Sie sind auf Seite 1von 6

Transformer Regulation & Losses Calcualation (As per Trans

:Three Phase Transformer Detail:


Transformer Make
Transformer Serial No
KVA rating of Transformer 16000 VA
Primary voltage 11000 Volts
Secondary voltage 433 Volts
Primary side Connection
Scondary side Connection
No load losses 72 Watts
No load current 0.59 Amps
Full load losses 394 Watts
Impedance voltage 480 Volts
Lv resistance in milli ohms 219.16 M Ohms
Hv resistance in ohms 215.33 Ohms
Amb temperature 30 Deg c
Total Connected Load on Transformer 10000 VA
% Loading of Transformer 63%

Jignesh.Parmar
jiguparmar@yahoo.com
www.electricalnotes.wordpress.com

Formulas
HV Full load current = VA / (1.732xVolt)
LV Full load current = VA / (1.732xVolt)
HV Side I2R losses = IR x1.5

TEST ENGINEER
LV Side IR losses = IR x0.5x3
Total I R lossses @ Amb temp = Hv losses+ Lv losses
Total Stray losses @ Amb temp =Measured losses -I R losses
I R lossses @75 c temp = ((225+75) x losses) / (225+ Amb temp)
Stray losses @ 75 c temp=((225+Amb temp)(Stray losses at amb)) / 300
Total Full load losses at @75 c = IR losses at 75c+Stray losses at 75c
Total Impedance at ambient temp =(Imp voltage x1.732) / Full load current
Total Resistance at amb temp = IR losses / I
Total Reactance (X) =SQRT(Impedance - Resitance )
Resistance at@ 75 c =(300 x resistance at amb ) /(225+Amb temp)
Impedance at 75 c =SQRT(R at 75 + X)
Percentage Impedance =(Z at 75 c x I x 100)/V1
Percentage Resistance =( R 75 c x I x 100)/V1
Percentage Reactance =(X x I x 100) / V1

Regulation at Unity P.F =(%R cos+%Xsin) .


Regulation at 0.8 p.f.= (%R cos+%Xsin)+1/200(%R sin-%Xcos)2"

Efficiency at Unity P.F


At 125 % of Transformer Loading =(Kva x 1.25 x 100)/((kva x 1.25)+(IR losses x 1.25)+(No Load Losses))
Efficiency at 0.8 P.F
At 125 % of Transformer Loading =(Kva x 1.25xp.f x 100)/((kva xp.fx 1.25)+(IR losses x 1.25)+(No Load Losse

TEST ENGINEER
TEST ENGINEER
Losses Calcualation (As per Transformer Name Plate)
:IR Losses Calculation:
HV Full load current : 0.84 Amps
LV Full load current : 21.33 Amps
HV Side I2R losses 227.800 Watts
LV Side IR losses 149.63 Watts
Total I R lossses @ Amb temp 377.43 Watts
Total Stray losses @ Amb temp 16.57 Watts
I R lossses @75 c temp 441.52 Watts
Stray losses @ 75 c temp 14.16 Watts
Total Full load losses at @75 c 455.69 Watts
Total Impedance at ambient temp 989.94 Ohms
Total Resistance at amb temp 535.15 Ohms
Total Reactance (X) : 832.82 Ohms
Resistance at@ 75 c 626.03 Ohms
Impedance at 75 c 1041.88 Ohms
Percentage Impedance 4.59 %
Percentage Resistance 2.76 %
Percentage Reactance 3.67 %
:Regulation Calculation:
Regulation at Unity P.F 2.76
Regulation at P.F of 0.8 4.43 0.6
:Efficiency Calculation:
Efficiency at P.F of Unity Efficiency
At Transformer Loading 125% 96.80 %
At Transformer Loading 100% 97.27 %
At Transformer Loading 75% 97.69 %
At Transformer Loading 50% 97.96 %
At Transformer Loading 25% 97.67 %

Efficiency at P.F of 0.8 Efficiency


At Transformer Loading 125% 99.52 %
At Transformer Loading 100% 96.61 %
At Transformer Loading 75% 97.12 %
At Transformer Loading 50% 97.47 %
At Transformer Loading 25% 97.10 %

TEST ENGINEER
25)+(IR losses x 1.25)+(No Load Losses))

p.fx 1.25)+(IR losses x 1.25)+(No Load Losses))

TEST ENGINEER
TEST ENGINEER

Das könnte Ihnen auch gefallen