Sie sind auf Seite 1von 6

i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0

Available online at www.sciencedirect.com

ScienceDirect
w w w . i i fi i r . o r g

journal homepage: www.elsevier.com/locate/ijrefrig

Performance improvement potentials of R1234yf


mobile air conditioning system

Zhaogang Qi*
Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, No. 800, Dongchuan Road,
Shanghai 200240, PR China

article info abstract

Article history: In this paper, the performance improvement potentials of R1234yf mobile air conditioning
Received 13 December 2014 (MAC) system under various operation conditions were studied based on thermodynamic
Received in revised form cycle analysis. The effects of superheat at evaporator outlet, subcooling at condenser outlet
16 March 2015 and compressor efficiencies on system performance were analyzed. It was found that
Accepted 17 March 2015 superheat was few benefits for both system coefficient of performance (COP) and cooling
Available online 24 March 2015 capacity. Increasing subcooling from 1K to 10K at condenser outlet, system cooling ca-
pacity and COP could be improved by 15% if compressor consumption power was fixed. The
Keywords: isentropic efficiency of the compressor was a key factor in system COP improvement. It
R1234yf was concluded that adding an internal heat exchanger and improving compressor effi-
Improvement potential ciencies would be good options for the future R1234yf MAC system enhancement.
Superheat 2015 Elsevier Ltd and IIR. All rights reserved.
Subcooling
Compressor efficiency

 lioration des performances de syste


Potentiels d'ame  me de
conditionnement d'air mobile fonctionnant avec le R1234yf
Mots-cles : R1234yf ; Potentiel dame
lioration ; Surchauffe ; Sous-refroidissement ; Efficacite
 du compresseur

in all vehicles in Europe from 2017 (Environment Committee,


1. Introduction 2006). For that requirement, there are several candidates
such as CO2 (Lorentzen, 1994), R152a (Ghodbane, 1999),
The car manufacturers are encountering more and more R1234yf and so on. So far, R1234yf is showing a promising
pressures from the legislature not only on energy consump- future in MAC systems and attracting more attentions by the
tion but also on environmental concern. The most urgent industry and academic because its thermal and physical
issue for mobile air conditioning (MAC) industry is to find the properties are very similar with R134a (Akasaka et al., 2010). In
suitable alternative refrigerant for R134a which will be banned order to improve R1234yf system performance to approach

* Tel.: 86 21 34206259; fax: 86 21 34206814.


E-mail address: qizhaogang@sjtu.edu.cn.
http://dx.doi.org/10.1016/j.ijrefrig.2015.03.019
0140-7007/ 2015 Elsevier Ltd and IIR. All rights reserved.
36 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0

and COP were lower than that of R134a system. The


Nomenclature compressor volumetric efficiency of R1234yf was about 5%
lower because of higher frictional pressure drop in suction
COP coefficient of performance ()
tubes. An internal heat exchanger could improve system
Disp compressor displacement (m3 rev1)
COP and cooling capacity significantly comparing with
h enthalpy (kJ kg1)
R134a system in a drop-in experimental study (Navarro-
m_ mass flow rate (kg s1)
Esbr et al., 2013b). Wang (2014) did a comprehensive liter-
Q cooling capacity (kW)
ature review on R1234yf and its system application and
RPM compressor speed (rev min1)
pointed out some future research topics on R1234yf perfor-
W consumption power (kW)
mance enhancement.
Greek letters In this paper, the R1234yf MAC system performance
r density (kg m3) improvement potentials would be discussed based on the
h efficiency () simplified thermodynamic cycle analysis. The effect of su-
perheat at evaporator outlet, subcooling at condenser outlet
subscripts
and compressor performance on system COP and cooling ca-
1,2,20 ,3,4 state points
pacity would be mainly focused.
comp compressor
evap evaporator
isen isentropic
vol volumetric
2. MAC thermodynamic cycle analysis

2.1. Basic MAC cycle


R134a system, many researches were conducted in the fun-
damentals and system applications.
In general, mobile air conditioning system is a vapor
Many researchers' results concluded that evaporation heat
compression cycle driven by engine through clutch or electric
transfer coefficient of R1234yf is approximately the same as
motor. The simplified thermodynamic cycle was shown as
that of R134a (Park and Jung, 2010; Saitoh et al., 2011; Lu et al.,
Fig. 1 which was composed of four processes. There were
2013). Col et al. (2010) and Longo's and Zilio's (2013) experi-
some assumptions in the cycle as the following:
mental result revealed that the condensation heat transfer
coefficient of R1234yf was lower than that of R134a by 12~35%
 The superheat at evaporator outlet and subcooling at
depending on the test conditions and heat exchanger. Wang
condenser outlet were 5K if it was not a variable,
(2013) summarized the recent research advances on the two-
respectively.
phase heat transfer characteristics of R1234yf including in-
 The pressure drops in evaporator, condenser and connec-
tube convective boiling and in-tube condensation. For the
tion tubes were ignored.
evaporator and condenser in MAC system, the overall thermal
 The throttle process in expansion valve was isenthalpic.
resistance is dominated by air side. On these basis, redesign
 The compressor had a constant displacement
and performance improvement of MACs heat exchangers
(120  106m3 rev1).
could be easier in the next step.
 The compressor efficiencies changed with vehicle opera-
Mathur (2010a; 2010b; 2011a; 2011b) performed a thor-
tion conditions.
ough R1234yf drop-in experiments in R134a MAC system.
The parallel flow condenser, laminated plate evaporator and
internal heat exchanger were selected for the system coef-
ficient of performance (COP) and cooling capacity compen-
sation. Zilio et al. (2011) carried out a numerical simulation
on R1234yf MAC system. The simulation results showed
that if condenser and evaporator heat transfer area could be
augmented by 20% and 10% respectively, R1234yf system
could show a better COP than the baseline R134a system at
the same cooling capacity. Lee's and Jung's (2012) experi-
mental results showed COP and cooling capacity of R1234yf
MAC system were lower by 0.8~2.7% and up to 4.0% than
that of R134a system with tube-in-tube condenser and
evaporator, respectively. Qi (2013) experimentally studied
the performance differences in laminated plate evaporator
and minichannel evaporator using R134a and R1234yf as
working fluid. The test results showed that minichannel
tube parallel flow evaporator was a good option in R1234yf
drop-in replacement. Navarro-Esbr et al. (2013a) set up an
R1234yf MAC system for hybrid electric vehicle. The Fig. 1 e R1234yf basic thermodynamic cycle in logPeh
experimental data showed that both cooling capacity diagram.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0 37

Table 1 e MAC operation conditions.


Idle City High speed
Condenser air side 35  C 40  C 45  C
temperature
Compressor RPM: 800 RPM: 1800 RPM: 3000
rpm, hisen rpm, hisen rpm, hisen
and hvol:0.75 and hvol:0.65 and hvol:0.55

Table 2 e Variables in the present study.


Variables (Unit) Range
Superheat (K) 1~10
Subcooling (K) 1~10
Compressor volumetric efficiency () 0.55~0.95
Compressor isentropic efficiency () 0.55~0.95

 The evaporation temperature was constant (5  C) for all Fig. 2 e The effect of superheat on system performance and
vehicle operation conditions and the temperature differ- COP under idle condition.
ence between condensation and ambient air was constant
(20K).
previous assumptions, evaporation temperature was constant
 The above parameters could be a variable during the
although operation conditions changed and the condensation
following analysis.
temperature would change with air temperature at condenser
outside. In the present study, the superheat, subcooling and
The cooling capacity, compressor consumption power,
compressor performance would be set as variables as shown
system COP and refrigerant mass flow rate were calculated by
in Table 2. But only one of them was a variable at one time and
Eqs. (1)e(4):
the others were kept constant under the specific operation
Qevap m_  h1  h4 (1) condition.

Wcomp m_  h2'  h1 =hisen (2)


3. Results and discussion
Qevap
COP (3)
Wcomp The theoretical R1234yf system performance was compared
with that of R134a system as shown in Table 3. It was implied
RPM that both system COP and cooling capacity of R1234yf system
m_  Dispcomp  r1  hvol (4)
60 were smaller than that of R134a for all the vehicle operation
All the above equations and calculations were carried out conditions. The gap ranges of system COP, cooling capacity
using Engineering Equation Solver (EES, F-Chart Software, and compressor consumption power were 4.8~7.0%, 7.7~10.6%
2014). The thermodynamic properties of R1234yf and R134a and 3.1~3.8%, respectively. The following discussions were
were from the data provided by Richter et al. (2011) and explained from the effect of superheat, subcooling and
Tillner-Roth and Baehr (1994), respectively. compressor performance on the system performance
improvement potentials.
2.2. Vehicle operation conditions and analysis variables
3.1. Effect of superheat and subcooling
MAC system can operate under a wide range ambient condi-
tions. Three typical ambient and operation conditions were During the calculation, the subcooling and compressor per-
selected as idle (low ambient air temperature), city (moderate formance were fixed when superheat was changed. As shown
ambient air temperature) and high speed (high ambient air in Fig. 2 and Fig. 3, superheat has little influence on system
temperature) conditions shown in Table 1(Qi, 2008). As the performance. The system COP and cooling capacity were only

Table 3 e R1234yf and R134a MAC System performances under three typical conditions.
Idle City High speed
R1234yf R134a Deviation (%) R1234yf R134a Deviation (%) R1234yf R134a Deviation (%)
Qevap(kW) 2.488 2.696 7.7 4.503 4.952 9.1 5.852 6.544 10.6
Wcomp (kW) 0.802 0.828 3.1 1.946 2.015 3.4 3.466 3.604 3.8
COP() 3.100 3.257 4.8 2.314 2.457 5.8 1.689 1.816 7.0
38 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0

Fig. 3 e The effect of superheat on compressor power and Fig. 5 e The effect of subcooling on compressor power and
refrigerant mass flow rate under idle condition. refrigerant quality at evaporator inlet under city condition.

increased by 2.6% and 3.7% with the superheat increasing to 10K if the compressor power was fixed as shown in Fig. 4
from 1K to 10K, respectively. It was shown in Fig. 2 that it under city condition. Comparing to R134a system, it would
would be almost impossible for R1234yf system to reach the be possible to approach the same system COP and cooling
same COP and cooling capacity only by increasing superheat capacity with subcooling increasing. For example, R1234yf
comparing with that of R134a system. The increasing super- system with 7K subcooling almost had the same COP (2.4) as
heat reduced the refrigerant mass flow slightly with the fixed R134a system with 3K subcooling. R1234yf system with 10K
compressor efficiencies and state points because of lower subcooling almost had the same cooling capacity (4.8 kW) as
vapor density with higher refrigerant vapor temperature as R134a system with 3K subcooling.
shown in Fig. 3. On the other hand, R1234yf system needs Refrigerant quality at evaporator inlet was decreased with
higher refrigerant mass flow because of smaller latent heat subcooling increasing from 1K to 10K which would result in a
(Akasaka et al., 2010). Higher superheat also would bring a larger enthalpy difference in evaporator as Fig. 5. It seemed
potential deterioration to compressor discharge temperature that 10K subcooling was not sufficient because the quality was
and lubricant oil. still a little large (0.39). More subcooling was needed and then
A suitable subcooling at condenser outlet will guarantee placing an internal heat exchanger at evaporator outlet and
the liquid state at expansion valve inlet and a proper refrig- condenser outlet would be a good option to compensate the
erant quality at evaporator inlet. The COP and cooling capacity performance decline (Mathur, 2011a; Cho et al., 2013).
were increased by 15.0% with subcooling increasing from 1K

Fig. 6 e The effect of compressor volumetric efficiency on


Fig. 4 e The effect of subcooling on system performance system COP and cooling capacity under high speed
and COP under city condition. condition.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0 39

Fig. 7 e The effect of compressor volumetric efficiency on Fig. 9 e The effect of compressor isentropic efficiency on
compressor power and refrigerant mass flow rate under compressor power under high speed condition.
high speed condition.
R1234yf system cooling capacity could be improved by 72.8% if
compressor volumetric efficiency (hvol) was increased from
0.55 to 0.95. It should point out that a higher mass flow rate
would result in higher pressure drop in compressor which was
worse for compressor consumption power (Navarro-Esbr
et al., 2013a).
On the other hand, if compressor isentropic efficiency
(hisen) was increased, system cooling capacity would be con-
stant when the compressor volumetric efficiency and cycle
state points were constant as shown in Fig. 8. The benefit from
compressor isentropic efficiency (hisen) improvements was the
system COP increasing which resulted from the compressor
consumption power reduction. Under high speed condition,
R1234yf system COP could be lifted to the same level as R134a
system when compressor isentropic efficiency (hisen) was
increased from 0.55 to 0.59. From the theoretical analysis,
R1234yf system COP could be improved by 72.7% if compressor
isentropic efficiency (hisen) was increased from 0.55 to 0.95. The
biggest gain from compressor isentropic efficiency (hisen)
Fig. 8 e The effect of compressor isentropic efficiency on improvement was compressor consumption reduction as
system COP and cooling capacity under high speed shown in Fig. 9.
condition.

3.2. Effect of compressor efficiency 4. Conclusions

The compressor plays a key role in mechanical vapor In this paper, the thermodynamic analysis for R1234yf mobile
compression refrigeration system performance improvement. air condition system was performed association with R134a
The effect of compressor volumetric efficiency (hvol) on MAC system under three typical vehicle operation conditions. The
system performance improvement was shown in Fig. 6 and performance improvement potentials by superheat, subcool-
Fig. 7 when the other MAC cycle state points were constant. ing and compressor performance were mainly focused and
From these figures, system COP was constant since the discussed.
compressor consumption power and cooling capacity The analysis results revealed that the R1234yf system COP
increased with refrigerant mass flow rate at the same level. and cooling capacity were lower by 4.8~7.0% and 7.7~10.6%
Obviously, increasing the mass flow rate was an easy way to than that of R134a system under all three conditions (idle, city
improve the system cooling capacity based on the thermo- and high speed), respectively. Increasing subcooling tempera-
dynamic cycle analysis. R1234yf system could reach the same ture from 1K to 10K could improve system COP and cooling
cooling capacity (~6.5 kW) as R134a system by improving capacity by 15.0%. And the effect of superheat on COP and
compressor volumetric efficiency (hvol) from 0.55 to 0.62 under cooling capacity was tiny and was adverse for larger refrigerant
high speed condition. Based on the theoretical analysis, mass flow rate. R1234yf system cooling capacity could increase
40 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 8 ( 2 0 1 5 ) 3 5 e4 0

by 72.8% with compressor volumetric efficiency (hvol) from 0.55 dx.doi.org/10.4271/2010-01-0328. SAE Technical Paper 2010-
to 0.95 if the other compressor efficiency and state points were 01-0328.
fixed. On the other hand, compressor isentropic efficiency Mathur, G., 2010b. Experimental Investigation of AC System
Performance with HFO-1234yf as the Working Fluid. http://
(hisen) improvement could reduce the power consumption
dx.doi.org/10.4271/2010-01-1207. SAE Technical Paper 2010-
dramatically which resulted in system COP increasing. It was 01-1207.
concluded that adding an internal heat exchanger and Mathur, G., 2011a. Enhancing AC System Performance with a
improving compressor efficiency would be better options in the Suction Line Heat Exchanger with Refrigerant HFO-1234yf.
future R1234yf MAC system enhancement. http://dx.doi.org/10.4271/2011-01-0133. SAE Technical Paper
2011-01-0133.
Mathur, G., 2011b. Experimental investigation of the performance
of a laminate evaporator with HFO-1234yf as the Working
Acknowledgments Fluid. SAE Int. J. Mater. Manuf. 4, 1231e1243. http://dx.doi.org/
10.4271/2011-01-1170.
The author is very grateful for the financial support from the Navarro-Esbr, J., Moles, F., Barraga
 n-Cervera, A., 2013a.
Experimental analysis of the internal heat exchanger
National Natural Science Foundation of China (Grant No.
influence on a vapor compression system performance
51406113).
working with R1234yf as a drop-in replacement for R134a.
Appl. Therm. Eng. 59, 153e161.
Navarro-Esbr, J., Mendoza-Miranda, J.M., Mota-Babiloni, A.,
references Barraga  n-Cervera, A., Belman-Flores, J.M., 2013b.
Experimental analysis of R1234yf as a drop-in replacement for
R134a in a vapor compression system. Int. J. Refrigeration 36,
Akasaka, R., Tanaka, K., Higashi, Y., 2010. Thermodynamic 870e880.
property modeling for 2,3,3,3-tetrafluoropene (R-1234yf). Int. J. Park, K.J., Jung, D., 2010. Nucleate boiling heat transfer
Refrigeration 33, 52e60. coefficients of R1234yf on plain and low fin surfaces. Int. J.
Cho, H., Lee, H., Park, C., 2013. Performance characteristics of an Refrigeration 33, 553e557.
automobile air conditioning system with internal heat Qi, Z.G., 2008. Performance Optimization of Mobile Air
exchanger using refrigerant R1234yf. Appl. Therm. Eng. 61, Conditioning Components and System (PhD thesis). Shanghai
563e569. Jiao Tong University, Shanghai (In Chinese).
Col, D.D., Torresin, D., Cavallini, A., 2010. Heat transfer and Qi, Z.G., 2013. Experimental study on evaporator performance in
pressure drop during condensation of the low GWP refrigerant mobile air conditioning system using R-1234yf as working
R1234yf. Int. J. Refrigeration 33, 1307e1318. fluid. Appl. Therm. Eng. 53, 124e130.
Environment Committee, 2006. Regulation (EC) No 842: 2006 of the Richter, M., McLinden, M.O., Lemmon, E.W., 2011.
European parliament and of the council of 17 May 2006 on Thermodynamic properties of 2,3,3,3-Tetrafluoroprop-1-ene
certain fluorinated greenhouse gases. Off. J. Eur. Union 161, 1e8. (R1234yf): vapor pressure and p-rho-T measurements and an
F-Chart Software, 2014. Engineering Equation Solver LLC. equation of state. J. Chem. Eng. Data 56, 3254e3264.
Ghodbane, M., 1999. An Investigation of R152a and Hydrocarbon Saitoh, S., Dang, C.B., Nakamura, Y., Hihara, E., 2011. Boiling heat
Refrigerants in Mobile Air Conditioning. http://dx.doi.org/ transfer of R-1234yf flowing in a smooth small-diameter
10.4271/1999-01-0874. SAE Technical Paper 1999-01-0874. horizontal tube. Int. J. Refrigeration 34, 1846e1853.
Lee, Y., Jung, D., 2012. A brief performance comparison of R1234yf Tillner-Roth, R., Baehr, H.D., 1994. An international standard
and R134a in a bench tester or automobile applications. Appl. formulation for the thermodynamic properties of 1,1,1,2-
Therm. Eng. 35, 240e242. Tetrafluoroethane (HFC-134a) for temperatures from 170 K to
Longo, G.A., Zilio, C., 2013. Condensation of the low GWP 455 K and pressures up to 70 MPa. J. Phys. Chem. Ref. Data 23,
refrigerant HFC1234yf inside a brazed plate heat exchanger. 657e729.
Int. J. Refrigeration 36, 612e621. Wang, C.C., 2013. An overview for the heat transfer performance
Lorentzen, G., 1994. Revival of carbon dioxide as a refrigerant. Int. of R-1234yf. Renew. Sustain. Energy Rev. 19, 444e453.
J. Refrigeration 17, 292e301. Wang, C.C., 2014. System performance of R-1234yf refrigerant in
Lu, M.C., Tong, J.R., Wang, C.C., 2013. Investigation of the two- air-conditioning and heat pump system e an overview of
phase convective boiling of R-1234yf in a 3.9 mm diameter current status. Appl. Therm. Eng. 73, 1412e1420.
tube. Int. J. Heat. Mass Transf. 65, 545e551. Zilio, C., Brown, J.S., Schiochet, G., Cavallini, A., 2011. The
Mathur, G., 2010a. Experimental Performance of a Parallel Flow refrigerant R1234yf in air conditioning systems. Energy 36,
Condenser with HFO-1234yf as the Working Fluid. http:// 6110e6120.

Das könnte Ihnen auch gefallen