Beruflich Dokumente
Kultur Dokumente
Part VII
Examples
Read extra examples from Text Book (Wight and
MacGregor) 6th ed. (Example 18-2 page 1028,
and Example 18-3 page 1031)
1
EXAMPLE I
EXAMPLE I
2
EXAMPLE I
EXAMPLE I
3
EXAMPLE I
EXAMPLE I
Check:
4
EXAMPLE I
Revised to 10# 8
Revised to 10# 8
EXAMPLE II:
Check moment and shear strength at the base of the structural wall
shown in Fig. below.
Also, show that the given horizontal and vertical reinforcement satisfies all
of the ACI Code requirements regarding minimum reinforcement
percentage and maximum spacing.
The given lateral loads are equivalent wind forces, considering both direct
lateral forces and the effects of any torsion.
The given vertical loads represent dead loads, and you can assume that the
vertical live loads are equal to 60 percent of the dead loads.
5
EXAMPLE II
(Each Floor)
11
EXAMPLE II
A st f y
w h f c '
12
6
EXAMPLE II
c <0.375d
13
EXAMPLE II
14
7
Example III:
The structural wall shown in Fig. below is subjected to gravity loads (D = 150 kips
and L = 100 kips) and an equivalent, static, lateral earthquake load, E = 150 kips)
(torsion effects included).
Check the moment strength at the base of the structural wall assuming that the
distance, x , from the base of the structure to the lateral force, E , is equal to two-
thirds of the wall height.
Use a capacity-design approach to check the shear strength of the wall and
assume the distance, x , is equal to one-half of the wall height for this check.
Also, show that the given horizontal and vertical reinforcement in the web of the
structural wall satisfies all of the ACI Code requirements regarding minimum
reinforcement percentage and maximum spacing. Assume the wall is constructed with
normal-weight concrete that has a compressive strength of 5000 psi. Assume all
of the steel is Grade-60.
15
(Each Floor,
Each Wall)
16
8
Example III
c = a/1 <0.375d
17
Example III
c = a/1 <0.375d
18
9
Example III
Based on Probable flexural strength
c = a/1 <0.375d
19
Example III
20
10
Example IV
Design the shear wall section at the base.
(1176 kN) D.L = 120t
Solution: (490 kN) L.L = 50t
Determine minimum vertical & horizontal
reinforcement requirements in the wall (wall
height hw = 18 m & SDS=0.333)
5m0.25m
Check if two curtains of reinforcement are required:
V u 0.17Acv f c '
Acv 5 0.25 1.25m 2
V u 0.98MN 0.17 1.25 28 1.124MN (7840 kN.m)
784t.m
(980kN)
According to the above equation, no need for two 100t
curtains but as the wall thickness is 250 mm the code
recommend to use two curtains of reinforcement.
21
Example IV
The minimum reinforcements ration are
Horizontal steel:
h 0.0025
Vertical steel:
hw/Lw = 18/5 = 3.6 > 2.5
v 0.0025
Use 612 @ 100cm in both sides of the wall and in the vertical &
horizontal directions.
22
11
Example IV
A Using two curtains of 12mm
or s , horz 0.0025
S 2h
12@35cm
(1.13) x 2
0.0025 S 36cm 35cm
S 2 (25)
lw
5 =100 cm 35cm
S 2,max The smallest of 45 cm =45 cm
3h =75 cm
12@35cm
Use 112 @ 35cm in each side of the wall in the vertical and horizontal
direction
23
Example IV
Determine reinforcement requirements for shear
Shear strength of wall
V n Acv c f c ' v f y
c = 0.17 for hw/Lw = 18/5 = 3.6 2
V n 1.25 0.17 28 0.0026 420 2.489MN V u 0.98MN
24
12
Example IV
Determine reinforcement requirements for combined flexural
& axial loads
Example IV
Therefore Pu = 2195 kN
0.25 53 A g 5 0.25 1.25m 2
Ig 2.6m 4
12
Pu M u Lw
0.2f c '
Ag Ig 2
2195 7840 5
9295kN 0.2f c ' 5600kN / m 2
1.25 2.6 2
26
13
Example IV
2 0.85
1.13 2 500
A st f y 420
35
0.039
w h f c ' 500 25 28
Pu 2195 / 1000
0.063
w hf c ' 5 0.25 28
0.039 0.063
0.13
2 0.039 0.85 0.85
27
Example IV
Lager of c/2, 0.1 , 45 cm or
65
32.5
2 2
0.1 65 0.1 500 15
500
31
16 16
Take the boundary length as 45 cm as its the larger value.
Check moment capacity Mn using approximate equation
Pu c
M n 0.5A st f y w 1 1
A st f y w
28
14
Example IV
32.29 2195 / 1000
M n 0.9 0.5 420 5 1
32.29 1 0.13 6.95MPa
10000 420
10000
Mn = 6.95MPa < Mu = 7.84 MPa
Therefore additional reinforcements are required for flexural
M u M n d 0.8Lw 0.8 5 4m
As
0.9f y d
7.84 6.95
As 6cm 2 = 316mm
0.9 420 4
(As = 6.03 cm2)
Use 216 at each edge of the boundary zone (As,provided = 8 cm2) as the
minimum vertical reinforcement in the boundary zone.
29
Example IV
Confinement ( transverse) Reinforcement
Maximum Hoops and cross-ties vertical spacing
Spacing of transverse reinforcement s shall not exceed the
smallest of:
(1) 150 mm
(2) Six times the diameter of the smallest longitudinal bar 6db=6*16=96 mm
(3) so, as defended by:
15
Example IV
31
#6
and Problem
18-2 from
Wight and
MacGregor
page 1041
32
16
97
33
97
34
17
35
36
18
37
38
19
39
40
20
41
42
21
43
44
22
45
46
23
47
48
24
49
1.6
UBC -1997:
50
25
51
52
26
= 0.02 hsx
53
54
27
55
56
28
57
58
29
59
60
30
61
31
(Mu/bd2) =2.0 = 0.005 Asreq =27200 mm2
As = 39 * 804 = 31356 mm2
63
64
32
65
66
33
67
68
34
Drift of Structure Due
to Seismic Load
69
system .
70
35
Using Conjugate-beam method to determine the
deflection at point B
71
The stiffness EI
Modulus of elasticity EC B
When WC = 1440 to 2480 kg/m3
Y1
E C W C 1.5 0.043 f c ' M1
EI 1 Y2
For normal weight concrete
Y3
E C 4700 f c ' M2
EI 2
Moment of inertia I M3
For columns EI 3 A
0.35Ig
For beams
0.7Ig
For walls uncracked 0.7Ig
cracked
0.35Ig 72
36
The stiffness EI
0.2E c I g E s I se
EI
1 d
0.4E c I
EI g
1 d
73
37
Example
Determine the total and story drift of the cantilever
shear wall due to seismic load as shown. fc = 28MPa,
shear wall dimension 3m 0.2m from A to B.
Modulus of elasticity Ec 3m
0.2 33 25t D
Ig 0.45m 4 2943kN.
12
m 3m
The stiffness EI
5592kN.m
0.4 24870 0.45 A
EI 4476600kN .m 2 75
1 0
1 3
5592 2943 8 2943 3 7.5
EI 2
129348
B 100 2.89cm
4476600
76
38
Second story drift, point D to point C
1 3
DC 2943 1030 2 1030 3 1.5
4476600 2
3
5592 2943 5 2943 3 4.5 AD
2
CB B DC AD
A
78
39
Drift of frame structure due to seismic load
3
Q3
2
Q2
Rigid joint
1
Q1
K s
h IC
Stiffness KS for column Ib2 Ib2
40
Where
0.4Ec I g
E = modulus of elasticity EI
1 d
IC = moment of inertia of the column
h = floor height
Ib = moment of inertia of the beam
Lb = length of the beam
12EI C 1
K SC
h3 1
2I C
I
h b 1 0.
Lb 1
81
total
Q i
K s
82
41
Stiffness KSC for column or the shear-wall
12 EI C 1
K SC
h3 1
2I C
I I
h b1 b 2
Lb1 Lb 2
Shear-Wall
shear wall, exactly as a
column & this column has a
large moment of inertia I or
stiffness
83
42