Beruflich Dokumente
Kultur Dokumente
DESCRIPTION
Switch: 4PDT key switch:
This Key Maintenance Switch is a key-switch that one set of contacts control
disconnects actuation circuits in the system to prevent indicators on the
accidental discharge during maintenance operations. mounting plate.
Three remaining contacts
Two LEDS indicate "SYSTEM ARMED" or are available for
application wiring.
"SYSTEM INACTIVE" when the key is inserted and
turned. The key can only be removed in the armed Device Current: 10 A @ 250 Vac
position. 15 A @ 125 Vac
Key Maintenance Switch mounts to a 4-inch 15 A @ up to 30 Vdc Key Maintenance Switch
backbox and operates on 24 Vdc. Operating Temperature 0 to 150F (-18 to 66C) Installation Sheet
Designed for mounting on the wall with a back box. Range:
Key Maintenance Switch can be installed in either
Electrical Life: 50,000 cycles - maintained
surface mount or flush mount configurations. 25,000 cycles - momentary
Key Maintenance Switch physically disconnects the
release circuit wiring in addition to the trouble open Mechanical Life: 100,000 cycles
signal, the switch provides a means to generate a Switch Plate Construction: Stainless Steel
supervisory condition.
Backbox Construction: 18 gauge cold rolled steel
Shipping Weight
ORDERING INFORMATION Key Maintenance Switch: 8-1/2 oz. (241 g)
Backbox: 14 oz. (397 g)
Description Part Number AI Module: 2.7 oz. (77 g)
Bracket: 2.6 oz. (74 g)
Maintenance Switch 65-600000-200
Backbox 06-236881-001
AI Module 70-407008-001
These instructions do not purport to cover all the details or variations in the
equipment described, nor do they provide for every possible contingency to
be met in connection with installation, operation, and maintenance. All
specifications subject to change without notice. Should further information
be desired, or should particular problems arise which are not covered suffi- 400 Main Street
ciently for the purchasers purposes, the matter should be referred to Ashland, MA 01721
KIDDE-FENWAL, INC., Ashland, MA 01721. Ph: 508.881.2000
Fax: 508.881.8920
06-236878-001 Rev AA 2008 Kidde-Fenwal, Inc. Printed in U.S.A. www.chemetron.com
WIRING DIAGRAMS INSTALLATION INSTRUCTIONS
Note: To comply with ADA standards, the 3. Make all wiring connections as shown in the
Maintenance Switch must be mounted less wiring diagram. Ensure that all wiring is free of
ADDRESSABLE
than 48 in. (1219 mm) above floor level for opens, shorts and ground faults. Verify that all
PANEL
CONVENTIONAL
TO
CONTROL UNIT
front wheelchair access or less than 54 in. wires are insulated up to the terminal block, and
TO
TB1
4 3 2 1
SUPERVISORY
AI MODULE (1372 mm) for side wheelchair access. that each terminal screw is tight.
P/N 70-407008-001
SLC
4. The AI Device must be installed vertically with the
ALL TERMINALS ARE POWER LIMITED
SEE INSTALLATION
CAT. NO. 70-407008-001
ASHLAND, MA 01721
400 MAIN ST.
KIDDE-FENWAL, INC.
C N.O.
GREEN LED
SYSTEM ARMED
has conduit knockouts on all four sides and the
INITIATOR 1 INITIATOR 2 THE KEY CAN BE REMOVED
RELEASING DEVICE
N.C.
MAINTENANCE SWITCH
AI/AO MODULE AI/AO MODULE
BRACKET BRACKET SCREW
Figure 1. Wiring Configuration Using Initiators/Metron
- Switch Shown in ARMED Position
ADDRESSABLE
PANEL
CONVENTIONAL
CONTROL UNIT
TO
SYSTEM SYSTEM
ARMED INACTIVE
TO
SUPERVISORY
TB1
4 3 2 1 AI MODULE
P/N 70-407008-001
SLC MAINTENANCE SWITCH
ALL TERMINALS ARE POWER LIMITED
SEE INSTALLATION
CAT. NO. 70-407008-001
06-235578-001
INSTRUCTIONS
PC PC PC PC SW SW LED LED
(+) (-) (+) (-) A B (+) (-)
1 2 3 4 5 6 7 8
REFER TO SYSTEM MANUAL
FOR MAXIMUM-LENGTH
ESTIMATION. MAINTENANCE
NOTE: ALL WIRING IS
POWER-LIMITED AND SWITCH
SUPERVISED.
N.C.
CAN BE 10K EOL
REPEATED FOR Resistor
N.O.
SECOND CIRCUIT C
N.C.
C N.O.
BACKBOX AI/AO MODULE MAINTENANCE
N.C. BRACKET SCREW SWITCH
SOLENOID 1 N.O.
GREEN LED SYSTEM ARMED
N.C.
THE KEY CAN BE REMOVED
RELEASING DEVICE
(06-220023-001) C N.O. SYSTEM DISABLED
THE KEY CANNOT BE REMOVED
SOLENOID 2
KEY SWITCH RED LED Figure 3. Key Maintenance Switch and Backbox Installation
RELEASING DEVICE MAINTENANCE SWITCH