Sie sind auf Seite 1von 3

TEST REPORT

IEC 61727
Photovoltaic (PV) systems
Characteristics of the utility interface

Report reference number .............. : PV130105N008_1


Date of issue .......................... ...: 2013-02-22
Total number of pages ........... ...: 132 pages

Testing laboratory name ............... : Bureau Veritas Shenzhen


Co.,
Ltd., Dongguan Branch
Address ............................................ : No.34,Chenwulu Section,
Guantai Rd., Houjie Town,
Dongguan City,Guangdong
Province, China.

Applicant's name............................ : Huawei Technologies Co., Ltd.


Address ............................................ : Administration Building, Headquarters of Huawei Technologies Co.,
Ltd., Bantian, Longgang District, Shenzhen, 518129, P.R.C.

Test specification
Standard ........................................... : IEC 61727:2004-12
EN 61727:1995
DIN EN 61727:1996

Certificate ........................................ : Certificate of compliance


Test report form number .................. : IEC 61727
Master TRF ...................................... : Bureau Veritas Consumer Products Services Germany GmbH

Test item description ..................... : SOLAR INVERTER


Trademark ........................................ :

Model / Type .................................... : SUN2000-8KTL, SUN2000-10KTL, SUN2000-12KTL,


SUN2000-15KTL, SUN2000-17KTL, SUN2000-20KTL
Ratings ............................................ : SUN2000- SUN2000- SUN2000- SUN2000- SUN2000- SUN2000-
8KTL 10KTL 12KTL 15KTL 17KTL 20KTL
MPP DC voltage range [V] ............... : 320-800 380-800 400-800 480-800
Input DC voltage range [V] ............... : Operation voltage range: 250-850, Max. Voltage: 1000
Input DC current [A] ......................... : 18/18 18/18/18
Output AC voltage [V] ...................... : 400, 3W+N+PE
Output AC current [A] ....................... : 12,8 16 19,2 24 27,2 32
Output power [VA] ............................ : 8000 10000 12000 15000 17000 20000

Copyright Bureau Veritas Consumer Products Services Germany GmbH


Page 2 of 132 Report No.: PV130105N008_1

Testing Location ............................ : Huawei Technologies Co., Ltd.


Address ............................................ : No.901, Tanglu Road, Pudong, Shanghai, 201206, P.R.China

Tested by
Corney Zhang
(name and signature) ....................... :

Approved by
(name and signature) ....................... : Ted Wu

Manufacturers name ..................... : Huawei Technologies Co., Ltd.


Factory address ............................... : No. 2 City Avenue, Songshan Lake Sci. & Tech. Industry Park,
523808 Dongguan, Peoples Republic of China.

Document History
Date Internal reference Modification / Change / Status Revision
2013-01-14 Corney Zhang Initial report was written 0
2013-02-22 Corney Zhang Corrected the output AC current on page 1 for Model 1
SUN2000017KTL to 27,2A.
Supplementary information:

Copyright Bureau Veritas Consumer Products Services Germany GmbH


Page 3 of 132 Report No.: PV130105N008_1

Test items particulars

Equipment mobility ........................... : Permanent connection


Operating condition .......................... : Continuous
Class of equipment .......................... : Class I
Protection against ingress of water .. : IP65 according to EN 60529
Mass of equipment [kg] .................... : SUN2000-8KTL, SUN2000-10KTL, SUN2000-12KTL: 40kg,
SUN2000-15KTL, SUN2000-17KTL, SUN2000-20KTL: 48kg

Test case verdicts


Test case does not apply
to the test object ............................... : N/A
Test item does meet
the requirement ................................ : P(ass)
Test item does not meet
the requirement ................................ : F(ail)

Testing
Date of receipt of test item ............... : 2012-11-27
Date(s) of performance of test ......... : 2012-11-27 to 2013-01-05

General remarks:
The test result presented in this report relate only to the object(s) tested.
This report must not be reproduced in part or in full without the written approval of the issuing testing
laboratory.
(see Annex #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a comma is used as the decimal separator.

The IEC61727does not provide any limits of accuracy for the utility voltage and frequency measurement of the
PV-system. Therefore the values for tolerances given in EN 50438, Table 2 are used.
Tolerances on trip values tabel 2 EN50438:
- Voltage: +/- 1% of the nominal voltage;
- Frequency: +/- 0,5% of the nominal frequency
- Clearance time: +/- 10%

This Test Report consists of the following documents:


1. Test Results
2. Annex No. 1 EMC Test Report
3. Annex No. 2 Pictures of the unit
4. Annex No. 3 Test equipment list

Copyright Bureau Veritas Consumer Products Services Germany GmbH

Das könnte Ihnen auch gefallen