DC super vision relay 2 6 12
Total load 170
I 220kV Bus coupler control panel SAS BCCB
1 Multifunction panel meter 1 10 10
2 Bay control unit 1 45 45
3 36 Window Annunciator 1 54 54
4 Trip Circuit Supervision Relay 6 8.5 51
Total load 160
J 220kV Bus coupler Relay panel SAS-BCRB
1 Directional Over Current & Earth Fault Protection 1 45 45
2 Numerical Relay for LBB Protection 1 45 45
3 Trip Relay Supervision 2 6 12
4 DC supervision relay 2 6 12
Total load 114
K 132kV Bus protn relay panel SAS BBRA
1 Busbar Differential protection - 87BB1&2 1 130 130
2 12 Window Annunciator 1 18 18
3 Bay Unit 9 45 405
4 DC Supervision Relay 2 6 12
Total load 565
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS
Substation (including of IEC 61850 based DOC NO DATE
automation system) at existing 132KV
PROJECT :
Substation along with terminal bays including
Equipments / materials, Erection , Testing & O10221-E-IS-CB-DC-0107 30.03.11
Commisioning)
220/132kV Manasarovar GIS - 220V Battery PREPARED CHECKED APPROVED
TITLE :
sizing calculation RVS RSA AKL
No. of relay
Continuous Total cont.
Description /Eqpt per
Load per relay Load
feeder
L 220kV Bus protn relay panel SAS BBRB
1 Busbar Differential protection - 87BB1&2 1 130 130
2 Bay Unit 7 45 315
3 12 Window Annunciator 1 18 18
4 DC Supervision Relay 2 6 12
Total load 475
132kV LCC
M
1 Semaphore Indicator for Iso & CB 4 2.5 10
2 Semaphore Indicator for E/S 3 2.5 7.5
Total load 17.5
220kV LCC
N
1 Semaphore Indicator for Iso & CB 4 2.5 10
2 Semaphore Indicator for E/S 3 2.5 7.5
Total load 17.5
O SAS & Auxiliary System
1 DC Fail Supervision 6 6 36
2 Ethernet Switch 19 36 684
Total load 720

P Substation Auxiliary Monitoring Panel SAS -SAMP


1 BCU 1 45 45
2 36 Window Annunciator 1 54 54
Total load 99
Q DC for Indicating Lamps
1 Lamps for ACDB & DCDB 16 2.5 40
2 Multifunction Meter for ACDB 2 10 20
3 Multifunction Meter for Main Switchboard 2 10 20
4 Multifunction Meter for Main AC LDB 2 10 20
5 Multifunction Meter for DG Incoming Board 2 10 20
Total load 120

R Inverter Loads
1 Station HMI (including monitor) 2 375 750
2 Station HMI - Hot stand by 1 375 375
3 DR Work station 1 375 375
4 Gateway PC 2 375 750
5 Laser Printer (When Active) 1 630 630
6 Dot Matrix Printer 2 40 80
6 HMI view node 1 375 375
7 LVS 1 500 500
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS
Substation (including of IEC 61850 based DOC NO DATE
automation system) at existing 132KV
PROJECT :
Substation along with terminal bays including
Equipments / materials, Erection , Testing & O10221-E-IS-CB-DC-0107 30.03.11
Commisioning)
220/132kV Manasarovar GIS - 220V Battery PREPARED CHECKED APPROVED
TITLE :
sizing calculation RVS RSA AKL
No. of relay
Continuous Total cont.
Description /Eqpt per
Load per relay Load
feeder
Total load 3835
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS Substation
(including of IEC 61850 based automation system) at DOCUMENT NO
PROJECT existing 132KV Substation along with terminal bays
including Equipments / materials, Erection , Testing &
Commisioning) O10221-E-IS-CB-DC-0107
220/132kV Manasarovar GIS - 220V Battery sizing PREPARED CHECKED APPROVED
TITLE
calculation RVS RSA AKL

Momentaty Load Calculation

132kV Tripping Loads

No.of Trip Coils / 132kV Breaker = 2 (2 No. per Bay)


Power Consumed by each trip coil = 2860 W (Hysoung G.I.S GTP)
Maximum No. of breakers, that will operate for busbar
= 9
protection
Momentary tripping load per 132kV CB = 5720 W
Net tripping load for all 132kV CB considered = 51480 W (1)

Master trip relay (150W each) - 2 x 9 Nos. = 2700 W (2)

Sub-Total Tripping load = 54180 W (1 + 2)


= 246.27 A
Momentary Tripping Load
273.64 A
(Considering 90% of normal system voltage)

220 kV Tripping Loads

No.of Trip Coils / 220kV Breaker = 6 (2 No. per pole)


Power Consumed by each trip coil = 2200 W (Hysoung G.I.S GTP)
Maximum No. of breakers, that will operate for busbar
= 7
protection
Momentary tripping load per 220kV CB = 13200 W
Net tripping load for all 220kV CB considered = 92400 W (1)

Master trip relay (150W each) - 2 x 7 Nos. = 2100 W (2)

Sub-Total Tripping load = 94500 W (1 + 2)


= 429.55 A
Momentary Tripping Load
477.27 A
(Considering 90% of normal system voltage)

Max of 132KV & 220KV Tripping Loads

Max of tripping load = 94500 W


= ### A
O

-0107
DATE
30.03.11

er Bay)
g G.I.S GTP)

er pole)
g G.I.S GTP)
LARSEN & TOUBRO LIMITED

ECC Division - EDRC (Electrical)


Establishing of 2X160MVA, 220/132KV GIS Substation (including of DOCUMENT NO
IEC 61850 based automation system) at existing 132KV Substation
PROJECT
along with terminal bays including Equipments / materials, Erection ,
Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED APPROVED DATE


TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA AKL 30.03.11

Continuous Total
No of
S. No Description Load / feeder Continuous
Feeders
(Watts) Load (Watts)

CONTINUOUS LOAD

Protection Panel

A) 132KV System

i) 132KV Feeder Control & Relay Panel A & B 6 195 1170

ii) 132KV Bus Coupler Control & relay Panel 1 195 195

iii) 132KV Bus bar protection Panel 1 565 565

iv) 220kV Transformer Control Panel (132kV Side) 2 126 252

v) 220kV Transformer Protection Panel (132kV Side) 2 69 138

vii) LCC for 132KV System 9 17.5 157.5

B) 220kV Sytem

i) 220kV Transformer Control Panel (220kV Side) 2 150 300

ii) 220kV Transformer Relay Panel (220kV Side) 2 249 498

iii) 220kV Feeder Control Panel 4 117 468

iv) 220kV Feeder Relay Panel 4 170 680

v) 220kV Bus Coupler Control Panel 1 160 160

vi) 220kV Bus Coupler Relay Panel 1 114 114

vii) 220kV Bus Protection Relay Panel 1 475 475

viii) LCC for 220KV System 7 17.5 122.5

C) SAS & Auxiliary Loads 1 720 720

D) Substation Auxiliary Monitoring Panel 1 99 99

E) Inverter Loads 1 3835 3835


LARSEN & TOUBRO LIMITED

ECC Division - EDRC (Electrical)


Establishing of 2X160MVA, 220/132KV GIS Substation (including of DOCUMENT NO
IEC 61850 based automation system) at existing 132KV Substation
PROJECT
along with terminal bays including Equipments / materials, Erection ,
Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED APPROVED DATE


TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA AKL 30.03.11

F) LT auxiliary system 1 120 120

Total Continous Load 10069 W

DC Load Estimation

a. Total Continuous load 10069 W

= (10069/220) A

45.77 A

Considering 90% of normal cell voltage 50.85 A

Momentary load

Momentary Tripping Load considered 477.27 A

Emergency Lighting Load

No. of GLS Lamps in Control Building & GIS hall 20

Total Emergency lighting considered for switchyard 2000.00 W

Considering 90% of nominal system voltage 10.10 A

Load Cycle

Duration Load Description

Momentary Tripping load + Continuous load +


1 min 538.23 A
Emergency lighting load

59 min Continuous load + Emergency lighting load 60.95 A

120 min Continuous load 50.85 A

Note:

Maximum loads have been considered among various manufacturers for battery sizing
LARSEN & TOUBRO LIMITED

ECC Division - EDRC (Electrical)


Establishing of 2X160MVA, 220/132KV GIS Substation (including of DOCUMENT NO
IEC 61850 based automation system) at existing 132KV Substation
PROJECT
along with terminal bays including Equipments / materials, Erection ,
Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED APPROVED DATE


TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA AKL 30.03.11
LOAD CYCLE

750
700
650
600
550
500
450 538.23
400
350
300
250
200 60.95
150 50.85
100
50
0
0 20 40 60 80 100 120 140 160 180 200
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS Substation (including of DOCUMENT NO
IEC 61850 based automation system) at existing 132KV Substation
PROJECT
along with terminal bays including Equipments / materials, Erection ,
Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED
TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA

CELL SIZING CALCULATION

1. NOMINAL SYSTEM VOLTAGE (Vn) = 220 Volts


2. HIGHEST SYSTEM VOLTAGE (Vh) = 242 Volts
3. LOWEST SYSTEM VOLTAGE AT END OF DUTY CYCL (Vl) = 198 Volts
4. END CELL VOLTAGE = 1.85 Volts
5. NO. OF CELLS = 107 Nos

CAPACITY REQUIRED SECTION S


DURATION (AH)
PERIOD LOAD (A) CHANGE IN RATING FACTOR
OF PERIOD TIME TO END OF SECTION
(1) (A1) LOAD (A) AT T Min
(Mins) POS VALUE
Rate(Kt)

SECTION-1- FIRST PERIOD ONLY


1 A1=538.23 A1-0 =538.23 M1= 1 T=M1=1 0.5 269.11
TOTAL 269.11
SECTION-2- FIRST TWO PERIOD ONLY
1 A1=538.23 A1-0 =538.23 M1= 1 T=M1+M2=60 1.88 1011.87
A2-A1=
2 A2=60.95 M2= 59 T=M2=59 1.86
-477.27
TOTAL 124.14
SECTION-3- FIRST THREE PERIOD ONLY
1 A1=538.23 A1-0 =538.23 M1= 1 T=M1+M2+M3=180 4.10 2206.73
A2-A1=
2 A2=60.95 M2= 59 T=M2+M3=179 4.08
-477.27
A3-A2=
3 A3=50.85 M3= 120 T=M3=120 3.07
-10.10
TOTAL 228.45

Maximum section size = 269.11 Ah

Required Size = Maximum section Size *Design margin* Ageing factor*


Temperature correction factor

Battery Size Calculated = 440 Ah (269.11*1.10*1.25*1.19)


Battery Size Chosen = 440 Ah
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Establishing of 2X160MVA, 220/132KV GIS Substation (including of DOCUMENT NO
IEC 61850 based automation system) at existing 132KV Substation
PROJECT
along with terminal bays including Equipments / materials, Erection ,
Testing & Commisioning) O10221-E-IS-CB-DC-0107

PREPARED CHECKED
TITLE 220/132kV Manasarovar GIS - 220V Battery sizing calculation
RVS RSA
FLOAT CUM BOOST CHARGER SIZING CALCULATION

A) ON LINE FLOAT CHARGER RATING


Float Charger Rating = 1.2 x Average DC Load
Average DC Load = Area of Load Cycle / Time of Load Cycle
= 56.872 Amps
Float Charger rating calculated = 68.25 Amps
Float Charger rating chosen = 70 Amps

B) OFF LINE BOOST CHARGER RATING


Boost Charger Rating = 20% of Ah Rating of battery
= 0.2 * 440 Amps
Boost Charger rating calculated = 105.6 Amps (With Design Margin 1.20)
Boost Charger rating chosen = 110 Amps
Charager Rating Chosen = 70/110 Amps

CONCLUSION
No.of Battery Cells = 107 Nos.
Ah Capacity = 440 Ah.
Float cum Boost Charger rating = 70/110 Amps.
DOCUMENT NO

O10221-E-IS-CB-DC-0107

APPROVED
AKL

Volts
Volts
Volts

REQUIRED SECTION SIZE


(AH)

NEG VALUE

ON-1- FIRST PERIOD ONLY


-

2- FIRST TWO PERIOD ONLY


-

-887.73

- FIRST THREE PERIOD ONLY

-1947.27

-31.01

(269.11*1.10*1.25*1.19)
DOCUMENT NO

O10221-E-IS-CB-DC-0107

APPROVED
AKL

(With Design Margin 1.20)