Sie sind auf Seite 1von 64

Release Date: Nov. 2009 / Manual Revision: 1.

00

ETR300S DNP3.0 Remote


Communication
Technical Manual

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright 2008 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
DNP3.0 PROTOCOL http://www.entecene.co.kr

TABLE OF CONTENTS

A. DNPTM 3.0 Communication Inroduction .....4

B. DNP Communication H/W Composition .....6

C. Configuration for DNPTM 3.0 ...13

D. Dialling Modem Support ...... 18

E. DNPTM 3.0 Device Profile ... ..21

F. DNPTM 3.0 Implementation Table ...25

G. DNPTM 3.0 Point Table . ..31

H. DNPTM 3.0 File Transfer .....61

ENHANCED TECHNOLOGY 3
DNP3.0 PROTOCOL http://www.entecene.co.kr

A. DNP 3.0 Communication Introduction


This documents is technical specification about DNP 3.0 communication protocol and consists
of DNP 3.0 communication H/W composition and setting, DNP 3.0 Profile Document, DNP
3.0 Implementation Table and DNP 3.0 Point List.

This document is based on DNP 3.0 Basic 4 Document. It describes the communication method
between ETR300 and main device, based on DNP 3.0 protocol.

Characteristics

Binary Input Points Point Remapping


Binary Input Points can be reset regarding the users need. Resetting is changed through operating
program.

Cold/Warm Restart
When DNP function code Cold/Warm restarts, only communication port and DNP process shall
be designed to be reset. It does not affect Recloser protection process.

Unsolicited Response
Configurable Enable or Disable to Configuration for DNP 3.0 whether Unsolicited Response
transmit or not to Master station. When Master stations request and devices Unsolicited Response
were transmitted simultaneously, Data collision is avoidable by having unsolicited response delay
time.

Time Synchronization
Because Time sync request interval setting, Reclosers Event, Protection, Faultwave shall be
maintained in detail timing. We provide Object 50, Variation 01 and Object 52, Vairation 02 which
are DNP function, the user can set the time via a DNP master.

Flow Control
Depending on DNP network, it is recommended to adjust data transmission property. In this case,
Tx Delay, RTS Off Dly setting can be used to adjust signal interval between real data transfer and
RTS. It can help solid communication.

Setting change from Master-Station


Analog Control in DNP support Function can be used to change Recloser Setting in local through
DNP Master. It is very useful for a feeder management.
Dialling Modem Support

ENHANCED TECHNOLOGY 4
DNP3.0 PROTOCOL http://www.entecene.co.kr

ETR300 can support a Hayes compatible Modem on Port1(RS-232) for remote dial up access using
DNP 3.0.

ENHANCED TECHNOLOGY 5
DNP3.0 PROTOCOL http://www.entecene.co.kr

B. DNP Communication H/W Composition


ETR300 has 4 communication port as Table B-1. Communication Port H/W Composition and
DNP3.0 communication is possible in PORT1, PORT2 and PORT3.

Table B-1. Communication Port H/W Composition


Port Type Speed Parity bit Data bit Stop bit Location

PORT1 RS-232 1200 - 19200 bps None, Odd, Even 7, 8 1, 2 User Interface Side Panel

PORT2 RS-485/422 1200 - 19200 bps None, Odd, Even 7, 8 1, 2 User Interface Side Panel

PORT3 RJ45 10BASE-T/100BASE-T User Interface Side Panel

2TX 10M/100M LINK


A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 B01 B02 B03 B04 B05 B06 B07 B08 1 2 3 2RX

TX RJ45
950-10 950-08 950
XPORT
RX 9
RCV Antenna Antenna
1TX 1:DCD 2:RXD 3:TXD 4:DTR
485+ 485- SG 1RX
5:GND 6:DSR 7:RTS 8:CTS
+ + + + 9:N/C
OUT101 OUT102 OUT103 OUT104 N.C IN101 IN102 IN103 IN104 GPS PORT RF PORT2 PORT1 PORT3

E01 E02 E03 E04 E05 E06 E07 E08 E09 E10 F01 F02 F03 F04 F05 F06 G01 G02 G03 G04 G05 G06 G07 G08

I01 I02 I03 IN Ise V11 V12 V13 V21 V22 V23 V0

Picture B- 1. Table B-1. Communication Port H/W Composition

ENHANCED TECHNOLOGY 6
DNP3.0 PROTOCOL http://www.entecene.co.kr

PORT 1(RS-232)
Communication method: RS-232
Port setting: 1200~19200bps
Connector: DB9S(female)
1T LED(Port1 TX LED): Flash when transmit Data
1R LED(Port1 RX LED): Flash when receive Data

Table B- 1. PORT1 Pin Description

Pin Signal Description

1 DCD Data Carrier Detect

2 RXD Receive Data(IN) 1

3 TXD Transmit Data(OUT) 1T


1R 9
4 DTR Data Terminal Ready(OUT) 1: DCD2: RXD 3: TXD 4: DTR
5: GND6: DSR 7: RTS 8: CTS 9: N/C
5 GND Ground
PORT1
6 DSR Data Set Ready(IN)
Picture B- 2. PORT1
7 RTS Request To Send(OUT)

8 CTS Clear To Send(IN)

9 N/C No Connection

PORT 2(RS-485)
Communication method: RS-485
Port setting: 1200~19200bps
Connector: BONAB STLZ950-8P
2T LED(Port2 TX LED): Flash when transmit Data
2R LED(Port2 RX LED): when receive Data

Table B- 2. PORT2 Pin Description

Pin Description 1 2 3
2T
1 RS485+ 2R
950
2 RS485-

3 SG (Cable Shield) 485+ 485- SG

PORT2

Picture B- 3. PORT2

ENHANCED TECHNOLOGY 7
DNP3.0 PROTOCOL http://www.entecene.co.kr

. Note) PORT2 provides RS-485 communication and uses Digital power and insulated power
of CPU Part for surge protection. Each terminal is Anti-Over-voltage.
To minimize the noise of communication line, use Terminal Registor in the both end of
the line and Twisted Shield Cable for the communication cable.

PORT 3(ETHERNET)
Table B- 3. PORT3 Pin Description
10Base-T Signal
Pin Wire Color 10M/100M LINK
100Base-TX Signal
1 White/Green Transmit+
RJ45
2 Green Transmit- XPORT
3 White/Orange Receive+

4 Blue Unused PORT3


5 White/Blue Unused Picture B- 4. PORT3
6 Orange Receive-

7 White/Brown Unused

8 Brown Unused

PORT3 is RS-45 and consists of 8 pins. The composition is same as Table B- 3. PORT3 Pin
Description.PORT 3 provides 10 BASE-T /100 BASE-T ethernet and in the top of both side has
10M/100M LED (left) and LINK LED (right). 10M/100M LED shows data transfer rate and LINK
LED shows cable connection and communication status. Refer to Table B- 4. LED Function for
more details.

Table B- 4. LED Function


LED Status Description
Flash Data transmitting or receiving
10M/100M ON Data transmitting or receiving
OFF LAN connection is not established
Orange 100Mbps Data rate
LINK Green 10Mbps Data rate
OFF LAN connection is not established
B-1. Communication Port Setting

Each communication port can set communication rate and others related to communication.

ENHANCED TECHNOLOGY 8
DNP3.0 PROTOCOL http://www.entecene.co.kr

(1) PORT1(RS-232)
Table B- 5. PORT1 Setting item
Title Description Level Initial value
Baud Rate PORT1 Baud Rate (1200, 2400, 4800, 9600, 19200 bps) - 1200 bps

Parity Bit Whether to use Parity Bit (NONE, ODD, EVEN) - NONE

Data Bit Data Bit number setting (7, 8) 1 8

Stop Bit Stop Bit number setting (1, 2) 1 1

Modem Sel Communication modem setting (2W, 4W, D1, D2, NONE) - 4W

CTS Usage Whether to use CTS signal (ON, OFF) - ON

DCD Usage Whether to use DCD signal (ON, OFF) - ON

RTS Usage Whether to use RTS signal (ON, OFF, AUTO) - AUTO

CTS CheckOut CTS check-out time (1 ~ 255 sec) 1 2

DCD CheckOut DCD check-out time (10 ~ 30000 msec) 5 5000

RTS OffDelay RTS off time delay (10 ~ 500 msec) 5 50

Baud Rate
Select communication rate of PORT1.

Parity Bit
Select whether to use Parity Bit and its type.

Data Bit
Select Data Bit for communication.

Stop Bit
Select the Stop Bit for communication.

Modem Sel
Select a modem for communication.
2W : 2 wire private line is used and continuously Carrier is monitored to control data flow by
DCD(Data Carrier Detect).
4W : 4 wire private line is used and RTS(Request To Send) and CTS(clear to Send) signal are
used to control data flow.
D1 : Dial-Up1 modem is used.
D2 : Dial -Up2 modem is used.

ENHANCED TECHNOLOGY 9
DNP3.0 PROTOCOL http://www.entecene.co.kr

. Note) ETR300 supports Hayes compatible modem in PORT1 for remote dial up access. Details
about Dialup Modem support are same as B-2. Dialup Modem Setting.

CTS Usage
Select whether to use CTS signal.
ON: After confirm CTS signal is Asserted, transfer a data.
OFF: Regardless of CTS signal, transfer a data.

DCD Usage
Select whether to use DCD signal.
ON: After confirm DCD signal is Deasserted, transfer a data.
OFF: Regardless of DCD signal, transfer a data.

RTS Usage
ON: RTS signal of ETR300 is always ON (Assert).
OFF: RTS signal of ETR300 is always OFF (Deassert).
AUTO: On requesting data transfer to Modem, after RTS signal of ETR300 is ON and after
data transfer completion, RTS signal of ETR300 is OFF.

Modem Setting (RTS OffDelay, CTS ChkOut, DCD Timeout)


This setting is for an effective transmission according to use modem characteristics.
RTS Off Delay : Set the delay time of RTS OFF after data transmission.
CTS CheckOut : Set a waiting time that waits CTS signal after RTS signal is ON. In case of
radio communication system, when transfer data at the same time from various Slave, it
produces transmission permission delay time due to the wireless network traffic congestion.
By this setting, try the transmission with high RTS during that checkout time. It is available if
CTS Usage setting is ON.
DCD Timeout : Set a delay time of DCD in case that use 2 wire type. It is available if DCD
Usage setting is ON.

ENHANCED TECHNOLOGY 10
DNP3.0 PROTOCOL http://www.entecene.co.kr

(2) PORT2(RS-485)
Table B- 6. PORT2 Setting item
Title Explanation Level Initial Value
Baud Rate PORT2 Baud Rate (1200, 2400, 4800, 9600, 19200 bps) - 1200 bps

Parity Bit Whether to use Parity Bit (NONE, ODD, EVEN) - NONE

Data Bit Data Bit Setting (7, 8) 1 8

Stop Bit Stop Bit Setting (1, 2) 1 1

Line Type Physical Communication Port(RS422, RS485) - RS422

CA Delay Collision Avoidance Delay time (0.0 ~ 240.00 sec) 0.01 1.00

Baud Rate
Select Baud Rate of PORT1.

Parity Bit
Set whether to use Parity Bit, and set a type.

Data Bit
Select the Data Bit for communication.

Stop Bit
Select Stop Bit for communication.

Line Type
Select a physical port for communication.

CA Delay
Set a delay time from data received till transferring a reply data.

ENHANCED TECHNOLOGY 11
DNP3.0 PROTOCOL http://www.entecene.co.kr

(3) PORT3(ETHERNET)
Table B- 7. PORT3 Setting item
Title Description Level Initial Value
IP Addr Oct1 IP Address First of ETR300 (0 ~ 255) 1 0

IP Addr Oct2 IP Address Second of ETR300 (0 ~ 255) 1 0

IP Addr Oct3 IP Address Third of ETR300 (0 ~ 255) 1 0

IP Addr Oct4 IP Address Fourth of ETR300 (0 ~ 255) 1 0

Gateway Oct1 Gateway Firs of ETR300 t (0 ~ 255) 1 0

Gateway Oct2 Gateway Second of ETR300 (0 ~ 255) 1 0

Gateway Oct3 Gateway Third of ETR300 (0 ~ 255) 1 0

Gateway Oct4 Gateway Fourth of ETR300 (0 ~ 255) 1 0

Subment Mask Oct1 Subment Mask First of ETR300 (0 ~ 255) 1 0

Subment Mask Oct2 Subment Mask Second of ETR300 (0 ~ 255) 1 0

Subment Mask Oct3 Subment Mask Third of ETR300 (0 ~ 255) 1 0

Subment Mask Oct4 Subment Mask Fourth of ETR300 (0 ~ 255) 1 0

IP Addr Oct1 ~ 4
Set the IP Address for ETR300. For example, if IP Adress of ETR300 is 255.255.255.255, set as
following.
IP Addr Oct1 : 255
IP Addr Oct2 : 255
IP Addr Oct3 : 255
IP Addr Oct4 : 255

Gateway Oct1 ~ 4
Set the Gateway Address. Setting method is same as IP Address.

Subment Mask Oct1 ~ 4


Set the Subment Mask Address. Setting method is same as IP Address.

ENHANCED TECHNOLOGY 12
DNP3.0 PROTOCOL http://www.entecene.co.kr

Configuration for DNP 3.0


Table C- 1. DNPTM 3.0 Protocol Setting Item

Title Description Level Initial Value


Function Whether to use DNP1(or DNP2) (ON, OFF) - ON
COM Port Communication Port Setting (PORT1, PORT2, PORT3) - PORT1
D/L Confirm Data Link Confirm Mode (NO, YES, SOME) - SOME
D/L FrameDly Data Link frame Delay Time (10 ~ 5000 msec) 10 100msec
D/L Retries Data Link Retries (0 ~ 2) 1 0
D/L Timeout Data link layer time-out (1 ~ 255 sec) 1 10sec
A/L Retries Application Link Retries (0 ~ 2) 1 0
A/L Timeout Application layer time-out (1 ~ 255 sec) 1 15sec
Fault I Report Fault Event Report Method Setting (NO, YES, 1SHOT) - YES
Fault I Reset Fault Event Reset Method Setting (NO, YES) NO
Master Addr Master Station Address Setting (0 ~ 65534) 1 65534
DNP Address Slave(ETR300) Address (0 ~ 65534) 1 1
SBO Time Select before operate time-out (1 ~ 255 sec) 1 15sec
Debounce Time Debounce Time Setting (10 ~ 100 msec) 5 20msec
Aver.Load Calc T Aver. Load Current Calc. Time (1,2,3,4,5,6,10,12,15,20,30 min) - 15min
Daily Max I Whether to process Daily Max. Load Current Event (DISABLE, - ENABLE
ENABLE)
Init Unsol Whether to use Init Unsol when restart (DISABLE, ENABLE) - ENABLE
Class1 Unsolicited mode Setting of Class 1 (DISABLE, ENABLE) - ENABLE
Class2 Unsolicited mode of Class 2 (DISABLE, ENABLE) - ENABLE
Class3 Unsolicited mode of Class 3 (DISABLE, ENABLE) - ENABLE
Unsol Time Transfer time to Master station when occurs unsolicited event(0 1 5sec
~ 60 sec)
VOC Level(%) VOC(Value of Change) Detect Level (OFF, 1 ~ 50%) 1 OFF
VOC Min VOC Minimum value (0 ~ 630A) 100A
VOC Select VOC Detect Current Setting (RMS, AVER) - AVER
TCT/IP Port TCP/IP Port Setting (0 ~ 65535) 1 0
Master IP Oct1 Master IP Address First(0 ~ 255) 1 0
Master IP Oct2 Master IP Address Second(0 ~ 255) 1 0
Master IP Oct3 Master IP Address Third(0 ~ 255) 1 0
Master IP Oct4 Master IP Address Fourth(0 ~ 255) 1 0

ENHANCED TECHNOLOGY 13
DNP3.0 PROTOCOL http://www.entecene.co.kr

Function
Select whether to use DNPTM 3.0 Protocol.

COM Port
Set physical port to use DNPTM 3.0 Protocol.

. Note) If DNPTM 3.0 Protocol use RS-485 Port (PORT2), even Unsolicited Class is ENABLE,
does not produce Unsolicited Response to prevent a physical damage.

D/L Confirm
Set whether to request Confirmation from Data Link system.
Sometime: Use Data Link Confirm only in case of Multi-frame (Request link reset at first
Reset) .
Yes : Request Confirm of every transfer D/L Frame.
No : Does not Request Confirm of every transfer Frame.

D/L FrameDly
Set Data Link frame Delay Time. If D/L Confirm setting is OFF, it is transfer interval between
frames when occur Multi-frame.

D/L Setting(Retries, Timeout)


Set Retries and Time out of Data Link Layer. These settings are applied when transfer D/L data that
request Confirm from Slave to Master.
As D/L Timeout is a waiting time till receiving D/L confirm(ACK) of Master side after D/L
frame transfer, if becames CTS, DCD timeout regards as transfer failure and handle the D/L,
A/L timeout as fail.
Progress D/L timer from the first byte transmission of D/L frame and receive all datas that
first byte of Master D/L confirm (ACK) started to receive within D/L timeout.

A/L Setting (Retries, Timeout)


Set Retries and Timeout of Application Link Layer.
A/L Timeout is a transfer time that Confirm Data reach to Slave Appliation from Master
Application, in case that request Confirm when transfer data from Slave Application to
Master Application.
If it is D/L Timeout, A/L Timer is not processed and handle in fail.

ENHANCED TECHNOLOGY 14
DNP3.0 PROTOCOL http://www.entecene.co.kr

Application data receive timeout about reqeust is also applied identically (ACK is included
when transfer application user data ).
Retry by Confirm Timeout is not performed. Perform only A/L Retry.

Fault I Report
Set whether to transfer Sequence Fault Current Event.
NO: All Sequence Fault Current Event are not transfered.
YES: All Sequence Fault Current are transferred to event.
1SHOT: Transfer the first Sequence Fault current of Fault Sequence to the event.

D/L Confirm
Set whether to initialize the Fault Current.
NO: Maintain the final Fault Current value even Fault Event is cleared
YES: When Fault Event is cleared, fault current is initialized in 0.

Address(Master Address, DNP Address)


Master Address : Set Master Address. Set Reference Address when transfer Unsolicited
Response Message.
DNP Address : Set DNP Address. (ETR300)

SBO Time
Select time interval of Select Function and Operate Function. After receiving Select order, if there
isnt an operation order during SBO Time, Select order is cancelled.

Debounce Time
Set Contact Chattering Time. Chattering Time of ooor open information is fixed in 1 second.

Aver. Load Calc T


Set the time interval to measure the Average Lpad Calculation Time.

ENHANCED TECHNOLOGY 15
DNP3.0 PROTOCOL http://www.entecene.co.kr

Daily Max I
Select whether to transfer Daily Maximum Load Current.
DISABLE: Daily Max. Load Current is not handled as Event.
ENABLE: Daily Max. Load Current is handled as Event.

Unsolicited Mode (Init Unsol, Unsol time)


Init Unsol: Set whether to use Initial Unsolicited Response when restart.
- If Init Unsol is Enable, Initial Insolicited Response Message is produced shen Power Up.
When Event is produced according to the Master Class designaiton or local setting value,
can be transferred voluntarily.
- Request Application Layer Confirm when transfer Unsolicited Response Message.
- If request D/L Confirm(Yes, Sometimes), Link Reset and then transfer Unsolicited
Response if Link Rest has not done before.
- If Unsolicited Class is Enable, transfers Initial Unsolicited Response Message with the
unsent Event Data. (Does not IIN Class Bit Set).
- If Unsolicited Class is Disable, transfer the Unsolicited Response Message with the
relevant INN Class Bit Set of Event Data.
Unsol Time is Unsolicited Response Delay Time. It is stabilization wait time from the last
Event till unchanged status.
It is to solve other RTU communication faulty and main device information processing
overburden caused by wireless frequency channel occupancy increase by increased
communication number because of the meaningless information produced during RTU
fault and control side fault.
Unsolicited Confirmation Timeout applies Application Timeout( Because requests the
Application Confirm).
Retry of Unsolicited Response(Initial and Event Unsolicited Response) applies Application
Retries.
When Device waits Confirmation of Intial Unsolicited Response, respond normally about All
Function Request(Read Function Request included) (Test Procedure apply).
If the Device has received Confirm of Initial Null Unsolicited Response Message in case that
Unsolicited Class is Disable, it does not send Unsolicited Response until receiving function
code 0x14(enable data-filled unsolicited message) request from Master or is set in Enable the
Insolicited Class of local LED.
Maintain the setting information about prior Class when Restart the RTU.
Event Data that did not receive A/L Confirm after transfer (A/L retry included) prior
Unsolicited Response Message is sent when occurs the next Event or when receive Event

ENHANCED TECHNOLOGY 16
DNP3.0 PROTOCOL http://www.entecene.co.kr

Polling Request from Master


Unsolicited Class (Class1, Class2, Class2)
Set Unsolicited response of each Event Class. In ENABLE setting case, transfer the Unsolicited
Message if Event is produced.

Value of Change (VOC Level, VOC Min, VOC Select)


VOC Level Set VOC(Value of Change) Detect Level.
- If is OFF does not make the Event information.
- Analog input fluctuation rate is displayed in percentage and it is reported if the
fluctuation rated is higher than setting point.
VOC Min set Minimum Current to detect VOC.
- It is a setting value to prevent the transfer through the communication in case that Analog
input is under minimum value.
VOC Select choose the current used for VOC judgement.
- RMS : Applies effective value to VOC detection.
- AVER : Applies Average value to VOC detection.

TCP/IP Port
Set the TCP/IP Port number of RTU.

Master IP Oct1 ~ 4
Set Master IP Address. For example, If Master IP address is 192.168.32.4 set as following.
Master IP Oct1 : 192
Master IP Oct2 : 168
Master IP Oct3 : 32
Master IP Oct4 : 4

ENHANCED TECHNOLOGY 17
DNP3.0 PROTOCOL http://www.entecene.co.kr

C. Dialling Modem Support

ETR300 can support a Hayes compatible Modem on Port 1(RS-232) for remote dial up access
using DNP3.

(1) Configure modem with AT commands


Before using of Modem connected with ETR300, following setting shall be confirmed.

Configure port speed(must be done)


Set DNP communication speed the same as the speed between ETR300 and Modem, and set DNP
communication speed slower than the speed between modems.

Configure answer mode(frequently)


The modem will answer an incoming call on the second ring using the command ATS0=2.

Configure Data Carrier Detect(must be done)


Data Carrier Detect should follow the presence or absence of a calling modem.
The AT command is AT&C1.

Configure Data Terminal Ready(must be done)


Data Terminal Ready should control the modem. If DTR is high the modem is ready to receive
calls. If DTR is low the modem should not receive any more calls and should hang up any existing
call.
The AT command is AT&D2.

Configure Data Set Ready(must be done)


Data Set Ready should verify the modem. DSR is always ON.
The AT command is AT&S0.

Configure no CONNECT messages(must be done)


A Hayes AT-style modem usually outputs a message when a call is received. For example:

CONNECT 9600
The modem has a "quiet mode" that disables these messages.
The AT command is ATQ1. There will be no OK printed in response to this command.

ENHANCED TECHNOLOGY 18
DNP3.0 PROTOCOL http://www.entecene.co.kr

Configure no echo of commands(must be done)


Echoing commands can confuse the console, so turn off command echoing.
The AT command is ATE0.

Configure silent connection(must be done)


Most modems have a speaker. By default this is connected whilst a modem is connecting and
negotiating a common protocol and speed. This is very useful for a dialing modem, as it prevents a
human being accidentally repeatedly called. The speaker can be annoying on answering modems.
The AT command is ATM1.

(2) H-2 Operation functions when to use Dialling Modem


Transmitting a DNP3.0 Packet
Checks DCD is asserted(Check Online)
The DNP3.0 packet is transmitted
Dial when DCD is Deassert

Receiving a DNP3.0 Packet


Checks DCD is asserted(Check Online)
The DNP3.0 packet is received
if DCD is Deassert, receiving is not working.

Dialling
The user should insert an order for Reset.
Wait 0.5 second
Make a phone call by using Dialling String and Dialling Number.
Checks DCD is Asserted
Dial connection waiting time is depending on Data Link Timeout set by the user.

Hang up
DTR Line is deasserted
Wait 2 second
DTR Line is asserted
Wait 2 second
ETR300 will hang up the modem after a delay of 30 seconds with no valid packet received or transmitted.

ENHANCED TECHNOLOGY 19
DNP3.0 PROTOCOL http://www.entecene.co.kr

(3) Configuration for Dialling Modem


Table D-1. Configuration for Dialling Modem
Setting Item Definition In step of Initial Value
Dialling String Dialling Method (ATD, ATDT, ATDP) - ATD

Dialling Number Master Station Phone Number (16Digits number) - -

Initial String AT Commands for Initialized (30 digits(Alphabet capital or symbol) - AT+FCLASS=0

Dialing String
Select a proper dial string in accordance with communication circumstance(Master or Switchboard
dial method)
- ATD : Default Dial Type(Already setup in modem;Default Dial)
- ATDT : Tone Dial
- ATDP : Pulse Dial

Dialling Number
Insert call number to call to. [Modem(Master station) phone number]. Total 16 digits shall be used
from the first digit space and empty space shall be filled up by X.

Initial String
Modem can be reset by inserting total 30 digits String.
ETR300 should be reset before making a phone call(connection).
Continuous double Space or / shall ingnor next String.

ENHANCED TECHNOLOGY 20
DNP3.0 PROTOCOL http://www.entecene.co.kr

D. DNP 3.0 Device Profile


Table E-1. DNP 3.0 Device Profile (1/4)

DNP V3.00
DEVICE PROFILE DOCUMENT

This document must be accompanied by a table having the following headings :

Object Group Request Function Codes Response Function Codes


Object Variation Request Qualifiers Response Qualifiers
Object Name (optional)

Vendor Name : ENTEC Electric & Electronic CO.,LTD

Device Name : Recloser Control(ETR300-S01)

Highest DNP Level Supported : Device Function :


For Requests Level 2 Master Slave
For Responses Level 2

Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP
Levels Supported (the complete list is described in the attached table) :

Supports Enabling and Disabling of Unsolicited Report On a Class basis


Supports 16-Bit Delta Counter Change Event with Time.
__________________________________________________________

Maximum Data Link Frame Size (octets) : Maximum Application Fragment Size (octets) :
Transmitted 292 Transmitted 2048
(if>2048,must be configurable)
Received (must be 292) Received 2048 (must be >= 249)

ENHANCED TECHNOLOGY 21
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table D-1. DNP 3.0 Device Profile (2/4)

Maximum Data Link Re-tries : Maximum Application Layer Re-tries :


None None
Fixed at Configurable, range 0 to 2
Configurable, range 0 to 2 FF(Fixed is not permitted)

Requires Data Link Layer Confirmation :

Never
Always
Sometimes If Sometimes, when?
Configurable If Configurable, how? By Setting (If Sometime, when Reporting
multi-frame.)

Requires Application Layer Confirmation :

Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes If Sometimes, when?
Configurable If Configurable, how?

Timeouts while waiting for :

Data Link Confirm None Fixed at ___ Variable Configurable


Complete Appl. Fragmen None Fixed at ___ Variable Configurable
Application Confirm None Fixed at ___ Variable Configurable
Complete Appl. Response None Fixed at ___ Variable Configurable

Others
Attach explanation if 'Variable' or 'Configurable' was checked for any timeout.

ENHANCED TECHNOLOGY 22
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table E-1. DNP 3.0 Device Profile (3/4)


Sends/Executes Control Operations :

WRITE Binary Outputs Never Always Sometimes Configurable


SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable
Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.

Reports Binary Input Change Events when Reports time-tagged Binary Input Change
no specific variation requested : events when no specific variation requested :

Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the other Configurable (attach explanation)
fff(attach explanation)

Sends Unsolicited Responses : Sends Static Data in Unsolicited Responses :

Never Never
Configurable (attach explanation) When Device Restarts
Only certain objects When Status Flags Change
Sometimes (attach explanation)

ENABLE/DISABLE UNSOLICITED No other options are permitted.


ffffunction codes supported

ENHANCED TECHNOLOGY 23
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table E-1. DNP 3.0 Device Profile (4/4)

Default Counter Object/Variation : Counters Roll Over at :

No Counters Reported No Counters Reported


Configurable (attach explanation) Configurable (attach explanation)
Default Object 20 16 Bits
fffDefault Variation 6 32 Bits
Point-by-point list attached Other Value
Point-by-point list attached

Sends Multi-Fragment Responses : Yes No

ENHANCED TECHNOLOGY 24
DNP3.0 PROTOCOL http://www.entecene.co.kr

E. DNP 3.0 Implementation Table


Table F-1. DNP 3.0 IMPLEMENT (1/6)
REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(hex) Codes(dec) Codes(hex)

1 0 Binary Input All Variations 1 00, 01, 06

07, 08, 00, 01, 07


1 1* Binary Input 1 129
17, 28 08, 17, 28

07, 08, 00, 01, 07


1 2 Binary Input with Status 1 129
17, 28 08, 17, 28

2 0 Binary Input Change - All Variations 1 06, 07, 08

2 1 Binary Input Change without Time 1 06, 07, 08 129, 130 17, 28

2 2* Binary Input Change with Time 1 06, 07, 08 129, 130 17, 28

2 3 Binary Input Change with Relative Time

00, 01,

10 0 Binary Output - All Variations 1 06, 07,

08, 17, 28

10 1 Binary Output

00, 01
00, 01 07,
10 2* Binary Output Status 1 06, 07, 129
08, 17, 28
08, 17, 28

12 0 Control Block - All Variations

echo of
12 1 Control Relay Output Block 3, 4, 5, 6 17, 28 129
request

12 2 Pattern Control Block

12 3 Pattern Mask

00, 01
1
20 0 Binary Counter - All Variations 06, 07,

08, 17, 28

20 1 32-Bit Binary Counter

20 2 16-Bit Binary Counter

20 3 32-Bit Delta Counter

20 4 16-Bit Delta Counter

ENHANCED TECHNOLOGY 25
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table F-1. DNP 3.0 IMPLEMENT (2/6)


REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(hex) Codes(dec) Codes(hex)

1 00, 06, 07, 00, 01, 07,


20 5 32-Bit Binary Counter without Flag 129
08, 17, 28 08, 17, 28

1 00, 06, 07, 00, 01, 07,


20 6* 16-Bit Binary Counter without Flag 129
08, 17, 28 08, 17, 28

20 7 32-Bit Delta Counter without Flag

20 8 16-Bit Delta Counter without Flag

21 0 Frozen Counters - All Variations

21 1 32-Bit Frozen Counter

21 2 16-Bit Frozen Counter

21 3 32-Bit Frozen Delta Counter

21 4 16-Bit Frozen Delta Counter

32-Bit Frozen Counter with Time of


21 5
Freeze

16-Bit Frozen Counter with Time of


21 6
Freeze

32-Bit Frozen Delta Counter with Time


21 7
of Freeze

16-Bit Frozen Delta Counter with Time


21 8
of Freeze

21 9 32-Bit Frozen Counter without Flag

21 10 16-Bit Frozen Counter without Flag

32-Bit Frozen Delta Counter without


21 11
Flag

16-Bit Frozen Delta Counter without


21 12
Flag

22 0 Counter Change Event - All Variations 1 06, 07, 08

32-Bit Counter Change Event without


22 1 1 06, 07, 08 129 17, 28
Time

16-Bit Counter Change Event without


22 2 1 06, 07, 08 129 17, 28
Time

ENHANCED TECHNOLOGY 26
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table F-1. DNP 3.0 IMPLEMENT (3/6)


REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(dec) Codes Codes(hex)

32-Bit Delta Counter Change Event


22 3
without Time

16-Bit Delta Counter Change Event


22 4
without Time

22 5 32-Bit Counter Change Event with Time 1 06, 07, 08 129 17, 28

22 6 16-Bit Counter Change Event with Time 1 06, 07, 08 129 17, 28

32-Bit Delta Counter Change Event with


22 7 1 06, 07, 08 129 17, 28
Time

16-Bit Delta Counter Change Event with


22 8* 1 06, 07, 08 129, 130 17, 28
Time

23 0 Frozen Counter Events - All Variations

32-Bit Frozen Counter Event without


23 1
Time

32-Bit Delta Counter Change Event


22 3
without Time

16-Bit Delta Counter Change Event


22 4
without Time

32-Bit Frozen Delta Counter Event


23 3
without Time

16-Bit Frozen Delta Counter Event


23 4
without Time

23 5 32-Bit Frozen Counter Event with Time

23 6 16-Bit Frozen Counter Event with Time

32-Bit Frozen Delta Counter Event with


23 7
Time

16-Bit Frozen Delta Counter Event with


23 8
Time

00, 01,

30 0 Analog Input - All Variations 1 06, 07,

08, 17, 28

ENHANCED TECHNOLOGY 27
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table F-1. DNP 3.0 IMPLEMENT (4/6)


REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(hex) Codes(dex) Codes(hex)

00, 01,
00, 01, 07
30 1 32-Bit Analog Input 1 06, 07, 129
08, 17, 28
08, 17, 28

00, 01,
00, 01, 07
30 2* 16-Bit Analog Input 1 06, 07, 129
08, 17, 28
08, 17, 28

00, 01,
00, 01, 07
30 3 32-Bit Analog Input without flag 1 06, 07, 129
08, 17, 28
08, 17, 28

00, 01,
00, 01, 07
30 4 16-Bit Analog Input without flag 1 06, 07, 129
08, 17, 28
08, 17, 28

31 0 Frozen Analog Input - All Variations

31 1 32-Bit Frozen Analog Input

31 2 16-Bit Frozen Analog Input

32-Bit Frozen Analog Input with Time


31 3
of Freeze

16-Bit Frozen Analog Input with Time


31 4
of Freeze

32-Bit Frozen Analog Input without


31 5
Flag

16-Bit Frozen Analog Input without


31 6
Flag

32 0 Analog Change Event - All Variations 1 06 ,07, 08

32-Bit Analog Change Event without


32 1 1 06 ,07, 08 129 17, 28
Time

16-Bit Analog Change Event without


32 2 1 06 ,07, 08 129 17, 28
Time

32 3 32-Bit Analog Change Event with Time 1 06 ,07, 08 129 17, 28

32 4* 16-Bit Analog Change Event with Time 1 06 ,07, 08 129, 130 17, 28

ENHANCED TECHNOLOGY 28
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table F-1. DNP 3.0 IMPLEMENT (5/6)


REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(hex) Codes(dec) Codes(hex)

33 0 Frozen Analog Event - All Variations

32-Bit Frozen Analog Event without


33 1
Time

16-Bit Frozen Analog Event without


33 2
Time

33 3 32-Bit Frozen Analog Event with Time

33 4 16-Bit Frozen Analog Event with Time

40 0 Analog Output Status - All Variations 1 00 ,01, 06

07, 08 00, 01, 07


40 1 32-Bit Analog Output Status 1 129
17, 28 08, 17, 28

07, 08 00, 01, 07


40 2* 16-Bit Analog Output Status 1 129
17, 28 08, 17, 28

41 1 32-Bit Analog Output Block

echo of
41 2 16-Bit Analog Output Block 3, 4, 5, 6 17, 28 129
request

50 0 Time and Date - All Variations 1 06, 07, 08 129 07

07,
2
quantity=1
50 1* Time and Date
07, 00, 07
1 129
quantity=1 quantity=1

50 2 Time and Date with Interval

51 0 Time and Date CTO - All Variations

07,
51 1 Time and Date CTO 129
quantity=1

07,
51 2 Unsynchronized Time and Date CTO 129
quantity=1

52 0 Time Delay - All Variations

07,
52 1 Time Delay Coarse 129
quantity=1

07,
52 2 Time Delay Fine 129
quantity=1

ENHANCED TECHNOLOGY 29
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table F-1. DNP 3.0 IMPLEMENT (6/6)


REQUEST RESPONSE
DNP 3.0 IMPLEMENT
(salve must parse) (master must parse)

Var Func Qual Func Qual


obj Description
* Default Codes(dec) Codes(hex) Codes(dec) Codes(hex)

60 0 Not Defined

60 1 Class 0 Data 1 06

60 2 Class 1 Data 1 06, 07, 08

20, 21 06

60 3 Class 2 Data 1 06, 07, 08

20, 21 06

60 4 Class 3 Data 1 06, 07, 08

20, 21 06

70 1 File Identifier 2 1b 129 1b

80 1 Internal Indications

00, index=7

81 1 Storage Object

82 1 Device Profile

83 1 Private Registration Object

83 2 Private Registration Object Descriptor

90 1 Application Identifier

100 1 Short Floating Point

100 2 Long Floating Point

100 3 Extended Floating Point

101 1 Small Packed Binary-Coded Decimal

ENHANCED TECHNOLOGY 30
DNP3.0 PROTOCOL http://www.entecene.co.kr

F. DNP 3.0 Point Table


Table G-1. DNP 3.0 INDEX - BINARY INPUT (1/4)
Index Assigned
Classification Point Name Object/Variation Remark
No. Class
0 Switch Status 0, 1 01/01,01/02,02/02

1 Switch Trouble 0, 1 01/01,01/02,02/02


Switch
2 Handle Status 0, 2 01/01,01/02,02/02

3 Reserved 0, 2 01/01,01/02,02/02

4 Control Mode 0, 2 01/01,01/02,02/02

5 Control Status 0, 2 01/01,01/02,02/02

6 External Power Fail 0, 2 01/01,01/02,02/02


Control Box
7 Door Status 0, 2 01/01,01/02,02/02

8 Battery & Charger Fail 0, 1 01/01,01/02,02/02

9 Battery Discharge 0, 1 01/01,01/02,02/02

10 Section Lockout 0, 1 01/01,01/02,02/02


Auxiliar
11 Section Running 0, 1 01/01,01/02,02/02
cooperation
12 Setting Group 0, 1 01/01,01/02,02/02

13 Phase Loss A 0, 2 01/01,01/02,02/02

14 Phase Loss B 0, 2 01/01,01/02,02/02

15 Phase Loss C 0, 2 01/01,01/02,02/02

16 Phase Loss R 0, 2 01/01,01/02,02/02

17 Phase Loss S 0, 2 01/01,01/02,02/02

18 Phase Loss T 0, 2 01/01,01/02,02/02


Line
19 Phase Sync Fail 0, 2 01/01,01/02,02/02
Information
20 Lin Status (Source) 0, 1 01/01,01/02,02/02

21 Lin Status (Load) 0, 1 01/01,01/02,02/02

22 Power flow Forward 0, 2 01/01,01/02,02/02

23 Power Flow Reverse 0, 2 01/01,01/02,02/02

24 Over Current A 0, 2 01/01,01/02,02/02

25 Over Current B 0, 2 01/01,01/02,02/02

26 Over Current C 0, 2 01/01,01/02,02/02

27 Over Current N 0, 2 01/01,01/02,02/02

ENHANCED TECHNOLOGY 31
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-1. DNP 3.0 INDEX - BINARY INPUT (2/4)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
28 FI A 0, 1 01/01,01/02,02/02
29 FI B 0, 1 01/01,01/02,02/02
30 FI C 0, 1 01/01,01/02,02/02

31 FI N 0, 1 01/01,01/02,02/02

32 SEF 0, 1 01/01,01/02,02/02
Fault 33 Zero Seq. Voltage Detect 0, 1 01/01,01/02,02/02

34 Fault Permanent 0, 1 01/01,01/02,02/02

35 Fault Temporary 0, 1 01/01,01/02,02/02

36 Fault Direction Forward 0, 1 01/01,01/02,02/02

37 Fault Direction Reverse 0, 1 01/01,01/02,02/02

38 Inrush Current Detect 0, 1 01/01,01/02,02/02

39 SAG A 0, 3 01/01,01/02,02/02

40 SAG B 0, 3 01/01,01/02,02/02

41 SAG C 0, 3 01/01,01/02,02/02

42 SWELL A 0, 3 01/01,01/02,02/02

43 SWELL B 0, 3 01/01,01/02,02/02

44 SWELL C 0, 3 01/01,01/02,02/02

45 INTERRUPTION A 0, 3 01/01,01/02,02/02

46 INTERRUPTION B 0, 3 01/01,01/02,02/02

47 INTERRUPTION C 0, 3 01/01,01/02,02/02

48 Over Voltage A 0, 3 01/01,01/02,02/02

49 Over Voltage B 0, 3 01/01,01/02,02/02


PQM
50 Over Voltage C 0, 3 01/01,01/02,02/02

51 Over Voltage R 0, 3 01/01,01/02,02/02

52 Over Voltage S 0, 3 01/01,01/02,02/02

53 Over Voltage T 0, 3 01/01,01/02,02/02

54 Under Voltage A 0, 3 01/01,01/02,02/02

55 Under Voltage B 0, 3 01/01,01/02,02/02

56 Under Voltage C 0, 3 01/01,01/02,02/02

57 Under Voltage R 0, 3 01/01,01/02,02/02

58 Under Voltage S 0, 3 01/01,01/02,02/02

59 Under Voltage T 0, 3 01/01,01/02,02/02

60 Voltage Unbalance (Source) 0, 3 01/01,01/02,02/02

ENHANCED TECHNOLOGY 32
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-1. DNP 3.0 INDEX - BINARY INPUT (3/4)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
61 Voltage Unbalance (Load) 0, 3 01/01,01/02,02/02

62 Current Unbalance 0, 3 01/01,01/02,02/02

63 Under Frequency 0, 3 01/01,01/02,02/02

64 Voltage THD(A) 0, 3 01/01,01/02,02/02

PQM 65 Voltage THD(B) 0, 3 01/01,01/02,02/02

66 Voltage THD(C) 0, 3 01/01,01/02,02/02

67 Current THD(A) 0, 3 01/01,01/02,02/02

68 Current THD(B) 0, 3 01/01,01/02,02/02

69 Current THD(C) 0, 3 01/01,01/02,02/02

70 RTU Self Diagnosis 0, 2 01/01,01/02,02/02


Diagnosis
71 Reserved 0, 2 01/01,01/02,02/02

Binary Input (BI) Definition


Contact Input or correspondent logic is [0] means removed status of correnspondent contact and
RESET status of logic. [1] means adhered status of correspondent contact and SET status of logic.

(1) Switch Status


Indicates Close/Open of Switch. Close is indicated in 1 and Open in 0.
(2) Switch Trouble
In case of Switch Trouble failure, 1 is displayed.
(3) Handle Status
Lock: 1 is displayed / Unlock: 0 is displayed
In case that switch is opened manullay, it is to take a quick step by checking the Lock in
local if closing is.
(4) Control Mode
Indicates Control operation status.
Local: 1 is displayed / Remote: 0 is displayed.
When Control Switch is set in local, all remote control and changes are impossible except
battery test.

(5) Control Status


Indicates Lock/Unlock status of Switch control box.

ENHANCED TECHNOLOGY 33
DNP3.0 PROTOCOL http://www.entecene.co.kr

Lock: 1 is displayed / Unlock: 0 is displayed.


All control function except Battery Test, Lamp Test, Local/Remote and Open Order are
stopped when it is Locked. (But, Fault Detect Function and Setting(Main Device, Control
Box) are available)
(6) External Power Fail
External Power Fail: 1 is displayed / Normal Status: 0 is displayed.
Internal Event storages live event considered the contact chattering tiem and is produced
considering the delay time. It is occurred if External Power Fail status is maintained during
AC Detect time of Delay time
(7) Door Status
Open: 1 is displayed / Close: 0 is displayed.
This information is to understand the local status (Consider whether to local access and
local device supervision).
Contact chattering time is fixed in 1 second.
(8) Battery and Charger Fail
Battery and Charger Fail: 1 is displayed / Normal Status: 0 is displayed.
Battery and Charger Contact Status Chattering Time are considered.
(9) Battery discharge
Battery discharge: 1 dis displayed / Normal Status: 0 is displayed.
When external power is lost and battery discharge signal is ON, battery is separated from
charger after 3 min, and manages with own event.
(10) Section Lockout
Lockout status after compledted section function: 1 is displayed / Normal Status: 0 is
displayed.
Light when open in local or remotely.
When close, Lockout is cleared after checking the close contact.
(11) Section Running
1 is displayed if the section function is running and 0 is displayed when Reset or Lockout
the section function.
(12) Setting Group
There are Primary and Alternate in Setting Bank.
1 is displayed if it is operating by Alternate setting group and 0 is displayed if it is operating
by Primary setting group.

(13) Phase Loss (Source Sid ABC, Load Side RST)


Phase Loss: 1 is displayed / Normal: 0 is displayed.

ENHANCED TECHNOLOGY 34
DNP3.0 PROTOCOL http://www.entecene.co.kr

As this information does not request quick answer, if maintain the status during On/Off
Level setting time of Delay Time, produces an Event with valid information.
(14) Phase Sync Fail
1 is displayed when Phase Sync is failure and 0 in normal status.
If Phase Sync Fail setting point is 0, status value is fixed in normal.
As this information does not request quick answer, if mainiain the status during Phase Sync
Fail Detection Time of Delay Time, produces an Event with valid information.
It is applied when contact is Opened and in Trouble.
(15) Lin Status(Source, Load)
1 is indicated if souce and load side is dead. 0 is displayed if are hot.
(16) Power Flow (Forward/Reverse)
Handle in Double Point, and indicates the Power Flow status.
(17) Retated to Fault
Fault Detect(A,B,C,N,SEF)
When detects Fault, indicates Fault Detect phase.
Permanent/Temporary Fault
When detects Fault, indicates Fault Type.
Fault Direction (Forward/Reverse)
When detects Fault, indicates Fault Direction by detecting current phase.
This element is activated when operates direction relay elements.
(18) Zero Seq. Voltage Detect
1 is displayed if Zero Seq. Voltage is detected over Pickup and 0 is displayed in normal
status.
This element is activated when high sensitivity ground element operates.
(19) Inrush Current Detect
1 is displayed when Inrush Current is detected and 0 is displayed in normal status.
(20) Related to PQ
Sag Detect (A,B,C)
1 is displayed when detects Sag and 0 in normal status.
RESET by PQ information clear order.
Swell Detect (A,B,C)
1 is displayed when detects Swell and 0 in normal sataus.
RESET by PQ information clear order.
Interruption Detect (A,B,C)
1 is displayed when detects Interruption and 0 in normal status.
RESET by PQ information clear order.

ENHANCED TECHNOLOGY 35
DNP3.0 PROTOCOL http://www.entecene.co.kr

Over Current(A,B,C,N)
Produces an Over Current when line current of each phase are maintained during over
current setting time.
1 is displayed when occur Over Current and 0 in normal status.
RESET by PQ information clear order.
Over Voltage (A,B,C,R,S,T)
Produces an Over Voltage when line current of each phase are maintained during over
voltage setting time.
1 is displayed when occur Over Voltage and 0 in normal status.
RESET by PQ information clear order. .
Under Voltage(A,B,C,R,S,T)
Produces an Under Current when line current of each phase are maintained during under
current setting time.
1 is displayed when occur UnderCurrent and 0 in normal status.
RESET by PQ information clear order.
Voltage Unbalance(Source/Load)
1 is displayed when detect Voltage Unbalance of Source and Load side and 0 in normal
status.
RESET by PQ information clear order.
Current Unbalance Detect
1 is displayed when detect Current Unbalance and 0 in normal status.
RESET by PQ information clear order.
Under Frequency
Produces an Under Frequency when line voltage of frequency is maintained during under
frequency setting time.
1 is displayed when produce Under Frequency and 0 in normal status.
RESET by PQ information clear order.
Voltage THD(A,B,C)
Produces Voltage THD when voltage THD distortion factor of each line phase is maintained
during the setting time.
1 is displayed when occurs Voltage THD and 0 in normal status.
RESET by PQ information clear order.

Current THD(A,B,C)
Produces Current THD when current THD distortion factor of each line phase is maintained
during the setting time.

ENHANCED TECHNOLOGY 36
DNP3.0 PROTOCOL http://www.entecene.co.kr

1 is displayed when occur Voltage THD and 0 in normal status.


RESET by PQ information clear order.
(21) RTU Self Diagnosis
Self diagnosis failure: 1 is displayed / Normal status: 0 is displayed.
ETR300 self diagnoses the following items related to operation.
DSP failure
- Handling period: within 200msec
- Handling method: Change to Fault Detect Restrain
ADC related circuit failure
- Handling period: every 1/4cycle
- Handling method: Change to Fault Detect Restrain
RTC failure
- Handling period: 1 hour, when booting
- Handling method: Change the date to Jan. 1st, 1970
Memory Failure
- Handling period: 1 hour, when booting
- Handling method: Start rebooting
Flash-Rom Failure
- Handling period: When read and write Flash-Rom, booting
- Handling method: Start rebooting
Circuit Voltage Failure
- Handling period: every 1/4cycle
- Handling method: Change to Fault Detect Restrain
Global/Primary/Alternate Setting value failure
- Handling period: When first Booting, change setting
- Handling method: Change to default setting point
Evnet Failure
- Handling period: When save and read event
- Handling method: Event initialization
Count Failure
- Handling period: When write and read count
- Handling method: Count initialization
DO Failure
- Handling period: Every 50msec
- Handling method: Block the output source
Closing Failure

ENHANCED TECHNOLOGY 37
DNP3.0 PROTOCOL http://www.entecene.co.kr

- Handling period: When close


- Handling method: Need to check in local
Opening Failure
- Handling period: When open
- Handling method: Need to check in local
Produes Self Diagnosis Failure Event when occurs Diagnosis failure.

ENHANCED TECHNOLOGY 38
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-2. DNP 3.0 INDEX ANALOG INPUT(1/3)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
0 RTU Self Diagnosis (Detail) 0 30/02,30/04 -

1 Device/Revision No. 0 30/02,30/04 -


Control Box
2 Marker / Version No. 0 30/02,30/04 -

3 RTU Temperature 0 30/02,30/04 1/1Count

4 Current A 0,2 30/02,30/04,32/04 1A/1Count

5 Current B 0,2 30/02,30/04,32/04 1A/1Count

6 Current C 0,2 30/02,30/04,32/04 1A/1Count

7 Current N 0,2 30/02,30/04,32/04 1A/1Count

8 Current SEF 0 30/02,30/04 0.001A/1Count

9 Current Angle A 0 30/02,30/04 0.1/1Count

10 Current Angle B 0 30/02,30/04 0.1/1Count

11 Current Angle C 0 30/02,30/04 0.1/1Count

12 Current Angle N 0 30/02,30/04 0.1/1Count

13 Current Angle SEF 0 30/02,30/04 0.1/1Count

14 Voltage A 0 30/02,30/04 1V/1Count

15 Voltage B 0 30/02,30/04 1V/1Count

16 Voltage C RMS 0 30/02,30/04 1V/1Count

17 Voltage R 0 30/02,30/04 1V/1Count


Power
18 Voltage S 0 30/02,30/04 1V/1Count
Information
19 Voltage T 0 30/02,30/04 1V/1Count

20 Voltage Angle A 0 30/02,30/04 0.1/1Count

21 Voltage Angel B 0 30/02,30/04 0.1/1Count

22 Voltage Angel C 0 30/02,30/04 0.1/1Count

23 Voltage Angel R 0 30/02,30/04 0.1/1Count

24 Voltage Angel S 0 30/02,30/04 0.1/1Count

25 Voltage Angel T 0 30/02,30/04 0.1/1Count

26 Apparent Power A 0 30/02,30/04 1KVA/1Count

27 Apparent Power B 0 30/02,30/04 1KVA/1Count

28 Apparent Power C 0 30/02,30/04 1KVA/1Count

29 Apparent Power (3) 0 30/02,30/04 1KVA/1Count

30 Active Power (3) 0 30/02,30/04 1KW/1Count

31 Reactive Power (3) 0 30/02,30/04 1KVar/1Count

32 Power Factor (3) 0 30/02,30/04 1%/1Count

ENHANCED TECHNOLOGY 39
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-2. DNP 3.0 INDEX ANALOG INPUT(2/3)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
33 Average Load Curent A 0,2 30/02,30/04,32/04 1A/1Count

34 Average Load Curent B 0,2 30/02,30/04,32/04 1A/1Count

35 Average Load Curent C 0,2 30/02,30/04,32/04 1A/1Count

36 Average Load Curent N 0,2 30/02,30/04,32/04 1A/1Count

Yesterday Maximum Load


37 0,2 30/02,30/04,32/04 1A/1Count
Current A

Yesterday Maximum Load


38 0,2 30/02,30/04,32/04 1A/1Count
Current B

Power Yesterday Maximum Load


39 0,2 30/02,30/04,32/04 1A/1Count
Information Current C
Yesterday Maximum Load
40 0,2 30/02,30/04,32/04 1A/1Count
Current N

41 Line-Line Voltage AB 0 30/02,30/04 1V/1Count

42 Line-Line Voltage BC 0 30/02,30/04 1V/1Count

43 Line-Line Voltage AB CA 0 30/02,30/04 1V/1Count

44 Line-Line Voltage RS 0 30/02,30/04 1V/1Count

45 Line-Line Voltage AB ST 0 30/02,30/04 1V/1Count

46 Line-Line Voltage AB TR 0 30/02,30/04 1V/1Count

47 First Fault Current A 0,1 30/02,30/04,32/04 1A/1Count

48 First Fault Current B 0,1 30/02,30/04,32/04 1A/1Count

49 First Fault Current C 0,1 30/02,30/04,32/04 1A/1Count

50 First Fault Current N 0,1 30/02,30/04,32/04 1A/1Count

Fault 51 Fault Current A 0,1 30/02,30/04,32/04 1A/1Count

52 Fault Current B 0,1 30/02,30/04,32/04 1A/1Count

53 Fault Current C 0,1 30/02,30/04,32/04 1A/1Count

54 Fault Current N 0,1 30/02,30/04,32/04 1A/1Count

55 Fault Current SEF 0,1 30/02,30/04,32/04 0.001A/1Count

56 SAG Duration A 0,3 30/02,30/04,32/4 1cycle/1Count

57 SAG Duration B 0,3 30/02,30/04,32/4 1cycle/1Count

58 SAG Duration C 0,3 30/02,30/04,32/4 1cycle/1Count

PQ 59 SWELL Duration A 0,3 30/02,30/04,32/4 1cycle/1Count

60 SWELL Duration B 0,3 30/02,30/04,32/4 1cycle/1Count

61 SWELL Duration C 0,3 30/02,30/04,32/4 1cycle/1Count

62 INTERRUPTION Duration A 0,3 30/02,30/04,32/4 1cycle/1Count

ENHANCED TECHNOLOGY 40
DNP3.0 PROTOCOL http://www.entecene.co.kr

63 INTERRUPTION Duration B 0,3 30/02,30/04,32/4 1cycle/1Count

64 INTERRUPTION Duration C 0,3 30/02,30/04,32/4 1cycle/1Count

65 SAG Magnitude A 0,3 30/02,30/04,32/4 1V/1Count

Table G-2. DNP 3.0 INDEX ANALOG INPUT(3/3)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
66 SAG Magnitude B 0,3 30/02,30/04,32/4 1V/1Count

67 SAG Magnitude C 0,3 30/02,30/04,32/4 1V/1Count

68 SWELL Magnitude A 0,3 30/02,30/04,32/4 1V/1Count

69 SWELL Magnitude B 0,3 30/02,30/04,32/4 1V/1Count

70 SWELL Magnitude C 0,3 30/02,30/04,32/4 1V/1Count

71 INTERRUPTION Magnitude A 0,3 30/02,30/04,32/4 1V/1Count

72 INTERRUPTION Magnitude B 0,3 30/02,30/04,32/4 1V/1Count

73 INTERRUPTION Magnitude C 0,3 30/02,30/04,32/4 1V/1Count


Voltage Unbalance Rate
74 0 30/02,30/04 1%/1Count
PQ (Source)
75 Voltage Unbalance Rate (Load) 0 30/02,30/04 1%/1Count

76 Current Unbalance Rate 0 30/02,30/04 1%/1Count

77 Frequency 0 30/02,30/04 0.01Hz/1Count

78 Voltage THD A 0 30/02,30/04 0.1%/1Count

79 Voltage THD B 0 30/02,30/04 0.1%/1Count

80 Voltage THD C 0 30/02,30/04 0.1%/1Count

81 Current THD A 0 30/02,30/04 0.1%/1Count

82 Current THD B 0 30/02,30/04 0.1%/1Count

83 Current THD C 0 30/02,30/04 0.1%/1Count

84 Reserved 0 30/02,30/04 1/1Count

85 Reserved 0 30/02,30/04 1/1Count

86 Battery Voltage 0 30/02,30/04 0.1V/1Count

87 Charger Voltage 0 30/02,30/04 0.1V/1Count

Diagnosis 88 Switch Life Time A 0 30/02,30/04 0.01%/1Count

89 Switch Life Time B 0 30/02,30/04 0.01%/1Count

90 Switch Life Time C 0 30/02,30/04 0.01%/1Count

91 Trasducer 1 0 30/02,30/04 0.1mA/1Count

92 Trasducer 2 0 30/02,30/04 0.1mA/1Count

ENHANCED TECHNOLOGY 41
DNP3.0 PROTOCOL http://www.entecene.co.kr

(Analog Input) AI Definition


(1) Diagnostics Details
This point is 16 bit data that shows switch diagnosis. When 1 is set in each set, indicates
that the following failures occurred.
- bit 0: Self diagnosis DSP Failure
- bit 1: Self diagnosis ADC Failure
- bit 2: Self diagnosis RTC Failure
- bit 3: Self diagnosis Memory Failure
- bit 4: Self diagnosis Flash-Rom Failure
- bit 5: Self diagnosis Circuit Voltage Failure
- bit 6: Self diagnosis Global Setting Failure
- bit 7: Self diagnosis Pri' Setting Failure
- bit 8: Self diagnosis Alt' Setting Failure
- bit 9: Self diagnosis Event Failure
- bit 10: Self diagnosis Count Failure
- bit 11: Self diagnosis DO Failure
- bit 12: Closing Failure
- bit 13: Opening Failure
- bit 14: Reserved
- bit 15: Reserved

(2) Type and Standard Revision Number

Table G-3. Point Definition


Point Definition
Classification Note
Upper 8bit Down 8bit
Standard Revision
No. 1 Device Type
Number

Indicates the device type (256 type possible setting).

Table G-4. Device Type Code


Device Type Code Binary code Hexadecimal Note
Load Break Switch 0000 0000 0
Recloser 0000 0001 1
Pad mount Switch 0000 0010 2
Pad mount Switchgear 0000 0011 3
Multi-function RTU 0000 0100 4

ENHANCED TECHNOLOGY 42
DNP3.0 PROTOCOL http://www.entecene.co.kr

Intelligent RTU 0000 0101 5


Intelligent Recloser 0000 0110 6
Standard Revision Number(no. 255 revision possible) is displayed.

Table G-5. Standard Revision Number Code


Standard Revision Number Binary code Hexadecimal Note
0(first written) 0000 0000 0
1(Revision 1) 0000 0001 1
2(Revision 2) 0000 0010 2
3(Revision 3) 0000 0011 3

(3) Company and Program version

Table G-6. Point Definition


Pint Definition
Classification Note
Upper 8bit Down 8 bit
No. 2 Supplier Program Version

Indicates Suppliers (possible to distinguish 256supplier, KEPCO supplier information


order).

Table G-7.Supplier Code


Supplier Binary code Hexadecimal Note
SHINSUNG Industrial Elec. 0000 0000 0
EN Technologies 0000 0001 1
ENTEC Electric and Electronic 0000 0010 2
JINKWANG E&C 0000 0011 3
Korea Electric Power Data Network 0000 0100 4

Indicates Program Version(Firmware Version).

Table G-8.Version Code


Classification Binary code Hexadecimal Note
Ver. 1.0 0001 0000 10
ver. 1.3 0001 0011 13
Ver. 2.0 0010 0000 20
Ver. 2.3 0010 0011 23

ENHANCED TECHNOLOGY 43
DNP3.0 PROTOCOL http://www.entecene.co.kr

(4) Current
Fundamental Wave RMS(A, B, C, N) : 1A/1Count
Fundamental Wave RMS(SEF(ZCT)) : 0.001A/1Count
(5) Current Angle
A, B, C, N : 0.1/1Count
SEF(ZCT) : 0.1/1Count
(6) Voltage
Fundamental Wave RMS (A, B, C, R, S, T) : 1V/1Count
Line-line Voltage(AB, BC, CA, RS, ST, TR) : 1V/1Count
(7) Voltage Angle
Voltage Angle(A, B, C, R, S, T) : 0.1/1Count
(8) Power
Apparent Power(A, B, C, 3phase) : 1kVA/1Count
Active Power(3phase) : 1kW/1Count
Reactive Power(3phase) : 1kVar/1Count
(9) Power Factor(3phase) : 1%/1Count
(10) Average Load Current(A, B, C, N) : 1A/1Count
Caluculate and update the Average Load Current every 15 minutes.
Update and Record internally in maximum value applying Block Demand value once in
Demand Calculation time.
1 hour maximum load current record the maximum value among 15 min. value.
(11) Yesterday Maximum Load Current (A, B, C, N) : 1A/1Count
Updates every midnight.
If System Restarts in the middle, update the value from Restart point to midnight.
(12) First Fault Current(A,B,C,N) : 1A/1Count
Indicates First Fault Current among Sequence Fault Current.
(13) Fault Current
Fault Current(A,B,C,N) : 1A/1Count
Faut Current(SEF) : 0.001A/1Count
If Event Set of Fault I Report is set in No all Sequence Fault Current (A,B,C,N) does not
produce Event. (All Fault Current sending is managed by self diagnosis)
If Event Set of Fault I Report is set in Yes all Sequence Fault Current (A,B,C,N) produce
Event. If 1 Shot is set, Fault Current of first FI occurrence is managed ad Event
Handle time of Fault Current Event is Permanent Fault and Temporary Fault Detect Time.
- All Fault Current Sendig is managed by Self Event.
- Fault Current save the maximum value of RMS that was maintained during each

ENHANCED TECHNOLOGY 44
DNP3.0 PROTOCOL http://www.entecene.co.kr

Sequence.
- Static Data is Updated every time that operates Sequence.
If Static Reset of Fault I Report is NO, Static Fault Current is maintained without being
Cleared and Update in next fault occurrence.
If Static Reset of Fault I Report is YES, Static Fault Current is Cleared in 0 when FI is
Reseted.
(14) SAG Duration(A,B,C) : 1cycle/1Count
(15) SWELL Duration(A,B,C) : 1cycle/1Count
(16) INERRUPTION Duration(A,B,C) : 1 cycle /1Count
(17) SAG Magnitude (A,B,C): 1V/1Count
Indicates the Voltage size when SAG is occurred.
(18) SWELL Magnitude (A,B,C): 1V/1Count
Indicates the Voltage size when SWELL is occurred.
(19) INTERRUPTION Magnitude(A,B,C): 1V/1Count
Indicates the Voltage size when INTERRUPTION is occurred.
(20) Current Unbalance Rate : 1%/1Count
Phase Rate [%] based on normal
(21) Voltage Unbalance (Source,Load) : 1%/1Count
Phase Rate [%] based on normal
(22) Frequency : 0.01Hz/1Count
(23) Voltage THD and relative harmonic factor (A,B,C) : 0.1%/1Count
THD, 1 ~ 31 relative harmonic factor is indicated.
(24) CurrentTHD and relative harmonic factor(A,B,C,N) : 0.1%/1Count
THD, 1 ~ 31 relative harmonic factor is indicated..
(25) Switch Life Time(A,B,C) : 0.01%/1Count
(26) Battery Voltage : 0.1V/1Count
Control box battery voltage is measured and displayed. Tolerance is 0.1V.
(27) Charger Voltage : 0.1V/1Count
(28) Control box charger voltage is measured and displayed. Tolerance is 0.1V. TD(1,2) :
0.1mA/1Count
Tranduser Input Current is displayed.

ENHANCED TECHNOLOGY 45
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-9. DNP 3.0 INDEX COUNTER INPUT(1/2)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
Switch 0 Switching Count 0 20/02, 20/06 0~65535

Control Box 1 RTU Restart Count 0 20/02, 20/06 0~65535

2 Permanent FI Count (Total) 0 20/02, 20/06 0~65535

3 Temporary FI Count (Total) 0 20/02, 20/06 0~65535

4 Permanent FI Count A 0 20/02, 20/06 0~65535

5 Permanent FI Count B 0 20/02, 20/06 0~65535

6 Permanent FI Count C 0 20/02, 20/06 0~65535

Fault 7 Permanent FI Count N 0 20/02, 20/06 0~65535

8 FI Count SEF 0 20/02, 20/06 0~65535

9 Temporary FI Count A 0 20/02, 20/06 0~65535

10 Temporary FI Count B 0 20/02, 20/06 0~65535

11 Temporary FI Count C 0 20/02, 20/06 0~65535

12 Temporary FI Count N 0 20/02, 20/06 0~65535

13 SAG Count (Total) 0 20/02, 20/06 0~65535

14 SAG Count A 0 20/02, 20/06 0~65535

15 SAG Count B 0 20/02, 20/06 0~65535

16 SAG Count C 0 20/02, 20/06 0~65535

17 SAG Instantaneous Count 0 20/02, 20/06 0~65535

18 SAG Momentary Count 0 20/02, 20/06 0~65535

19 SAG Temporary Count 0 20/02, 20/06 0~65535

20 Under voltage Count 0 20/02, 20/06 0~65535

21 SWELL Count (Total) 0 20/02, 20/06 0~65535

PQ 22 SWELL Count A 0 20/02, 20/06 0~65535

23 SWELL Count B 0 20/02, 20/06 0~65535

24 SWELL Count C 0 20/02, 20/06 0~65535

25 SWELL Instantaneous Count 0 20/02, 20/06 0~65535

26 SWELL Momentary Count 0 20/02, 20/06 0~65535

27 SWELL Temporary Count 0 20/02, 20/06 0~65535

28 Over Voltage Count 0 20/02, 20/06 0~65535

29 INTERRUPTION Count (Total) 0 20/02, 20/06 0~65535

30 INTERRUPTION Count A 0 20/02, 20/06 0~65535

31 INTERRUPTION Count B 0 20/02, 20/06 0~65535

ENHANCED TECHNOLOGY 46
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-9. DNP 3.0 INDEX COUNTER INPUT(2/2)


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
32 INTERRUPTION Count C 0 20/02, 20/06 0~65535

33 INTERRUPTION Momentary Count 0 20/02, 20/06 0~65535

34 INTERRUPTION Temporary Count 0 20/02, 20/06 0~65535

35 INTERRUPTION Sustained Count 0 20/02, 20/06 0~65535

INTERRUPTION Total Cumulitive


36 0 20/02, 20/06 0~65535 (sec)
Time

37 INTERRUPTION Cumulitive Time A 0 20/02, 20/06 0~65535 (sec)

38 INTERRUPTION Cumulitive Time B 0 20/02, 20/06 0~65535 (sec)

39 INTERRUPTION Cumulitive Time C 0 20/02, 20/06 0~65535 (sec)

INTERRUPTION Momentary
40 0 20/02, 20/06 0~65535 (sec)
Cumulitive Time

PQM INTERRUPTION Temporary


41 0 20/02, 20/06 0~65535 (sec)
Cumulitive Time

INTERRUPTION Sustained Cumulitive


42 0 20/02, 20/06 0~65535 (sec)
Time

43 Voltage THD Count (Total) 0 20/02, 20/06 0~65535

44 Voltage THD Count (A) 0 20/02, 20/06 0~65535

45 Voltage THD Count (B) 0 20/02, 20/06 0~65535

46 Voltage THD Count (C) 0 20/02, 20/06 0~65535

47 Current THD Count (Total) 0 20/02, 20/06 0~65535

48 Current THD Count (A) 0 20/02, 20/06 0~65535

49 Current THD Count (B) 0 20/02, 20/06 0~65535

50 Current THD Count (C) 0 20/02, 20/06 0~65535

51 RTU Self Diagnosis Error Count 0 20/02, 20/06 0~65535


Diagnosis
52 Reserved 0 20/02, 20/06 0~65535

Counter Definition
(1) Switching Count
1 Count is increased when it is opened.(16bit).
(2) RTU Restart Count
Restart Count is indicated (16bit).
(3) Permanent FI Count(, A, B, C, N, SEF)
It is increased when fault is detected(increase regardless of FI reset) (16bit).

ENHANCED TECHNOLOGY 47
DNP3.0 PROTOCOL http://www.entecene.co.kr

(4) Temporary FI Count(Total, A, B, C, N)


It is increased when fault is detected (increase regardless of FI reset) (16bit).
(5) SAG Count(Total, A, B, C, Instantaneous, Momentary, Temporary)
It is increased when Sag is occurred Sag (increase regardless PQM reset) (16bit).
(6) Swell Count(Total, A, B, C, Instantaneous, Momentary, Temporary)
It is increased when Swell is occurred (increase regardless PQM reset) (16bit).
(7) Interruption Count(Total, A, B, C, Momentary, Temporary, Sustained)
It is increased when Interruption is occurred (increase regardless PQM reset)(16bit).
(8) Interruption Cumultive Time (Total, A, B, C, Momentary, Temporary, Sustained)
Interruption duration time is displayed. (1sec/1Count), (16bit)
(9) Under Voltage Count
It is increased when occurs Under Voltage (increase regardless PQM reset) (16bit).
(10) Over Voltage Count
It is increased when Over Voltage is occurred (increase regardless PQM reset) (16bit).
(11) Harmonic Count
Voltage THD (Total, A, B,C), Increases when it is occurred over Voltage Waveform 2~15
detect setting value (16bit)
Current THD (Total, A, B,C), Increases when it is occurred over Current Waveform 2~15
detect setting value (16bit)
(12) Self Diagnosis Error Count
Self Diagnosis Error Count is indicated (16bit).

ENHANCED TECHNOLOGY 48
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-10. DNP 3.0 INDEX BINARY OUTPUT


Index Assigned
Classification Point Name Object/Variation Remark
No. Class
Switch 0 Switching Command NULL 10/02,12/01 CLOSE=Close, TRIP=Open

1 Locking Command NULL 10/02,12/01 CLOSE=Lock, TRIP=Unlock


Control Box
2 Battery Test NULL 10/02,12/01 CLOSE

3 Setting Group Change NULL 10/02,12/01 CLOSE=Primary, TRIP=Alternate


Auxiliar
SECTION Lockout
Cooperation 4 NULL 10/02,12/01 CLOSE
Clear

Line PQ Waveform Capture


5 NULL 10/02,12/01 CLOSE
Information (Manual)

6 Fault Event Clear NULL 10/02,12/01 CLOSE


Fault
7 Fault Waveform Clear NULL 10/02,12/01 CLOSE

8 PQ Event Clear NULL 10/02,12/01 CLOSE

9 PQ Count Initialize NULL 10/02,12/01 CLOSE

PQM PQ Interruption Time


10 NULL 10/02,12/01 CLOSE
Initialize

11 PQ Waveform Clear NULL 10/02,12/01 CLOSE

12 Reserved NULL 10/02,12/01 CLOSE

Diagnosis 13 Reserved NULL 10/02,12/01 CLOSE

14 Reserved NULL 10/02,12/01 CLOSE

Binary Output (BO) Definition


SBO (Select Before Operate) and DO (Direct Operate) are provided for all control point(H/W and
S/W process).

(1) Switching Command


It is Swith Open/Close order.
Apply SBO at first (DO supply).
(2) Locking Command
It is Switch Lock/Unlock order.
Lock Location: All function are stopped except Battery Test, Lamp Test and Open Control.
(3) Battery Test
It is Battery Test order.
Test report is sent to the main device when remotely and locally tested.
(4) Setting Group Change

ENHANCED TECHNOLOGY 49
DNP3.0 PROTOCOL http://www.entecene.co.kr

Change to one of two setting bank composed of Primary and Alternate.


(5) SECTION Lockout Clear
Section Lockout Information is Reseted.
(6) PQ Waveform Capture (Manual)
Save Voltage/Current Waveform of present system.
(7) Fault Event Clear
FI information and Manual Current Change Detect Information are Reseted.
(8) Fault Waveform Clear
Fault Waveform Event Data is cleared.
(9) PQ Event Clear
PQM Event is Reseted.
After PQ item occurrence, if occurs again before local or remote Reset, prior PQM
information is deleted and indicates lastest PQ Information.
(10) PQ Count Initialize
PQM Count is initialized.
(11) PQ Interruption Time Initialize
Duration time related PQM is initialized.
(12) PQM Waveform Clear
PQM Waveform Event Data is cleared.
(13) Control Function Principle
All function except battery test are stopped when control box is locked.
If control switch is in local status, all remote control and changes are not available except
battery test.
If control switch is in remote status, all local controls are not available except battery test
and setting.
Control Switch (local/remote) can be changed in control box regardless of control locking.
Switch locking information does not affect control function.
When Response the control, Response after set the Success or Failure in Control Status
field.

ENHANCED TECHNOLOGY 50
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-11. DNP 3.0 INDEX ANALOG OUTPUT(1/4)


Clas Remark
sific Index Assigned Object
Point Name
atio No. Class /Variation Range Step Default
n
Phase Sunc Fail Detect
0 NULL 40/02,41/02 0(OFF), 5 ~ 80deg 5 30
Level

Phase Sync Fail Detect


1 NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 4
Time

2 Hot Line Detect Level NULL 40/02,41/02 0.10 ~ 0.90pu 0.01 0.3

Over Current Detect Level


3 NULL 40/02,41/02 0(OFF), 50 ~ 630A 5 300
(Phase)
Line Information

Over Current Detect Time


4 NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 2
(Phase)

Over Current Detect Level


5 NULL 40/02,41/02 0(OFF), 25 ~ 315A 5 100
(Ground

Over Current Detect Time


6 NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 2
(Ground

7 Phase Loss ON Level NULL 40/02,41/02 70~85% 5 80%

8 Phase Loss OFF Level NULL 40/02,41/02 30~75% 5 50%

9 Phase Loss Detect Time NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 4

Fault Pickup Current


10 NULL 40/02,41/02 0(OFF), 50 ~ 630A 5 400
(Phase)

Fault Pickup Current


11 NULL 40/02,41/02 0(OFF), 25 ~ 315A 5 70
(Ground)

Fault Pickup Current


Fault and Protection Cooperation

12 NULL 40/02,41/02 0(OFF), 0.1 ~ 10.0A 0.1 0.2


(SEF)

Permanent Fault Detect


13 NULL 40/02,41/02 1 ~ 180sec 1 20
Time

Temporary Fault Detect


14 NULL 40/02,41/02 1 ~ 180sec 1 2
Time

15 SEF Detect Time NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 2.0

16 Inrush Block Time (Phase) NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 0.2

Inrush Block
17 NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 0.2
Time(Ground)

18 Inrush Block Multiple NULL 40/02,41/02 1 ~ 20 1 4

ENHANCED TECHNOLOGY 51
DNP3.0 PROTOCOL http://www.entecene.co.kr

(Phase)

Inrush Block
19 NULL 40/02,41/02 1 ~ 20 1 4
Multiple(Ground)

20 Section Enable NULL 40/02,41/02 Disable(0), Enable(1) - Disable

21 Section Type NULL 40/02,41/02 V-T(0), O-T(1) - V-T

22 Auto Reclosing Enable NULL 40/02,41/02 Disable(0), Enable(1) - Disable

23 Close Direction NULL 40/02,41/02 Always(0), Source(1), Load(2) - Always

24 Open Delay Time NULL 40/02,41/02 0.1 ~ 25.5sec 0.1 3

25 Clpse Wait Time NULL 40/02,41/02 1 ~ 255sec 1 17

26 Close Delay Time NULL 40/02,41/02 1 ~ 255sec 1 2

27 Section Lockout Time NULL 40/02,41/02 1 ~ 255sec 1 1

28 Lockout Time (Source) NULL 40/02,41/02 1 ~ 255sec 1 4

29 Reset Time (Source) NULL 40/02,41/02 1 ~ 255sec 1 4

30 Block Time NULL 40/02,41/02 1 ~ 255sec 1 60

31 Operation Count NULL 40/02,41/02 1~4 1 2

Table G-11. DNP 3.0 INDEX ANALOG OUTPUT(2/4)


Index Assigned Object Remark
Point Name
No. Class /Variation Range Step Default
32 Direction Enable (Phase NULL 40/02,41/02 Disable(0), Enable(1) - Disable

33 Max. Torque Angle (Phase) NULL 40/02,41/02 0-345 15 60 (lag)

Min. Polarixing Voltage


34 NULL 40/02,41/02 0(NONE), 10 ~ 80% 1 30
Fault and Protection Cooperation

(Phase)

35 Direction Enable (Ground) NULL 40/02,41/02 Disable(0), Enable(1) - Disable

36 Max. Torque Angle (Ground) NULL 40/02,41/02 0-345 15 60 (lag)

Min. Polarixing Voltage


37 NULL 40/02,41/02 0(NONE), 10 ~ 80% 1 30
(Ground)

38 Direction Enable (SEF) NULL 40/02,41/02 Disable(0), Enable(1) - Disable

39 Max. Torque Angle (SEF) NULL 40/02,41/02 0-345 15 90 (lag)

Max. Polarixing Voltage


40 NULL 40/02,41/02 0(NONE), 10 ~ 80% 1 30
(SEF)

41 PQM Enable NULL 40/02,41/02 Disable(0), Enable(1) Disable

42 SAG Detect Level NULL 40/02,41/02 0(OFF),0.50 ~ 0.99pu 0.01 0.80

PQM 43 SAG Detect Time NULL 40/02,41/02 0.5 ~ 10.0cycle 0.5 2

44 SWELL Detect Level NULL 40/02,41/02 0(OFF),1.01 ~ 1.50pu 0.01 1.20

45 SWELL Detect Time NULL 40/02,41/02 0.5 ~ 10.0cycle 0.5 2

ENHANCED TECHNOLOGY 52
DNP3.0 PROTOCOL http://www.entecene.co.kr

INTERRUPTION Detect
46 NULL 40/02,41/02 0(OFF), 0.10 ~ 0.49pu 0.01 0.1
Level

INTERRUPTION Detect
47 NULL 40/02,41/02 0.5 ~ 10.0cycle 0.5 2
Time

48 Voltage THD Detect Level NULL 40/02,41/02 0(OFF), 0.5 ~ 100.0% 0.1 OFF

49 Voltage THD Detect Time NULL 40/02,41/02 0.2 ~ 60.0sec 0.1 1

50 Current THD Detect Level NULL 40/02,41/02 0(OFF), 0.5 ~ 100.0% 0.1 OFF

51 Current THD Detect Time NULL 40/02,41/02 0.2 ~ 60.0sec 0.1 1

Voltage Unbalance Detect


52 NULL 40/02,41/02 0(OFF), 1 ~ 100% 1 30
Level

Voltage Unbalance Detect


53 NULL 40/02,41/02 0.1 ~ 60.0sec 0.1 1
Time

Current Unbalance Detect


54 NULL 40/02,41/02 0(OFF), 1 ~ 100% 1 30
Level

Current Unbalance Detect


55 NULL 40/02,41/02 0.1 ~ 60.0sec 0.1 1
Time

Under Frequency Detect


56 NULL 40/02,41/02 0(OFF), 46.00 ~ 59.98Hz 0.01 59.5
Level

57 Under Frequency Detect Time NULL 40/02,41/02 0.03 ~ 10.00sec 0.01 0.1

58 Under Voltage Detect Level NULL 40/02,41/02 0(OFF), 0.30 ~ 0.95pu 0.01 0.8

59 Under Voltage Detect Time NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 60

60 Over Voltage Detect Level NULL 40/02,41/02 0, 1.05 ~ 1.50pu 0.01 1.2

61 Over Voltage Detect Time NULL 40/02,41/02 0.0 ~ 180.0sec 0.1 60

Table G-11. DNP 3.0 INDEX ANALOG OUTPUT(3/4)


Clas Remark
sific Index Assigned Object
Point Name
atio No. Class /Variation Range Step Default
n
62 Reserved NULL 40/02,41/02 - - -

63 Reserved NULL 40/02,41/02 - - -


Diagnosis

64 Reserved NULL 40/02,41/02 - - -

65 Reserved NULL 40/02,41/02 - - -

66 Reserved NULL 40/02,41/02 - - -

67 Reserved NULL 40/02,41/02 - - -

ENHANCED TECHNOLOGY 53
DNP3.0 PROTOCOL http://www.entecene.co.kr

68 Reserved NULL 40/02,41/02 - - -

69 Reserved NULL 40/02,41/02 - - -

70 Reserved NULL 40/02,41/02 - - -

71 Reserved NULL 40/02,41/02 - - -

72 Reserved NULL 40/02,41/02 - - -

73 Reserved NULL 40/02,41/02 - - -

74 Battery Check Time NULL 40/02,41/02 1 ~ 720 Hour 1 24

75 Nominal Voltage NULL 40/02,41/02 1000 ~ 30000V 10 11500

76 Nominal Frequency NULL 40/02,41/02 50, 60Hz - 50

77 CT Direction NULL 40/02,41/02 Forward(0), Reverse(1) - Forward

78 Reference Phase Select NULL 40/02,41/02 A(0), B(1), C(2) A

79 Phase Rotation Select NULL 40/02,41/02 A-B-C(0), A-C-B(1) - A-B-C

80 ZCT Direction NULL 40/02,41/02 Forward(0), Reverse(1) - Forward

81 Waveform Sampling Rate NULL 40/02,41/02 16(0), 32(1), 64(2), 128(3) Sample - 64

Waveform Storage Trigger


82 NULL 40/02,41/02 1 ~ 5cycle 1 5
Pre Cycle

Waveform Storage Trigger


83 NULL 40/02,41/02 1 ~ 5cycle 1 5
Operation Information

Post Cycle

84 Waveform Storage Link NULL 40/02,41/02 1 ~ 10cycle 1 5

Cycle

85 CTS Checkout Time NULL 40/02,41/02 1 ~ 255sec 1 2

86 RTS Off Delay Time NULL 40/02,41/02 10 ~ 500msec 5 50

87 DCD Timeout NULL 40/02,41/02 10 ~ 30000msec 5 5000

88 D/L Confirm Select NULL 40/02,41/02 No(0), Yes(1), Sometime(2) - Sometime

D/L Confirm Multiframe


89 NULL 40/02,41/02 10 ~ 5000msec 10 100
Interval

90 D/L Retry Count NULL 40/02,41/02 0~2 1 0

91 D/L Timeout NULL 40/02,41/02 1 ~ 255sec 1 10

92 A/L Retry Count NULL 40/02,41/02 0~2 1 0

93 A/L Timeout NULL 40/02,41/02 1 ~ 255sec 1 15

ENHANCED TECHNOLOGY 54
DNP3.0 PROTOCOL http://www.entecene.co.kr

Table G-11. DNP 3.0 INDEX ANALOG OUTPUT(4/4)


Class Remark
Index Assigned Object
ificati Point Name
No. Class /Variation Range Step Default
on
94 Unsolicitied Message (Power Up) NULL 40/02,41/02 Disable(0), Enable(1) - Enable

95 Unsolicited Message Delay Time NULL 40/02,41/02 0 ~ 60sec 1 5

96 Unsolicited Class 1 Enable NULL 40/02,41/02 Disable(0), Enable(1) - Enable

97 Unsolicited Class 2 Enable NULL 40/02,41/02 Disable(0), Enable(1) - Enable

98 Unsolicited Class 3 Enable NULL 40/02,41/02 Disable(0), Enable(1) - Enable

99 VOC Current Type NULL 40/02,41/02 RMS(0), Aver(1) - Aver

100 VOC Rate NULL 40/02,41/02 0(OFF), 1 ~ 50% 1 OFF


Operation Information

101 VOC Level NULL 40/02,41/02 0 ~ 630A 1 100

Current Unbalance/THD Detect


102 NULL 40/02,41/02 0 ~ 630A 1 60
Limit

Aver. Load Current Calculation


103 NULL 40/02,41/02 1,2,3,4,5,6,10,12,15,20,30M - 15
Time

Daily Maximum Load Current


104 NULL 40/02,41/02 Disable(0), Enable(1) - Enable
Enable

105 Fault Current Report Type NULL 40/02,41/02 No(0), Yes(1), 1Shot(2) - Yes

106 SBO timeout NULL 40/02,41/02 1 ~ 255sec 1 15

107 Relay Chattering Time NULL 40/02,41/02 10 ~ 100msec 5 20

Setting (AO) Definition


(1) Phase element
Phase Sync Fail Detect Level: O(OFF), 5 ~ 80(In step of : 5), 1/1Count
Phase Sync Fail Detect Time: 0.0 ~ 180.0sec(In step of: 0.1sec), 100msec/1Count
As Phase Sync Fail does not request quick answer, if the status is maintained continually
during Detect time produces valid information Event.
(2) Hot Line element
Hot Line Detect Level: 0.10 ~ 0.90pu(In step of 0.01pu), 0.01/1Count
As Hot Line Detect Information does not request quick answer, if the status is maintained
continually produces a valid information Event.
(3) Over Current element
Over Current Detect Level (Phase): 0(OFF), 50 ~ 630A(In step of : 5A), 1A/1Count

ENHANCED TECHNOLOGY 55
DNP3.0 PROTOCOL http://www.entecene.co.kr

Over Current Detect Time(Phase) : 0.0 ~ 180.0sec(In step of: 0.1sec), 100msec/1Count
Over Current Detect Level(Ground) : 0(OFF), 25 ~ 315A(In step of : 5A), 1A/1Count
Over Current Detect Time(Ground) : 0.0 ~ 180.0sec(In step of: 0.1sec), 100msec/1Count
(4) Phase Loss element
ON Level : 70% ~ 85%(In step of : 5%), 1%/1Count
OFF Level : 30% ~ 75%(In step of : 5%), 1%/1Count
Phase Loss Detect Time : 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
As Phase Loss Information does not request quick answer, if the status is maintained
continually during Detect Settiing Time produces a valid information Event.
(5) Fault Pickup Current Change
Phase : 0(OFF), 50 ~ 630A(In step of : 5A), 1A/1Count
Ground : 0(OFF), 25 ~ 315A(In step of : 5A), 1A/1Count
SEF : 0(OFF), 0.1 ~ 10.0A(In step of : 0.1A), 0.1A/1Count
(6) FI Set Time Change
Permanent Fault Detect Time: 1 ~ 180sec (In step of : 1sec), 1sec/1Count
Temporary Fault Detect Time: 1 ~ 180sec (In step of : 1sec), 1sec/1Count
SEF Detect Time: 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
(7) Cold Load Pick Up
Pick up Current
- Phase : 1 ~ 20xMCT(In step of : 1xMCT), 1xMCT/1Count
- Ground : 1 ~ 20xMCT(In step of : 1xMCT), 1xMCT/1Count
Inrush Block Time
- Phase : 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
- Ground : 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
(8) Section Function
Whether to use : 0:Disable, 1:Enable (In step of : 1), 1/1Count
Section Type: 0:V-T, 1:O-T (In step of : 1), 1/1Count
- If select V-T mode, operates in Section.
- If select O-T mode, operates in Tie.
Auto Reclosing Enable: 0:Disable, 1:Enable (In step of : 1), 1/1Count
Close Direction : 0:Always, 1:Source, 2:Load (In step of : 1), 1/1Count
Open Delay Time: 0.1 ~ 25.5sec (In step of : 0.1sec), 0.1sec/1Count
Close Wait Time: 1 ~ 255sec (In step of : 1sec), 1sec/1Count
Colse Delay time: 1 ~ 255sec (In step of : 1sec), 1sec/1Count
Section Lockout Time : 1 ~ 255sec (In step of : 1sec), 1sec/1Count
Lockout Time (Source) : 1 ~ 255sec (In step of : 1sec), 1sec/1Count

ENHANCED TECHNOLOGY 56
DNP3.0 PROTOCOL http://www.entecene.co.kr

Reset Time (Source): 1 ~ 255sec (In step of : 1sec), 1sec/1Count


Block Time: 1 ~ 255sec (In step of : 1sec), 1sec/1Count
Operation Count : 1 ~ 4time (In step of : 1time), 1time/1Count
(9) Phase Direction element
Direction Detect Enable: 0:Disable, 1:Enable(In step of : 1), 1/1Count
Maximum Torque Angle(MTA) : 0 ~ 345(In step of : 15), 1/1Count
Minimum Polarizing Voltage : 0(None), 10 ~ 80%(In step of : 1%), 1%/1Count
(10) Ground Direction element
Direction Detect Enable: 0:Disable, 1:Enable(In step of : 1), 1/1Count
Maximum Torque Angle (MTA) : 0 ~ 345(In step of : 15), 1/1Count
Minimum Polarizing Voltage: 0(None), 10 ~ 80%(In step of : 1%), 1%/1Count
(11) SEF Direction element
Direction Detect Enable: 0:Disable, 1:Enable(In step of : 1), 1/1Count
Maximum Torque Angle (MTA) : 0 ~ 345(In step of : 15), 1/1Count
Minimum Polarizing Voltage: 0(None), 10 ~ 80%(In step of : 1%), 1%/1Count
(12) PQ element
PQ Enable : 0:Disable, 1:Enable(In step of : 1), 1/1Count
Sag Detect Level : 0(OFF), 0.50 ~ 0.99pu(In step of : 0.01pu), 0.01pu/1Count
Sag Detect Time: 0.5 ~ 10.0cycle(In step of 0.5cycle), 0.1cycle/1Count
Swell Detect Level : 0(OFF), 1.01 ~ 1.50pu(In step of : 0.01pu), 0.01pu/1Count
Swell Detect Time : 0.5 ~ 10.0cycle(In step of 0.5cycle), 0.1cycle/1Count
Interruption Detect Level : 0(OFF), 0.10 ~ 0.49pu(In step of : 0.01pu), 0.01pu/1Count
Interruption Detect Time : 0.5 ~ 10.0cycle(In step of 0.5cycle), 0.1cycle/1Count
(13) Harmonics element
Voltage THD Detect Level : 0(OFF), 0.5 ~ 100.0%(In step of : 0.1%), 0.1%/1Count
Voltage THD Detect Time : 0.2 ~ 60.0sec(In step of : 0.1sec), 100msec/1Count
Current THD Detect Level : 0(OFF), 0.5 ~ 100.0%(In step of : 0.1%), 0.1%/1Count
Current THD Detect Time : 0.2 ~ 60.0sec(In step of : 0.1sec), 100msec/1Count
(14) Voltage Unbalance element
Detect Level : 0(OFF), 1 ~ 100%(In step of : 1%), 1%/1Count
Detect Time : 0.1 ~ 60.0sec(In step of : 0.1sec), 100msec/1Count
(15) Current Unbalance element
Detect Level : 0(OFF), 1 ~ 100%(In step of : 1%), 1%/1Count
Detect Time : 0.1 ~ 60.0sec(In step of : 0.1sec), 100msec/1Count
(16) Under Frequency element
Detect Level: 0(OFF), 46.00 ~ 59.98Hz(In step of : 0.01Hz), 0.01Hz/1Count

ENHANCED TECHNOLOGY 57
DNP3.0 PROTOCOL http://www.entecene.co.kr

Detect Time : 0.03 ~ 10.00sec(In step of : 0.01sec), 10msec/1Count


(17) Under Voltage element
Detect Level: 0(OFF), 0.30 ~ 0.95pu(In step of : 0.01pu), 0.01pu/1Count
Detect Time : 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
(18) Over Voltage element
Detect Level : 0(OFF), 1.05 ~ 1.50pu(In step of : 0.01pu), 0.01pu/1Count
Detect Time : 0.0 ~ 180.0sec(In step of : 0.1sec), 100msec/1Count
(19) Battery Test
Check Time : 0(OFF), 1 ~ 720hour(In step of : 1hour), 1hour/1Count
(20) Nominal Voltage : 1000 ~ 30000V(In step of : 10V), 1V/1Count
(21) Nominal Frequency : 0:50Hz, 1: 60Hz(In step of : 1), 1/1Count
(22) CT Direction: 0:Forward, 1:Reverse(In step of : 1), 1/1Count
(23) Reference Phase Select : 0:A, 1:B, 2:C(In step of : 1), 1/1Count
(24) Phase Rotation Select : 0:A-B-C, 1:A-C-B(In step of : 1), 1/1Count
(25) ZCT Direction: 0:Forward, 1:Reverse(In step of : 1), 1/1Count
(26) Related to Waveform
Waveform sampling Rate: 0:16sample, 1:32sample, 2:64sample, 3:128sample(In step of :
1), 1/1Count
Waveform Storage Trigger Pre Cycle : 1 ~ 5cycle(In step of : 1cycle), 1cycle/1Count
Waveform Storate Trigger Post Cycle : 1 ~ 5cycle(In step of : 1cycle), 1cycle/1Count
Wave \form Storage Link Cycle: 1 ~ 10cycle(In step of : 1cycle), 1cycle/1Count
(27) Retated to Communication
CTS Checkout Time : 1 ~ 255sec(In step of : 1sec), 1sec/1Count
- CTS Checkout Time is waiting time of modem reply about RTS signal which indicates
that RTU is ready for data transfer. RTU that does not send CTS answer within setting
time is handled as CTS Fail and does not send data.
- Specially, when try the Data transmission from various RTU applied in Wireless
Communication method at the same time, RTS is set in high during the Checkout Time,
preparing transmission permission delay time caused by wireless Traffic congestion.
- It is to manage flexibly according to various communication type
characteristics(wire/wireless).
RTS Off Delay Time : 10 ~ 500msec(In step of : 5msec), 1msec/1Count
- RTS Off Delay Time sets the delay time of RTS signal that become OFF after data
transmission.
DCD Timeout : 10 ~ 30000msec(In step of : 5msec), 1msec/1Count
- If DCD signal exists after DCD signal test delay time that check modem failure before

ENHANCED TECHNOLOGY 58
DNP3.0 PROTOCOL http://www.entecene.co.kr

sending RTS signal in 2-wire communication method, RTU does not sent data and it is
handled as DCD Fail.
D/L confirm Select : 0:No, 1:Yes, 2:Sometime(In step of : 1), 1/1Count
- Sometime : Apply only Multifram (Request link reset at first Reset).
When apply Unsolicited Response at Power Up, Link Reset and send Initial
Unsolicited Response Message.
- Yes : Request Confirm about all D/L Frame transfer.
- No : Does not request Confirm about all Frame.
Refer to Multiframe interval and set the best communication status (wire/wireless)
of each Frame Interval when transfer Multi Frame.
- Application layer data request that use Confirmed link service, NACK if the prior link
reset is not done.
The side which received NACK requests link reset and when link reset is completed
responds the application user data.
- Device is application data treatment method of DATA request with wrong FCB
link reset completed status: Handle ACK with link layer confirm(0x00).
When link reset of one side is not completed : Nack by link layer confirm(0x00).
As Timeout is performed in sending side, Link Reset is performed in NACK receiving
part.
D/L Multi-frame Interval: 10 ~ 5000msec(In step of : 10msec), 1msec/1Count
D/L Retries : 0 ~ 2(In step of : 1), 1/1Count
D/L Timeout : 1 ~ 255sec(In step of : 1sec), 1sec/1Count
- Apply when transmit application data that request Confirm from Slave to Master.
- Waiting time of D/L confirm (ACK) reception from Master side after D/L frame
transmission: In case of CTS, DCD timeout consider as transfer failure. D/L, A/L timeout
are not performed.
- Progress D/L timer from the first byte transmission of D/L frame and receive all datas
that first byte of Master D/L frame started to receive within D/L timeout.
- Receive all datas that the firsty byte of Master D/L frame(ACK)
A/L retries : 0 ~ 2(In step of : 1), 1/1Count
A/L Timeout : 1 ~ 255sec(In step of : 1sec), 1sec/1Count
- It is a time that Confirm Data is transferred from Master Application to Slave Application
in case that Confirm is requested during data transmission from Slave Application to
Master ApplicationD/L Timeout.
- In case of Request about application data receive timeout are applied identically (in case
of application user data transmission ACK is included).

ENHANCED TECHNOLOGY 59
DNP3.0 PROTOCOL http://www.entecene.co.kr

- Retry by A/L Confirm Timeout is not performed, only A/L Retry is performed.
Unsolicited Mode
- Whether to use Restart Unsol : 0:Disable, 1:Enable(In step of : 1), 1/1Count
- Unsol Delay Time: 0 ~ 60sec(In step of : 1sec), 1sec/1Count
- Whether to use Unsol Class1,2,3: 0:Disable, 1:Enable(In step of : 1), 1/1Count
- In case that Restart Unsol Use is Enable, Initial Unsolicited Response Message is
produced when restart (Power Up) and transfer voluntarily the Event according to main
device type or lpcal LCD (Unsolicited Class) setting value.
When transfer Unsolicited Response Message, Application Layer Confirm shall be
requested.
Treatment method of D/L Confirm (Yes, Sometimes) request is first Link Reset and
transfer Unsolicited Response.
When Unsolicited Class is Enable: When Power Up, Initial Unsolicited Response
Message and before produced Event Data are sent. (Does not IIN Class Bit Set).
When Unsolicited Class is Disable: When Power Up, Initial Unsolicited Response
Message and IIN Class Bit set of before produced Event Data are sent.
- Unsolicited Confirmation Timeout applies(because request Application Confirm)
Application Timeout.
- Retry of Unsolicited Response(Initial and Event Unsolicited Response) applies
Application Retries.
- Unsol Delay Time is stabilization waitting time of the last Event occurrence till no status
change.
It is to solve other FRTU communication faulty and main device information handling
overburden, caused by wireless frequency channel occupancy increase by increased
communication number because the meaningless information produced during RTU
fault, switch and control fault occurrence.
- Device answers normally about All Function Request (Read Function Request included)
during waiting Initial Unsolited Response Confirmation. (Apply Test Procedure)
- In case that Unsolicited Class is Disable and has received Confirm about Initial Null
Unsolicited Response Message, Device does not send Unsolicited Response until receive
function code 0x14(enable data-filled unsolicited message) request from main device or
before setting Unsolicited Class of local LED in Enable.
- When Restart the RTU, setting information of prior Class is maintained.
- It is a treatment about Event Data that have not received A/L Confirm after transferring
prior Unsolicited Response Message (A/L retry included)
Transfer in next Event occurence

ENHANCED TECHNOLOGY 60
DNP3.0 PROTOCOL http://www.entecene.co.kr

Transfer if have received Event Polling Request from the main device
Collision prevention step of , : Apply Test Procedure.
- Application Layer Sequence Number
Polled Response : 0 ~ 15
Unsolicited Response : 16 ~ 31
(28) VOC Setting Value
VOC Current Type: 0:RMS, 1:Aver(In step of : 1), 1/1Count
- Select VOC application between RMS current or Aver current.
VOC Rate: 0(OFF), 1 ~ 50%(In step of : 1%), 1%/1Count
VOC Level : 0 ~ 630A(In step of : 1A), 1A/1Count
(29) Current Unbalance/THD Detect Limit: 0 ~ 630A(In step of : 1A), 1A/1Count
(30) Average Load Current Caluculation Time : 0:1min, 1:2min, 2:3min, 3:4min, 4:5min, 5:6min,
6:10min, 7:12min, 8:15min, 9:20min, 10:30min(In step of : 1), 1/1Count
Time interval setting for Average Load Current measurement.
(31) Daily Maximum Load Current Enable: 0:Disable, 1:Enable(In step of : 1), 1/1Count
Disable: Daily Maximum Load Current is not processed in Event.
Enable: Daily Maximum Load Current is processed in Event.
- Event saves Daily Maximum Load Current and Occurrence time for more than 7 days in
Backup Memory.
- Static Data is updated.
(32) Fault Current Report Type: 0:No, 1:Yes, 2:1Shot(In step of : 1), 1/1Count
If Fault Current Report Type is NO, all Sequence Fault Current (A, B, C, N) is not
processed in Event.
If Fault Current Report Type is YES, all Sequence Fault Current (A, B, C, N) is processed
in Event.
If Fault Current Report Type is 1 Shot, Fault Current of first Sequence (A,B, C, N) is
processed in Event.
Fault Current Event
Fault Current Event handling time is, Sequence Lockout time in case of permanent fault
and reset time in case of instantaneous time. In case of wireless, as all RTU experience
Event when line fault is occurred, communication burden is added.
Event saves all Sequence.
(33) SBO timeout(Select Before Operate Timeout) : 1 ~ 255sec(In step of : 1sec), 1sec/1Count
Set the time interval of Selection Function and Operate Function.
If there isnt an Operation order during setting value, Select order is cancelled.
(34) Relay Chattering Time : 10 ~ 100msec(In step of : 5msec), 1msec/1Count

ENHANCED TECHNOLOGY 61
DNP3.0 PROTOCOL http://www.entecene.co.kr

Chattering time of Door Opening is fixed in 1second..

ENHANCED TECHNOLOGY 62
DNP3.0 PROTOCOL http://www.entecene.co.kr

G. DNP 3.0 File Transfer


Table H-1. DNP 3.0 File Transfer
Assigned
Classification Point Name Object/Variation Remark
Class
Wave
Wave Information 70/01 WAVE_INFO
Information

FI_WAVE_1
FI_WAVE_2
FI_WAVE_3
FI_WAVE_4
Fault Fault Waveform 70/01
FI_WAVE_5
FI_WAVE_6
FI_WAVE_7
FI_WAVE_8

INRUSH_WAVE_1
INRUSH_WAVE_2
Inrush Inrush Waveform 70/01 INRUSH_WAVE_3
INRUSH_WAVE_4
INRUSH_WAVE_5

PQ Waveform (Manual) 70/01 PQ_WAVE_0

PQ_WAVE_1
PQ_WAVE_2
PQM PQ_WAVE_3
PQ Waveform 70/01
PQ_WAVE_4
PQ_WAVE_5
PQ_WAVE_6

Others RTU Information 70/01 FRTU_INFO

ENHANCED TECHNOLOGY 63