Interference and Immunisation


14th March 2014

Ever since electric traction was invented, measures have been needed to stop unwanted
electric currents from interfering with signalling, telecoms, lineside power supplies and
outside organisation interests. Writes Clive Kessell

The resultant protection is collectively known as immunisation, sometimes confused


with medical activities using the same name. Ask the switchboard for the immunisation
department and you will as likely get the doctors surgery!

The science of understanding electrical interference has been ongoing for many years,
engaging the top brains in universities and research establishments. As new forms of rai

1 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

electrification and traction emerge, so new technologies for S&T and power supply
protection need to be devised. The interference is likely to have an adverse impact on
many systems, often leading to disputes as to the method and cost of remedial action.

To better understand the latest situation, the IRSE ran a seminar recently entitled Track,
Traction and S&T The Final Frontier. It was chaired by David Bradley, a signal engineer
with many years of experience in the subject, and it was an interesting day proving, if
nothing else, that the word final remains a pipedream.

The Dark Art

Ken Webb from Mott Macdonald used this title to describe the subject, noting that othe
names Arcane Discipline, Black Magic and Not
(http://railengineer.uk/wp-content/uploads
/377-refresh-2-online.jpg) for After Dinner
Speeches had also been attributed. The main
criteria are:

Current management getting amperes to


and from the train;
Frequency management avoiding the
creation of frequencies that can interfere
with other systems, particularly for unsafe
signalling conditions;
Minimise coupling eliminating or minimising the conductive, inductive or radiatio
linkage between the traction current and affected systems;
EMC (Electro Magnetic Compatibility) design ensuring that engineers responsible
for minimising interference understand the established techniques and standards.

Safety and standards

Someone once said the wonderful thing about standards is that there are so many to
choose from! This was never more true than for electrical interference and
immunisation, where a plethora of standards and instructions exist within Europe, the
UK and Network Rail. Getting the responsible engineer to search all these out, realise
how they relate to each other and then devise a practical compliance is a challenge in

2 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

itself. The base standards were said to be:

EC 61508 setting out the functional safety of electrical and electronic


equipment for safety related systems;
IEC/TS 61000-2:2008 describing the methodology for achieving the above;
IET Guide on EMC functional safety.

These relate to the general control of electrical interference and are not railway specific.
UK railway standards derive from the European EN 50121 series and RSSB Group
Standards GE/RT8015 and GE/RT8270. However these will not guarantee immunisation
safety. Three basic types of interference occur that can cause connection to other
systems; conduction as a direct connection, induction as an electromagnetic coupling
and radiation relating to high frequency radio waves.

All of these may occur on an electrified railway, be it 25kV AC overhead or both overhea
and third-rail DC systems. Down the years, a portfolio of protective measures have been
designed to limit induced voltages and currents to within prescribed limits. These can
add considerable cost to an electrification scheme and thus the different engineering
disciplines may argue as to their necessity.

In the UK, infrastructure owner Network Rail has responsibility for ensuring that railway
systems are protected from electrical interference and that staff are not exposed to
dangerously high voltages. To obtain optimum solutions, the company liaises with other
European rail bodies to produce a suite of standards and instructions that give guidance
on what can be expected and the remedial measures needed.

Maya Petkova, a principal engineer in the Asset Management Group, works with
colleagues in Europe to both produce and update standards and to relate these to UK
conditions. The resultant Railway Group and Network Rail standards set out the
conditions and practices that must be met. This is not a static situation and the
documents regularly need review and update to reflect emerging circumstances. Recen
examples are:

The growing impact of radio systems for rail control and communication including
track mounted balises and train aerials;
New types of track circuits (TCs) and axle counters;

3 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

Transient effects of neutral sections on electrified lines;


The impact of interoperability on both infrastructure and rolling stock;
Pressure to use more COTS (Common off the Shelf) equipment which may have a
lower EMC performance.Dominant in all of this is understanding how frequency
management will be possible over the range from 0-1MHz to prevent unsafe
operation of track circuits.

Dominant in all of this is understanding how frequency management will be possible


over the range from 0-1MHz to prevent unsafe operation of track circuits.

The electrification engineer

So how do the different disciplines cope with the competing pressures of obtaining the
most cost effective electrification configuration whilst keeping the railway safe?

For nearly 60 years, electrification on main lines has used the 25kV 50Hz AC overhead
line system. The advantages are well known, since adopting the domestic mains
frequency means avoiding expensive rectification and distribution networks. The curren
in the catenary wire does, however, produce an inducing electric field that affects
lineside copper cables. It can be loosely regarded as a long single turn transformer and
ways of preventing large induced voltages had to be found.

The most common solution is the use of booster transformers and return conductors.
These transformers are mounted on the stanchions at roughly two kilometre intervals
and inserted in series with both the catenary and the return conductor, the latter also
being strung on the stanchions. Half way between transformers, the conductor is
connected to the traction return rail. The effect is to suck return current out of the rail
into the return conductor that creates an opposing electric field to that of the catenary
so as to balance each other out. The induced voltage limits into cables are 60V steady
state and 430V under short circuit conditions, the latter only being present for a few
milliseconds until the breakers shut off the traction supply.

The electrification engineer traditionally regards booster transformers as a necessary


nuisance since they increase the impedance of the system thus losing potential power.

Even the 25kV system, however, is not capable of delivering sufficient power for high
speed or very heavy load trains and so has been developed the 50kV auto transformer

4 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

(A/T) system described at the seminar by David Hewings, the Network Rail electrificatio
engineer. In this case, a transformer at the electrification feeder station which takes
power from the grid delivers 50kV to an auto transformer with a centre tap connected to
the return rail, one 25kV feeding the catenary and the other to a separate 25kV
conductor mounted on the stanchions. The two feeds are in anti phase so help to cance
out the resultant electric fields. The presentation to traction units remains 25kV and is
thus unchanged. Because the system can deliver more power, the currents in the two
feeds are higher, thus increasing the inductive effect.

In the same period, the means of controlling the system has been updated and the
control of individual feeder stations by separately switched circuits has been replaced b
a network known as a station bus system using IEDs (Intelligent Electronic Device). With
more power comes a potentially higher fault current up from 600A to 1200A and thu
much faster circuit breaker switches are needed to keep induced voltages within the
prescribed limit. The package has led to GOOSE (General Operating Optical Sensing
Equipment) that is based around a fibre optic LAN network, suitable for transmission of
safety critical messages.

(http://railengineer.uk/wp-content/uploads
/377-604-online.jpg)The telecommunications
engineer

For many years, interference into telecom


circuits represented a major problem. With long
distance copper cable-based circuits, the
longitudinal induced voltages could be very
large, posing a risk to circuit performance,
equipment damage and staff safety. The protection methods of booster transformers
and additional cable screening were virtually mandatory, not only to prevent
interference to railway circuits but also to British Telecom and other telecom providers
systems which were routed close to an electrified railway.

This method is not perfect and such circuits may need to be further protected by either
an aluminium screen on the cable(s) or the provision of a separate mutual screening
conductor located in the cable route, these being earthed down to copper rods at 1km

5 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

intervals so as to also carry an opposite phase current.

As well as high voltages, because the wires of a pair in a telecom cable were not always
identical as to resistance and capacitance characteristics, the inducing field could
introduce noise on to the circuit by what is called a transverse voltage. Under
internationally agreed limits, this had to be restricted to 1mV, and required cable
balancing techniques for this to be achieved.

Fortunately, the advent of fibre optic cables has been the solution to most problems and
for over twenty years, railways and public telecom operators have invested in this
technology for long distance telecom links. It is not a complete solution since there
remain a lot of trunk telecom copper cables in existence and copper tail cables are
needed to connect from fibre hubs to the end device. Keeping the length of the latter t
broadly a 2km limit is good practice.

Telecom equipment at the lineside must be bonded to earth in a similar manner to


signalling. Because some equipment is susceptible to high voltage transients caused
either by electrification short circuits or lightning, the provision of fast transient earths a
individual equipment cabinets protect against any high voltage strike.

The signalling engineer

Since signalling copper circuits are of relatively short length, induced longitudinal
voltages are not the main problem. Of more concern is the potential interference to
track circuits by conduction direct from the rails. This can be influenced by the type of
track circuit deployed and whether it is based on single or double rail design. Success is
measured by how well the TC operating frequency can be different from the 50Hz
overhead line frequency and the harmonics that derive from this.

Unwanted frequencies can also be generated by the sophisticated types of traction unit
now in service and the objective is to prevent traction return currents from causing
unsafe operation of track circuit equipment. The TI 21 track circuit used for many years is
designed around frequency shift keying (fsk) with the frequencies chosen outside of the
normal 50Hz harmonic range but recent tests with Class 90 locomotives have shown
that the fsk principle is not good enough and that in certain circumstances, wrong side
TC failures can occur. Thus digital encoding of track circuits, making each one unique, is

6 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

the ongoing design preference.

Earthing and bonding remain a challenge and Peter Brown, the E&P design manager in
Network Rail, described how a return screening conductor (RSC) connected periodically
to the traction return rail can negate the need for individual earth rods at signalling
lineside locations. Such an arrangement is ideal in areas using single rail track circuits or
axle counters but impedance bonds will be needed if double rail TCs are in use. This
arrangement has been chosen for the forthcoming Great Western main line
electrification, subject to it passing a generic safety case approval.

The traction engineer

Every rolling stock designer is aware of the risk posed to signalling and other equipment
by return currents and inappropriate frequencies generated by the train. Colin Place
from Bombardier described the devices that are installed on Class 377 DC units in servic
on Southern and South East Trains.

Firstly, there is 1.5 tonnes per power car of filter equipment, intended to protect TCs
from conducted electro-magnetic interference.

Also introduced when the trains were built was a Line Interference Monitor (LIM) based
on Railtrack standards but experience in practice showed this to be so onerous that
traction power was removed too often when the third rail experienced ice conditions
and trains became stranded. The replacement is an Interference Current Monitoring Uni
(ICMU) but even here when ice is present, drivers are trained to keep power on when
coasting to ensure an arc keeps flowing to the third rail.

On older fleets where an ICMU does not exist, cruder monitoring systems were provided
but proved less reliable than the on-board systems being protected. The latest thinking
is that the next generation of trains is unlikely to be fitted with monitoring equipment
since the desired limits are known to be exceeded many times daily but are of short
duration. Protection systems to prevent over voltage, over current and device failure in
the traction power electrics will be sufficient.

The power supply engineer

Providing a reliable power supply for S&T equipment at the trackside is vital; without
power, nothing can function. Traditionally this has been via a 650V single-phase cable

7 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

with a transformer provided at every lineside cabinet from which the local 110V AC and
50V DC power sources are derived. Later designs have adopted a 400V three-phase
arrangement but both used a cable with a separate earth core.

In electrified areas, this earth was connected to the collective earthing system of the line
and this could lead to high touch voltages if double earth fault conditions occurred.

A design to simplify and reduce the cost of lineside power supplies has recently
emerged from Network Rail; known as a Class II supply this is based around an earth fre
system using only a two-core cable and its features were described at the seminar by
Tahir Ayub from Network Rails Signalling Innovations Group. A full explanation of this
power supply is contained within a separate article in this magazine.

Mixed Electrification Areas

The protective measures needed to protect vulnerable equipment in AC and DC


electrification are quite different: in AC, earthing plays a vital role whereas DC systems
should be kept earth free (or at least only a local equipment earth) so as to prevent high
traction return currents using S&T cables as a return path. However, it is known that DC
stray currents can exist well beyond the immediate rail area and there are
(http://railengineer.uk/wp-content/uploads
/ThamesLink_V2-online1.jpg) many locations
where the two systems are in close proximity,
bringing with it the risk of equipment mis-
operation.

Crossrail and Thameslink

Any new piece of electrified railway will raise fears as to whether interference will cause
problems to existing co-located railways.

One such consideration is Crossrail on its east-west route across London it will have
two 400kV supply points at Pudding Mill Lane and Kensal Green and will use the 50kV
A/T system delivering 67MVA from Stratford to Shenfield and Paddington to
Maidenhead and 30MVA in the central section.

James Greatbanks from Bechtel described how an interference model has been
produced looking at 16 engineering elements that might be affected. These included

8 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

earth potentials, stray currents, electrolytic corrosion, resonance, rail voltage, screening
factors and equipment loading. Modelling is based around short circuit conditions with
and without a supplementary earth wire on the surface sections. The conclusion is that
there will be negligible 50Hz flow between Crossrail and other railways.

The biggest risk is at joint stations and also at Heathrows baggage and airside terminals
with their many electronic systems. London Underground continues to have reservation
with the Hammersmith & City line being the most likely to be affected. Whilst modelling
is much cheaper than live tests, no doubt confirmatory tests will be necessary once the
line is built and equipped.

The north-south Thameslink project is an upgrade scheme to hugely increase the


number of trains using the route. Martin Sigrist from Network Rail explained that it
means converting the Midland main line electrification to the 50kV A/T system but
retaining 25kV and booster transformers from St Pancras to Blackfriars and with the
complication of having to change from overhead to third-rail electrification between
Farringdon and Blackfriars, which will be dual voltage. The expected high DC currents
raise the risk of these straying well into AC areas with risk to track circuit operation
because of insulated rail joint (IRJ) arcing.

Early tests suggest 180 amps of stray current in the quiescent state (no trains) and 300+
amps with trains running, but measurements on the East Coast main line have shown
only 0.5 amps detected there. The earthing and bonding plan for the central section is
thus a complex issue with the multiplicity of cables, equipment cabinets and a fire main
between Kings Cross and Farringdon all making possible parallel return paths for single
rail track circuits and traction return. Contactors have been installed at Blackfriars to
minimise the DC flow from southwards of this point, but many more tests and
adjustments to the design will be needed as the project progresses.

At the end of the day, this seminar demonstrated that interference and immunisation is
anything but a precise science. Whilst broad order protective measures have been
established for 25kV lines over a number of years, the emergence of new types of rolling
stock, computerised based signalling systems and more power from the overhead
catenaries have needed improved methods of testing and monitoring.

In the past, engineers may have taken an over cautious approach and perhaps the

9 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

adverse effects are not as bad as some would have us believe. Some technology
advances for example fibre optic cables and Class II power supplies have made
immunisation easier. The situation with DC electrification and particularly third rail is les
well documented and adverse weather can vary traction current conditions thus
impacting on interference levels.

The work to understand and protect against electrical interference will need to continue
for many years yet.

The ongoing NW electrification project brings AC systems near to the Manchester Metro
(tram) network. Recent tests carried out at three sites, Ordsall Lane, Castlefields and
Eccles, were described by David Bradley to see if a problem would result. Four basic
measurements were made at each site two of voltage and two current to determine
any flows between the two rail operations. Both short circuit and steady state condition
were tested. Happily, stray currents did not penetrate as much as expected and thus it is
concluded that track circuits will continue to function correctly.

(https://www.facebook.com/sharer/sharer.php?u=htt
%3A%2F
%2Fwww.railengineer.uk%2F2014%2F03%2F14%2Finterferen
and-immunisation%2F)
(https://twitter.com
/home?status=Interference+and+Immunisation+-+http
%3A%2F
%2Fwww.railengineer.uk%2F2014%2F03%2F14%2Finterferen
and-immunisation%2F)
(https://plus.google.com/share?url=http%3A%2F
%2Fwww.railengineer.uk%2F2014%2F03%2F14%2Finterferen
and-immunisation%2F)

10 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

(https://pinterest.com/pin/create/button/?url=http
%3A%2F
%2Fwww.railengineer.uk%2F2014%2F03%2F14%2Finterferen
and-immunisation%2F&media=http://www.railengineer.u
/wp-content/uploads/shutterstock-online.jpg&
description=Interference+and+Immunisation

summary=Ever+since+electric+traction+was+invented%2C+

Watford Out of the naughty corner Bottle it! (http://www.railengineer.uk


(http://www.railengineer.uk/2014/03 /2014/03/18/bottle-it/)
/11/watford-naughty-corner/)

11 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

0 Comments Rail Engineer

Sort by Best
Recommend Share

Start the discussion

Be the first to comment.

ALSO ON RAIL ENGINEER

Craigentinny does it all London Bridge station Another milestone


5 comments 4 months ago 2 comments 15 days ago
owen evans Good stuff, it seems like the Andrew Gwilt Plus the new platforms
depot has a good future ahead of it. open this summer or this autumn and
of the platforms to follow and the whole

Digitising Euston High ideas


2 comments a month ago 3 comments 8 days ago
Andrew Gwilt https://en.wikipedia.org/wiki/... Andrew Gwilt Aswell local and rural
coming in & out of Birmingham Moor
and Birmingham Snow Hill that could

Subscribe d Add Disqus to your site Add Disqus Add Privacy

12 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

LATEST

Advanced A moving story


energy (http://www.rai
management /2016/08/30/a-
(http://www.railengineer.uk (http://www.railengineer.uk
/2016/09 (http://www.railengineer.uk
/2016/08/30/a- moving-story/
/02/advanced- High
/2016/09ideas moving-story/)
energy-
management/) (http:/ /www.railengineer.uk
/02/advanced-
/2016/08
energy-
(http://www.railengineer.uk
/2016/08 /26/high-
management/)
/26/high-ideas/) ideas/)

RELATED POSTS

13 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

(http://www.railengineer.uk/2016/09/02/advanced-energy-management/

Advanced energy management (http://www.railengineer.uk


/2016/09/02/advanced-energy-management/)

InnoTrans 2016 (http://www.railengineer.uk/2016/08


/26/innotrans-2016/)

Subway Revival Glasgow to introduce UTO


(http://www.railengineer.uk/2016/08/23/subway-revival-
glasgow-to-introduce-uto/)

14 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

(http://www.railengineer.uk/2016/08/30/a-moving-story/)

A moving story (http://www.railengineer.uk/2016/08/30/a-


moving-story/)

Class 707 breaks cover (http://www.railengineer.uk/2016/08


/25/class-707-breaks-cover/)

Video: National Records Centre (http://www.railengineer.uk


/2016/08/22/video-national-records-centre/)

15 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

(http://www.railengineer.uk/2016/08/26/high-ideas/)

High ideas (http://www.railengineer.uk/2016/08/26/high-


ideas/)

4LM+1 (http://www.railengineer.uk/2016/08/24/4lm1/)

Planning for a worlds first ElevArch masonry arch jacking


trial (http://www.railengineer.uk/2016/08/19/planning-for-a-
worlds-first-elevarch-masonry-arch-jacking-trial/)

16 of 17 03/09/2016 23:11
Interference and Immunisation Rail Engineer http://www.railengineer.uk/2014/03/14/interfer...

Rail Engineer
(http://www.railengineer.uk/)
FEATURE SCHEDULE 2016 (HTTP://WWW.RAILENGINEER.UK/FEATURE-SCHEDULE-2016/

PRIVACY (HTTP://WWW.RAILENGINEER.UK/PRIVACY/)

T&CS (HTTP://WWW.RAILENGINEER.UK/TERMS-AND-CONDITIONS/)

SUPPORT (HTTP://WWW.RAILENGINEER.UK/SUPPORT/)

CONTACT (HTTP://WWW.RAILENGINEER.UK/CONTACT/)

17 of 17 03/09/2016 23:11

Das könnte Ihnen auch gefallen