Protection Relays MiCOM P111

Relay maintenance mode Fault recording


the last 3 faults are stored inside P111 relay.
Selected logic input can put output relays
The fault records are available from the front
in Maintenance State to allow make testing
panel or via RS485.
without any trip or signalling outside of relay.
Each fault includes phase and earthfault currents
record together with a fault indication.
Fault indicator helps the user to identify clearly the
fault and to monitor relay setting and operation.
Measurements
Event recording (model E only)
MiCOM P111 can operate in 1, 2, or 3-phase 200 logic events are stored in MiCOM P111 model E.
arrangement (the missing phase should be not
The events are written in non-volatile memory
connected).
(P111 has no battery).
The measured values are available from the front
Events include inputs/outputs, change of status,
panel or via RS485 port.
alarms and contact operation.
All measurements could be shown in primary or
All events are time stamped to 10ms.
secondary values.
The events can be read by rear RS485 port by
True RMS phase current measurements are
a supervisory control system or EventBrowser
made within a frequency range from 10Hz to
software.
1000Hz.
Earthfault current value measurement is made
USER INTERFACE
within a frequency range from 40Hz to 70Hz.
All functions, including protection, automation,
Model E and F have expended setting range to be
communication, inputs and output can be
according to old electromechanical relays.
programmed and modified using front panel user
Inputs and outputs interface.

The P111 includes configurable digital inputs The menus have a pull-down structure allowing
and output relays for CB (contactor) control and easy and quick access to any data.
signalling.
4 digit LED display with 5 additional signalling
Inputs can be configured for blocking, resetting, LEDs informs the user about settings,
control, etc. measurements, faults, etc.
The number of binary inputs and output relays
can be selected by choosing the type of model.
Model A and B have 2 free-potential logic inputs
and 2 relay outputs. Model E and F have
additional 2 potential logic inputs and 2 additional
relay outputs.

The P111 has 6 signalling LED on the front panel.


LEDs are fixed (not programmable).
Simple and efficient solution for easy handle.
They present the reason of trip or alarm (I>, Ip>,
I>>, Io> or Io>>, etc).