Indoor Unit R410A
SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Air Conditioner Service Manual
TABLE OF CONTENTS
Part 1 General Information .......................................................................................................3
Model Names ...............................................................................................................................4
External Appearance ...................................................................................................................5
Nomenclature ...............................................................................................................................6
3. Nomenclature .............................................6
1. Model Names
Capacity(Btu/h(kW))
Chassis
Category 7.5 9.6 12.3 15.4 19.1 24.2 28.0 30.0 36.2 42.0 48.1 54.0 76.4 95.5
Name
(2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (8.8) (10.6) (12.3) (14.1) (15.8) (22.4) (28.0)
ARNU07 ARNU09 ARNU12 ARNU15
SE 3SE*2 3SE*2 3SE*2 3SE*2
Wall Mounted
(General) ARNU18 ARNU24
S5 3S5*2 3S5*2
ARNU07 ARNU09 ARNU12 ARNU15
SE 3SE*2 3SE*2 3SE*2 3SE*2
ART
Mirror
COOL ARNU18 ARNU24
S8 3S8*2 3S8*2
1 Way TJ ARNU07 ARNU09 ARNU12
3TJ*2 3TJ*2 3TJ*2
ARNU18 ARNU24
2 Way TL 3TL*2 3TL*2
ARNU07 ARNU09 ARNU12
TR 3TR*2 3TR*2 3TR*2
Ceiling ARNU15 ARNU18
TQ
Cassette 3TQ*2 3TQ*2
ARNU24 ARNU28
4 Way TP 3TP*2 3TP*2
ARNU36
TN 3TN*2
ARNU42 ARNU48
TM 3TM*2 3TM*2
ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24
BH 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2
ARNU28 ARNU36 ARNU42
BG 3BGA2 3BGA2 3BGA2
High Static
ARNU483
BR BRA2
URNU76 URNU96
Ceiling B8 3B8A2 3B8A2
Concealed
Duct ARNU07 ARNU09 ARNU12 ARNU15
B1 3B1G2 3B1G2 3B1G2 3B1G2
Low Static
ARNU18 ARNU24
B2 3B2G2 3B2G2
ARNU07 ARNU09 ARNU12 ARNU15
B3 3B3G2 3B3G2 3B3G2 3B3G2
Built In
ARNU18 ARNU24
B4 3B4G2 3B4G2
ARNU09 ARNU12
Ceiling & Floor VE 3VEA2 3VEA2
ARNU18
Ceiling Suspended VJ 3VJA2
ARNU07 ARNU09 ARNU12 ARNU15
CE 3CEA2 3CEA2 3CEA2 3CEA2
With Case
ARNU18 ARNU24
CF
Floor 3CFA2 3CFA2
Standing ARNU07 ARNU09 ARNU12 ARNU15
CE 3CEU2 3CEU2 3CEU2 3CEU2
Without
Case ARNU18 ARNU24
CF 3CFU2 3CFU2
ARNU18 ARNU24 ARNU30 ARNU36
NJ 3NJA2 3NJA2 3NJA2 3NJA2
Vertical AHU
ARNU42 ARNU48 ARNU54
NK 3NKA2 3NKA2 3NKA2
h *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable))
*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma
2. External Appearance
Ceiling Cassette- 1Way Ceiling Concealed Duct - High Static
ARNU073TJ*2 ARNU073BHA2 ARNU363BGA2
ARNU093TJ*2 ARNU093BHA2 ARNU423BGA2
ARNU123TJ*2 ARNU123BHA2 ARNU483BRA2
ARNU153BHA2 URNU763B8A2
ARNU183BHA2 URNU963B8A2
* A:Basic, C:Plasma
ARNU243BHA2
ARNU283BGA2
3. Nomenclature
ARN U 07 3 TJ A 2
Generation
Combinations of functions
A: Basic function
L: Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
U: Floor Standing without Case
ART COOL Type Panel Color
B:Blue R:Mirror V: Silver
Chassis Name
Electrical Ratings
1:1, 115V, 60Hz 2: 1, 220V, 60Hz
6:1, 220 - 240V, 50Hz 7: 1, 100V, 50/60Hz
3:1, 208/230V, 60Hz
Ceiling Cassette
1 Way .................................................................................8
2 Way...............................................................................13
4 Way(1)...........................................................................20
4 Way(2)...........................................................................23
Art Cool Series
ART COOL Miror..............................................................34
ART COOL Gallery ..........................................................45
Ceiling Concealed Duct
Low Static ........................................................................55
Built In ..............................................................................62
High Static........................................................................67
Wall Mounted(General)
Wall Mounted ...................................................................76
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................87
Floor Standing
Floor Standing..................................................................94
Vertical Air Handling Unit................................................117
1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
n Auto Swing Control
This function is to swing the louver up and down automatically.
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
Indoor pipe
Temperature
36C(96F)
33C(92F)
25C(76F)
20C(68F)
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
n Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
Pipe
temperature
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
LO
LOW
ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
275.8
206.6
Number Name Descripition
106.8
861 88 1 Liquid pipe connection Unit size(7k, 9k, 12k):6.35
3. Dimensions
Note
168.3
96.5
1. Unit should be installed in compliance with the installation manual
57.4
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
- 12 -
1,100 applicable national codes.
(Panel Name: PT-UUC)
881(Air outlet Hole)
500
34
354.3
453
275.8
206.3
106.8
(unit : mm)
168.3
96.5
Note
57.4
1. Unit should be installed in compliance with the installation manual
in the product box.
1100
2. Unit shall be grounded in accordance with the local regulations or
- 13 -
applicable national codes.
109.5 109.5 (Panel Name: PT-UUD)
46.5
500
34
117
ARNU18GTT*2
Dimensions
ARNU24GTT*2
453.8
(unit : mm)
180.6
1 Liquid pipe connection Unit size(18k):6.35, (24k):9.52
65.3
2 Gas pipe connection Unit size(18k):12.7, (24k):15.88
1176.4 65.1
1332 453.8 3 Air suction grill
Note
1. Unit should be installed in compliance with the installation manual
173.8
91
96.1
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
31.7
- 14 -
20.6 57.4
applicable national codes.
500
34
453.8
247.5
180.6
(unit : mm)
65.3
1332 1 Liquid pipe connection Unit size(18k):6.35, (24k):9.52
2 Gas pipe connection Unit size(18k):12.7, (24k):15.88
3 Air suction grill
453.8
Note
1. Unit should be installed in compliance with the installation manual
173.8
132
91
97.1
57
in the product box.
14
2. Unit shall be grounded in accordance with the local regulations or
57.4
31.7
15.2
20.6
- 15 -
applicable national codes.
46.5
500
44
34
76, Seongsan-dong, Changwon City, Gyeongnam,
641-713, Korea CHASSIS CODE: TT
Dimensions
1. Functions ....................................................................................17
2. Operation Details........................................................................18
3. Dimensions .................................................................................20
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
High head Drain pump Built-in drain pump automatically drains water.
A standard drain-head height of up to 700mm
(27-9/16inch) is possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
n Auto Swing Control
This function is to swing the louver up and down automatically.
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
Indoor pipe
Temperature
36C(96F)
33C(92F)
25C(76F)
20C(68F)
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
n Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
Pipe
temperature
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
LO
LOW
ARNU183TL*2
ARNU243TL*2
A
830(32-11/16) B
47.9(1-7/8)
[Unit : mm(inch)]
275(10-13/16)
3. Dimensions
550(21-11/16)
69.5(2-3/4)
Note
1. Unit should be installed in compliance with the installation manual
889.2(35) in the product box.
TL 2. Unit shall be grounded in accordance with the local regulations or
- 20 -
A 225(8-7/8) applicable national codes.
B 126.5(5)
1050(41-5/16)
28.5(1-1/8)
640(25-3/16)
3
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: TL
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
1. Functions ....................................................................................22
2. Operation Details........................................................................23
3. Dimensions .................................................................................25
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
High head Drain pump Built-in drain pump automatically drains water.
A standard drain-head height of up to 700mm
(27-9/16inch) is possible.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
n Auto Swing Control
This function is to swing the louver up and down automatically.
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
Vane 1 Vane 3
Vane 4
Indoor pipe
Temperature
36C(96F)
33C(92F)
25C(76F)
20C(68F)
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
n Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
Pipe
temperature
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
LO
LOW
ARNU05GTR*2
128
4R20 ARNU07GTR*2
69
517
ARNU09GTR*2
4
5 ARNU12GTR*2
(unit : mm)
700
Number Name Descripition
517
570
523
1 Liquid pipe connection Unit size(5k, 7k, 9k, 12k):6.35
376(Inlet Grille)
3. Dimensions
461
5 Air discharge grill
380(Air outlet hole) 570
473 6 Air suction grill
2 1
700
165
Note
1. Unit should be installed in compliance with the installation manual
- 25 -
59.5
214
79
22.5
in the product box.
84.5
48
53
2. Unit shall be grounded in accordance with the local regulations or
34.5
30 19 63 applicable national codes.
142.5
570
3
Branch Duct Connection
REQUIRED SPACE
B
CEILING OPENING
500mm or more*
500mm or more*
500mm or more*
500mm or more*
174
Dimensions
4R20
ARNU18GTQ*2
68
517
4
5
(unit : mm)
700
517
570
523
1 Liquid pipe connection Unit size(15k, 18k):6.35
376(Inlet Grille)
2 Gas pipe connection Unit size(15k, 18k):12.7
3 Drain pipe connection VP25(32)
2 1
6 Air suction grill
380(Air outlet hole)
473
Note
700
165
- 26 -
1. Unit should be installed in compliance with the installation manual
59.5
in the product box.
256
22.5
79
125
2. Unit shall be grounded in accordance with the local regulations or
95.5
94
76
48
applicable national codes.
30 19 63
142.5
570
CEILING OPENING
B
500mm or more*
500mm or more*
500mm or more*
A
A ARROW VIEW B ARROW VIEW
1. Functions ....................................................................................28
2. Operation Details........................................................................29
3. Dimensions .................................................................................31
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C(76F).
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
n Auto Swing Control
This function is to swing the louver up and down automatically.
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE
+0.5C(33F))
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
Indoor pipe
Temperature
36C(96F)
33C(92F)
25C(76F)
20C(68F)
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
n Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C(76F).
The operation diagram is as following.
Pipe
temperature
35C(94F)
30C(86F)
27C(80F)
25C(76F)
22C(72F)
LO
LOW
154
204
6
ARNU28GTP*2
950
614(Inlet Grille)
787 (unit : mm)
950
25
3 Drain pipe connection VP25(32)
671
684
840
5 Air discharge grill
870-920(CEILING OPENING SPACE)
786(SUSPENSION POSITION) 6 Air suction grill
300
OR LESS
Note
420
393
420
1. Unit should be installed in compliance with the installation manual
- 31 -
Ceiling opening A in the product box.
2. Unit shall be grounded in accordance with the local regulations or
787
applicable national codes.
682(SUSPENSION POSITION)
669(SUSPENSION POSITION)
840
79
32
26
50
62
79
500mm or more*
50
204
500mm or more*
71
82
99
60
65 40
70 13- 3, 3 Hole
108 60 80
41.5
840 53.5
2 3 500mm or more*
13- 3, 3 Hole 165 165
10
Branch Duct Connection 350
A ARROW VIEW
B ARROW VIEW
195
Dimensions
ARNU36GTN*2
246
6
950
614(Inlet Grille)
(unit : mm)
25
VP25(32)
300
OR LESS
6 Air suction grill
Note
420
393
420
1. Unit should be installed in compliance with the installation manual
Ceiling opening
- 32 -
A in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
682(SUSPENSION POSITION)
669(SUSPENSION POSITION)
870-920(CEILING OPENING SPACE)
475
B
44
CONNECTION
80
43
500mm or more*
70
71
60
40
246
100
100
500mm or more*
60
141
500mm or more*
107
103
78
52
13- 3, 3 Hole
2 110 60 80 3
840 53.5 13- 3, 3 Hole
A ARROW VIEW
B ARROW VIEW
ARNU42GTM*2
ARNU48GTM*2
840
950
237
288
614(Inlet Grille)
(unit : mm)
25
4 Power supply connection
300
OR LESS
Note
420
393
420
1. Unit should be installed in compliance with the installation manual
- 33 -
Ceiling opening in the product box.
A
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
682(SUSPENSION POSITION)
669(SUSPENSION POSITION)
870-920(CEILING OPENING SPACE)
475
B
71
OUTDOOR AIR INTAKE 92 92 92 92
31 35
4
(DIRECT CONNECTION) 350 REQUIRED SPACE
1
165
BRANCH DUCT
100
76
75
110
60
70
100
500mm or more*
60
500mm or more*
71
BRANCH DUCTCONNECTION
84
53.5
13- 3, 3 Hole 3 13- 3, 3 Hole
2 500mm or more*
165 10 165
Branch Duct Connection
350
A ARROW VIEW
B ARROW VIEW
1. Functions ....................................................................................35
2. Operation Details........................................................................36
3. Dimensions .................................................................................43
1. Functions
Indoor Unit
Airflow Direction Control The indoor fan does not rotate until the
evaporator pipe temperature will be reached
The louver can be set at the desired position or swing
up and down automatically. at 28C(82F).
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5C(33F) above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off.
When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on.
Themo ON Temp. => Setting Temp. +2C(36F)
Themo OFF Temp. => Setting Temp.+4C(39F)
While in compressor on, when above 38C(100F), it operates with setting airflow speed (while in sleep mode,
with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C (92F), when above
35C(94F) , it operates with the low airflow speed.
While in defrost control, both of the indoor and outdoor fans are turned off.
n Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp < 26C(78F)=> Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp<24C(76F) => Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp<22C(72F) => Intake Air Temp
Intake Air Temp < 18C(64F) => 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
n Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
n On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
n Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
W [Unit : mm(inch)]
165(6-1/2)
ARNU153SE*2
169(5-5/8)
- 43 -
Note
53(2-1/16)
282(11-1/8)
282(11-1/8)
1. Unit should be installed in compliance with the installation manual
in the product box.
51(2-1/16)
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
567(22-3/8)
265(10-1/2)
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SE
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Dimensions
ARNU24GS8*2
299
4 1 Front panel
10
63
2 2 Display & signal receiver
53 Air suction grille
93
48
- 44 -
72
58 122
804
Note
1. Unit should be installed in compliance with the installation manual
281
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
1. Functions ....................................................................................46
2. Operation Details........................................................................47
3. Dimensions .................................................................................54
1. Functions
Indoor Unit
Airflow Direction Control The indoor fan does not rotate until the
evaporator pipe temperature will be reached
The louver can be set at the desired position or swing at 28C(82F).
up and down automatically.
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5C(33F) above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
n Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
ature
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
n Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
n On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
n Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
ARNU093SF*2
ARNU123SF*2
H
[Unit : mm(inch)]
ARNU123SF*2
[Unit : mm(inch)]
- 54 -
500(19-5/8) 1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
525(20-5/8)
Fix Hole
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: SF
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
1. Funtions ......................................................................................56
2. Operation Details........................................................................57
3. Dimensions .................................................................................60
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C(76F).
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C(86F).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
ARNU073B1G2
ARNU093B1G2
ARNU123B1G2
ARNU153B1G2
ARNU183B2G2
ARNU243B2G2
A B C D
3. Dimensions
ARNU073B1G2
190(7-7/16)
ARNU093B1G2 820 728 856 794
65(2-1/2) 60(2-3/8)
14(1/2) 161(6-5/16)
(32-5/16) (28-11/16) (33-11/16) (31-5/16)
ARNU153B1G2
1
ARNU183B2G2 1100 1008 1131 1072
ARNU243B2G2 (43-5/16) (39-11/16) (44-9/16) (42-3/16)
216(8-1/2)
2
277(10-7/8)
24(11/12)
[Unit : mm(inch)]
- 60 -
575(22-5/8)
Number Name Descripition
383(15-1/16)
Unit size(7k,9k,12k,18k):6.35(1/4)
3 1 Liquid pipe connection Unit size(24k):9.52(3/8)
Unit size(7k,9k,12k,18k):12.7(1/2)
2 Gas pipe connection Unit size(24k):15.88(5/8)
3 Drain pipe connection
C
4
4 Power supply connection
6
18(3/4)
5 Air discharge
6 Air suction
154(6)
190(7-7/16)
Note
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B1/B2
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
1. Funtions ......................................................................................62
2. Operation Details........................................................................63
3. Dimensions .................................................................................66
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C(76F).
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C(86F).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
ARNU073B3G2+PBSGB30(Accessory), PBSC30(Accessory)
Dimensions
ARNU093B3G2+PBSGB30(Accessory), PBSC30(Accessory)
ARNU123B3G2+PBSGB30(Accessory), PBSC30(Accessory)
ARNU153B3G2+PBSGB30(Accessory), PBSC30(Accessory)
190(7-7/16) ARNU183B4G2+PBSGB40(Accessory), PBSC40(Accessory)
6
65(2-1/2) 60(2-3/8)
ARNU243B4G2+PBSGB40(Accessory), PBSC40(Accessory)
277(10-7/8)
24(11/12) 216(8-1/2)
3. Dimensions
575(22-5/8)
388(15-1/4)
388(15-1/4)
618(24-5/16)
1
B_2
190(7-7/16)
250(9-13/16)
A_2 C_2
- 66 -
[Unit : mm(inch)]
With Suction Grille & Suction Canvas Number Name Descripition
Unit size(7k,9k,12k,18k):6.35(1/4)
1 Liquid pipe connection Unit size(24k):9.52(3/8)
Unit size(7k,9k,12k,18k):12.7(1/2)
2 Gas pipe connection Unit size(24k):15.88(5/8)
190(7-7/16)
3 Drain pipe connection
Btu/h A_1
4 Power supply connection
7,9,12k 820(32-5/16)
C_3
500(19-11/16)(Max)
5 Air discharge
18,24k 1100(43-5/16)
6 Air suction
A_3 B_3
A_2 B_2 C_2
PBSGB30 910(35-13/16) 359(14-1/8) 56(2-3/16) Note
PBSGB40 1188(46-13/16) 359(14-1/8) 56(2-3/16)
1. Unit should be installed in compliance with the installation manual
A_3 B_3 C_3 in the product box.
PBSC30 821(32-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) 2. Unit shall be grounded in accordance with the local regulations or
PBSC40 1100(43-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) applicable national codes.
1. Funtions ......................................................................................68
2. Operation Details........................................................................69
3. Dimensions .................................................................................72
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C(76F)
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C(86F).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
ARNU073BHA2
ARNU093BHA2
175(6-7/8) 20(3/4)
ARNU123BHA2
ARNU153BHA2
6 51(2-1/16) 101(3-15/16) ARNU183BHA2
49(15/16)
932(36-11/16) 70(2-3/4) 31(1-3/13)
48(1-7/8)
50(1-15/16)
114(4-1/2)
R3
52(2-1/16)
7.5
224(8-7/8)
165(6-7/13)
/8)
3. Dimensions
355(14)
60(2-3
355(14)
3
450(17-11/16)
450(17-11/16)
100(3-15/16)
1
140(5-9/16)
123(4-13/16)
87(3-7/16) 30(1-3/16) 260(10-1/4)
750(29-1/2)
5
882(34-3/4) 108(4-3/13)
- 72 -
65(2-9/16)
[Unit : mm(inch)]
Number Name Descripition
Unit size(7k,9k,12k,18k):6.35(1/4)
1 Liquid pipe connection Unit size(24k):9.52(3/8)
260(10-1/4)
158(6-1/4)
75(2-15/16)
Unit size(7k,9k,12k,18k):12.7(1/2)
106 127(5)
(4-1/8)
2 Gas pipe connection Unit size(24k):15.88(5/8)
3 Drain pipe connection
64(2-1/2) 243(9-9/16) 212(8-3/8) 243(9-9/16) 119(4-11/16)
4 Power supply connection
5 Air discharge
6 Air suction
Note
1. Unit should be installed in compliance with the installation manual
450(17-11/16)
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
882(34-3/4) applicable national codes.
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BH
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
20(3/4)
ARNU283BGA2
ARNU363BGA2
220(8-5/8)
ARNU423BGA2
50(1-15/16)
1
152(5-7/8)
165(6-7/13)
00
224(8-7/8)
53(2-1/16) 47(1-7/8)
/8)
60(2-3
87(3-7/16) 355(14)
140(5-9/16)
2
3
49(15/16)
122(4-13/16)
87(3-7/16) 29(1-3/8) 75(2-15/16) 261(10-1/4)
830(32-11/16)
5
- 73 -
1,182(46-5/8) 108(4-3/13)
[Unit : mm(inch)]
Number Name Descripition
186(7-5/16)
1 Liquid pipe connection Unit size(28k,36k,42k):9.52(3/8)
298(11-11/16)
2 Gas pipe connection Unit size(28k,36k,42k):15.88(5/8)
113(4-7/16) 158(6-1/4)
232(1-1/4) 243(9-9/16) 232(1-1/4) 243(9-9/16) 232(1-1/4) 3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction
Note
450(17-11/16)
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
1,182(46-1/2) applicable national codes.
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BG
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Dimensions
25(1)
ARNU483BRA2
303(12)
6 101(3-15/16)
[Unit : mm(inch)]
1,284(50-9/16)
83(3-1/4) Number Name Descripition
221(8-3/4)
72(2-13/16)
123(4-13/16)
312(12-1/4)
/8) 3 Drain pipe connection
60(2-3 3
90(3-9/16)
4 Power supply connection
590(23-3/16)
477(18-3/4)
144(5-11/16)
2
6 Air suction
135(5-5/16)
122(4-13/16)
50(1-15/16) 118(4-5/8) 114(4-7/16) 190(7-7/16)
56(2-3/16)
32(1-3/13)
260(10-1/4)
1,004(39-9/16) Note
5
1. Unit should be installed in compliance with the installation manual
- 74 -
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
168(6-5/8)
380(15)
140(5-9/16)
185(7-1/4)
241(9-1/2) 279(11) 241(9-1/2) 279(11) 215(8-1/2)
590(23-3/16)
1,230(48-7/16)
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: BR
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
20(3/4)
URNU963B8A2
2
440(17-3/8)
70(2-3/4)
6 120(4-3/4)
) 3
(5 -9/16
1,622(63-11/13) ) 14 0
64(2-1/2)
58(2-1/4)
18(3/4)
70(2-3/4)
60(2-3/8)
122(4-7/8)
109(4-1/4) [Unit : mm(inch)]
688(27)
560(22)
68(2-5/8)
64(2-7/13)
30(1-3/16)
5
3 Drain pipe connection
4 Power supply connection
- 75 -
5 Air discharge
6 Air suction
318(12-7/13)
460(18-1/13)
161 290(11-7/16)
(6-3/8)
293(11-7/13) 329(12-15/16) 320(12-5/8) 329(12-15/16)
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
688(27)
1,562(61-1/2)
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: B8
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Dimensions
1. Functions ....................................................................................77
2. Operation Details........................................................................78
3. Dimensions .................................................................................85
1. Functions
Indoor Unit
Intermittent
Sleep Mode operation of fan at low speed.
Auto Control
2. Operation Details
Function of Controls
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer(on/off) and Sleep timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
When the intake air temperature reaches 0.5C(33F) below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5C(33F) above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C(33F)
Compressor OFF Temp => Setting Temp-0.5C(33F)
While in compressor running, operating with the airflow speed set by the remote controller. While in com-
pressor not running, operating with the low airflow speed regardless of the setting.
n Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost the outdoor unit.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26C(78F) Intake Air Temp => 25C(76F)
24C(76F) Intake Air Temp<26C(78F) => Intake Air Temp+1C(34F)
22C(72F) Intake Air Temp<24C(76F) => Intake Air Temp+0.5C(33F)
18C(64F) Intake Air Temp<22C(72F) => Intake Air Temp
Intake Air Temp < 18C(64F) => 18C(64F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
n On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
n Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
n Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
n Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 181 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep".
If you want to stop the operation, re-press the button.
ARNU15GSE*2
(unit : mm)
- 85 -
567
5 Gas pipe 12.7 Flare connection
6 Drain pipe External dia. 17
7 Right side piping/wiring connection
265
8 Left side piping/wiring connection
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
PIPE AND DRAIN DIMENSION 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
Required space(unit:mm)
Lower than 2.3m
More than 200 mm
DIRECTION DIRECTION
ARNU24GS5*2
(unit : mm)
Model W H D
ARNU18GS5*2
1090 300 178
(unit : mm)
Number Name Descripition
PIPING DIRECTION
1 Front panel
- 86 -
7 Right side piping/wiring connection
8 Left side piping/wiring connection
281
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
PIPE AND DRAIN DIMENSION applicable national codes.
Required space(unit:mm)
Lower than 2.3m
More than 200 mm
1. Funtions ......................................................................................88
2. Operation Details........................................................................89
3. Dimensions .................................................................................92
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator piping
temperature reaches 25C(76F).
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C(86F).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
ARNU09GVEA2
ARNU12GVEA2
(unit : mm)
Model W H D
(unit : mm)
Number Name Descripition
3. Dimensions
- 92 -
9 Piping connection Slit hole
10 Signal receiver & Operation indicator
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
Required space(unit:mm)
587 More than 200mm
More than 200mm
(unit : mm)
Model W H D
(unit : mm)
Number Name Descripition
1 Liquid pipe 6.35 Flare connection
- 93 -
8 Wiring connection Slit hole
9 Piping connection Slit hole
10 Right side drain pipe connection Slit hole
11 Left side drain pipe connection Slit hole
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
1. Function ......................................................................................95
2. Operation Details........................................................................96
3. Dimensions .................................................................................99
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator piping
temperature reaches 25C(76F).
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C(86F).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
[Unit : mm(inch)]
635(25)
ARNU093CEA2 1067 635 203
3. Dimensions
70(2-3/4)
49(15/16)
ARNU093CEU2 978 639 190
148.3 148.3 (38-1/2) (31-1/4) (7-7/16)
<With Case> 2 ARNU123CEU2
(5-13/16) (5-13/16)
ARNU153CEU2
[Unit : mm(inch)]
Number Name Descripition
- 99 -
1 Air discharge grill
978(38-1/2) 190(7-7/16) 2 Air suction grill
794(31-5/16) 13(1/2) 161(6-5/16) 14(1/2)
Note
1. Unit should be installed in compliance with the installation manual
20.4(3/4)
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
639(31-1/4)
6.28
(1/4)
<Without Case>
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CE
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Dimensions
203
Dimensions
(7-15/16)
ARNU243CFA2 ARNU243CFU2
203(7-15/16)
1345(52-15/16) 1
635(25)
Model W H D
ARNU183CFA2 1345 635 203
ARNU243CFA2 (52-15/16) (25) (7-15/16)
70(2-3/4)
49.5(1-15/16)
ARNU183CFU2 1256 639 190
148.3 1048.4(41-1/4) 148.3
- 100 -
1256(49-7/16 Note
1098(43-1/4) 109.8(4-5/16) 190(7-7/16)
1072(42-3/16) 30(1-3/16) 1. Unit should be installed in compliance with the installation manual
21.4(1-3/16)
161(6-5/16) 14(1/2)
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
81.4(3-3/16)
639(31-1/4)
145
(5-11/16)
70
(2-3/4)
<Without Case>
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: CF
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
1. Funtions ....................................................................................102
2. Operation Details......................................................................103
3. Dimensions ...............................................................................107
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
If the electric heater has been installed, indoor fan continuous
will be.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C(76F)
2. Operation Details
(1) The function of main control
n Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. OFF
(SET TEMPERATURE More than More than
-0.5C(33F))
3 minutes 3 minutes
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates
at low speed, when it becomes lower than 40C(104F) fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
n Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22(71.6).
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
n Heater Operation
The unit will operate according to the setting temperature and the indoor unit Heat-Exchanger temperature.
A-1 (34)
A-2 (36)
Indoor unit
Heat-Exchanger
temperature 45 (113)
42 (108)
30 (86)
28 (82)
Heater 2 ON OFF ON
Heater 1 ON OFF ON
543(21-3/8)
40(1-9/16) 46(1-13/16)
457(18)
432(17)
308(12-1/8) 117.5(4-5/8) 40(1-9/16)
65
[Unit : mm(inch)]
- 107 -
(2-9/16) 364(14-5/16)
1236(48-5/8)
Number Name Descripition
Unit size(18k):6.35(1/4)
6 1 Liquid pipe connection Unit size(24k,30k):9.52(3/8)
5 1 Unit size(18k):12.7(1/2)
2 Gas pipe connection Unit size(24k,30k):15.88(5/8)
3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: NJ
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Dimensions
ARNU423NKA2
ARNU483NKA2
ARNU543NKA2
4
40 49 5
(1-9/16) (1-15/16)
(16-15/16)
52
(2-1/16)
635
(25)
610
(24)
39 118
(1-9/16) (4-5/8)
6
- 108 -
55
65 362
(2-3/16)
1400 (2-9/16) (14-1/4)
(55-1/8)
308 1418 [Unit : mm(inch)]
(12-1/8) (55-13/16)
540 Number Name Descripition
(21-1/4) 1
1 Liquid pipe connection Unit size(28k,36k,42k):9.52(3/8)
2 Gas pipe connection Unit size(28k,36k,42k):15.88(5/8)
3 Drain pipe connection
4 Power supply connection
5 Air discharge
6 Air suction
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
LG Electronics USA, HVAC Division 76, Seongsan-dong, Changwon City, Gyeongnam, CHASSIS CODE: NK
1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 641-713, Korea
www.lgusa.com / www.lghvac.com www.lgeaircon.com
Self-diagnosis function
Self-Diagnosis Function
Error Indicator
This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LEDof
outdoor unit control board as shown in the table.
If more than two troubles occur simultaneously, lower number of error code is first displayed.
After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 051 : No.105 error of master unit
0 5 - Transmission error : outdoor unit indoor unit Failing to receive outdoor unit signal in indoor unit PCB
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
0 7 - Different operation mode Operation mode between indoor unit and outdoor unit is different
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
** In case the value is more than 100k (open) or less than 100 (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(5% margin) Normal
Air temp sensor: 10C(50F) = 20.7k : 25C(76F)= 10k : 50C(122F)= 3.4k
Pipe temp sensor: 10C(50F) = 10k : 25C(76F)= 5k : 50C(122F)= 1.8k
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
* If there is no remote controller to replace : Use another units remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input units address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Error
Error Type Error Point Main Reasons
No.
Yes
float
MAX 450
700mm(27-9/16inch)
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking
* (Note1) Transmission from IDU is normal if voltage * If the DC voltage between transmission terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU transmission from outdoor unit is normal
Error
Error Type Error Point Main Reasons
No.
Indoor unit outlet pipe Indoor unit outlet pipe Refer to CH02
06 temperature sensor temperature sensor open
error or short
Error
Error Type Error Point Main Reasons
No.
Yes Yes
END
ON ON
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON ON
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Error
Error Type Error Point Main Reasons
No.
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
Error
Error Type Error Point Main Reasons
No.
Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault
Is connector No
connection proper? Connect properly
Yes
Is fan motor No
Replace indoor unit fan motor
normal?*
Yes
* It is normal when check hall sensor of indoor fan motor as shown below
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)