Quick-Guide

Cross section view Mitglied der

hd,min hd hd,max Deutsche Gesellschaft fr Nachhaltiges Bauen e.V.


German Sustainable Building Council

lightweight concrete slabs


Method 1, in-situ casting
e = center distance of void formers

1. layer

efficient economic sustainable


solid zone zone with void formers

hu hd - (cnom,o + hbew,o + ci,o + cnom,u + hbew,u + ci,u)

Method 2, semi-prefabricated elements


cobiax installed on site
e = center distance of void formers

S-hooks

Additional
solid zone zone with void formers
Documents
for (hbew,u + ci,u) cft,min Cobiax brochure
General information about the technology
hu hd - (cnom,o + hbew,o + ci,o + hft + hbew,u + ci,u) and
hk hd - (cnom,o + hbew,o + ci,o + hft) Cobiax reference projects
Various reference projects around the
world
for (hbew,u + ci,u) < cft,min with special fixing element
hks hd - (cnom,o + hbew,o + ci,o + hft ) Cobiax engineering manual
Detailed information about Cobiax tech-
nology and design
Method 3, semi-prefabricated elements
Cobiax software tool quick & light
cobiax installed in the factory Free software for defining the cross- Germany Heinze Cobiax Deutschland GmbH
Heinze Cobiax Deutschland GmbH, February 2017

e = center distance of void formers section of the slab and determining Cobiax Otto-von-Guericke-Ring 10
specific input parameters for structural D-65205 Wiesbaden
design Tel. +49 6122 918 45 00
Fax +49 6122 918 45 40
Approvals, expert reports and other info.de@cobiax.com
documents
A company of the Heinze Group
General German Technical Approvals
www.heinze-gruppe.de
according to Euro Code 2, Fire tests and
acoustics approvals & tests, LCA (Life Worldwide to be found on our website.
solid zone zone with void formers Cycle Assessment), EPD (Environmental sales partners
Product Declaration)
hft cnom,u + hbew,u + ci,u + 2,0 cm and
hu hd - (cnom,o + hbew,o + ci,o + cnom,u + hbew,u + ci,u) available upon request or free
download from www.cobiax.com
www.cobiax.com
Quick-Guide
Heinze Cobiax Deutschland GmbH, February 2017
Quick-Guide

Introduction Design and detailing solid zone must be provided along linear sup- prefabricated elements requires a design detail Execution on site and ready for the second layer of concrete.
ports with a width equal to at least the centre check for the transfer of horizontal shear forces This can be done within a few hours, depend-
This Quick-Guide is designed to give you a A Cobiax voided slab can be designed and distance e of the void formers. At the free edge in the joint between both concrete layers con- The contractor installs the Cobiax void ing on the temperature, weather conditions
short introduction to the Cobiax technolo- planned by any structural engineer in com- of a slab a solid zone with the width of hd has sidering the reduced bonding area due to the formers modules according to the Cobiax and concrete properties. With the semi
gy. Additional information is available upon pliance with the local building code and to be provided. void formers (see software tool quick & light). layout drawing between the top and bottom pre-fabricated solution with Cobiax modules
request or as a download from www.cobiax. standards. Cobiax also has achieved the reinforcement layers using a fixed distance installed on site (Method 2) uplift is prevented
com. We strongly recommend the use of our General German Technical Approval according 3. Second run of structural calculation min e
support device (to ensure required minimum spacing). by tying the upper reinforcement with S-hooks
free Cobiax software tool quick & light. Our to Euro Code 2: The self-weight and if necessary, the bending min hd
Insitu solution as well as semi prefabricated or to the lattice girders of the semi-prefabricated
sales personnel will also be happy to answer stiffness are adjusted (back to full dead load prefabricated solutions are possible. With the elements. With the semi prefabricated
your questions. 1. Slab cross-section and design parameters and stiffness) in the solid zones without void in situ solution (Method 1) the void formers solution with Cobiax modules installed in the

slab
After estimating the slab thickness hd, a formers and a second, final run of structural VRd,c,cobiax are usually secured against uplift by casting factory (Method 3) no additional assurance

free edge of
suitable Cobiax void former module (support calculation has to be done. u+2d the concrete in two separate layers. After the meashures have to be provided to avoid uplift.
height hu respectively total height of fixing first concrete layer (approx. 8 cm to 12 cm
Technology and products element hk or hks) is selected, taking into 4. Detailed design check thick only in the area of the void formers) has Cobiax can be combined for example with post
account concrete cover cnom, the rebar layers Casting the concrete in two layers (to prevent Approx. 50% to 80% of the slab area is fitted with hardened, the void formers are finally fixed tensioning or concrete core activation.
Cobiax technology uses recycled lightweight hbew and any intermediate layers ci (e.g. for uplift of the void formers) or the use of semi- void formers (according to the different structural
plastic void formers to replace the heavy additional spacers or concrete core thermal configuration)

concrete inside a slab where it is not required. activation) and if necessary, the thickness of
The resulting savings of up to 35% in concrete the semi-prefabricated element hft. Additional
and weight has a positive effect on the requirements for the fire resistance have to
Application data Slim-Line Eco-Line
S100- S120- S140- S160- S180- S200- S220- S240- S260- S260- S260- S260- E-270 E-315 E-360 E-405 E-450
be taken into account if necessary. The load 120c 140c 160c 180c 200c 220c 240c 260c1) 280c1) 300c1) 320c1) 340c1)
reduction of void formers, the associated Generally
Slim-Line Eco-Line stiffness factor for the bending stiffness fEI Min. slab thickness hd,min cm 22 (20)1) 24 (22)1) 26 (25)1) 28 30 32 35 38 40 42 44 46 40 45 50 55 60
and the shear resistance factor fV (or the Max. slab thickness hd,max cm 45 56 70
reduced shear resistance VRd,c,cobiax = Support height hu cm 12 14 16 18 20 22 24 26 28 30 32 34 27.5 32 36.6 41.1 45.7
fV VRd,c) can be found in the table on the Fixing element (FE) height hk cm 12.5 14.5 16.5 18.5 20.5 22.5 24.5 26.5 28.5 30.5 32.5 34.5 28.0 32.5 37.1 41.6 46.2
next page. Alternatively the free software Shear factor fV - 0.50 0.45 0.50 0.45
tool quick & light can be used for quick pre- Stiffness factor fEI - 0.95 0.93 0.93 0.91 0.90 0.89 0.89 0.89 0.87 0.90 0.91 0.92 0.92 0.91 0.91 0.90 0.89
Void former height Dcx cm 10 12 14 16 18 20 22 24 26 26 26 26 27 31.5 36 40.5 45
Slim-Line void former Eco-Line void former liminary calculation.
modules for slab thicknesses modules for slab thicknesses Void former diameter cm 31.5 27 31.5 36 40.5 45
between 20 und 56 cm between 40 und 70 cm Min. center distance of void formers e cm 35 30 35 40 45 50
2. First run of structural calculation
Void formers per m2 pcs/m 8.16 11.11 8.16 6.25 4.94 4.00
The calculation of a Cobiax voided slab is to
Cross section vertical rebars FE cm/m 6.41 8.73 6.41 7.07 5.59 6.16
construction of the slab itself (e.g. less be done in similar manner as that of a con-
Concrete strength and consistency class - C20/25 up to C45/55, F3 up to F4 C20/25 up to C45/55, up to F4
deflection, larger spans or thinner slab ventional concrete slab, taking into account
Maximum aggregate mm 16 16 32
thickness) and hence on the whole building these 3 input parameters. With the first run of
CO2 Emission reduction t/m 0.011 0.013 0.016 0.018 0.020 0.022 0.024 0.026 0.028 0.028 0.028 0.028 0.024 0.028 0.032 0.036 0.040
structure. Cobiax void former modules, the structural calculation the load reduction
In situ solution and prefabricated concrete solution
which are internationally patented, consist and the reduced stiffness is applied for the
Volume displacement hcx m/m 0.0528 0.0641 0.0754 0.0858 0.0961 0.1055 0.1149 0.1248 0.1348 0.1348 0.1348 0.1348 0.1145 0.1336 0.1527 0.1718 0.1909
of 2.50 m long linear fixing elements (FE) whole slab. A consideration of the shear forces
Weight reduction (25 kN/m) kN/m 1.32 1.60 1.88 2.14 2.40 2.64 2.87 3.12 3.37 3.37 3.37 3.37 2.86 3.34 3.82 4.29 4.77
made from steel reinforcement fitted with leads to the determination of the required solid
Semi prefabricated concrete solution
void formers made of 100% recycled post- zones. Areas with VEd > VRd,c,cobiax must remain Volume displacement (-10%) 1) hcx,ft m/m 0.0475 0.0577 0.0679 0.0772 0.0865 0.0950 0.1034 0.1123 0.1213 0.1213 0.1213 0.1213 0.1031 0.1202 0.1374 0.1546 0.1718
consumer plastic. without void formers. In areas of punching Weight reduction (25 kN/m) kN/m 1.19 1.44 1.70 1.93 2.16 2.37 2.59 2.81 3.03 3.03 3.03 3.03 2.58 3.01 3.44 3.87 4.30
shear it is necessary to check whether the solid Min. distance between surface of semi- cft,min cm 2 0 0
zone extends beyond the critical circular cross- prefabricated element and longitudinal
rebar of void former module 2)
section or the last row of shear links by at least
Special fixing element height hks cm 14 16 18 20 22 24 26 28 30 - -
the dimension 2d. Otherwise the solid zone
must be enlarged accordingly. Additionally, a 1) Increased center distance of void formers caused by additional lattice girders 2) e.g. additional spacers or with special fixing element

Heinze Cobiax Deutschland GmbH, February 2017