Beruflich Dokumente
Kultur Dokumente
3. Perform the study with the aid of digital computer program that has
integrated arc-flash analysis that retrieves short circuit values and
protective device clearing times and uses these values for the
calculations.
5. The flash protection boundary and the incident energy shall be calculated
at all significant locations in the electrical distribution system as defined by
NFPA 70 (NEC) Section 110.16. Additionally, transformers, enclosed
circuit breakers, safety disconnect switches and other equipment shall be
evaluated for all voltage levels up to the limit of the IEEE 1584 standard,
where work could be performed on energized parts.
6.
Note: The required maximum incident energy noted here may be required
by site specific requirements to be lower. Some facilities require incident
energies do not exceed 8 cal/cm2.
13. For each equipment location with a separately enclosed main device
(where there is adequate isolation between the line side terminals of the
main protective device and distribution bus), the calculations for each
incident energy and flash protection boundary shall include both the line
and load side of the main breaker or the system modeled to treat these as
separate locations.
14. For equipment locations with integral main devices that are not isolated
from the distribution bus, the main device shall be ignored for the
calculations or the performed only on the line side of the main breaker.
15. Miscoordination must be checked among all devices with the branch
containing and a sufficient number of upstream devices such that
calculations utilize the fastest device to compute the incident energy for
the corresponding location. Where possible, protective device settings
shall be adjusted to minimize miscoordination. Locations where
miscoordination exists shall be identified in the report
16. Arc flash calculation shall be based on the actual overcurrent protective
device clearing time. A maximum clearing time of two seconds (based on
IEEE 1584-2002 section B.1.2) shall be used. For locations where it is not
physically possible to move outside of the flash protection boundary in
less than two seconds during arc flash event, the actual clearing time for
the specific location shall be used.
19. Summarize results of system study in a final report. The following shall be
included in the report:
For existing system, the collection of field data is also required and should be
included in the specifications.
1. The field data shall be collected by personnel familiar with the data
requirements to perform power system studies and be trained and have
appropriate personnel protective equipment to safely collect the data.
Field data collection personnel should be familiar with NEC requirements
such that obvious violations of the NEC can be documented.
3. The data collected shall be entered into a tabulated format that includes:
3.2. Trip type, and as-found settings for adjustable protective devices.
3.3. Size, type, quantity, conduit type and length of all conductor runs
within the scope of work.
3.5. Utility source data that includes maximum and minimum fault duties
(3-phase and line-ground) and X/R ratios.
3.7. Identify locations of egress that in the event of arc-flash event would
take more than 2 seconds.