Indian Institute of Management, Raipur

DATA POINT SUMMARY

S. No. Description AI DI AO DO SI Remarks

A Chiller (6 nos ) Integration through BACnet Protocol


1 Chillers - ON / OFF Command 6 signal from BMS to Chiller MCC panel
2 Chillers run status 6 signal to BMS from Chiller MCC panel
3 Chillers Auto / Manual switch 6 signal to BMS from Chiller MCC panel
4 Chillers Trip / Fault 6 Signal to BMS from Chiller MCC panel
Signal from Immersion temperature
5 CHW temp. at chillers outlet 6
sensor to BMS
Signal from Immersion temperature
6 CDW temp. at chillers outlet 6
sensor to BMS
Common Header CHW supply / return Signal from Immersion temperature
7 4
temp. sensor to BMS
Common Header CDW supply / return Signal from Immersion temperature
8 4
temp. sensor to BMS
Motorised Butterfly Valves at chiller & signal from B/F valve Actuator to BMS for
9 Condenser outlet with on/ off command & 24 12 valve status & signal from BMS to B/F
monitoring actuator for on/off.
Signal From Ambient temp/Humidity
10 Ambient Temperature & Humidity 2
sensor to BMS
Differential pressure sensor and Signal from Water Differential Pressure
11 12
transmitter across chillers & Condensor. Sensor to BMS
Chilled Water Thermal BTU Measurement
12 2 Signal from Ultrasonic BTU Meter to BMS
at header
13 Flow Status in De-Coupler line 4 Signal from Flow Switch to BMS

B Primary Chilled Water Pumps (6 Nos)


1 Pump ON / OFF Command 6 signal from BMS to Pump Starter panel
Signal From DP Switch across Pumps to
2 Pump run status 6
BMS
3 Pump Auto / Manual switch status 6 Signal from Auto/ Manual switch to BMS
4 CHW pump trip status. 6 signal from MCC panel to BMS.

C Secondary Chilled Water Pumps (6 Nos)


1 Pump ON / OFF Command 6 signal from BMS to Pump Starter panel
Signal From DP Switch across Pumps to
2 Pump run status 6
BMS
3 Pump Auto / Manual switch status 6 Signal from Auto/ Manual switch to BMS
4 CHW pump trip status. 6 signal from Pump Starter to BMS.
0-10 V DC or 4-20 ma output from BMS
5 Pump Speed Control through VFD 6
to VFD
Integration of VFD through Bacnet /
6 VFD Pump operation & Monitoring
Modbus Protocol.

D Condenser Water Pumps (6 Nos.)


1 Condenser Water pump ON/ OFF Command. 6 Signal from BMS to Pump Starter panel
Signal From DP Switch across Pumps to
2 Condenser Water pump Run status. 6
BMS
3 Condenser Water pump Auto/ Manual status. 6 Signal from Auto/ Manual switch to BMS

BMS IO Summary Page-1


Indian Institute of Management, Raipur

DATA POINT SUMMARY

4 Condenser Water pump trip status. 6 Signal from Starter panel to BMS

E Cooling Towers (6 Nos.) With 12 Motors


Signal from Immersion temperature
1 Cooling Tower In/ Out temperature. 12
sensor to BMS
Signal from BMS to the cooling tower
2 Cooling Tower fan ON/ OFF command. 12
MCC panel.
3 Cooling Tower fan run status. 12 Signal from Current Relay to BMS
4 Cooling Tower fan Auto/ Manual status. 12 Signal from MCC Panel to BMS
5 Cooling Tower fan Trip status. 12 Signal from MCC Panel to BMS
Signal from B/F valve Actuator to BMS &
Cooling Tower isolation Motorised valves
6 24 12 Signal from BMS to B/F actuator for
(In+Out) ON/OFF command & status.
on/off.
Common Header CDW supply / return Signal from Immersion temperature
7 4
temp. sensor to BMS
8 Sump level monitoring high / low 12 Signal from level switch to BMS
9 Make up water tank low level monitoring 1 Signal from level switch to BMS
10 Hardness Analyser for cooling tower make 1 Signal from Hardness Analyser to BMS
11 PH Monitoring 1 Signal from PH Analyser to BMS
12 CT - Water TDS 1 Signal from TDS Analyser to BMS

Sub Total (A+B+C+D+E) 55 173 6 60

F Air Handling Units (71 Nos.)


AHU ON/OFF Command, VFD Speed
1 71 71 signal from BMS to AHU MCC/VFD Panel
Control & feedback
Signal From DP Switch across fans to
2 AHU Air Flow status 71
BMS
3 AHU Auto / Manual status 71 Signal from Auto/Manual Switch to BMS
4 AHU Trip status 71 Signal from AHU panel to BMS
Signal from DP Switch across filter to
5 AHU filter status 71
BMS
Signal from Duct temperature cum RH
6 Return Air Temperature & Humidity 142
Sensor to BMS
Signal from BMS to CHW Control valve
7 Chilled Water Valve Command & feedback 71 71
Actuator
Signal from Duct Pressure Sensor to
8 AHU Duct Pressure Monitoring 71
BMS
Sub Total (F) 284 284 142 71

G Treated Fresh Air Units (9 Nos.)


1 TFA ON/OFF Command 9 9 signal from BMS to TFA MCC/VFD Panel
TFA Air Flow status (VFD Speed Controls Signal From DP Switch across fans to
2 9
Feedback) BMS
3 TFA Auto / Manual status 9 Signal from Auto/Manual Switch to BMS
4 TFA Trip status 9 Signal from TFA panel to BMS
Signal from DP Switch across filter to
5 TFA filter status 9
BMS
Signal from Duct temperature cum RH
6 Supply Air Temperature & Humidity 18
Sensor to BMS

BMS IO Summary Page-2


Indian Institute of Management, Raipur

DATA POINT SUMMARY

Chilled Water/ Expansion Valve Command Signal from BMS to CHW Control valve
7 9 9
& feedback Actuator
Signal from Duct Pressure Sensor to
8 TFA Duct Pressure Monitoring 9
BMS
Sub Total (G) 36 36 18 9

H Heat Recovery Units (1 Nos.)


HRU Supply & Exhaust Fans ON/OFF
1 2 signal from BMS to HRU panel
Command
HRU Supply & Exhaust Fans Air Flow Signal From DP Switch across fans to
2 2
status BMS
HRU Supply & Exhaust Fans Auto /
3 2 Signal from Auto/ Manual switch to BMS
Manual status
4 HRU Supply & Exhaust Fans Trip status 2 Signal from HRU Panel to BMS
Signal from DP Switch across filters to
5 HRU fresh air filter status 1
BMS
Signal from Duct temperature cum RH
6 Return Air Temperature & Humidity 2
Sensor to BMS
Signal from Duct temperature cum RH
7 Supply Air Temperature & Humidity 2
Sensor to BMS
8 Heat Recovery Wheel ON/OFF Command 1 signal from BMS to Wheel control panel

9 Heat Recovery Wheel Run status 1 signal from Wheel control panel to BMS
Heat Recovery Wheel Auto / Manual
10 1 signal from Wheel control panel to BMS
status
Sub Total (H) 4 9 0 3

I Ventilation Fans - 42 Nos.


1 Fan ON/OFF Command 42 signal from BMS to fan Starter panel
2 Fan Auto / Manual Status 42 Signal from Auto/ Manual switch to BMS
3 Fan Trip Status 42 Signal from fan starter panel to BMS
4 Fan Run Status 24 Signal from fan starter panel to BMS
signal from DP Switch across Fans (Only
5 Fan Air Flow status 18
for Centrifugal Fans) to BMS

Sub Total (I) 0 126 0 42

J Air Washer/Scrubber - 16 Nos.


Air Washer / Scrubber ON / OFF
1 16 signal from BMS to fan Starter panel
Command
signal from DP Switch across Fans to
2 Air Washer / Scrubber Air Flow Status 16
BMS
Air Washer / Scrubber Fan Auto / Manual
3 16 Signal from Auto/ Manual switch to BMS
Status
4 Air Washer / Scrubber Fan Trip Status 16 Signal from fan starter panel to BMS
signal from DP Switch across Filters to
5 Air Washer / Scrubber Filter Status 16
BMS
6 Pump ON / OFF 16 signal from BMS to fan Starter panel
Signal From DP Switch across Pumps to
7 Pump run status 16
BMS

BMS IO Summary Page-3


Indian Institute of Management, Raipur

DATA POINT SUMMARY

8 Pump Auto / Manual switch status 16 Signal from Auto/ Manual switch to BMS
9 Pump trip status. 16 signal from MCC panel to BMS.

Sub Total (J) 0 112 0 32

K Fire Fighting System


1 Hydrant pressure monitroing 1 signal from Pressure Transmitter to BMS

2 Sprinkler pressure monitroing 1 signal from Pressure Transmitter to BMS


Fire Water tank Overhead 20 Nos. high /
3 40 Signal from Level Switch to BMS
low status
4 Fire Pump Run Status (Terrace) 20 signal from DP Switch across Pumps
5 Main Plant Jockey Pump run status 1 signal from DP Switch across Pumps
Main Plant Fire Pump Run Status
6 2 signal from DP Switch across Pumps
(Electrically driven)
Main Plant Fire Pump Run Status (Diesel
7 1 signal from DP Switch across Pumps
driven)
Fire Water tank Underground 2 Nos. high /
8 4 Signal from Level Switch to BMS
low status
Sub Total (K) 2 68 0 0

L Individual Building Water Tanks


Domestic Water tank Overhead 20 Nos.
40 Signal from Level Switch to BMS
high / low status
Flushing Water tank Overhead 20 Nos.
40 Signal from Level Switch to BMS
high / low status

Sub Total (L) 0 80 0 0

M Water Treatment Plant


Domestic Water Supply Flow Signal from Ultrasonic Water Flow Meter
1 1
Measurement 150 mm Dia to BMS
Hardness Analyser at Domestic Water Signal from Hardness Analyser to BMS
2 1
Header
3 PH monitoring at Domestic Water Header 1 Signal from PH transmitter to BMS
TDS Monitoring at Domestic Water
4 1 Signal from TDS Transmitter to BMS
Header
Irrigation Water Supply Flow Measurement Signal from Ultrasonic Water Flow Meter
5 1
100 mm Dia to BMS
Hardness Analyser at Irrigation Water Signal from Hardness Analyser to BMS
6 1
Header
7 PH monitoring at Irrigation Water Header 1 Signal from PH transmitter to BMS

8 TDS Monitoring at Irrigation Water Header 1 Signal from TDS Transmitter to BMS

Sub Total (M) 8 0 0 0

N Sewage Treatment Plant (STP)

BMS IO Summary Page-4


Indian Institute of Management, Raipur

DATA POINT SUMMARY

Flushing Water Supply Flow Measurement Signal from Ultrasonic Water Flow Meter
1 1
150 mm Dia to BMS
Hardness Analyser at Flushing Water Signal from Hardness Analyser to BMS
2 1
Header
3 PH monitoring at Flushing Water Header 1 Signal from PH transmitter to BMS

4 TDS Monitoring at Flushing Water Header 1 Signal from TDS Transmitter to BMS
Garden Hydrant Water Supply Flow Signal from Ultrasonic Water Flow Meter
5 1
Measurement 100 mm Dia to BMS
Hardness Analyser at Garden Hydrant Signal from Hardness Analyser to BMS
6 1
Water Header
PH monitoring at Garden Hydrant Water
7 1 Signal from PH transmitter to BMS
Header
TDS Monitoring at Garden Hydrant Water
8 1 Signal from TDS Transmitter to BMS
Header
Soft Water Supply Flow Measurement 80 Signal from Ultrasonic Water Flow Meter
9 1
mm Dia to BMS
Signal from Hardness Analyser to BMS
10 Hardness Analyser at Soft Water Header 1
11 PH monitoring at Soft Water Header 1 Signal from PH transmitter to BMS
12 TDS Monitoring at Soft Water Header 1 Signal from TDS Transmitter to BMS
Sub Total (N) 12 0 0 0

O RADIANT COOLING CONTROL SYSTEM


1 Room Temp Monitoring 90 Signal from T/ RH Sensor to BMS
2 Slab Temp Monitoring 90 Signal from Slab Sensor to BMS
Signal from BMS to Motorized valve
3 Manifold motorized valve command 100
actuator
Sub Total (O) 180 0 100 0

P Lifts - 27 Nos.
1 Lift Alarm Monitoring 27 signal from Lift Control Panel to BMS
2 Push Button Alarm Monitoring 27 signal from Lift Control Panel to BMS
Sub Total (P) 0 54 0 0

Integration of SCADA system for


Q Electrical System integration electrical control & monitoring through
Bacnet / Modbus Protocol.

Integration of FAS through


R Fire Alarm System Modbus/Bacnet/OPC Protocols of all
devices/detectors

Integration of VAV box controllers


S VAV Boxes controllers (158 Nos) through Modbus/Bacnet/OPC
Protocols.

Integration of Energy Meters through


T Energy Meters (150 Nos)
Modbus/Bacnet/OPC Protocols.

BMS IO Summary Page-5


Indian Institute of Management, Raipur

DATA POINT SUMMARY

Integration of Sewerage Treatment


U STP integration
Plant through Open Protocol.

Integration of Water Treatment Plant


V WTP integration
through Open Protocol.

Domestic Hydropneumatic System Integration of Hydropneumatic System


W
integration (2W+1S) through Open Protocol.

Flushing Hydropneumatic System Integration of Hydropneumatic System


X
integration (2W+1S) through Open Protocol.

Irrigation Hydropneumatic System Integration of Hydropneumatic System


Y
integration (1W+1S) through Open Protocol.

Integration of PACs through Open


Z Precision Air Conditioners Integration
Protocol.

Grand Total (A to P) 545 906 248 208

TOTAL 1907

BMS IO Summary Page-6


Indian Institute of Management, Raipur

ESTIMATE

S.No Description Unit Qty RATE AMOUNT

[A] BUILDING AUTOMATION SYSTEM:

Supply, installation, testing, commissioning & handing


over of the following :

BMS Server System in Plant Room: Supply, installation,


testing and commissioning of I7 Processor, PowerEdge(TM)
T110 Server Heat Sink or Equivalet Server PC, Intel(R)
Xeon(R) Processor X3470, 2.93GHz, 8MB Cache with 8 GB
RAM, & 500GB HDD, 10/100 Mbps Ethernet card, USB
connection & internal modem, Microsoft(R) Windows(R)
Server 2008 x64 R2 SP1 Standard Edition Media,16x DVD-
ROM Drive (with RAM) for Ms 2008 R2 SAS6ir / S300
Controller Cable, 100/1 000 Mbps NIC for Network
1.0 connection and anti virus software with 21" colour graphics No. 1 321,640 321,640
LED monitor as per Tender Specifications/ relevant
standards/ as per direction of engineer-in-charge .If the
vendor SERVER requirement is more than what is specified
here, the vendor shall quote the configuration that meets
their requirement at no additional cost to owner. Accessories
included Optical Mouse, Key Pad, 132 Column, 240 CPS
Printer Coloured with the above BMS System configuration.

2.0 BMS Computer System in Building: Supply, installation,


testing and commissioning of I7 processor with EISA bus
and with 3GHz minimum CPU speed, minimum of 4 GB
RAM, 512 KB cache, 52X32X52X CDRW Drive & 320GB
171,511.20 171,511.20
HDD, optical Mouse, 106 keys keyboard, 10/100 Mbps
Ethernet card, USB connection & internal modem, 21" colour
graphics LED monitor, A4 size laser jet printer & Original
Windows 7 loaded. No. 1

BMS System Software: SITC of the unlimited multi user


with simultaneous minimum 5 user web based Server
Software for Building Management System with dynamic
graphics. The software shall have unlimited number of user
license with minimum up 5 simultaneous users. The Web-
2.1 Based Server software shall permit use of Standard Web- No. 1 564758 564,758.25
Browsers such as Microsoft Internet Explorer, Netscape
Navigator, etc and unlimited users. Software should be have
licensce of 20,000 points (hardwired 3500 points & software
16500 points both).

BMS Estimate Page-7


Indian Institute of Management, Raipur
Web Based Energy Management & Reporting Tool
software for Monitoring Building efficiency and store the
data into separate application database (SQL server) for
analysis. The Information should be available as "Screen In
Dashboards,
This Software should have the following Key features:
1. User Defined dashboard. Any Number of dashboard can
be added by user .
2. Universal Dashboard: Ability to create dashboard
for any point and monitor/compare it with any /multiple
points as a function of time.
2.2 3. Monthly Calender Dashboard: Monitor the demand/ Lot 1 393,483.30 393,483.30
consumption pattern for all days in a a month in a single
screen.
4.Segmentation of Energy Information at
a glance
5. Web based tool .
5. EMAIL OPTION AVAILABLE
6. Mobile Platform:
IPAD/ Android Compatible

Note: EMS Vendor should be same as BMS Vendor for


Seamless integration.

INTEGRATION UNIT & FIELD LAYER BOQ


SPECIFICATION

A. HVAC Control & Field Layer

Required Software (for BACnet /IP) & Hardware Interface


3.0 for (Modbus RTU) Unit Open Protocol Software compatable
to BACNET /IP and Modbus RTU .

For 6 nos. Chillers Interface on BACnet /IP (software) (33


3.01 I/O's per Chiller = 198 points) Lot 1 2,252,250 2,252,250

For 27 nos. Lift interface on Modbus RTU.


3.02 (10 I/O's per Lift = 270 points) Lot 1 inc. above

For 1 no FAS control Panel on BACnet /IP or Modbus (2000


3.03 Detectors & Modules) Lot 1 inc. above

For 158 nos. VAV Controllers on Modbus RTU/BACnet


3.04 (10 I/O's per Controller = 1580 points) Lot 1 inc. above

3.05 For 150 nos. Energy Meters Lot 1 inc. above

For Variable Pumping system, Pump VFD


3.06 (Total 100 Soft Points) Lot 1 inc. above

For 18 nos. AHU VFD Integration (13 points per VFD=1040


3.07 Points) Lot 1 inc. above

Integration with SCADA System on Modbus/Bacnet protocol


3.08 Lot 1 inc. above

3.09 For WTP & STP Lot 1 inc. above

3.10 For Hydropneumatic Systems Lot 1 inc. above

BMS Estimate Page-8


Indian Institute of Management, Raipur
For 5 nos. Precision ACs (22 points per PAC=110 Points)
3.11 Lot 1 inc. above

Additional Interfaces Features to various building


4.0
control and automation systems

1. Fire System Interface: Mapping of messages to


appropriate alarm types and zones
2. Co-relation of messages for different zones to generate
4.01 high level alarms. Lot 1 inc. above
3. Interface to lift sub-system to send message about the
zones under fire threat.
4. Interface to the Integrated Operations Centre

HVAC interface additional features:


1. Energy Consumption Management
2. Chiller temperature monitoring for condensation threat,
4.02 based on data from chillers and AC areas and climate Lot 1 inc. above
information
3. Interface to the Integrated Operations Centre

Electrical System Interface


1. Collation and analysis of electrical energy usage data
from difference sub-systems from the sub-meters using
BACNet over IP or standard TCP/IP protocol.
4.03 3. Plotting of energy footprint of the building including Lot 1 inc. above
segmented energy information.
4. Long term trend and performance analysis and
identification of improvement measures.
5. Interface to the integrated operations centre

WEB SERVER ENGINES (NETWORK/ SUPERVISORY


CONTROLLERS)
SITC of Microprocessor based 32 Bit ,UL Listed Embedded
Web Server Engine-cum-Network & Supervisory controller
on BACnet/IP units for connecting all field DDC controllers
and 3rd party System Integration Units to it and for
transferring data from field devices to BMS Web-Server
Software . The Network Controller shall support BACnet
standard MS/TP or Lonworks Protocol. The Network
5.0 supervisory Controller shall have imbedded graphic Lot 1 1,239,000 1,239,000
capability for generating web based user graphics &
support minimum of Five Concurrent User .The Web user
shall have the capability to access all system data through
one Network Controller. In case of PC/Software Failure, User
can access the system using web server using IP Port.The
Web server shall allow multiple simultaneous user access
( minimum 5) (Seperate for each buildings i.e., 23
Buildings)

BMS Estimate Page-9


Indian Institute of Management, Raipur
DDC Controller with SITC of Programmable and Application
specific 32 bit with Real Time clock , UL Listed BACnet/
Lonworks/ Modbus controllers, field mounted configured as
per Data Point Summary for respective building services and
as per below distributions. The controller shall be housed in
vandal proof lockable MS cabinets. For AHU's Maximum of
One Controller/ 2AHU Shall be used. For Other Equipments,
6.0 the controller selection shall be such that distance from
controller to field devices should not go beyound 40 Mtrs.
The Expansion controller connected with Controller shall
also be 32 Bit, UL Listed BACnet controller and
communication with Expansion units to Main Controller shall
be on BACnet MS/TP.
Proprietry Protocol shall not be accepted

6.01 Panel for AC Plant Room Lot 1 651000 651,000

Panel for AHUs, TFAs & HRUs. 2 AHUs/ HRUs on One


6.02 Lot 1 3580500 3,580,500
Controller

6.03 Panel for Ventillation Fans Lot 1 432915 432,915

6.04 Panel for Individual Building water Tanks/Pumps Lot 1 276675 276,675

6.05 Panel for Fire Fighting System Lot 1 211575 211,575

6.06 Panel for Air Washer/ Scrubber Lot 1 349913 349,913

6.07 Panel for Sewage Treatment & Water treatment plant Lot 1 138338 138,338

6.08 Panel for Elevator System Lot 1 219713 219,713

6.09 Panel for Radiant Cooling System Lot 1 1041600 1,041,600

Note:
a MAX. 2 AHU should be provided with one controller

System architecture shall be submitted along with the tender.


b

Provision of integration with any BMS system conforming to


ASHRAE BACnet/IP or Protocol RTU MODBUS shall be
c
provided by chiller manufacture.

B) Sensors and field devices

Supply, installation, testing, commissioning of


necessary Input sensor transmitters/ transducers
comprising the following:

Immersion Temp Sensor (Resistance type) for CHW line with


measuring Range 32-160 deg. F. The accuracy shall be at
1.0 Nos. 36 2468 88,830
least 0.33 degrees F. The pressure rating shall be 10
kgf/sq cm .

2.0 Ultrasonic BTU Meters


BMS Estimate Page-10
Indian Institute of Management, Raipur
250 mm Dia Nos 1 341250 341,250
200 mm Dia Nos 1 273000 273,000

3.0 Ultrasonic Water Flow Meter


150 mm Dia Nos 2 273000 546,000
100 mm Dia Nos 2 245700 491,400
80 mm Dia Nos 1 220500 220,500

Outside air temperature , humidity RH & Wetbulb sensors


for measuring outside air temperature (Range 35-130 F).
4.0 The accuracy of temperature sensor shall be 0.33 degrees No. 1 17233 17,233
F and RH sensor is 3% . It should be provided with IP66
and sun sheild and rain protection.

5.0 Current Relay Nos. 12 3031 36,376

6.0 IP 66 protected Level Switches for Water Level (Hi/Low) Nos. 47 7014 329,658

IP 66 protected Differential Pressure Switch across the


7.0 Nos. 38 9954 378,252
Pumps

8.0 Differential pressure sensor for water Nos 12 21037 252,441

Differential pressure switches across the Air Handling Unit


Filter for indicating the Filter status. Pressure differential 0 to
9.0 200 Pascal. The switch shall be with connecting tube and Nos. 81 3090 250,302
metal bends for connections to the duct. The housing
shall be IP 54 rated.

Differential pressure switches across the Air Handling Unit,


Air washer & scrubber and Blower for indicating the Blower
status. Pressure differential 0 to 1000 Pascal. The switch
10.0 Nos. 132 3090 407,900
shall be with connecting tube and metal bends for
connections to the duct. The housing shall be IP 54
rated.

Duct Temp & RH Sensor shall capable to measure relative


humidity of 0 to 100%, suitable for duct installation and
accuracy shall be 0.33F at 70F & 2% RH & Resistance
11.0 Nos. 82 9923 813,645
Change approx 3ohms/F for Measuring return air
Temprature & Humidity of AHUs/ TFAs .

UL Listed Pressure Transmiter with IP 67 protection for


12.0 Nos. 2 8257 16,514
measuring line pressure in Hydrant / Sprinkler lines

13.0 IP 66 protected Water Flow Switches Nos. 4 5084 20,336

14.0 IP 66 protected Flameproof Level Switch Nos. 0 7872 -

15.0 Voltage Transducers Nos. 0 6725 -

16.0 Duct Pressure Sensor Nos 80 10138 811,020

17.0 Hardness Anayser Nos 6 871716 5,230,298

18.0 PH Analyser Nos 6 82226 493,353

BMS Estimate Page-11


Indian Institute of Management, Raipur

19.0 TDS Anayser Nos 6 93384 560,303

Room Temp. Sensor with LCD display, with set point key
20.0 Nos 90 6825 614,250
Pods.

Slab embedded sensor with thermowell, Measuring range 0-


21.0 Nos 90 14805 1,332,450
50 Deg C, Response time should be 1 Minute.

C) Conduiting, Wiring and cabling

Supply, installation, testing and commissioning of


1.0
following cables:

3 Core 1.5 Sqmm, unarmoured ATC conductor


1.1 RM 3000 88 264,600
multistranded, cable for Powering DDC , Actuators.

2 Core 1.0 Sqmm, unarmoured ATC conductor


1.2 RM 63000 65 4,101,300
multistranded, Shielded cable.

1.3 CAT6 cable. RM 600 42 25,200

Supplying and laying of following sizes of FRLS PVC


1.4 conduit on surface/recess including cutting/filling chases
along with conduit accessories etc. complete as required.

a) 25 mm dia RM 32000 86 2,755,200


b) 20 mm dia RM 15000 80 1,197,000

Supplying and laying of following sizes of PVC Flexible


Steel Reinforced conduit on surface/recess including
1.5 cutting/filling chases along with conduit accessories such as
coupless etc. complete as required.

a) 25 mm dia RM 4000 53 210,000


b) 20 mm dia RM 2000 47 94,500

1.6 Online UPS with 15 min Backup and required extensions.

a) 600 VA Nos 40 4200 168,000

GRAND TOTAL 34185982

BMS Estimate Page-12