TechnicalInformationabouttheSpacingofEquipmentin
PetrochemicalPlants
March15,2012qdzung1comment
Equipmentspacingintheplantdesignandpipingdisciplineisoneareathatcontinuestoresist
automation.Surethereareinhouseandthirdpartyprogramsouttherethatassistdesignersin
developingplotplans.MostoftheseprogramsarejustoverlaysonCADDproducts.These2D/3DCADD
overlaysmaygivefeedbackoncostsofthearrangementorthese2D/3DCADDoverlaysmayspeedup
thedevelopmentoftheplotbyautomatingthegenerationofequipmentgraphicsandstructuralgraphics.
Howevertherearenotoolsouttherethatwillarrangeaplotplanautomatically.
Themainreasonforthislackofequipmentarrangementautomationistheinabilitytodeveloprulesthat
completelydefinehowalistofequipmentshallbearrangedonaplot.Thedifficultyindefining
equipmentarrangementrulesisduetothecomplexityinvolved.
Hereisapartiallistoftheequipmentarrangementdesignconsiderationsthatmustbeaddressedoneach
project.
Highhazardoperations
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 1/136
4/26/2017 PlantLayout|ABCEngineering
Groupedoperations
Criticaloperations
Numberofpersonnelatrisk
Concentrationofpropertyandbusinessinterruptionvalues
Equipmentreplacementandinstallationtime
Interdependencyoffacilities
Criticalcustomerorsupplierrelationships
Marketshareconcerns
Fireandexplosionexposures
Corrosiveorincompatiblematerialsexposures
Vaporcloudexplosions
Sourcesofignition
Maintenanceandemergencyaccessibility
Drainageandgradesloping
Prevailingwindconditions
Naturalhazardsandclimate
Futureexpansions
Externalexposures
ThedesignconsiderationforVaporCloudExplosionsaloneisasubjectthatfillsbooks.Theanalytical
automationtoolsforstudyingBoilingLiquidEvaporatingVaporExplosions(BLEVE)arefewandare
proprietary.ThereisdocumentationonhowtoevaluateBLEVEimpactsusinghandcalculations,suchas
theTNTequivalencymethod.Howeveritisgenerallyacceptedthatthesehandcalculationmethodsdoa
poorjobofpredictingBLEVE.
AndBLEVEsarejustoneformofVaporCloudexplosions!Othertypesofvaporcloudexplosionsrequire
differentanalyticaltechniques.
Sowhatdoesthedesignerdo?Designerstheworldovergenerallyrelyontheircompanys(ortheir
clients)tablestandardthatlistshowfaronepieceofequipmentneedstobefromanotherpieceof
equipment.Thesetablesaretypicallygeneratedbasedonexperienceparticularlytheexperienceofthe
insuranceindustry.AsamplechartfromtheBausbacher/Huntbookisshownabove.
Thefollowingpagesaregoingtocompareanddiscussthevariousspacingcriteriaavailableinthepublic
domain.Wewillalsotrytopointoutwherethesecriteriaconflict,andwheretheymaybeweak.
Bytheway,thepicturetotherightisofarecentexplosioninaplantwherethespacingcriteriasatisfied
aninsurancegroupsrequirementsforequipmentspacing.Theinitialexplosioncausedadominoeffect
thatleveledthreeunits.
Categories:PlantLayoutTags:plantlayout,TechnicalInformation
PlantLayoutStorageTanks
March15,2012qdzung1comment
TableofContents
1.TankageGrouping
2.ClassificationofCrudeOilandItsDerivatives
3.TankageLayout
4.PumpAreas
5.FireProtection
6.RoadandRailLoadingFacilities
1.TankageGrouping
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 2/136
4/26/2017 PlantLayout|ABCEngineering
Tankageareawillbesubdividedintovariousgroupsdeterminedbythecontentsofthetanksandthe
relativeshapeandareaoftheplotavailable,accessandfirefightingmustalsobeconsidered.Seebelow
tableAPItanksizeforlayoutpurposes.
2.ClassificationofCrudeOilandItsDerivatives
Crudeoilanditsderivativesarepotentiallyhazardousmaterials.Thedegreeofthehazardisdetermined
essentiallybyvolatilityandflashpoint.
TheInstituteofPetroleumhasspecifiedthefollowingclasses:
Class0 Liquifiedpetroleumgases(LPG)
ClassI Liquidswhichhaveflashpointsbelow21oC
Liquidswhichhaveflashpointsfrom21oC
ClassII (1) uptoandincluding55oChandled,below
flashpoint
Liquidswhichhaveflashpointsfrom21oC
ClassII (2) uptoandincluding55oChandled,ator
aboveflashpoint
Liquidswhichhaveflashpointsabove55oC
ClassIII (1) uptoandincluding100oChandled,below
flashpoint
Liquidswhichhaveflashpointsabove55oC
ClassIII (2) uptoandincluding100oChandled,above
flashpoint
Unclassified. Liquidswithflashpointsabove100oC
ForfurtherinformationseeIPrefinerysafetycodepart3.
3.TankageLayout
3.1General
Thelayoutoftanks,asdistinctfromtheirspacing,shouldalwaystakeintoconsiderationtheaccessibility
neededforfirefightingandthepotentialvalueofastoragetankfarminprovidingabufferareabetween
processplantandpublicroads,houses,etc.,forenvironmentalreasons.
Thelocationoftankagerelativetoprocessunitsmustbesuchastoensuremaximumsafetyfrompossible
incidents.
Primarilyrequirementsforthelayoutofrefinerytanksfarmsaresummarisedasfollows.
1.Intertankspacingsandseparationdistancesbetweentankandboundarylineandtankandotherfacilities
areoffundamentalimportance.(See3.2).
2.Suitableroadwaysshouldbeprovidedforapproachtotanksitesbymobilefirefightingequipmentand
personnel.
3.Thefirewatersystemshouldbelaidouttoprovideadequatefireprotectiontoallpartsofthestoragearea
andthetransferfacilities.
4.Bundinganddrainingoftheareasurroundingthetanksshouldbesuchthataspillagefromanytankcan
becontrolledtominimisesubsequentdamagetothetankanditscontents.Theyshouldalsominimisethe
possibilityofothertanksbeinginvolved.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 3/136
4/26/2017 PlantLayout|ABCEngineering
5.Tankfarmsshouldpreferablynotbelocatedathigherlevelsthanprocessunitsinthesamecatchment
area.
6.Storagetanksholdingflammableliquidsshouldbeinstalledinsuchawaythatanyspillwillnotflow
towardsaprocessareaoranyothersourceofignition.
3.2.SpacingofTanksforLPGStocksofClass0
Recommendations
Factor forLPGStoredin
PressureTanks
Onequarterofthe
sumofthe
1.BetweenLPGpressurestorage
diametersofthe
tanks
twoadjacent
tanks.
15Mfromthetop
2.ToClassI,II,orIIIproduct ofthesurrounding
tanks. ClassI,IIorIII
producttanks.
Onediameterof
thelargestlow
pressure
3.Tolowpressurerefrigerated
refrigerated
LPGtanks.
storagetanksbut
notlessthan30
M.
4.Tobuildingcontaining
flammablemateriale.g.filling 15M
shed,storagebuilding.
Relatedtowater
5.Toboundaryoranyfixed
capacityoftankas
sourceofignition.
follows:
CapacityUpto
135cu.MOver Distance15M
135to565cu.M 24M30M
Over565cu.M
Thedistancegivenintheabovetableareminimumrecommendationsforabovegroundtanksandreferto
thehorizontaldistanceinplanbetweenthenearestpointonthestoragetankandaspecifiedfeature,e.g.
anadjacentstoragetank,building,boundary.Thedistancesareforbothsphericalandcylindricaltanks.
3.3BundingandGroupingofLPGTanks
TheprovisionofbundsaroundLPGpressurestoragetanksisnotnormallyjustified.
Separationkerbs,lowtoavoidgastraps,maximum600mmhigh,maybelocatedtopreventspillage
reachingimportantareas,e.g.pumpmanifoldarea,pipetrack.
Groundundertanksshouldbegradedtolevelswhichensurethatanyspillagehasapreferentialflow
awayfromthetank.
Pitsanddepressions,otherthanthosewhichhavebeenprovidedascatchmentareas,shouldbeavoidedto
preventtheformingofgaspockets.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 4/136
4/26/2017 PlantLayout|ABCEngineering
PressurestoragetanksforLPGshouldnotbelocatedwithinthebundedenclosuresofClassI,IIorIII
producttankageoroflowpressurerefrigeratedLPGtankage.
Thelayoutandgroupingoftanks,asdistinctfromspacing,shouldreceivecarefulconsiderationwiththe
viewofaccessibilityforfirefightingandtheavoidanceofspillagefromonetankflowingtowardsthe
othertankortowardsanearbyimportantarea.
3.4SpacingofTanksforLowPressureRefrigeratedLPGStorage
Class0
RecommendationsforLow
Factor PressureRefrigeratedLPG
Storage
Onehalfofthesumofthe
1.BetweenrefrigeratedLPG
diametersofthetwoadjacent
storagetanks
tanks.
Onediameterofthelargest
2.ToClassI,II,orIIIproduct
refrigeratedstoragetankbutnot
tanks.
lessthan30M.
Onediameterofthelargest
3.Topressurestoragetanks. refrigeratedstoragetankbutnot
lessthan30M.
4.Toprocessunits,office
building,workshop,laboratory,
45M
warehouse,boundary,oranyfixed
sourceofignition.
Thedistancegivenintheabovetableareminimumrecommendationsandrefertothehorizontaldistance
inplanbetweenthenearestpointonthestoragetankandaspecifiedfeature,e.g.anadjacentstorage
tank,building,boundary.
3.5.BundorImpoundedBasinforRefrigeratedLPGStorage
AbundshouldbeprovidedaroundalllowpressuretankscontainingrefrigeratedLPG.Thetankshould
becompletelysurroundedbythebund,unlessthetopographyoftheareaissuch,eithernaturallyorby
construction,thatspillscanbedirectedquicklyandsafely,bygravitydrainageanddiversionwallsif
required,toadepressionorimpoundingbasinlocatedwithintheboundaryoftheplant.
Bundsshouldbedesignedtobeofsufficientstrengthtowithstandthepressuretowhichtheywouldbe
subjectedifthevolumewithinthebundedenclosurewerefilledwithwater.Theareawithinthebund,
depression,orimpoundingbasisshouldbeisolatedfromanyoutsidedrainagesystembyavalve,normally
closedunlesstheareaisbeingdrainedofwaterundercontrolledconditions.
Whereonlyonetankiswithinthebund,thecapacityofthebundedenclosure,includingthecapacityof
anydepressionorimpoundingbasis,shouldbe75percentofthetankcapacity.Wheremorethanone
tankiswithinthemainenclosure,intermediatebundsshouldbeprovided,soastogiveanenclosure
aroundeachtankof50percentofthecapacityofthattank,andtheminimumeffectivecapacityofthe
mainenclosure,includinganydepressionorimpoundingbasin,shouldbe100percentofthecapacityof
thelargesttank,afterallowingforthevolumeoftheenclosureoccupiedbytheremainingtanks.Itis
desirablefortherequiredcapacitytobeprovidedwithbundsnotexceedinganaverageheightof6footas
measuredfromtheoutsidegroundlevel.
Theareawithinthebundshouldbegradedtolevelswhichensurethatanyspillagehasapreferentialflow
awayfromthetank.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 5/136
4/26/2017 PlantLayout|ABCEngineering
NotankageotherthanlowpressuretankageforrefrigeratedLPGshouldbewithinthebund.Thelayout
andgroupingoftanks,asdistinctfromspacing,shouldreceivecarefulconsiderationwiththeviewof
accessibilityforfirefighting.
3.6PipingInstallationandFlexibility
Liquidandvapourpipelinesshouldhaveadequateflexibilitytoaccommodateanysettlementoftanksor
otherequipment,thermalexpansionorotherstressesthatmayoccurinthepipeworksystem.
Precautionmustbetakentopreventdrainorsamplevalvesfreezingintheopenposition.Theflow
diagramwillindicatethetypeofdoublevalvingtobeinstalled,withaminimumdistancebetweenthe
valvesof1meter.Donotallowliquidtrapsinventlines.
3.7SpacingofTankforPetroleumStocksofClassesI,IIandIII(2).
Typeof
RecommendedMinimum
Factor Tank
Distance
Roof
Determinedsolelyby
1.Withinagroupof Fixedor
construction/maintenance
smalltanks Floating
operationalconvenience
2.Betweenagroupof 10Mminimum,otherwise
Fixedor
smalltanksorother determinedbythesizeofthe
Floating
largertanks. largertanks(see3below)
3.Betweenadjacent Halfthediameterofthelarger
individualtanks(other (a)Fixed tank,butnotthan10Mandneed
thansmalltanks). notbemorethan15M.
0.3timesthediameterofthe
largertank,butnotlessthan10M
(b)Fixed andneednotbemorethan15M.
(Inthecaseofcrudeoiltankage
this15Moptiondoesnotapply)
Distanceequaltonotlessthan
4.Betweenatankand
halftheheightofthetank.
thetopoftheinsideof Fixedor
(Accessaroundthetankat
thewallofits Floating
compoundgradelevelmustbe
compound
maintained)
5.Betweenanytankina
groupoftanksandthe
Fixedor
insidetopofthe
Floating
adjacentcompound
wall.
6.Betweenatankanda Fixedor
Notlessthan30M
publicboundaryfence. Floating
7.Betweenthetopof
theinsideofthewallof
atankcompoundanda
Notlessthan15M
publicboundaryfence
ortoanyfixedignition
source.
8.Betweenatankand Fixedor Notlessthan30M
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 6/136
4/26/2017 PlantLayout|ABCEngineering
thebatterylimitofa Floating
processplant.
9.Betweenthetopof
theinsidewallofatank
compoundandthe Notlessthan15M
batterylimitofa
processplant
ThetableabovegivesaguidanceontheminimumtankspacingforClassI,IIandIII(2)storagefacilities,
thefollowingpointsshouldbenoted.
1.Tanksofdiameterupto10Mareclassedassmalltanks
2.Smalltanksmaybesitedtogetheringroups,nogrouphavinganaggregatecapacityofmorethan8000
m3.Suchagroupmayberegardedasonetank.
3.Wherefuturechangesofserviceofastoragetankareanticipatedthelayoutandspacingshouldbe
designedforthemoststringentcase.
4.Forreasonsoffirefightingaccessthereshouldbenomorethantworowsoftanksbetweenadjacent
accessroads.
5.Fixedroofwithinternalfloatingcoversshouldbetreatedforspacingpurposesasfixedrooftanks.
6.Wherefixedroofandfloatingrooftanksareadjacent,spacingshouldbeonthebasisofthetank(s)with
themoststringentconditions.
7.Wheretanksareerectedoncompressiblesoils,thedistancebetweenadjacenttanksshouldbesufficientto
avoidexcessivedistortion.Thiscanbecausedbyadditionalsettlementsofthegroundwherethestressed
soilzoneofonetankoverlapsthatoftheadjacenttank.
8.ForClassIII(1)andunclassifiedpetroleumstocks,spacingoftanksisgovernedonlybyconstructional
andoperationalconvenience.However,thespacingofClassIII(1)tankagefromClassI,IIorIII(2)
tankageisgovernedbytherequirementsforthelatter.
9.Fortypicaltankinstallation,illustratinghowthespacingguidesareinterpretedseebelowfigures.
Fordetailsofatypicalverticaltankfoundationseebelowfigures.
3.8TankFarmPipingandLayout
Pipelinesconnectedtotanksshouldbedesignedsothatstressesimposedarewithinthetankdesignlimits.
Thesettlementofthetankandtheoutwardmovementoftheshellunderthefullhydrostaticpressure
shouldbetakenintoaccount.Thefirstpipesupportfromthetankshouldbelocatedatasufficient
distancetopreventdamagebothtothelineandtotankconnections.Considerationmaybegivento
installingspringsupportsneartotankconnectionforlargeborepipework.
Aslargediametertankshaveatendencytosettleontheirfoundations,provisionmustbemadeinthe
suctionandfillingpipingtotakecareoftanksettlement.Thismayrequiretheuseofexpansionjoints,
victauliccouplings,oralapjointflangeinstalledasshowninseebelowfigure.
Thefollowingnotemustbeaddedtoallpipingdrawingscontainingstoragetanks:
Allpipingmustbedisconnectedfromtankduringhydrostatictestofstoragetank
Thenumberofpipelinesintankcompoundsshouldbekepttoaminimum.Theyshouldberoutedinthe
shortestpracticablewaytothemainpipetrackslocatedoutsidethetankcompounds,withadequate
allowanceforexpansion.
Flexibilityinpipingsystemsmaybeprovidedthroughtheuseofbends,loopsoroffsets.Wherespaceisa
problemsuitableexpansionjointsofthebellowstypemaybeconsideredforinstallationinaccordance
withmanufacturersdesignspecificationsandguides.Theseexpansionjointsshouldbeusedonlyin
serviceswherethefluidpropertiesaresuchthatpluggingofthebellowscannotoccur.Theyshouldbe
anchoredandguided,shouldnotbesubjectedtotorsionalloads,andshouldbecapableofready
inspection.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 7/136
4/26/2017 PlantLayout|ABCEngineering
Tankfarmpipingshouldpreferablyberunabovegroundonconcreteorsteelsupports.Groundbeneath
pipingshouldbesogradedastopreventtheaccumulationofsurfacewaterorproductleakage.Manifolds
shouldbelocatedoutsidethetankbunds.
Pipingshouldpassoverearthbundwalls,however,ifthisisimpossible,asuitablepipesleevewillbe
providedtoallowforexpansionandpossiblemovementofthelines.Theannularspaceshouldbe
properlysealed.Likewiselinespassingthroughconcretebundwallswillbeprovidedwithpipesleeves.
Pedestrianwalkwaysshouldbeprovidedtogiveoperationalaccessovergroundlevelpipelines.
Pipelinesshouldbeprotectedagainstunevengroundsettlementwheretheypassunderroadways,
railwaysorotherpointssubjecttomovingloads.
Buriedpipelinesshouldbeprotectedexternallybycorrosionpreventingmaterials,orbycathodicmeans.
Routesofburiedpipelinesshouldbeadequatelymarkedabovegroundandrecorded.
Piperackscarriedacrosspathsorroadsshouldhaveadequateclearancefromgrade.Adequateaccess
stairwaysorladdersandoperatingplatformsshouldbeprovidedtofacilitateoperationandmaintenance
attanks.Tanksmaybeinterconnectedatrooflevelbybridgeplatforming.
Allnozzles,includingdrainsonatankshell,shouldhaveblockvalvesadjacenttothetankshellorasclose
aspracticable.
3.9TankBundCompoundCapacities
AbovegroundtanksforClassI,II(1),II(2)andIII(2)petroleumliquidsshouldbecompletely
surroundedbyawallorwalls.Alternatively,itisacceptabletoarrangethatspillageoramajorleakfrom
anytankaredirectedquicklyandsafelybygravitytoadepressionorimpoundingbasisataconvenient
location.
Thedistancebetweentheedgeoftheimpoundingbasinandthenearesttankortheinsidetopofthe
nearestbundwallshouldbeaminimumof30M.Thedistancebetweentheedgeofthebasinandroad
fencebatterylimitofaprocessplantshouldnotbelessthan15M.
Theheightofthebundwallasmeasuredfromoutsidegroundlevelshouldbesufficienttoafford
protectionforpersonnelwhenengagedinfirefightingandthewallshouldbelocatedsothatareasonably
closeapproachcanbemadetoatankfiretoallowuseofmobilefirefightingequipment.Accessroads
overbundwallsintoverylargecompoundsarehelpfulincertainfiresituations.
Separatewallsaroundeachtankarenotnecessary,butthetotalcapacityofthetanksinonebundedarea
shouldberestrictedtothefollowingmaximumfigures:
Singletanks Norestriction
Groupsoffloatingrooftanks 120,000m3
Groupsoffixedrooftanks 60,000m3
Notmorethantwotanksof
Crudetanks greaterindividualcapacitythan
60,000m3
Thefiguresforb.andc.maybeexceededforgroupsofnotmorethanthreetanks,wheretherecanbeno
riskofpollutionorhazardtothepublic.
Intermediatewallsoflesserheightthanthemainbundwallsmaybeprovidedtodividetankageinto
groupsofaconvenientsizesoastocontainsmallspillagesandactasfirebreaks.
Buried,semiburiedormoundedtanksneednotbeenclosedbyabundwallexceptwhentheyarelocated
ingroundhigherthanthesurroundingterrain.However,considerationshouldbegiventotheprovisionof
smallbundwallsaroundassociatedtankvalves.
Thenetcapacityofthetankcompoundshouldgenerallybeequivalenttothecapacityofthelargesttank
inthecompound.However,areductionofthiscapacityof75%willprovidereasonableprotectionagainst
spillageandmaybeadoptedwhereconditionsaresuitable(e.g.wheretherecanbenoriskofpollutionor
hazardtothepublic).Thenetcapacityofatankcompoundshouldbecalculatedbydeductingfromthe
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 8/136
4/26/2017 PlantLayout|ABCEngineering
totalcapacitya.thevolumeofalltanks,otherthanthelargest,belowthelevelofthetopthecompound
wallandb.thevolumeofallintermediatewalls.
Alowwallwhichneednotbemorethan0.5mhigh,shouldbeconstructedforClassIII(1)and
unclassifiedpetroleumproducttankagewhereconditionsaresuchthananyspillageorleakagecould
escapefromtheinstallationandcausedamagetothirdpartypropertydrainagesystems,riversor
waterways.
WherethereisapossibilitythattanksstoringtheseproductsmaybeinthefuturerequiredforClassI,II
(1)orIII(2),thenthecompoundwallsshouldbesuitableforthispotentialsituation.
4.PumpAreas
Pumpswillbelocatedoutsidebundareas.Thevesselspracticeistogroupthepumpsintobays.Keepthe
suctionlinesasshortaspractical.Thedischargepipingwillrunonlowleveltrackstotheprocessor
loadingareas.Thesetrackswillusuallypassunderroadsinculverts,butmaypassoveronapipebridge.
Longpiperunsmayrequireexpansionloopstoprovideflexibility.Consultwithstresssection.
5.FireProtection
Forstorageareasthemajorfirefightingeffortwillbeprovidedbymobileequipmentlayingdownlarge
blanketsoffoamand/orapplyinglargevolumesofwaterforcoolingpurposes.
Itisessentialtoprovideagoodsystemofallweatherroadstofacilitatethetransferoffireprotection
materialsandequipmenttothesceneofthefire.Theseroadsmustbeofadequatewidthand,wherever
possible,withnodeadends.
Itisimportantinthesitingoftanks,bundwallsandaccessroadsthatthetankscanbeprotectedby
coolingwaterorfoamappliancessituatedoutsidethecompoundwalls.Accountmustbetakenofthe
heightofthetankandthepossibleneedtocooltherooforprojectfoamontoatank.
Dryrisersforfoammaybeprovidedtothetopofstoragetankswiththeirconnectionsadjacenttoaccess
roads,fixedmonitorsmayalsobeemployed.Theflowdiagramwilldefinethesystemtobeemployed.
6.RoadandRailLoadingFacilities
Roadandrailloadingfacilitiesareusuallyassociatedwithstoragearea.Thesafelocationofthesein
relationtostoragetanksislaiddowninsection3.7.
Theroadorrailcarwillbefilledfromaloadingisland,thesupplylineswillbeeitherroutedunderground,
oronanoverheadpipebridge.Checkforclearances.
Belowfiguresshowsuchinstallations.
Ithasbecomecommonpracticetoprovideavapourcollectionsystemforthesaferemovalofvapours
duringtheloadingprocess.Thissystemwouldemployunloadingarmswhichareconnectedtoacollection
systemandpipedtoaventstackatasafelocation.
Whenlayingoutaloadingareaconsiderationmustbegiventothenumberofvehiclesorrailcarsper
hourtobeloaded.Asuitablemovementpatternmustbeestablishedforincomingandoutgoingvehicles
orrailcars.Weighbridgeswillberequired,thesystemofmovingrailcarsmustbedefined,building
housing,operationofficesandfacilitiesfordrivesetc.,mustbeprovided.
Figures:
APITANKSIZEFORLAYOUTPURPOSE
BasedonAPI650
Capacity
Diameter Height
Approximately
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 9/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 10/136
4/26/2017 PlantLayout|ABCEngineering
3NOINTERTANKSPACINGREQUIREMENTS
OTHERTHANFORCONSTRUCTION/OPERATION/MAINTENANCECONVENIENCE.TANKS
D1&D2ARETANKSWITHDIAMETERSGREATERTHAN10m.,&WITHDIAMETEROFD2
GREATERTHAND1.
Intertankspacingsbetweensmallandlargertanks.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 11/136
4/26/2017 PlantLayout|ABCEngineering
FLOATINGROOFTANKSOFDIAMETERD1D2D3GREATERTHAN10m.WITHINTHESAME
COMPUND.D1GREATERTHAND2&D2GREATERTHAND3.
Figure3.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 12/136
4/26/2017 PlantLayout|ABCEngineering
FIXED&FLOATINGROOFTANKSWITHINTHESAMECOMPOUND.D1GREATERTHAND2,
D2EQUALTOD3.
Figure4.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 13/136
4/26/2017 PlantLayout|ABCEngineering
Intertankspacingsforfixedandfloatingrooftanks(greaterthan10mdiameter)
LapjointFlangeDetailforTankSettlement
Figure5.
Foundationforverticaltank
BasedonBS2654
Figure6.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 14/136
4/26/2017 PlantLayout|ABCEngineering
Categories:PlantLayoutTags:designguide,plantlayout,StorageTanks
PlantLayoutColumn
March15,2012qdzungLeaveacomment
TableofContents
1.General
2.Layout
3.Internals
4.Overheads
5.Reflux
6.Feeds
7.Instruments
8.ReboilerConnections
9.Platforms
10.Piping
11.TopHeadReliefValves
12.Clips
1.General
Thefractionationcolumncomprisesaverticalcylinderinterspacedatequalintervalswithtrays.Often
theseareintheformofsimpleperforateddisks,butmorecomplexarrangementsoccurdependingupon
columnfunction.Contentsareheatednearthebottomproducingvapourswhichriseupthroughthe
trays,meetingaflowofliquidpassingdownasaresultofcondensationoccuringatvariouslevels.
Itisessentialtoensuremaximumsurfacecontactbetweenvapourandliquid.Thelightestfractionsare
drawnfromthehighestelevations,theheaviestresiduebeingdepositedatthebottom.
2.Layout
Itisnecessarytoestablishwhethercolumnisworkingasasingleunitorinconjunctionwithothers
similar.Dependentuponprocessarrangementsflowmaybesequentialfromonetothenext.Thusfor
maximumeconomyorderofcolumnsmustbearrangedtogiveshortestpipingrunsandlowestpumping
losses.Considerationshouldbegiven,wherenecessary,tomaterialused,sincealthoughcorrectsequence
mayhavebeeneffectedunnecessaryexpensemaybeinvolvedwithalloylines.Suchcasesmustbetreated
ontheirmerits.
Columnisinterconnectedwithotherprocessequipmentsoitmustbelocatedadjacenttopiperackto
allowpipingconnectionstoruntoandfromtherackinorderlyfashion.Automaticallythismeansthat
manways(providedforerectionoftraysandmaintenance)shouldbelocatedontheoppositesideofthe
columnawayfromtheracktoprovidesuitableaccessforequipmentrequiredtoberemoved(seebelow
figures).Thisisnotmandatorysinceoccasionsarisewhenotherarrangementsarenecessary.
3.Internals
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 15/136
4/26/2017 PlantLayout|ABCEngineering
Havinglocatedmanways,orientateinternaltraystoensureunimpededaccess.Dependinguponthetype
oftrayusedoneormoredowncomerpartitionsmayberequired.Iftheseareorientatedincorrectlyentry
willbeimpossibleviamanholeunlessthecolumnisexceptionallylarge.Preferablydowncomersare
arrangednormaltomanwayaccesscenterline.Processconnectionscanbelocatedinlogicalsequence,
startingfromthetopwhentrayorientationisestablished.
4.Overheads
Highestconnectionistheoverheadvapourlinewhichisusuallyconnectedtoacondensingunit.Anairfin
typeunitmaybelocatedontopofthepiperack.Alternativelyashellandtubeexchangertypecondenser
isusuallylocatedonastructureadjacenttothecolumn(asmayairfinunit).
Overheadvapourconnectionmayprojectverticallyfromtopofthecolumnfollowedbya90bendorit
mayemergefromthesideat45,usinganintegralprojectionextendingupalmosttothecentertopinside
thehead(seebelowfigure9).
Thelatterismoreeconomicinpipingsinceiteliminatesuseofsomeexpensivefittingsespeciallywhen
largediameteroverheadlinesareinvolved.Italsomakespipingsupportingsimplerasuseofa45elbow
enablespipetorundownclosetothecolumn.Disadvantageisgreaterrigiditymakingstressanalysis
moredifficult.
Oftenpermittedpressuredropbetweenoutletnozzleandexchangerislow(i.e.approximately0.5PSI)
thusitisessentialtoobtainstraightestandshortestrunpossible.Ifconnectionisfromthetopspecial
arrangementsmustbemadeforsupportingthelinewhichisoftenlargediameter.
Thecondenserisusuallyselfdraining.Oftensomeofthecondensedliquidisrequiredtobepumpedback
intothecolumn(reflux).Thusthecondensedliquidflowsbygravitytoarefluxdrumsituated
immediatelybelowtheexchanger.Thisdrumcanalsobemountedinthesamestructuresupportingthe
exchanger.Thisisimportantsinceifitwerelocatedelsewhereanadditionalpumpwouldberequiredif
theliquidhadtobeelevatedagainafterflowingfromthecondenser.
Furthermore,sincetheliquidintherefluxdrumhastobereturnedtothecolumnbyapumpitis
convenienttolocatethisunderneaththerefluxdrumatthebaseofthestructure.
Itfollows,therefore,thattheorientationoftheoutletofthevapourconnectionwillautomaticallyfixthe
locationoftheexchangerandtherefluxdrumorviceversa.Therefluxpumpdischargesbackintothe
towerusuallyatahighelevation,andsincethepipingshouldbestraightandasshortaspossible,itwill
probablycomeupatthesideasthevapourconnection.
5.Reflux
Traysarenumberedstartingfromthetop.Thefirstdowncomeristhereforeanoddone.Oftenthereflux
connectionislocatedabovethetoptray(seebelowfigure3).Thismeansthatorientationoftheoddand
eventrayscanbefixedsincetoutilizethetraycontactsurface,therefluxconnectionmustoccuronthe
oppositesideofthedowncomer.
6.Feeds
Themostimportantconnectionsarethefeeds(seefigures4and6).Thesemayoccurovertheoddoreven
traysoracombinationofboth.Theirelevationallocationisentirelyafunctionofprocessdesign.
Dependinguponthis,orientationofthenozzlewillfollow,butensurethatthenozzleisnotlocatedbehind
thedowncomerfromthetrayabove.Thiswouldresultinaliquidbuildupinthedowncomerrestricting
flowthroughthetraybelowandpreventingcorrectoperation.
Feedconnectionsareusuallylocatedinthetrayareabetweenthedowncomersinamannertoensure
maximumuseofthetrayareaaspossible.Oftenaninternalfeedpipeorspargerisusedtofacilitatethis.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 16/136
4/26/2017 PlantLayout|ABCEngineering
7.Instruments
Instrumentconnectionsmustbearrangedsothatpressureconnectionsareinthevapourspaceand
temperatureconnectionsareimmersedintheliquid.
Sometimesitisbettertoputthetemperatureconnectionsinthedowncomerpartofthetraysincethe
depthofliquidwillbegreateranditwillbeeasiertoobtaineffectivecoverage.
Probelengthandmechanicalinterferencemaypreventthis,ifsolocatethermowelloverthetrayitself.
Thisshouldbedoneonlyoninstallationswheretheliquiddepthonthetrayissufficient(seebelowfigure
8).
Thebaseofthetowercontainsalevelofliquidwhichiscontrolledbyhighandlowlevelcontrollers,liquid
levelalarmsandlevelgauges(seebelowfigure7).Careshouldbetakenwhenorientatingthese
instruments,thattheydonotobstructaccessontheplatform.Physicalspacethattheseinstruments
occupycanbeexcessive.Donotpositionimmediatelyadjacenttoladdersormanholes.
8.ReboilerConnections
Reboilerliquidandvapourconnectionsarelocatedeitherrelevanttoliquidhead(elevation)orstress
requirements,orboth.Twoconfigurationsarepossible:
1.Vertical
2.Horizontal
Forhorizontalreboilers,considerationmustbegiventoshortestmostdirectconnectionroutetoreduce
pressuredropwhichwillprobablygoverndesignlayout.Inbothcasestheremaybesupportproblems.
Usually,averticalreboiler(thermosyphonoperated)offerstheeasiestsolution.
Flexibilityisobtainedonthelowerconnectionwhereentryintothebottomofthetowercanbevariedas
requiredandsupportproblemsaresimplified.
9.Platforms
Alloftheaboverequiresaccessofsomekind.Tominimisecostminimumplatformingshouldbeprovided
consistentwithsafety.
Orientationarrangementsshouldbedesignedtoavoidneedfor360platforms.
Aplatformshouldnotextendalmostentirelyroundthecolumnsimplytoprovideaccesstoatemperature
connectionwhichcouldhavebeenlocatedontheopositeside.Whereseveralcolumnsmaybeworking
together,linkplatformsmayberequiredtomovefromonetothenext.Inthesecasesstrictconsideration
mustbegiventomaximiseeconomy.
Overallheightisgovernedbya.numberoftrays,b.pumpNPSHrequirementsand,c.staticliquidhead.
Thislatterheadnecessaryforthermosyphonreboilerestablishestheskirtheight.
10.Piping
Somecircumstancesrequireroutinglinespartiallyaroundthecolumn.Shouldtheselinescrossaplatform
sufficientheadroomclearancemustbeprovided.
11.TopHeadReliefValves
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 17/136
4/26/2017 PlantLayout|ABCEngineering
Reliefvalvesvaryinnumberandsize.Locationcandependonwhetherdischargeistoatmosphereora
closedsystem.Ifdischargingtoaclosedsystem,locateataconvenientplatformdownthecolumnabove
thereliefheaderseebelowfigure5).Ifdischargingtoatmospherelocateontopofthecolumn,withthe
openendofthedischargeaminimumof3000mmabovethetopplatform.Formaintenanceremoval,
valveshouldbelocatedtoallowtopheaddavittopickitup.Dependentuponsizemultiplereliefvalves
mayrequireagantrystructureonthetophead.
12.Clips
Earlyorientationofnozzlesandroutingoflinesallowplatformsandpipesupportcliplocationstobe
passedtocolumnvendorquickly.
Itisbecomingmorearequirementthatclipsbeweldedoninthevesselfabricationshopparticularlyfor
alloysteels.
Whenlocatingplatformsandladders,themaximumladderlengthshouldnotexceed9Mwithoutarest
platform.
Platformsshould,wherepossible,beelevated900mmbelowmanways.
ManwaysDavitsorhingesshouldbepositionedtoavoidswingofcoverfoulinginstrumentsorother
connections.
Whenpositioningverticalpiping,tosimplifysupporting,attainacommonbackofpipedimensionfrom
columnshellof300mm.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 18/136
4/26/2017 PlantLayout|ABCEngineering
Figures18Incl.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 19/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 20/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 21/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 22/136
4/26/2017 PlantLayout|ABCEngineering
Categories:PlantLayoutTags:column,designguide,plantlayout
PlantLayoutCompressors
March15,2012qdzung1comment
TableofContents
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 23/136
4/26/2017 PlantLayout|ABCEngineering
1.Introduction
2.ReciprocatingCompressors
3.CentrifugalCompressors
4.Drives
1.Introduction
Compressorsarethemechanicalmeanstoincreasevaporpressure,aspumpsareusedtoincreaseliquid
pressure.
Therearetwobasictypesofcompressors,reciprocatingandcentrifugal.Eachhasonespecificdutyto
intakevaporatlowpressure,compressitanddischargeitatahigherpressure.Thequantityofvaporto
bemovedanddischargepressureitusuallythedecidingfactorinthetypeselected.
1.1Reciprocatingcompressors
Reciprocatingcompressionistheforceconvertedtopressurebythemovementofthepistoninacylinder.
Thesemachinearegenerallyspecifiedforlowervolumesthancentrifugalcompressors.Ifseveralstagesof
compressionareemployed,extremelyhighpressuresmaybedeveloped.Becauseoftheirreciprocating
actionthesemachinescausepiping,ifnotproperlydesignedandsupported,topulsate,vibrateand
generatefatigue.
1.2CentrifugalCompressors
Centrifugalcompressionistheforceconvertedtopressurewhenagasisejectedbyanimpellerat
increasingvelocity.Centrifugalcompressorsarespecifiedforlargequantitiesofvapor.Pressure
differentialmaybesmallorlarge.Thesemachinesarenotsubjecttopulsationandthereforedonot
producevibrationaleffects.
1.3CompressorDrives
Driversfallintothreecategories,i.e.electric,steamandgas.
Electricaldriversrangefromsmallflameproofmotorstolargemotors,2000HPormore,requiringtheir
owncoolingsystems.Steamdriversarecomprisedofsingleormultistageturbines,eitherfully
condensingofbackpressure.Gasdriverscovergasturbinesorgasengines.
2.ReciprocatingCompressors
2.1TypesofMachines
Reciprocatingcompressorscanbeobtainedinavarietyofpatternsfromasimplesinglecylinderto
multicylindermultistagemachines.Seefigure1,2,3forthemostwidelyusedpatterns.
Figure1belowisasinglecylindermachine.Itwilloperateatlowspeed,maybesingleordoubleacting.
Figure2isabalancedhorizontallyopposedmulticylindermachine.Itwilloperateatlowspeed,maybe
singleordoubleacting,itcanalsobemultistage.
Figure3isagasfuelledangletypeengine.Thecompressioncylindersareallononesideoftheframe,
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 24/136
4/26/2017 PlantLayout|ABCEngineering
cylinderdiametersandlengthsvaryaccordingtothecomposition,pressureandvolumeofgastobe
compressed.Dimensionsfromframecenterlinetocylindernozzleswillvarywithcompressionforces.
2.2TypesofCylinders
Figure3.Gasenginedrivenmachine(note:gasenginemaytakeVform)
Figures4,5fordetailsofcylinderarrangements.
Figure4:singleactingcylinder,havingonesuction,compressionanddischargeareapercylinder.
Figure5:doubleactingcylinder,havingtwosuction,compressionanddischargeareaspercylinder.
Multicompressionstages:numberoftimesthevaporiscompressedbygoingthroughaseriesof
compressioncylinderstoincreasepressure.
Gascompressionraisestemperature.Inareciprocatingmachine,compressionisviolentandheatriseis
great.Inlettemperaturesof40oCmayberaisedtoover100oCbytheactofcompression.Thecylinder
getshotanddependingonthevaporbeingcompressed,willneedsomeformofcooling.Thiswillusually
beintheformofcoolingwater,butforlowheatincreasesaglycolfilledjacketmaysuffice.
2.3CompressorFoundation,CylinderandSnubberSupports
ThefoundationforLPreciprocatingcompressorsmustbeindependentfromallotherfoundations.It
mustsupportthecompressorandallitsauxiliaryequipment.
Cylindersupportsaresuppliedbythevendoriftheyarerequired.
Theymustbeattachedtothefoundationconcrete.Likewisethesnubbersupportsmustbeattachedtothe
foundationconcrete,springswillbeusedlocallytosupportthesnubbers.
2.4CompressorLayout
Effectivecompressorlayoutresultsincostsavingsonprocessandutilitypiping,goodmaintenance
accessibilityandpossiblyreducedpulsationinsuctionanddischargepiping.Poorlayoutdoesthe
opossite.
SeebelowfigureTYPICALLAYOUTOFCOMPRESSORHOUSE&SUCTIONKNOCKOUTDRUM
Forangletypecompressors,locatethecrankshaftparalleltothesuctionanddischargeheaders.For
balancedhorizontallyopposedcompressors,thecrankshaftshouldrunatrightanglestothesuctionand
dischargeheaders.Compressorhousescontainingmorethanonemachine,particularlyiftheyarelong,
willprobablybeequippedwithatravellinggantrycranewhichwillbemanuallyorelectricallyoperated.
Thisfeaturecaninfluencetheoveralldimensionsofthehouse,asinadditiontothenecessarybuilding
andmaintenanceclearances,theverticalreactionsoftheloadedcranewillincreasefoundationsize.Since
thesemustnotbeconnectedtothemachinefoundations,thebuildingsizewillbeaffected.Itisusualfor
compressorvendorstoindicatetheoverallfoundationdimensionsontheirlayoutdrawings.(Theseshould
berequestedasearlyaspossible).
Thecompressorbuildingmustbesizedveryearlyinthelayoutstagewhenonlypreliminarydimensions
areavailable.Itmaybeknownthattheoveralllengthofthemachineis6metersandthewidthis4
meters.Tothesedimensionsmustbeaddedadequateclearanceformaintenancepluspossiblecontrol
valvestations,lubeoilequipment,localcontrolpanel,etc.Allow2metersallaroundtheoriginal
dimensions.Inpracticethis2meterallowancewillprovideawalkwayofonly12001500mmdueto
otheritemsoccupyingfloorspace.Withtwoormoremachines,allow2metersbetweencompression
cylinderstoallowforadequatepistonremoval.Alldimensionsmustbeconfirmedfromcertifiedvendor
drawings.
Allowamaintenanceareaatoneendofthebuilding.A6meterbayshouldbesufficient.Pits,trenches
andsimilargastrapsshouldbeavoidedingascompressorhouses.Largereciprocatinggascompressors
willusuallybeelevatedabovegradewithmezzaninefloorlevelwiththetopofthefoundationfor
operationandmaintenance.Theheightofthemezzaninefloorabovegradewillbekepttoaminimum
consistentwiththeadequacyofspaceforpipingandaccess,especiallytovalvesanddrains.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 25/136
4/26/2017 PlantLayout|ABCEngineering
2.5PipingLayout
Thepipinglayoutwillfollowtheplowdiagramsasissuedforthejob.Iftheyconflictwithanyofthe
followingnotes,theflowdiagramswillalwaystakeprecedence.Itisusualforthesuctionpipingtobe
routedtothetopofthecylinderanddischargepipingfromthebottom.Liquidsmustbepreventedfrom
enteringthecompressors.Asliquidsdonotcompress,extensiveprecautionsmustbetakentoensurethat
absolutelynoliquidentersthecompressorcylinderasmallquantitywoulddoextensivedamage.
Ifthereisanydoubtthatthevaporisnearitsdewpoint,thesuctionlinemustbesteamtracedbetween
thesuctiondrumandthecompressorinletorlocaltothecompressorinlet.ProcessDepartmentwill
advisetheextentanditwillbeshownontheflowdiagram.
Suctionanddischargeheaderswillbelocatedatgradelevelonsleepersuptothefirstpieceofconnecting
equipment,e.g.suctionKOdrumoraftercooler.Branchconnectionstothecompressorfromthesuction
headerwillbetakenfromthetopoftheheader.Suctionanddischargepipingwillbekeptasstraightas
possiblebetweenthecompressorsandheaders.Theuseofshortradiusbendsorteesandsimilar
installationsgivingopposedflowshallnotbepermitted.
Pipingshallnotbelessthancompressornozzlesize.Pipinglocaltocylindersshallclearthecylinderby
sufficientdistancetopermitpropermaintenanceonthecylindervalves.Whencompressorsareelevated
withamezzaninefloor,pipingandvalveswillnormallyrununderthefloor.
Whenmorethanonecompressorisemployedonthesameservice,allpipingtoandfromthecompressors
willbevalvedsothatanycompressormaybeshutdownandtakenoutofservice.Spectacleblindeswillbe
installedatthecompressorsideoftheisolatingvalves.
Startupbypassesaretobeinstalledbetweensuctionanddischargepipesofcompressorsandwillbe
locatedbetweenthecompressorandthelineblockvalve.Whennotfurnishedbythemanufacturer,a
reliefvalvewilltakebeinstalledbetweenthecompressordischargeandblockvalve.Thisreliefvalvewill
dischargeintothesuctionlinedownstreamoftheblockvalve.Thereliefvalvewillbeprovidedwitha
bypassforhandventing.
Distancepieceandpackingventpipingwillbemanifoldedintosystemsasindicatedontheflowdiagrams.
Thesesystemsareeitherventedtoatmosphereoutsidethecompressorhouseorconnectedtoacollection
system.
Utilitypipingwillcomprisecoolingwatersupplyandreturntolubeoilcooleralsotocylinderjackets.The
minimumlinesizeusedwillbe3/4.Sufficientventsanddrainswillbeprovidedsothatwaterlinesand
jacketsmaybecompletelydrainedatshutdown.Asteamorelectricalsupplymayberequirediflubeoil
heatersareprovidedforeitherthecompressororgearboxoil.Thissystemisusedpriortostartup.
Checkforlinesthathavetobechemicallyandensuredrawingsindicatethisrequirement.
3.CentrifugalCompressors
3.1TypesofMachine
Centrifugalcompressorscanbeobtainedinavarietyofpatterns.Seefigure8.CentrifugalRadial
Compressor
Centrifugalradialcompressors(figure8):thecompressionprocessiseffectedbyrotatingimpellersof
radialflowdesign(figure9RadialImpellor)infixedguideelements.
Centrifugalaxialcompressors(figure10):theforceisconvertedintopressurebyrotatingvanesbetween
fixedguidevanestheflowisaxial.
3.2SizeandPositionofNozzles
Centrifugalcompressormanufacturershavebasiccasedesignstheychangetherotorbladedesignto
meetvolumeandpressurerequirements.Forthisreasonsuctionnozzlesaresometimesmuchlargeror
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 26/136
4/26/2017 PlantLayout|ABCEngineering
smallerthanthelinesizeforhydrocarbonprocessapplications.Forexample,a30suctionnozzlemay
havea20or24suctionline.Itwillbenecessarytoincreasethesuctionlinediameterlocallyatthe
compressornozzle.Donotuseareducingflangeasthiswillintroducefullvelocitytotherotorbladesata
turbulentcondition.Use30flangeandaconcentricreducerasaminimum.Itisbetterifapipelengthof
3diasof30pipecanalsobeaccommodated.
Suctionanddischargenozzlesareeitherontheundersideorthetopofthecompressor.Onmultistage
compressorstwoormoreinletnozzlesmaybeprovidedthesuctionlinesareconnectedtosuctiondrums
controlledtomaintainthevariousinletpressures.
3.3CompressorFoundations
(Seefig.10Centrigfugalaxialcompressors)
Thefoundationofeachmachinewillbecombinedwithitsdirectcoupleddrivesbutmustbeindependent
fromallotherfoundations,includingthelubeconsole.
3.4CompressorLayout
(Seefig.11,12,13below)
Centrifugalcompressorsareusuallylargecapacitymachines.Theyaredrivenbyelectricmotors,steam
orgasturbine,thedrivemaybeviaagearbox.Itisusualtomountsuchmachinesonatabletopabout4
metershighwithelevatedaccessallaround.Thelubeandsealoilconsolesforboththecompressorand
turbine,ifused,willbelocatedatgrade.Thesuctionanddischargeconnectionsofthecompressorwill
mostlikelybeontheundersidetheselinescanbeanchoredatgrade.Shouldtheseconnectionsbeonthe
topofahorizontallysplitcasecompressor,seefig13fordetailsofremovablespools.
Atypicalcompressorhouselayoutisshowninfigures11and12.Hereanelectricalmotoranda
condensingtypeturbinehasbeenused.Notethewithdrawalandmaintenanceareas,alsotheacoustic
hoods.Determinethetypeoftravellinggantrycrane,andensurethatpiping,etc.isclearofit.Notethe
lubeoilheadertanks,thesemustbeelevatedabovethemachines,ifthevendorhasnotstatedaminimum
elevationuse10metersabovethecenterlineofthemachines.
Theirpurposeisforemergencylubrication,andaretrippedinshouldthenormallubricationsupply
systemfail.Theysupplyoiltothebearingsuntilthemachinecomestoastandstill.
Thelubeandsealoilconsolesarecomprisedofthefollowingitems:oilstoragetank,filters,pumps,oil
cooler,sometimesanoilheaterforstartup,controlinstruments.
Interconnectingpipingmustbeinaccordancewiththeflowdiagram,allreturnlinesmustbefree
drainingfromthemachinestotheconsole.
Suctionanddischargepipingmustbesupportedsothatthenozzlesarenotoverloaded,usereducersnot
reducingflangelocaltosuctionanddischargenozzles.Makeprovisionforremovalofstrainersintheinlet
line.Silencersmayberequiredinboththesuctionanddischargepiping.
Acoustichoodsmayberequiredforboththecompressorandturbineensurethatthetabletopislarge
enoughtoaccommodatethem.Theymaybeofsectionalconstruction.Thetravellinggantrycranewillbe
usedtodismantlethemthismustbetakenintoconsiderationwhendeterminingtheelevationofthecrane
hook.
Maintenanceareamustbelargeenoughtoaccommodatetheacoustichood,turbineandcompressorhalf
casingrotors,etc.
4.Drives
4.1ElectricalMotors
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 27/136
4/26/2017 PlantLayout|ABCEngineering
FlameproofmotorswillbeemployedforsmalltomediumHPmachines.
Ensurethatthecablescanberoutedtotheterminations,alsothatthereisspacebehindthemotorto
removetherotor.
LargeHPmachinestheirowncoolingsystemsthesefallintotwocategories:CACW(closeaircircuit
watercooledmachine)orCACA(closedaircircuitaircooledmachine).Thesetypesofmachines
mayrequireanareaof7mx7mand,therefore,determinethesizeofthecompressorhouse.
CACWmachines(seefig.14):maybemountedonatabletopwiththecoolerlocatedunder,inasealed
room.Thecoolingaircirculatingaroundthemotorisitselfcooledbywatercooledheatexchanger.
Provisionmustbemadeforremovalandserviceoftheexchanger.
Itispossibletoobtainmotorswiththecoolermountedaboveortoonesideofthemotor.
CACAmachineconsiderationmustbegivenregardingthesafelocationoftheairintake,whichwillbe
outsidethecompressorhouse.Ifafilterisrequiredintheintakesystem,provideaccessforreplacement
orcleaning.
4.2SteamTurbines
Twotypesofsteamturbinesmustbeconsidered,condensingandnoncondensing.Thenoncondensingtype
useshighpressuresteamandexhaustslowerpressuresteamtoastreamheader.Thecondensingturbine
exhauststoasurfacecondenser(whichisusuallyalargeexchangerwithhotwellattached,butmaytake
theformofanairfan)torecovercondensate.Surfacecondensersareoftengrademounteddirectlybelow
thecompressorsturbine.Thisarrangementemploysaturbinewithoutletnozzledirectlyconnectedviaan
expansionjointtothesurfacecondenser.(Seefig.16).Thesurfacecondensermaybemountedatgrade
alongsideagrademountedturbine.WitharrangementverylittleNPSHisavailable.
Ifanairfanisusedasasurfacecondenseritwillusuallybelocatedabovetheturbine,eitheronthe
compressorhouserooforoverapiperack.Ifthecondenseristheshellandtubetype,itwillmostlikely
beofthefixedtubeplatedesignandwillrequireaccessforroddingthetubes.Thecoolingwaterlines
associatedwiththecondenserarelargeboreandsomeconsiderationmustbegiventothepiping
arrangementandplacingofvalvestogivegoodoperationandutilizationofplotspace.
Thesteamsupplytotheturbinewillbetakenfromthetopofthesteamheader,abellowmayberequired
localtotheturbineandatemporarystrainerwillbeusedforstartup.
Theturbinewillrequiredasimilarlubeoilconsoletothatprovidedforthecompressor.Donotpocketthe
returndrains.Anelevatedlubeoilheadertankalsoberequired.
Noncondensingturbineassembliescompriseaturbine,lubeoilconsoleandheadertank.Thelowpressure
steamdischargelinewillbealargebore,abellowwillmostlikelyberequiredintheline,whichmustjoin
thetopoftheheader.Ifthelinehasalowpoint,asteamtrapanddrippocketmustbeprovided.
Maintenanceaccess:provisionmustbemadetodismantletheacoustichood,andremovehalfofthe
turbinecasingandtherotor.
4.3GasTurbines
Whenusingagasturbinetodriveacompressor,asimilararrangementtoasteamturbinecanbeused
thelubeoilconsoleandheadertankswillberequired.Inaddition,theexhaustsystemmustbe
consideredthiswillbecomprisedofductingtosomeheatrecoverysystem,eitherasteamraisingplantor
processheaters.
Combustionairtotheturbineburnermustbetakenfromasafelocationoutsidethecompressorhouse.
Inletsilencerandfilterwillmostlikelyberequired.Provisionforoperationandmaintenancetoall
machinerymustbeprovided.
4.4GasEngines
Gasenginesareusedtodrivereciprocatingcompressors,eitherdirectlyorthroughagearbox.The
machinemayhavebothcompressionanddrivecylinderattachedtoacommoncrankshaft.Thesetypesof
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 28/136
4/26/2017 PlantLayout|ABCEngineering
enginesmaydevelop2,000HPormore.Ensurethatadequatespaceisallowedforremovalofcylinder
headsandpistons.Thelubeoilsystemmaybeintegralwiththeenginethatorintheformofaconsole.
Shouldthelatterbeused,ensurethattheengineisatsuitableelevationtoallowforfreedrainingoil
returnlines.(seefig.17)
Theengineandcompressorwillbemountedonacommonfoundationthatisindependentofallother
foundations.Duetothevibrationproducedbythesemachines,alargemassconcretefoundationwillbe
employed.
Thegenerallayoutofthecompressorhousewillenabletheuseofatravellinggantrycraneforall
maintenance,thereforewhenroutingpipingthismustbeconsidered.Itisnotlikelythatamezzaninefloor
willbeemployedlocaltothemachines,enablingmostofthepipingtobekeptlow.
Combustionairmustbetakenfromasafelocationoutsidethecompressorhouse.Ifanairfilterwillbe
required,arrangeformaintenanceaccess.Likewise,theexhaustmustbedischargedoutsidethebuilding.
Thissystemwillbefittedwithasilencerandflametrap.Utilitysystemswillcompriseastartupair
system,alsofuelgas.Theenginewillmostlikelyhaveaclosedcircuitjacketwatercoolingsystem.
Thiswillcompriseashellandtubeexchangeroranairfan.Iftheformer,coolingwatersupplywillbe
requiredandtheusualclearancefortubepulling,etc.willbeprovided.(seefig.18).
Figuresincl.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 29/136
4/26/2017 PlantLayout|ABCEngineering
Figure6:DETAILOFFOUNDATION
&SUPPORTFORCYLINDER&SNUBBERS
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 30/136
4/26/2017 PlantLayout|ABCEngineering
Figure7:TYPICALLAYOUTOF
COMPRESSORHOUSE&SUCTIONKNOCKOUTDRUM
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 31/136
4/26/2017 PlantLayout|ABCEngineering
FIG.11TYPICALLAYOUTFOR
COMPRESSORSONETURBINEDRIVENONEELECTRICMOTORDRIVEN
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 32/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 33/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 34/136
4/26/2017 PlantLayout|ABCEngineering
Categories:PlantLayoutTags:Compressors,designguide,plantlayout
PlantLayoutExchangers
March15,2012qdzungLeaveacomment
TableofContents
1.UseofExchangers
2.TypesofExchangers
3.TypesofShellandTubeExchangers
4.LayoutofShellandTubeExchangersinBanks
5.AlterationsThatCanBeMadetoShellandTubeExchangers
6.EstablishingElevationsofExchangers
7.Piping
8.LayoutofExchangersOtherThaninBanks
9.TypesofAirFins
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 35/136
4/26/2017 PlantLayout|ABCEngineering
10.LayoutofAirFins
11.Piping
12.FinTubeExchangers
13.Chillers
1.UseofExchangers
Heatexchangerstransferheatfromonemediatoanother.Inthepetrochemicalindustry,theycanbe
generallyclassifiedunderthefollowingheadings:
Exchanger:Heatsonestreamandcoolstheother.Thereisnoheatlossandphysicalchangeineither
flowingmedia.
Cooler:Coolsliquidorgaseswithoutcondensationappliesalsotointercoolerandaftercooler.
Condenser:Condensesvapourorvapourmixture.Canbewatercooledorbysufficientlycoldprocess
streamwhichrequiresheating.
Chiller:Usesrefrigerantforcoolingprocessstreambelowfreezingpointorbellowprevailingcooling
watertemperature.
Heater(nonfired)Heatsprocessstreamgenerallyuptoitsboilingpointwithoutappreciable
vaporization.Heatingmediumisusuallysteamappliesalsotopreheaters.
Reboiler:Reboilsthebottomstreamoftowerforthefractionationprocess.Heatingmediumcanbesteam
orhotprocessstream.Whenlargequantitiesofvaporhavetobeproducedthekettletypereboilerisused.
Wasteheatboiler:Useswasteheat,suchasinternalcombustionexhaustfromgasturbinesorsimilar
driversforsteamgeneration.
Steamgenerator:Usesheatofprocessliquidorgasforproducingsteam.
Vapourizer:Vapourizespartofaprocessliquidstreamasdoesanevaporator.
2.TypesofExchangers
Briefly,exchangers,etc.,canbedividedintothefollowingthreegroups:
Shellandtube:Whichcanbeverticalorhorizontalwiththehorizontalonessingleorstackedinmulti
units.Asthenamesuggests,theyconsistofacylindricalshellwithanestoftubesinside.
Fintube:Thisconsistofafinnedtubethroughwhichpassesonemediajacketedbyanothertubethrough
whichpassestheothermedia.Theycanbeusedassingleormultiunits.
Airfins:Comeintwoshapesflatboxunitsandaframeunits.Bothconsistofbanksoffinnedtubes
throughwhichpassesthemediatobecooled.Largefansblowairfromatmospherethroughthebanks,
thuscoolingtheflowingmedia.Thereareothertypes,suchasplateexchangers,carbonblockexchanger,
etc.,buttheseareusedinfrequently.
3.TypesofShellandTubeExchangers
Floatingheadexchangersareusedwhenthemediabeinghandledcausesfairlyrapidfouling,andthe
temperaturecreatesexpansionproblems.Tubescanexpandfreelychannelheadandshellcover
arrangementisconvenientforinspection,andthetubebundlecaneasilyberemovedforcleaning.
Utubeexchangersareusedwhenfoulingofthetubesontheinsideisunlikely.Thetubesarefreeto
expandandthebundlecanberemovedfromtheshellforcleaningontheshellsideoftubes.
Fixedheadexchangershavenoprovisionforthetubeexpansionandunlessashellexpansionjointis
providedcanonlybeusedforrelativelylowtemperatureservice.
Theendcoversareremovablesothattheinsideofthetubescanbecleanedbyroddingorothersimilar
tools.Thistypeofcleaningisusuallycarriedoutinsitusosomespaceshouldbeallowedinthepiping
layouttoallowforthis.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 36/136
4/26/2017 PlantLayout|ABCEngineering
4.LayoutofShellandTubeExchangersinBanks
Forgoodmaintenanceandsafeworkingconditions,itisnecessarytospaceexchangerssuchthat
surroundingareaisadequateandclear.Theymaybespacedapartandgroupedinpairs.Whenapart,a
clearaccesswayof750mmisconsideredadequate,thisbeingtheclearspacebetweentheshellsand/or
theassociatedpipeworkandinsulation.Forpairedexchangersasimilarconditionisrequiredbetween
pairsandadjacentsingles,butbetweeneachshellofthepairthismaybereducedto450mmbetween
headflanges.Exchangersshouldalwaysbearrangedsuchthattheideallythereisaminimumof150mm
clearattherearforremovalofthebonnetandspaceprovidedfordroppingitclearoftheworkingarea.
Atthefrontorchannelend,aminimumdistanceofthetubelengthplus2500mmisconsideredgood.This
latterdoesnotofcourseapplytoexchangerslocatedinstructureswereatotalof1500mmwouldbe
sufficient.
Pipingconnectedtoheatexchangersisgenerallysimple.Pipingeconomyandgoodengineeringdesign
dependlargelyonknowingwhatalterationscanbemadetoexchangers.Inotherwords,thepiping
designercaninfluencetheexchangerdesign.Forexample,thedirectionofflow,nozzlelocations,etc.
Alterationstoexchangersofcourse,shouldnotaffecttheirdutyandcost.
Moneysavedonsimplerpipingshouldnotbespentoncostlyalterationstoexchangers.The
accompanyingchartshowsthepossiblealterationsthatmaybeinstigatedbythepipingdesignersto
typicalshellandtubeexchangerswithoutaffectingthethermaldesign.Whencontemplatingsucha
changeitshouldberememberedthatgenerallytheheatedmediashouldflowupward,andthecooled
mediaflowdownward.Thisisparticularlyimportantifthereisaphysicalchangetakingplacewithinthe
exchanger,suchasvaporizationorcondensation.Typicalexampleofthisare:
Reboilerswheretheprocessstreamenterstheshellatthebottomsasaliquidandleavesatthetopasa
vapourafterflowingthroughthetubes,andstreamenterstheshellnearthetopofthetubesandleavesat
thebottomontheshellascondensate.
Condenserswheretheprocessstreamenterstheshellatthetopasavapourandleavesthebottomasa
liquid,whilstcoolingwaterentersthetubessideatthebottomandleavesatthetop.
5.AlterationsThatCanBeMadetoShellandTube
Exchangers
Interchange,flowingmediabetweenthetubeandshellside.Thischangeisoftenpossible,moresowhen
theflowingmediaaresimilar,forexample,liquidhydrocarbons.Preferablythehottermediashouldflow
inthetubesidetoavoidheatlossesthroughtheshell,orthenecessityforthickerinsulation.
Changedirectiononflowoneithertubeorshellside.Onmostexchangersinpetrochemicalplants,these
changesarefrequentlypossiblewithoutaffectingtherequireddutyoftheexchangerifthetubesarein
doubleormultipassarrangementandtheshellhascrossflowarrangement.
Inexchangerswherecounterflowconditionscanbearranged,changingofflowdirectionshouldbemade
simultaneouslyintubeandshell.Somepointstoconsiderwhencontemplatingaflowchangeare:
Shellleakage:Whenwatercoolinggases,liquidhydrocarbonsorotherstreamsofdangerousnatureitis
bettertohavethewaterintheshellandtheprocessinthetubes,sinceanyleakageofgas,etc.,will
contaminatethewaterratherthanleakingtoatmosphere.
Highpressureconditions:Itisusuallymoreeconomicaltohavehighpressureinthetubesthaninthe
shellasthisallowsforminimumwallthicknessshell.
Corrosion:Corrosivefluidsshouldpassthroughthetubes,thusallowingtheuseofcarbonsteelforthe
shell.
Fouling:Itispreferabletopassthecleanstreamthroughtheshellandthedirtythroughthetubes.This
allowsforeasiercleaning.Mechanicalchanges,suchastangentialorelbowednozzlescansometimes
assistsinsimplifyingthepipingorloweringstackedexchangers.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 37/136
4/26/2017 PlantLayout|ABCEngineering
6.EstablishingElevationsofExchangers
Whereprocessrequirementsdictatetheelevation,itwillusuallybenotedonthePandIdiagram.
Fromtheeconomicpointofview,gradeisthebestlocation,whereitisalsomoreconvenientforthetube
bundlehandlingandgeneralmaintenance.Exchangersarelocatedinstructureswhengravityflowis
requiredtothecollectingdrum,orwheretheoutletisconnectedtoapumpsuctionwhichhasspecific
NPSHrequirements.Toelevateexchangerswithoutspecificrequirements,thefollowingprocedureis
recommended:
Selecttheexchangerwiththelargestbottomconnectionaddtothenozzlestandoutdimension(center
lineofexchangertofaceofflange)thedimensionthruhubofflange,elbow(11/2dia),onehalftheO/S
pipediameterand300mmforclearanceabovegrade.
Nowsubtractthecenterlinetoundersideofsupportdimensionfromabove,andthedimension
remainingisthefinishedheightofthefoundationincludinggrout.
Itispreferableifthisfoundationheightcanbemadecommonforalltheexchangersinthebank.Ifthisis
impracticableduetoextremesofshelland/orconnectionpipesizes,thenperhapstwoheightscanbe
decidedupon.
Whenstackingexchangers,twoorthreehigh,itisdesirablethatoverallheightdoesnotexceed120
(3650mm)duetotheproblemofmaintenance,bundlepulling,etc.
7.Piping
Planwisetheexchangerbankshouldbelaidoutspacedasnotedpreviously,andallthechannelnozzles
onacommoncenterline.
Thisisparticularlyimportantifthecoolingwaterheadersareunderground,astheCWinletscanrise
intothelowerchannelnozzles.
Theendoftheexchangeradjacenttotherackwillnormallybethefixedend,iftheCWheadersare
undergroundthefixedendwillbecomethechannelend.
AllchangesproposedmustbediscussedfullywithProcessEngineerandClientEngineerorVessel
Department.
Linesturningrightintheyardshouldberightfromtheexchangercenterlineandthoseturningleft
shouldapproachtheyardonthelefthandsideofexchangercenterline.Linesfrombottomconnections
shouldalsoturnupontherightortheleftsideofexchangersdependinguponwhichwaythelineturnsin
theyard.Lineswithvalvesshouldturntowardstheaccessaislewithvalvesandcontrolvalvesarranged
closetoexchanger.Utilitylinesconnectingtoaheaderintheyardcanbearrangedonanysideof
exchangercenterlinewithoutincreasingpipelength.
Accesstovalvehandwheelsandinstrumentswillinfluencepipingarrangementaroundheatexchangers.
Valvehandwheelsshouldbeaccessiblefromgradeandfromaconvenientaccessway.Theseaccessways
shouldbeutilizedforarrangingmanifolds,controlvalvesandinstruments.
Inthepipingarrangement,provisionfortuberemovalaccessshouldbeprovided.Thismeansaspool
pieceofflangedelbowinthepipelineconnectingtothechannelnozzle.
Therequirementsofgoodpipinglayoutgenerallyapplytothedesignofheatexchangerpiping.The
shortestlinesandleastnumberoffittingstemperaturepermittingwillobviouslyprovidethemost
economicalpipingarrangement.Thedesignershouldavoidloops,pocketsandcrossovers,andheshould
investigate,nozzletonozzle,thewholelengthofpipingroutedfromtheexchangertosomeother
equipment,aimingtoprovidenotmorethanonehighpointandonelowpoint,nomatterhowlongthe
line.
Veryoftenaflatturnintheyard,analternativepositionforcontrolvalvesormanifold,changednozzle
locationontheexchanger,etc.,canaccomplishthisrequirement.
Avoidexcessivepipingstrainsonexchangernozzlesfromactualweightofpipeandfittingsandfrom
forcesofthermalexpansion.
Forvalvesandblindesthebestlocationisdirectlyattheexchangernozzle.Inthecaseofanelbownozzle
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 38/136
4/26/2017 PlantLayout|ABCEngineering
onanexchangeritshouldbecheckedthatsufficientclearancesareprovidedbetweenvalvehandwheel
andoutsideofexchanger.Elevatedvalvesmayrequireachainoperation.Thechainshouldhangfreelyat
accessiblespotneartheexchanger.
Belowfigureshowssketcheshighlightingexchangerpipingdetails.Orificeflangesinexchangerpipingare
usuallyinhorizontalpiperuns.Theselinesshouldbejustaboveheadroom,andtheorificeitselfaccessible
withmobileladder.Orificesinaliquidlineandmercurytypemeasuringelementrequiremoreheight.At
gaslinestheUtubecanbeabovethelinewithorifice,consequentlytheheightisnotcritical.Lineswith
orificeflangesshouldhavethenecessarystraightrunsbeforeandaftertheorificeflangesrequiredin
specificationorstandards.
Locallymountedpressureandtemperatureindicatorsonexchangernozzles,ontheshellorprocess
lines,shouldbevisiblefromtheaccessaisles.Similarlygaugeglassesandlevelcontrollersonexchangers
shouldbevisibleandassociatedvalvesaccessiblefromthisaisles.Whenarranginginstrument
connectionsonexchangerssufficientclearancesshouldbeleftbetweenflangesandexchangersupport
betweeninstrumentsandadjacentpiping.Insulationofpipingandexchangersshouldalsobetakeninto
account.
8.LayoutofExchangersOtherThaninBanks
Processequipmentinmostplantsisarrangedinthesequenceofprocessflow.However,whateverlayout
systemisused,thegeneralevaluationregardingexchangerpositionsisverysimilar.
Inlayoutthefractionationtowersshouldbelocatedinpropersequencefirst,althoughoftenthe
arrangementofotherequipmentforexample,condensersdependdirectlyuponthetowerorientation,
andsometimesthedecisionwhethertouseastructureornotdependsuponthis.Thisrelativepositionof
exchangerscanbereadilyevaluatedfromflowdiagrams.Forexchangerpositionsinapetrochemical
plantthefollowinggeneralclassificationcanbemade.
Exchangerswhichmustbenexttootherequipment.Suchexchangersarethereboilerswhichshouldbe
locatedtotheirrespectivetowers,orcondenserswhichshouldbenexttotheirrefluxdrumsclosetothe
tower.
Exchangerswhichshouldbeclosetootherprocessequipment.Forexample,exchangersinclosedpump
circuitssuchassomerefluxcircuits.Overheadcondensersshouldalsobeclosetotheirtowertoensure
thatthelinepressuredropinminimal.Incaseoftowerbottomdrawoffexchangerpumpflow,
exchangersshouldbeclosetothetowerordrum,togiveshortsuctionlines.
Exchangerslocatedbetweendistantitemsofprocessequipment.Theseareforexample,exchangerswith
processlinesconnectedtobothshellandtubeside.Whereparallelrunistheideallocationforthistypeof
exchanger.Onthatsideoftheyard,wherethemajorityofrelatedequipmentisplaced.Otherlocations
willcostmoreinpiperuns.
Exchangerslocatedbetweenprocessequipmentandtheunitlimit.Suchexchangersareforexample
productcoolers.Thesearefrequentlylocatedneartheunitlimit.
Stackedexchangers.Afurtherstepinthelayoutistoestablishwhichexchangerscanbestackedfor
simplifyingpipingandsavingplotspace.Mostunitsinthesameservicearegroupedautomatically.Two
exchangersinseriesorparallelareusuallystacked.Sometimes,smalldiameterexchangersinseriescan
bestackedthreehigh.Twoexchangersindissimilarservicescanalsobestacked.Sufficientclearance
mustbeprovidedforshellandchannelsidepipingbetweenthetwoexchangers.Reboilersandsingle
condensersusuallystandbythemselvesbesidetheirrespectivetowers.Verticalthermosyphonreboilers
areusuallyhungfromthesideoftheirassociatedtower.
9.TypesofAirFins
Therearetwotypesofairfinconstruction:theboxtypeandtheAframetype.
Theboxtypecanbedividedintotwoforms:forceddraughtandinduceddraught.
Forceddraftairfinsarethemostcommonlyusedtype,possiblybecausemaintenanceofthefaniseasy
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 39/136
4/26/2017 PlantLayout|ABCEngineering
fromanunderslungplatform.
Aframetypeairfinslesscommonthantheboxtype.
Theyoffertheadvantageofrequiringlessplotareathanboxtypeairfinsofthesamecapacity.Theydo,
however,presentafewproblems.Duetophysicalshapeofthem,i.e.triangularsectionwiththeapex
uppermost,theinletheaderislocatedattheapex,withthecollectingheadersatbothbottomcorners.
Thismeansthatcooledproductlinesarecomingoffbothsidesoftherackwhichcanpresentpiping
problems.Also,with60osidescontainingtheproduct,itispossibletogetunevencoolingduetothesun
beingononeside,ortheprevailingwindtendingtoblowintothetubebankagainstthefan.
10.LayoutofAirFins
Airfinsarelargecomparedwithshellandtubeexchangers,anditisnotuncommonforthemtooccupy
severalthousandsquarefeetofplotareaonaunit.
Ifthisplotareaisrequiredatgrade,therecouldwellbesitingproblems,butfortunatelymostprocess
usingairfinsrequireagravityfeedthroughthem,whichmeanstheymustbeelevated.
Themostcommonsatisfactorylocationisontopofthemainpiperack.Piperackwidthisinvariably
determinedbytubelengthofairfinunits.Intheabsenceofsufficientroomontherack,theymaybe
locatedontopofanysuitablestructure,oranelevatedstructuremaybebuiltforthepurpose.
Whenlocatingairfinsontheplotanumberofpointshavetobeborneinmind.
Airfinofagivencapacitycouldbemadeupofseveralunitseachweighingseveraltons.
Itisimportantthateachunitbereachedbythesitecraneforerectionandmaintenancepurposes.
Therefore,theoverallplotlayoutmustprovideforthiscraneaccess.
Asmostairfinswillbecondensingoverheadsfromtowers,itisimportanttoconsidertheexplanation
problemsoftheoverheadlinewhensitingtherelevantairfin,asairfinsareunsuitableforacceptinghigh
loadsonthenozzles.
Accessplatformsarealwaysprovidedeithersideoftheairfinforaccesstotheheaderboxes,and
underneaththeunitsforaccesstofansandmotors.Provisionmustbemadeforgradetoallthese
platformsatleastateitherend.
Itisagoodideatoinvestigateconnectingtheseaccesswaystoadjacentstructurestoprovideintermediate
escapeandforoperationalconvenience.
11.Piping
Therearefourmajorproblemswhenpipingupairfins:
1.Correctconfigurationsofpipingtogiveequalorasnearequaldistributionaspossibleoftheproduct
througheachunitofmultiunitairfins.
2.Makepipingfromtoweroverheadasshortaspossibletominimizepressuredrop.
3.Obtainingapipingsystemthatissufficientlyflexibletoavoidoverloadingtheunitnozzles.
4.Providingsufficientlysuitablepipesupportsandanchors.
Belowfigureshowsdiagrammaticallythreemethodsofpipingfordistribution:
1.Showinggooddistribution
2.Showinggooddistribution
3.Showingbaddistribution
Whendesigningthepipingforairfinexchangers,thebasicrulesofpipingstillapply,thatthepipingruns
shouldbeasshortanddirectaspossible,butatthesametimebesufficientlyflexibletoavoidoverloading
theairfinnozzles.Thebelowfigureshowstwomethodsofrunningproductheaderstoairfins:
Byrunningtheinletheaderdownthecenteroftheunits,theofftakestotheunitdropoutofthebottom
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 40/136
4/26/2017 PlantLayout|ABCEngineering
oftheheader,runacrosstheunitsanddropintothenozzles.
Thus,wehaveaseriesofofftakessufficientlylongtoabsorbexpansion,atthesametimehavingthe
minimumofelbowsresultinginminimumpressuredrop.
Supportscanusuallybeattachedtothesteelmembersthatrunbetweenunitsandarethusshortand
minimal.Theheadermustbeflangedatintervalsalongitslengthtofacilitatetheremovalofunitsby
craneformaintenance.
Thepreferredpositionfortheheaderisdirectlyabovetheinletnozzles,keepingthebranchesasshortas
possible.Makesurethattheairfiniscapableofexceptingthemovementimposedontheheader.Support
fromtheracksteelisbetweentheheaderboxes.
Outletheadersarelessofaproblembecausethetemperatureislowerandthepipesizeusuallymuch
smaller.
Theycanusuallybesupportedofftheairfinlegsbeneaththeheaderboxplatform.
Anyvalvesrequiredtoisolateunitsarethebestlocatedontheunitnozzles.Sometimesairfinshandling
lighthydrocarbonsmayrequiresnuffingsteamsupply.
Theseshouldbetreatedinthesamewayassnuffingsteamtoheaters,insomuchasthevalvesshouldbe
locatedatleast15metersradiusplanwisefromtheperimeteroftheairfin.
Pipingrunsthatplaceloadsofanysortontheairfinstructuresshouldbeavoidedifpossible,or
communicatedtothevendorassoonaspossible.
12.FinTubeExchangers
Fintubeexchangersconsistofahairpinshapedinnertubewithheattransferfinsontheoutside,except
forthereturnbend.
Thetwolegsarejacketedwithlargerborepipe.
Theheatexchangeisachievedbythestreampassingthroughthehairpin,andtheotherpassingthrough
thejackets.Theymaybeusedsinglyorinmultiples.
Theprimaryusesareforheathersorcoolersthatis,theprocessstreampassesthroughtheinnertube
andeithersteamorcoolingwaterpassesthroughthejackets.Theyareusedmainlyasasourceoflocal
heatexchange,suchasoutletheatersfromthetanksanddrumstopumps,etc.
Ourimportantpointtorememberwhenlocatingfintubesisthatthehairpintubedrawsoutfromthe
backend,thatis,theoppositeendfromthenozzles,andsufficientroommustbeallowedforthispurpose.
Pipingdesignconsiderationsaresimilartothoseonshellandtubeexchangers.
13.Chillers
Chillersareusedwheretheprocessstreamrequirescoolingtolowertemperaturethanpossiblewith
coolingwater,andforthispurposeitisnecessarytousearefrigerant.
Dependinguponthesizeofthechillersinstallation,therefrigerantcaneitherbesuppliedbyaproprietary
packageunit,oracustombuiltjobusingLPG.Theconstructionissimilartofintube,insomuchasthe
tubewithinatubefeatureiscommon.
Chillersusuallyconsistofamultiunitbankwiththeprocessstreampassingthroughtheinnertubeand
therefrigerantpassingthroughthejackets.Onceagainspacemustbeallowedattherearfortube
withdrawal.Animportantthingtorememberwhenlayingouttheseexchangers,istheconsiderable
thicknessofinsulationrequiredonallthepipework,necessitatinglargerthannormalpipespacing.
Figures
TYPICALEXCHANGERSSHOWSPOSSIBLEALTERATIONSFORBETTERPIPING
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 41/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 42/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 43/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 44/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 45/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 46/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 47/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 48/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 49/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 50/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 51/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 52/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 53/136
4/26/2017 PlantLayout|ABCEngineering
AIRFINMANIFOLDLAYOUT
HEADERMOUNTINGSFORAIRFIN
Categories:PlantLayoutTags:designguide,Exchangers,plantlayout
PlantLayoutFiredHeaters
March15,2012qdzung1comment
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 54/136
4/26/2017 PlantLayout|ABCEngineering
TableofContents
1.General
2.Location
3.Safety
4.InletandOutletPiping
5.BurnerPiping
6.DecokingandSootblowing
7.Instruments
1.General
1.1.Function
Theprimaryfunctionofafiredheateristosupplyallheatrequiredbytheprocessinoneformor
another.Afiredheaterutilizesgaseousorliquidfuelsoftenproducedasabyproduct.Thenormal
processfunctionisraisingtheprocessstreamtoitsrequiredtemperaturefordistillation,catalytic
reaction,etc.Sizesofheatervaryconsiderably,dependentuponthetypeofdutyandthroughput.
1.2Types
Therearetwogeneralbasicdesignsortypesoffiredheaters:
Boxtype
Verticaltype.
Eitherofwhichmaybeforcedornaturaldraft.
BoxTypeHeaters(Seebelowfigures2and3.)
Aboxtypeheaterisconsideredtobeanyheaterinwhichthetubesarehorizontal.Inthistypeofheaterit
ispossibletohavelocationsorzonesofdifferentheatdensities.Thezoneofhighestheatdensityisthe
&ldquoradiantsection&rdquo.Thetubesinthissectionarecalled&ldquoradianttubes&rdquo.
Theheatpickupintheradianttubesismainlybydirectradiationfromtheheatingflame.Insomeheater
designsshieldtubesareusedbetweenradiantandconvectionsection.Thezoneoflowerheatdensityis
the&ldquoconvectionsection&rdquo.Thetubesinthissectionarecalled&ldquoconvection
tubes&rdquo.Thisheatpickupintheconvectionsectionisobtainedfromthecombustiongases
primarilybyconvection.
Boxtypeheatersmaybeupfiredordownfiredwithgasoroilfiredburnerslocatedintheendor
sidewalls,floor,rooforanycombinationthereof.
UpfiredHeaters
Inthehorizontalupfiredheater,productsofcombinationintheradiationchamberpassupwardthrough
banksofrooftubesandafirebrickdiffuserintoaplenumorcollectingchamber.Fromtheplenum
chamberfluegasesarepassedthroughanoverheadconvectionsectionandthentoanoverheadstack.
Suchheatersmaybefiredverticallyupwardbypanels,mountedintheheaterfloororhearth,theheater
floorbeingelevatedtoprovideheadroombeneath.Alternatively,theseheatersmayalsobefired
horizontallybyburnersmountedintheheaterendwalls,inwhichcasetheheaterfloorisonlyelevated
abovegradetoprovideaircoolingconvectiontotheheaterfoundations.Thistypeofheatermaycontain
singleormultipleradiationchambersdischargingfluegasestoacommonconvectionsectionandstack.
DownfiredHeaters
Inthedownfiredheater,combustiongasesgeneratedintheradiantchamberpassdownwardsthrougha
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 55/136
4/26/2017 PlantLayout|ABCEngineering
refractorycheckerhearthintoacollectingchamberbeneath.Fromtherethefluegasesflowupward
throughtheconvectionsectionandthenouttothestack.Thedownfiredheatersarebasicallyintendedto
fireonheavyresidualfuels,wherethefluegasesarecorrosiveandmayclogfluegaspassagesof
conventionalheaters.
Convectionsectionsarethusprotectedbyremovalofcombustionsolidsandareusuallyprovidedwith
inspectionports,sootblowingdevicesandtubefacilitiestokeepthecoilsclean.Burnersindownfired
heatersarealwaysmountedintheheaterendwalls.
VerticalHeaters(Seebelowfigures4,5and6)Verticalheatersareeithercylindricalorrectangular.They
mayhaveradiantsectiononlyorconvectionandradiantsections.Theradiantsectiontubeswillusually
bevertical,butsomecylindricalheatershavehelicalcoils.Theconvectionsectioncanbeeitherverticalof
horizontal.
TypesofHeaterFiring
Heaterscanbefiredfromanyposition,i.e.bottom,top,sideorend.
Byfarthemostcommonisbottomfired,mainlybecauseitismoreeconomical.Theburnerofabottom
firedheaterwillbelocated2.12.7Mabovegradeataheightwhichissuitableforanoperatortowork
underneath.Operatingfromundertheheaterismoredangerousthanothertypesoffiring,whichisthe
principlereasoncertainoperatingcompanieswillnotinstallabottomfiredheater.
Heatersarecommonlylightwithanelectricignitor.somerefineriesuseapropanetorchwhilesomestill
lighttheburnerswitharagsoakedinspiritsorkerosene.
ForcedorNaturalDraft
Considerationmustbegivenatthelayoutstagetoaccommodatetheadditionalequipmentassociatedwith
aforceddraftheater.Thiswillusuallycompriseanairinletductwithsilencer,forceddraftfanandanair
preheater.Theinletductmayrequireasupportstructure.
2.Location
Heatersarealwayslocatedatasafedistance15metersawayfromotherhydrocarbonbearingequipment
andpreferablyupwindhowever,onsomeprocessitispermittedforreactorstobewithinthisdistanceto
preventlightvolatilevaporsfrombeginblowntowardsanopenflame.
Spacemustbeallowedfortubereplacementforbothhorizontalandverticalheatersandthis,together
withampleaccessformobileequipment,shouldbeconsideredonpipinglayoutsanddrawings.Ample
accessisalwaysneededforfirefightingequipmentwithareasunderoraroundheatersusuallypavedand
curbed.
Nolowpointsinthepavingorgradingarepermittedastheseprovideexcellentsportsfortrapping
hydrocarbonliquidswhichcouldbeignitedbytheopenflamesoftheburners.
3.Safety
3.1SnuffingSteamStation
Seebelowfigure7.
Snuffingsteamconnectionsaresuppliedbytheheatermanufacturers,generallyinthecombustion
chamberandheaderboxes.
Thecontrolpointorsnuffingsteammanifoldisgenerallylocatedatleast15metersawayfromtheheater,
issuppliedbyalivesteamheaderandisreadyforinstantaneoususe.Smotheringlinesshouldbefree
fromlowpocketsandshouldbesoarrangedastohavealldrainsgroupednearthemanifold.
Collectedcondensate(apartfromfreezingandblockinglines)can,whenblownintoahotfurnace,result
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 56/136
4/26/2017 PlantLayout|ABCEngineering
inseriousdamage.(Lowpointsshouldbedrilled10mmdiameterorprovidedwithspringopeningauto
drainvalves).
3.2MonitorNozzles
Somecustomersrequestthatturretormonitornozzlesbelocatedaroundtheheatersothatwaterfor
fightingafireisinstantlyavailable.Controlsforsuchnozzlesshouldbelocatedatleast15metersaway
fromtheheater.
3.3UtilityStations
Steam,airandservicewaterconnectionsshouldbeprovidedneartubeendsofheaters.3.4.Process
ControlStationsProcessfeedanddischargingblockvalvesandflowcontrolvalvesshallbelocatedata
distancefromtheheater,ifindicatedasnecessarybytheengineeringflowdiagramorinstructedbythe
PipingSpecialistEngineerorProjectDepartment.
3.5ExplosionDoors
Pipingshallnotobstructexplosiondoorsortubeaccessdoors.
4.InletandOutletPiping
Seebelowfigures8and9.
Flowdistributionthroughamultipassheaterisaffectedbytheinletandoutletmanifolding.Thepiping
arrangementattheinletofthefurnaceisthemorecriticalandrequirescarefulattention.
4.1InletPiping
Inletpipingshouldpreferablybesymmetricalandofthesamelengthfromthepointwhereflowsplitsto
theheaterinlets.Thisreferstothenumberofbends,elbowsandvalves,aswellasthenumberofstraight
runsofpipeandtheirlocation.pipingshouldavoiddeadendteebranchesandsharpturns.Unequalflow
throughanypartoftheheaterwouldresultindepositsofcokeandoverheatingoftubewalls.
4.2OutletPiping
Onoutletpiping,symmetryisnotascriticalasontheinlethowever,nonsymmetricalpipingmay
contributetopossiblecokingandoverheatingoftubes.Anonreturnandashutoffvalveisusualatthe
outletofthefurnacetoeliminateanyreverseinthecaseoftubefailure.
4.3Flexibility
Becauseofthehightemperatureinvolvedandlengthofpiperunsrequiredtoisolatetheheaters,piping
flexibilitymustbeexaminedcarefully.Someheatermanufacturerswillpermitalimitedamountoftube
movementtotakeallorpartofthepipingexpansion.Thispossibilityshouldbeinvestigatedin
conjunctionwiththeStressDepartment,bythePipingDesignOfficeduringthestudystage.Itis
generallynecessarytoanchorthepipingadjacenttotheheatertoremovestressesfromthenozzles.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 57/136
4/26/2017 PlantLayout|ABCEngineering
5.BurnerPiping
Seebelowfigures8and9.
Supplyoffueltoindividualburnersisadjustedbyindividualvalves.Theseshouldbesolocatedthatthe
burnerscanbeoperatedwhileobservingtheflamethroughpeepholesorburneropenings.
Allburnerleadsforgasandsteam(atomizing)mustbetakenfromthetopoftheheaders,andfuelgas
pipingshouldbesoarrangedthattherearenopocketsinwhichcondensatecouldcollect.Thefueloil
headermusthavefullcirculationundernoconditionshallitbeadeadendline.Noncirculatingbranches
toburnersshouldbeasshortaspossibleorinsulatedtogetherwithatomizingsteam.
Aringheaderaroundthefurnacemountedashortdistanceabovethepeepholes,havingverticalleads
adjacenttotheverticaldoorstotheburners,providesthegreatestdegreeofvisibilityfromtheoperators
pointofview.
Atomizingsteamtobeusedinconjunctionwithfueloilshallbetakenthemainsteamsupplyheaderator
neartheheater.Steamtrapsshallbeprovidedtodrainalllowpointsintheatomizingsteamsystem.
Separateleadstoeachburnershallbetakenfromthetopoftheatomizingsteamsubheader.Shutoff
valvesshallbesolocatedthattheycanbeoperatedwhileobservingtheflamesfromtheobservations
ports.
6.DecokingandSootblowing
6.1Decoking
(Seebelowfigure12)
Theinternalcleaningoftubesandfittingsmaybeaccomplishedbyseveralmethods.Oneistocirculate
gasoilthroughthecoilaftertheheaterhasbeenshutdownbutbeforethecoilsaresteamedand
waterwashedandpriortotheopeningandstartofinspectionwork.
Thismethodiseffectiveifdepositsinthecoilaresuchthattheywillbesoftenedordissolvedbygasoil.
Whentubesarecokedorcontainharddeposit,othermethodsmaybeused,suchassteamairdecoking
andmechanicalcleaningforcokedepositsandchemicalcleaningforsaltdeposits.Chemicalcleaningand
steamairdecokingarepreferableastheytendtocleanthetubetobaremetal.Thechemicalcleaning
processrequirescirculationofaninhibitedacidthroughthecoiluntilalldepositshavebeensoftenedand
removed.Thisisusuallyfollowedbywaterwashingtoflushalldepositsfromthecoil.Steamairdecoking
processconsistsoftheusesteam,thecoil.Steamairdecokingprocessconsistsoftheuseofsteam,airand
heattoremovethecoke.Themechanicsofdecokingare:
a.Shrinkingandcrackingthecokeloosebyheatingtubesfromoutsidewhilesteamblowscokefromthe
coil.
b.Chemicalreactionofhotcokewithsteam.
c.Chemicalreactionofcokeandoxygeninair.
Steamandairservicesarepermanentlyconnectedtotheheater.Theheateroutletlineincorporatesa
swingelbowwhich,duringthedecokingoperation,isdisconnectedfromtheoutletlineandconnectedto
thedecokingheader.Caremustbetakentoallowsufficientaccessandplatformingwhentheswing
elbowsarechangedover.Cokeiscarriedbythisheadertothedrumorsump.
InsomeinstancesitmayrequestedbytheProcessDepartmentorClientthatthedecokingmanifoldis
connectedtoallowforreverseflowduringthedecoking.
6.2SootBlowing
Insomeheaterstheconvectionsectioncontainstubeswithextendedsurfaceintheformofeitherfinsor
studs.Extendedsurfacetubesareusedtoincreasetheconvectionheattransferareaatlowcapitalcost.
Becauseofthetendencyofextendedsurfacetubestofoulwhenburningheavyoils,sootblowersare
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 58/136
4/26/2017 PlantLayout|ABCEngineering
usuallyinstalled.
Sootblowersemployhighpressuresteamtocleanthetubeoutersurfacesofsootandotherforeign
material.Sootblowersmaybeeitherautomaticelectricmotoroperatedbyapushbuttonatgrade,or
manualrequiringoperationfromaplatformlocatedattheconvectionbanklevel.Caremustbetaken
thatsufficientclearanceisallowedforthewithdrawalofsootblowers.
Generallyheatersaresuppliedwithsootblowingfacilitiesintheconvectionsectionalthoughtubesmay
notbeoftheextendedsurfacetype.
7.Instruments
7.1Stack
a.Damper:Mechanicalorpneumaticallyoperatedtocontrolthedraftthroughthestack.
b.Draftgauge(PandI)
c.Fluetemperature(TI)
d.Orsat(O2COCO2analyzer).
Instrumentsb.,c.andd.areusedtoaccessthecorrectcombustionconditions.Steamissuppliedforthe
Orsatconnectioninthestack.WaterissuppliedtotheO2analyzer.Platformingfortheaccesstothestack
instrumentsissuppliedwiththeheater.
7.2HeaterBody
a.SkinthermocouplesortubewallTIs:toindicateoverheatingoftubes.
b.PIs:tomeasurethedraftpressurethroughthecombustionsectionoftheheater.
Figures111incl.Figure1.BOXTYPEHEATERPLAN
PROCESSPIPINGBOXHEATHER
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 59/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 60/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 61/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 62/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 63/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 64/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 65/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 66/136
4/26/2017 PlantLayout|ABCEngineering
AFTERTUBESBECIMEHEADED,STEAMISINJECTEDATCONVECTIONINLETS,VALVES
1,2,4&5ARECLOSED3ISOPEN.
TOSTARTBURNING,STEAMFLOWISREDUCED.AIRISINTRODUCEDBYOPENINGVALVE
4.FORREVERSEFLOW,VALVES2,3,4&6ARECLOSED,1&5AREOPEN.
VALVE2ISOPENEDONLYIFREVERSEBURNINGISREQUIRED.WHILEPASS1ISBEING
DECOKED,STEAMISINJECTEDINTOPASS2TOKEEPTUBESCOOL.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 67/136
4/26/2017 PlantLayout|ABCEngineering
Categories:PlantLayoutTags:designguide,FiredHeaters,plantlayout
PlantLayoutPumps
March15,2012qdzungLeaveacomment
TableofContents
1.General
2.CentrifugalPumps
3.ReciprocatingPumps
4.RotaryPumps
5.PumpDrivers
6.PumpHarnessPiping
1.General
1.1Definition
Inthiscontextapumpisdefinedasamachineusedtogenerateapressuredifferentialinordertopropel
liquidthroughapipingsystemfromonelocationtoanother.
1.2TypesofPump
Thethreebasictypesofpumparecentrifugal,reciprocating,androtary.Seebelowfigures.
Centrifugalpumpsarethemostcommon.Theyaremoreeconomicinserviceandrequireless
maintenancethanothertypes.Rotationoftheimpellerbladesproducesareductioninpressureatthe
centeroftheimpeller.Thiscausesliquidtoflowontotheimpellerfromthesuctionnozzlethrown
outwardsalongthebladesbycentrifugalforceleavingthebladetipsviathepumpvolutefinallyleaving
thedischargenozzle,inasmooth,nonpulsatingflow.
Reciprocatingpumpsareusedwhereapreciseamountofliquidisrequiredtobedelivered,alsowherethe
deliverypressurerequiredishigherthancanbeachievedwithothertypes.Theliquidismovedbymeans
ofapistoninacylinderafterbeingdrawnintothecylinder,throughaninletvalve,asthepistonmoves
downthecylinder.Asthepistonmovesbackupthecylindertheliquidisdischargedatapresetpressure
controlledbydeliveryvalve.
Theliquidisejectedfromthecylinderintothepipingsysteminpulseswhicharetransmittedtothe
suctionanddischargepiping,thusholddownscouldberequiredonthepipingsystem.Rotarypumpsare
usedtomoveheavyorveryviscousfluids.Theseemploymechanicalmeanssuchasgear,camandscrew,
tomovethefluid.
2.CentrifugalPumps
2.1NettPositiveSuctionHead
Centrifugalpumpsmusthavetheirsuctionlinesfloodedatalltimes.
Thesuctionpipinghastobedesignedtoavoidcavitationorpreventvopourenteringthepump.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 68/136
4/26/2017 PlantLayout|ABCEngineering
Therefore,suctionlinesshouldfallcontinuouslyforasufficientheightfromoverheadsourcetopump.
TheminimumverticalheightrequiredfromsourcetopumpsuctioniscalledtheNettPositiveSuction
Head,(NPSH).Thisiscriticalforefficientpumpoperationandmustnotbereduced.Vesselelevationsare
oftendependentontheNPSHofitsassociatedpump.Seebelowfigures.
2.2PumpTypes
Therearethreebasictypesofcentrifugalpumps.Horizontaldriveshaftwithpumpdrivemounted
remotefromtheline,verticaldriveshaftwithpumpanddrivemountedontheline,verticalbarreltype
withdirectimmersionsuctionfacility.Ineachcasethetypereferstodriveshaftdirection.
Themostcommonisthehorizontalwithitsshaftinthehorizontal,verticalinlinepumpshavetheirshafts
verticalandthepumpisinstalledinthepipeline,asavalvemustbe.Verticalcanpumpsareusually
singlestage,buthorizontalandverticalcantypescanbemultistagedtoobtainhigherdeliverypressures.
2.3SuctionPipingforHorizontalPumps
LineSize
Suctionpipingisusuallyoneortwolinesizeslargerthanthepumpsuctionnozzlesize.Suctionpiping
morethantwosizeslargershouldbequeriedwithProcessDepartment.
SuctionNozzleOrientation
Centrifugalpumpsaresuppliedwithsuctionnozzlesontheendofpumpcasing,axiallyinlinewith
impellershaft,alsoontoporsideofpumpcasing.Usuallypumpsarespecifiedwithendortopsuctionfor
generalservices.Sidesuctionpumps,withsidedischargearefrequentlyselectedforlargewaterduty.
Alsosidesuctionsidedischargepumpscanbeobtainedinmultistageformforhigherpressure
differentials.Thesepumpstendtobecomeverylong,soifplotspaceistight,considerationshouldbe
giventopurchasingthepumpinverticalformwithasumpatgrade.Seebelowfigures.
FlexibilityofSuctionLines
Consistentwithgoodpipingpractice,pumpsuctionlinesshouldbeasshortaspossible,butwithenough
flexibilitytoabsorbanypipemovementcausedbytemperaturedifferentialsandtomaintainpumpnozzle
loadstowithinthosepermittedbypumpvendor.Forfurtherdetailsrefertosectiononpipingflexibility.
SuctionLineFittings
Duetosuctionlinebeinglargerthanthesuctionnozzles,reducersarerequiredintheline.Reducers
shouldbeascloseaspossibletonozzle.Eccentricreducerswillbeusedwiththeflatontopforhorizontal
pumps.Seebelowfigures.Forpumpswithsuctionanddischargenozzlesontopofcasing,caremustbe
takentoensurethattheflatsoneccentricreducersareorientatedsothatsuctionanddischargelinesdo
notfouleachother.Seebelowfigures.
TemporaryStartupStrainers
Allpumpsmusthaveatemporarystartupstrainerinthesuctionlinetopreventanypipedebris
damagingthepump.Strainerswillbelocatedbetweenpumpsuctionblockvalveandpump.Strainersare
availableinthefollowingstyles:flat,basket,conicalandbathorteetype.
Forbasketandconicaltypesaremovablespoolpiecemustbeprovideddownstreamofsuctionblock
valve,whichmustnotinterferewithlinesupports.Bothtypeshavetheadvantagethatthepipingisleft
undisturbedandstrainerelementcanberemovedsimplybyremovingtheblindflangeonthetee,thus
leavingthepipingandsupportsundisturbed.Seebelowfigures.
2.4DischargePipingforHorizontalPumps
LineSize
Generally,dischargepipingisoneortwosizeslargerthanthepumpdischargenozzlesize.
DischargeLineFittings
Duetodischargelinebeinglargerthanthedischargenozzleeccentricreducersarerequiredintheline.
Reducersshouldbeascloseaspossibletothenozzle,withtopsuctiontopdischargepumps,caremust
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 69/136
4/26/2017 PlantLayout|ABCEngineering
betakentoensurethattheflatsoneccentricreducersareorientatedsothatthelinesdonotfouleach
other.
Apressuregaugeislocatedinthedischargeline,andshouldbeupstreamofthecheckandgatevalves
whichareusuallyflangedtogetherwithadripringbetweenthem.Whenalevelswitchforpump
protectionisinstalledinthedischargeline,upstreamofblockvalves,ensuregoodaccessformaintenance
ofswitch.
Toenablegoodaccesstovalvehandwheelsandeaseofsupporting,thedischargelineshouldbeturnedflat
afterreducer,andthelineangledawayfromthenozzletoenablethelinetobesupportedfromgrade.See
belowfigures.
Avoidsupportinglargelinesfrompiperackstructuresifpossible,thisenablesminimumsizebeam
sectionstobeusedandbetteraccessforpumpremovalandmaintenance.
2.5SideSuctionandDischargeHorizontalPump
Thistypeofpumpisusuallyinstalledinalargedutyservicewithlargeborelines.Neverconnectanelbow
flangefittingmakeuptothenozzleofsuctionlinecomingdowntothepump.Supplyastraightpieceof
pipetwopipediameterslongbetweenthenozzleandelbow.
Thetwodiameterpipelengthcanbeeliminatediftheelbowisinthehorizontal,onlyeliminatepipe
lengthifavailablespaceistight.Seebelowfigures
2.6VerticalPumps
Verticalpumps,alsocalledcantypeorbarreltypeareusedwhenavailableNPSHisverylowor
nonexistent.
VerticalInLinePumps
Thistypeofpumpismounteddirectlyintothepipeline,asavalvewouldbe.Forsmallersizes,thepiping
systemsupportsthepumpandmotor,thusitisessentialthatthelineissupportedlocaltothepumpto
preventthelinemovingwhenthepumpisremoved.Alsoensurethatthereisgoodaccesstopumpfor
maintenanceandwithdrawalwithnooverheadobstructionsforliftingoutpump.Largersizeinline
pumpshavefeetorlugsonthecasingforsupportingfromgradeorsteelwork.
VerticalCanorBarrelType
Usuallythistypeofpumpisinstalledincoolingtowerwatercirculatingservice,retentionponds,and
applicationswhereNPSHislowandsuctionistakenfromasumpbelowgrade.Inmostcases,thereisno
suctionpipingtobeconsidered,butthedischargelinemustberoutedtoensuregoodaccessforpump
maintenance,withnooverheadobstructionsforpumpremovalbyacrane.Seebelowfigures.
3.ReciprocatingPumps
3.1TypesofPumps
Therearethreeclassesofreciprocatingpumps,piston,plungeranddiaphragm.
Pistonpumpsaregenerallyusedwheremediumtohighdeliverypressuresarerequired,suchahigh
pressureflushingofvesselinteriors,etc.Thesecanbeobtainedinmulticylinderformandcanbesingle
ordoubleacting.Plungerpumpsareusuallyusedformeteringorproportioning.
Frequentlyavariablespeeddriveorstrokeadjustingmechanismisprovidedtovarytheflowasdesired.
Diaphragmpumpsareinvariablyairdrivenandverycompact,alsotherearenosealsorpackingexposed
totheliquidbeingpumpedwhichmakesthemidealforhandlinghazardousortoxicliquids.Theseare
oftenusedforsumppumpout.Seebelowfigures.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 70/136
4/26/2017 PlantLayout|ABCEngineering
4.RotaryPumps
4.1TypesofPumps
Therearetwomainclassesofrotarypumps,gearorscrew.
Gearpumpsareusuallyemployedtopumpoilsandnonabrasivefluids.
Screwpumpsareusuallyusedtopumpheavyviscousfluidsandnonabrasivesludges.Apartfrom
maintaininggoodaccesstopumpsforoperationandmaintenanceeachcaseshouldbetreatedonan
individualbasis.
5.PumpDrivers
5.1TypesofPumpDrivers
Thethreemostcommontypesofdriveraretheelectricmotor,dieselengine,andsteamturbine.
5.2Electricmotorsarethemostcommonpumpdriverandareofthetotallyenclosed,flameprooftype
suitableforzone1use.Theirsizesrangefromsmalltoverylargewhichrequiretheirowncooling
systems.
5.3Dieselenginesareusuallytobefoundasdriversforfirewaterpumpswhicharehousedinaseparate
buildingawayfromthemaincomplex.
5.4Steamturbinesusedforpumpdriversareussualysinglestageandthepumpthattheydriveare
invariablyforstandbyservice(spare).
5.4.1SteamNozzleOrientation
Thesteaminletnozzleisusuallyontherighthandsidewhenviewedfromthepumpcouplingendofthe
turbinewiththeexhaustonthelefthandsideasstandard.Turbinescanbepurchasedwithinletand
exhaustonthesameside.Thismeansthatthepipingdesignercanplacetheexhaustconnectioneitheron
thesameoroppositesidefromtheinlet.Generallyoppositesidelocationofnozzlesresultsinlesspiping
congestion.
5.4.2InletPiping
Steaminletsarefurnishedwithstrainersaspartoftheturbineforprotectionagainstpipedebris,
thereforeinletpipingmustbedesignedwitharemovablesectionforstrainerremoval.
Steamsupplytoturbinesmustbemoisturefreeatalltimes,otherwisedamagetotheturbinewilloccurif
condensateenterstheturbinewhileitisrunning.Toseparatecondensatefromsteamabootlegmustbe
installedupstreamoftheinletblockvalve.
Thetwobasicturbineinstallationsaremanualstartuporautomaticstartup.Themanualstartupwill
haveagatevalveinthesteamsupplyneartheturbineinlet.Upstreamoftheblockvalveabootlegmust
beinstalledwithconnectionsforblowdownandsteamtraptoremoveanycondensateinthesteam
supply.Forautomaticstartupthegatevalveisreplacedwithremoteoperatedcontrolvalve,thebootleg
andtrapsarestillrequiredupstreamasformanualstartup.
Steamtrapsshouldbeprovidedtokeeptheturbinecasingfreefromcondensate.Thesecanbeinstalledat
thecasinglowpointifaconnectionisprovidedor,ontheoutletpipingifthecasingdrainsintotheoutlet
system.
Notetheremustbeatrapbeforeanyverticalrisewhichcouldformapocketwherecondensatecould
collect.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 71/136
4/26/2017 PlantLayout|ABCEngineering
5.4.3WarmupBypass
Onautomaticstartupawarmupbypassmustbeprovidedaroundthecontrolvalve.Thisbypassis
usuallya1globevalve,andispartiallyopenedtoallowsteamtokeeptheturbineconstantlywarmand
slowlyturningtopreventtheshockofhotsteamenteringacoldturbine,andeliminatedamagetoturbine
blades.
Formanualstartupitisrecommendedthatawarmupbypassbeinstalled,butthejobflowsheetswill
govern.
Whenawarmupbypassisinstalledasteamtraponthecasingkeepsthesystemfreeofcondensate.See
belowfigures.
5.4.4ExhaustPiping
Turbineexhaustsareroutedeithertoaclosedexhauststeamsystemortoatmosphere.Whenexhaustisto
aclosedsystemtheremustbeablockvalvebetweenturbineandmainheader,thisblockisalwaysopen
duringnormalconditionsandonlyclosedforturbinemaintenanceorremoval.Thoughtshouldbegiven
tolocatingexhaustblockvalveonthepiperackimmediatelybeforelinesentermainheader,thiswill
preventaccidentalclosureofthisvalve.Iftheexhaustlineisroutedtoatmosphere,thesteamtrapon
turbinecasingwillnotbeinstalled,butreplacedbygatevalvepartiallyopentoallowcondensatetodrain
offfromcasing.Seebelowfigures.
5.4.5RotorWithdrawal
Mostsmallturbinecasingsaresplitalongtheirhorizontalaxisandenoughspaceabovetheturbine
shouldbekeptcleartoallowforthetopsectionofcasingtobeliftedclearofrotorbycrane.Seebelow
figures.
6.PumpHarnessPiping
Mostpumpsrequireexternalservicestobepipedtothemforbearingcooling,bearinglubrication,seal
flushing,ventinganddraining.
Theserequirementswillbeshownonutilityflowsheets,anditisthepipingdesignersresponsibilityto
ensurethattheactualgeographiclocationofpumpswithharnessesarecorrectlyshownontheflowsheets.
Thoughshouldbegiventorunningsubheaderstogroupsofpumpsthathaveharnessrequirements.
Thesesubheadersmustbesizedandmarkedonflowsheetmasters.Becausebranchlinestoindividual
pumpsaresmalldiameter,i.e.6mm,itisadvisabletotakebranchconnectionsfromthetopof
subheaders.Thiswilleliminatepipedebrisgettingintothebranchlineandintothepumpbearings,etc.
Careshouldbetakentoensureharnesspipingdoesnotinterferewithgoodoperationandmaintenance
space.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 72/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 73/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 74/136
4/26/2017 PlantLayout|ABCEngineering
Theabovediagramsindicatecorrectandincorrectmethodsofattachingsuctionpiping.
Fig.1Showsairpocketformedalonguppersideofpipebysingconcentricreducer.
Fig.2(A)Horizontalelldirectlyintopumpsuctionresultsinanunbalancedthrustonpumpbearings.(B)
Usespoolpiece3pipediameterslongorlongradiusellwithcenterverticalvane.(C)Maybeinstalled
withorwithoutspoolpiecebut2pipediametersspoolispreferred.
Fig.3Showspropermethodofconnectingpumpsuctiontoasuctionheaderinordertoavoidairpockets.
Fig.4Representsacommonerrormadesuctionpipingtoacentrifugalpumpbyplacingpipingoveran
embankmentofareservoir,orotherobstruction.
SUCTIONPIPING:Thesuctionpipingshouldbeasdirectandshortaspossible.Ingeneralitshouldbe
oneortwosizeslargerthanpumpnozzle.Ifchangesfromonepipesizetoanotherarenecessary,standard
reducersshouldbeused.Correctandincorrectwaysareshowninthepicturereferredtoabove.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 75/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 76/136
4/26/2017 PlantLayout|ABCEngineering
AUTOMATIC
STARTUP
Categories:PlantLayoutTags:designguide,plantlayout,pumps
PlantLayoutReliefSystem
March15,2012qdzungLeaveacomment
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 77/136
4/26/2017 PlantLayout|ABCEngineering
TableofContents
1.References
2.Scope
3.PressureReliefValveInstallations
4.ThermalReliefValveInstallations
5.RuptureDiskInstallation
6.VentingAtmosphericandLowPressureStorageTanks
1.References
Thedesignofareliefsystemisgovernedbythefollowing:
API.RP520designandinstallationofpressurerelievingsystemsinrefineries
BritishFactoryActs,inrelationtosteamraisingplants,ifapplicable
LocalauthoritiesandClientsrequirements
Goodengineeringpractice
Thedesignofatmosphericandlowpressureventingsystemsaregovernedbythefollowing:
API.RP2000Ventingatmosphericandlowpressurestoragetanks
LocalauthoritiesandClientsrequirements
Goodengineeringpractice
2.Scope
Thisguideisintendedtocovermethodsofinstallationforpressurereliefvalvesandtheirassociatedpipe
workandfittings.
Theinstallationofrupturedisks.
Ventingstoragetanks.
3.PressureReliefValveInstallations
Forgeneralrequirementsofreliefvalvesinstallationatvesselorpipework,seebelowfigures.
Reliefvalvesshouldbemountedinaverticalpositiononly.
Foroptimumperformancereliefvalvesmustberegularlyservicedandmaintained.Tofacilitatethis,
reliefvalvesshouldbelocatedtoenableeasyaccessandremoval.Sufficientplatformspacemustbe
providedaroundthevalve.Provisionofaliftingdeviceshouldbeconsideredforlargereliefvalves.For
typicalinstallationofreliefvalvesandpiping,seebelowfigures.
Thesysteminletandoutletpipingshallbedesignedtoprovideforpropervalveperformance.Tothisend
acompletereliefsystemisometricshowingtheinletanddischargepipingofallreliefvalvesincludedin
thesystemwillbeproduced.Belowfiguresshowspartofsuchasystem,overalldimensionsandlinesizes
shouldbeincluded.
ThesystemmustfirstbeapprovedbytheProcessDepartmentforpressuredrop,thenbytheStress
Sectionforstress.ShouldthepipingbereroutedduetostressrequirementsProcessDepartmentmust
reapprovethesystem.
Theinletpipingtoareliefvalveshallbedesignedsothatthepressuredropdoesnotexceed3percentof
thereliefvalvesetpressure,seebelowfigures.
Themostdesirableinstallationisthatinwhichthenominalsizeoftheinletbranchpipingisthesameas
orgreaterthan,thenominalsizeofthevalveinletflange,andinwhichthelengthdoesnotexceedtheface
tofacedimensionsofastandardteeandweldneckflangeoftherequiredpressureclass.The
configurationshownontheflowdiagrammustalwaysbefollowed.
Reliefvalvesystemsdesignedtodischargeagainstaconstantpressurecannottolerateabackpressure
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 78/136
4/26/2017 PlantLayout|ABCEngineering
greaterthan10%ofthesetpressure.BalancedbellowsorBalansealtypereliefvalveswhichoperate
practicallyindependentofthebackpressuretolerateamuchhigherfigure,butgenerallythehigherthe
backpressurethelowerthecapacityofthereliefvalve.Duetothisthedischargepipingshouldbekeptas
directaspossible,seebelowfigures.
Theflowdiagramwilldetermineifthedischargeistoatmosphere,ortoacloseddischargeheader,see
belowfiguresfordetails.
Itispoorpracticetomountthereliefvalveattheendofalong,horizontalinletpipethroughwhichthere
isnormallynoflow
Foreignmattermayaccumulateorliquidmaybetrappedandmayinterferewiththeoperationofthe
valveorbethecauseofmorefrequentvalvemaintenance.
Processlateralsgenerallyshouldnotbeconnectedtoreliefvalveinletpiping,seebelowfigure4.
Proximityofothervalvesandequipment,therecommendationslaiddowninbelowfigures4,6and7
shouldbefollowedifpossiblefortheminimumnumberofstraightpipediametersbetweenthedevice
causingturbulenceandthereliefvalve.Theabovedoesnotapplytoreliefvalvesfittedwithstopvalves,
seebelowfigures.
Reliefvalvesdischargingintoareliefheadermustbelocatedatanelevationabovethereliefheaderso
thatthedischargelineisfreedraining.Undernocircumstancesmaythedischargelineortherelief
headerbepocketed.
4.ThermalReliefValveInstallations
Thermalreliefvalvesareprovidedoncoolingserviceswhereasystemcanbelockedinbyisolatingvalves.
Thedischargefromthereliefvalveshouldbepipedtogradeinoffsiteareas,tothenearestdrainin
processareas,followdetailsasshownontheflowdiagram.Seebelowfiguresforfurtherdetails.
5.RuptureDiskInstallation
Arupturediskdeviceisanonreclosingpressurereliefdeviceactuatedbyinletstaticpressureand
designedtofunctionbytheburstingofapressurecontainingdisk.Thediskmaybemadeofmetalor
carbongraphiteandhousedinasuitableholder.
Thepurposeofinstallingarupturediskupstreamofareliefvalveistominimisethelossbyleakage
throughthevalveofvaluable,noxiousorotherwisehazardousmaterialsortopreventcorrosivegases
fromreachingthereliefvalveinternals,seebelowfigure11.Typicalburstingdiskinstallationatarelief
valve.
Theinstallationofarupturediskmaybecalledfordownstreamofareliefvalve.Inthiscaseitspurpose
istopreventcorrosivegasesfromacommondischargelinereachingthereliefvalveinternals.
Rupturedisksmayalsobeinstalledasasolereliefdevice,seebelowfigure10.
Rupturedisksmustalwaysbeinstalledasshownonthevendorsdrawing.ForexampleofaConcave
installationseefigure10andaConvexinstallationseefigure11.
6.VentingAtmosphericandLowPressureStorage
Tanks
Determinationofventingrequirements
Inbreathingresultsfrommaximumoutflowofoilfromtank,orfromcontractionofvaporscausedby
maximumdecreaseinatmospherictemperature.Avacuumbreakingdeviceisfitteddirectlytothelineor
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 79/136
4/26/2017 PlantLayout|ABCEngineering
vesseltopreventitscollapsewhentheinternalpressurefallsbelowatmospheric.Iftheadmissionof
oxygenintotheprocessishazardous,ainertgassupplyisconnectedtothevacuumbreakerviaapressure
reducingvalve.FollowthesystemdefinedontheFlowDiagram.
Outbreathingresultsfrommaximuminflowofoilintotanksandmaximumwhichresultfrommaximum
increaseinatmospherictemperature(thermalbreathing).Oneofthefollowingdevicesmaybespecified
ontheflowdiagram.
Reliefvalvemaybeusedeitherdischargingtoatmosphereorintoaclosedsystem.
Openventwithflamearrestingdevice.Manholeorgaugehatchthatpermitsthecovertolift.
Pressureandvacuumbreathingvalvesaredesignedtopreventevaporationfromstoragetanks,butto
allowbreathingwhenthepressureorvacuumexceedsthatspecified.Fordetailsseebelowfigures..
Figures18Incl.
RECOMMENDEDTYPICALRELIEFVALVEINSTALLATION(BASEDONAPIRP520)
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 80/136
4/26/2017 PlantLayout|ABCEngineering
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 81/136
4/26/2017 PlantLayout|ABCEngineering
RECOMMENDEDTYPICALRELIEFVALVEINSTALLATIONS(EXTRACTEDFROMAPIRP520)
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 82/136
4/26/2017 PlantLayout|ABCEngineering
RECOMMENDEDTYPICALRELIEFVALVEINSTALLATION
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 83/136
4/26/2017 PlantLayout|ABCEngineering
RECOMMENDEDTYPICALRELIEFVALVEINSTALLATION
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 84/136
4/26/2017 PlantLayout|ABCEngineering
RECOMMENDEDTYPICALRUPTUREDISKINSTALLATION
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 85/136
4/26/2017 PlantLayout|ABCEngineering
TYPICALPRESSURE&VACUUMBREATHINGVALVE
Categories:PlantLayoutTags:designguide,plantlayout,ReliefSystem
PlantLayoutPipewayDesign
March15,2012qdzung2comments
TableofContents
1.General
2.InformationRequired
3.EvaluationofInformation
4.LineIdentification
5.PiperackWidth
6.PiperackElevation
7.LineLocationinPiperacks
8.PipingEconomyinPiperackanditsInfluenceonPlantLayout
9.PiperackGeneralArrangementChecklist
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 86/136
4/26/2017 PlantLayout|ABCEngineering
10.Pipetracks
11.TrenchedPiping(CivilDepartment)
12.UndergroundPiping(byCivilDepartment)
1.General
Thepipewayconveysallmainprocesslinesconnectingdistantpiecesofequipment,reliefandblowdown
headers,alllinesleavingandenteringtheplant,utilitylinessupplyingsteam,air,coolingwaterandinert
gastotheplant.Electricalandinstrumentcabletraysareusuallyroutedinthepipeway.Pipewaysare
classifiedbytheirrelativeelevationtograde.
1.1Piperack
Overheadpipingsupportedonsteelorconcretebents.
1.2Pipetrack
Abovegroundpipingsupportedonconcretesleepersatgradelevel.(Offsiteareaswhereequipmentis
wellspacedout)
1.3TrenchedPiping(byCivilDepartment)
Belowgroundpipinglaidinconnectiontrenches.Costlyandusuallyundesirableunlesstrenchesare
wide,shallowandwellvented,heavygasesmaysettleandcrea
teafirehazardthroughthelengthofthetrench.Forthesereasons,onlypumpoutlines,chemicalsewers
orchemicaldraincollectionsystemsaresometimesplacedintrenchesandroutedtoapitorunderground
collectiontank.
1.4UndergroundPiping(byCivilDepartment)
Pipingdirectburiedbelowgroundlevel.Duetocostlymaintenanceandtheusuallycorrosivenatureof
soil,thismethodofroutingisgenerallyreservedforseweranddrainlines.Insomeplants,especiallyin
coldclimates,coolingwaterlinesareburiedbelowthefrostline.Thisshouldbedeterminedatthe
beginningofajob,isgenerallyaClientrequest.
2.InformationRequired
2.1JobSpecification
JobspecificationSP.C100containsdesigncriteria,agreedbetweenCompanyandClient,affecting
piperackdesign:
Batterylimit,valvingandspaderequirements.
Catwalk,platformandladderaccesstovalvesandreliefvalvesinpiperack.
Minimumheadroomandclearancesunderoverheadpipingorsupportingsteelwithinareas
Pipewaysandsecondaryaccessways
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 87/136
4/26/2017 PlantLayout|ABCEngineering
Mainaccessroads
Railroads
Standardtobeusedforminimumspacingoflinesinpaperacks
Handlingandheadroomrequirementsforequipmentpositionedunderpiperacks
Operatingandsafetyrequirementsaffectingpiperackandstructuredesign
Locationofcoolingwaterlinesundergroundoraboveground
Trenchedpiping,ifany.
2.2ProcessFlowDiagrams
Processflowdiagramsshowmainprocesslinesandlinesinterconnectingprocessequipment.
2.3EngineeringFlowDiagrams
Engineeringflowdiagramsaredevelopedfromprocessflowdiagramsandshow:
Pipesizes.Pipeclasses,andlinenumber.
Valving.
Manifolding.
Allinstrumentation.
Equipmentandlinesrequiringservices,i.e.watersteam,air,nitrogenetc.
2.4UtilityFlowDiagrams
Utilityflowdiagramsshowtherequiredservices:
Steam
Condensate
Water
Air
Gas
Andanyadditionalservicespeculiartotheplantbeingworkedon,e.g.:
Caustic
Acid
Andrefrigerationlines,etc.
3.EvaluationofInformation
3.1InitialEvaluation
Useplotplanandprocessflowdiagramstomakeapreliminaryassessmentofwhichportionofprocess
lineswillbelocatedinpiperackandwhichlineswillinterconnectdirectlytonozzlesonadjacentitemsof
equipment.Drawlinestobelocatedonpiperacksonprintofplotplan.Someideaofutilitypiping
requiredmustbeestablishedandincludedcoordinatewithInstrumentandElectricalSectiontoassess
whatadditionalrackspacemayberequiredtoaccommodatecabletrays.Thisactionprovidesa
preliminaryvisualideaofthepiperackspacerequired.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 88/136
4/26/2017 PlantLayout|ABCEngineering
3.2Development
Withthereceiptofengineeringflowdiagramsandutilityflowdiagrams,amorecompleteandaccurate
assessmentofrackspaceispossible.Utilityheadersgenerallyrunthewholelengthofthepiperack,so
shouldbetakenintoaccountwhenestimatingadditionalspacerequired.ToassistProcessDepartmentin
sizingutilityheadersinthepipewayalineroutingonareprooftheplotplan,showingorderoftakeoffs
isrequired.
4.LineIdentification
Certaintypesofpipingrequirespecialconsideration:
4.1ProcessLines
Linesinterconnectingnozzlesonprocessequipmentmorethan6Mapart(closerspecedequipmentmay
bedirectlyinterconnectinginsidepipingareas).
Productslineswhichrunfromvessels,exchangersorpumptobattery/unitlimits
Crudeorotherchargelinesenteringtheunitwhichrunalongpiperackbeforeconnectingtoprocess
equipment,furnaces,exchangers,holdingdrumsorboosterpumps.
4.2ReliefHeaders
Individualrelieflines,blowdownlinesandflarelinesshouldbeselfdrainingfromallreliefvalveoutletsto
knockoutdrum,flarestackortoapointattheplantlimit.Toachievethis,lineswillconnectintothetop
oftheheaderandat45degreesindirectionofflow.Toeliminatepockets,andobtainrequiredslopeto
knockoutdrumsomereliefheadersmustbeplacedabovethemainpiperack.
4.3InstrumentandElectricalCableTrays
Ofteninstrumentandelectricalcabletraysaresupportedonthepiperacktrack.Spacemustbeallocated
toaccommodatethemfromtheoutset.Duetothepossibilityofinducedcurrentinterferenceinstrument
andcommunicationcabletraysmustbelocatedawayfromelectricalandpowercabletrays.Consultwith
Instrument/ElectricalDepartmentforseparationrequirements.
5.PiperackWidth
Thewidthofpiperackisinfluencedby:
Thenumberoflines
Electrical/instrumentcabletrays.
Spaceforfuturelines.
Thewidthofapiperackmaybecalculatedusingthefollowingmethod:Firstestimatenumberoflinesas
described.Addupthenumberoflinesupto18diameterinthemostdensesectionofthepiperack.
Thetotalwidthinmeters willbe:
W=(fxNxS)+Ameters
Wheref,safetyfactor=1.5,ifthelineshavebeenlaidoutasdescribedininitialevaluation.
Wheref,safetyfactor=1.2,ifthelineshavebeenlaidoutasdescribedunderdevelopment.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 89/136
4/26/2017 PlantLayout|ABCEngineering
N=numberoflinesbelow18diameter
S=averageestimatedspacingbetweenlinesinmillimeters.
UsuallyS=300mm
UsuallyS=230mm(iflinesinpiperackaresmallerthan10)
A=additionalwidthrequiredmetersfor:
Lineslargerthan18.
Futurelines.
Instrumentandelectricalcabletrays.
Anyslotforpumpdischargelines500mm1meter.
Thetotalwidthisthusobtained.IfWisbiggerthan9Musuallytwopiperacklevelswillberequired.
Note:Atthebeginningofajob,`W`shouldusuallyinclude3040%ofclearspaceforfuturelines.
Thewidthofthepiperackmaybeincreasedordeterminedbythespacerequirement,and/oraccessto
equipmentarrangedunderthepiperack.
Belowfigureshowstypicalpiperacksbentswithtabulateddimensions.Totalavailablepiperackwidthof
eachtypeofsupportisincluded.Thistablecanbeusedforselection.Themostcommonlyusedpiperack
supportsaretypes2,3,4and5.
5.1SpacingbetweenPiperackBents
Normalspacingbetweenpiperackbentsvariesbetween4.6Mto6M.
Thismaybeincreasedtoamaximumof8Mconsiderationmustbegivento:
Smallerlineswhichmustbesupportedmorefrequently(seeCompanydesignspecification
recommendedspanbetweenpipesupports)
Liquidfilledlinesrequiringshorterspanthangasfilledlines
Hotlineswhichspanshorterdistancesthancoldlinesofthesamesizeandwallthickness
Insulatedlinessmallbore,coldinsulatedlinesduetoweightofinsulationmustbesupportedat
relativelyshortintervals
Spacerequirementsofequipmentatgradecansometimesinfluencepiperackbentspacing.
6.PiperackElevation
Piperackelevationisdeterminedbythehighestrequirementofthefollowing:
Headroomovermainroad
Headroomforaccesstoequipmentunderthepiperack
Headroomunderlinesinterconnectingthepiperackandequipmentlocatedoutside.
Thesizeofsteelorconcretebeamsupportingoverheadpipingmustbetakenintoconsideration.
HeadroomrequirementsforeachjobaredetailedinCompanyspecificationno.C100andcoordination
procedure.
6.1ElevationatPiperackIntersection
Wheretwotwotierpiperacksmeet,itisessentialthatelevationsoflateralpiperacksslotbetween
elevationsofmainpiperack.
Figure2Aillustratesthisrequirement.Choiceoftopelevationoflateralpiperackmidwaybetweenthetop
anbottommainpiperackelevationallowsturningupordownattheintersection.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 90/136
4/26/2017 PlantLayout|ABCEngineering
Generally,linesrunningatrightanglestomainpiperackareassignedelevations500mmto1meter
higherorlower(dependingonheadroomrequirements)thanlinesrunninginmainpiperack.500mm
differentialbetweenpiperunsistheabsoluteminimum.
Figure2Bshowsapiperackintersectionwheretherespectivemainandlateralpiperackelevationsdonot
slotbetweeneachother.Thisdesigncomplicatesroutingoflinesfrompiperacktotheother,especially
wherelinesrunonthebottomlevelsofbothpiperacks.Avoidthisdesignatallcost.
Whereasingletierpiperackturnsthrough90,andalllinescanbekeptinthesamesequenceinboth
directions,noelevationdifferenceisnecessary.Whenlinessequencechanges,introduceanelevation
changeattheturn.Seebelowfigures.
7.LineLocationinPiperacks
7.1OneTierPiperacks
Belowfigureshowsacrosssectionofasinglelevelpiperack.Heavylines(verylargediameterlines,large
borelinesfullofliquid)regardlessofserviceareplacedoverornearthepiperackcolumns.Thissimplifies
steelworkorconcretepiperackdesign.Centrallyloadedcolumnandreducedbendingmomentonthe
beamwillresultinalighteroveralldesign.
Placeprocessandrelieflinesnexttothese.Linesservinglefthandareasofplantonleft,linesserving
righthandareasontheright.
Thecentralpiperackportionisreservedforutilitylineswhichmayservebothrightandlefthandareas
ontheplant.However,utilitylinesservingoneortwopiecesofequipmentshouldbeonthesamesideof
thepiperackastheequipmenttowhichtheyconnect.
Processlineswhichinterconnectequipmentonbothsidesofthepiperackshouldbeplacedclosetoutility
lines,andcanbeoneithersideofpiperack,dependinguponlocationofequipmenttheyserve.The
positionofproductlinesisinfluencedbytheirroutingafterleavingtheunit,right,(left)turninglines
shouldbeontheright(left)handsideofthepiperack.
Ifpossible,acentrallyplacedsectionofthepiperackisreservedforfuturelines.Thissectionshouldrun
thewholelengthofthepiperack.Shouldthisbeimpracticable,aseriesofsmallersections,runningthe
wholelengthofthepiperack,aretobeprovided.(seebelowfigure).
7.2TwoTierPiperacks
Wherethenumberoflinesdictatetheuseofatwolevelpiperack,utilitylinesareplacedonthetoplevel
andprocesslinesonthebottomlevel.Thisisnotarigidruleandwherepipingeconomydictatescertain
processlinesmayberoutedonthetoplevel.Linesequencearrangementshouldfollowthephilosophy
outlinedpreviously.
7.3PositionofHotLines
Itisadvantageousforpipesupportstogrouphotlinesrequiringexpansionloopstogether,preferablyon
sideofthepiperack.Horizontallyelevatedloopsoverthepiperackarecommonlyusedtominimizethe
effectsofexpansiononhotlines,thehottestandlargestlinebeingontheoutside.Seebelowfigures.
7.4LineSpacing
ForlinespacinguserecommendedpiperackspacingpertableinJobSpecificationC100.Itshouldbe
notedthatincertaincases,itisnecessarytodeviatefromthestandardsquotedabove,e.g.,seebelow
figuresatpointAduetopossibledifferentialexpansionlinespacingmayhavetobeincreasedtoallow
formovementoflinesatstartup.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 91/136
4/26/2017 PlantLayout|ABCEngineering
Todetermineexpansionofhotlines,useCompanyengineeringguide,Attachmentthermalexpansionof
pipematerials.
8.PipingEconomyinPiperackanditsInfluenceon
PlantLayout
8.1PiperackLayout
Plantlayoutdeterminesthemainpiperackpipingruns.Theshapeofpiperackistheresultofplant
arrangements,siteconditions,Clientsrequirementsandoverallplanteconomy.Seebelowfigures.
Pipingeconomydependsprimarilyonthelengthoflinesroutedinthepiperack.Belowfiguresshows
criticaldimensionswhichinfluenceoverallcost.Thesedimensionsdependonoverallplantlayoutand
shouldbecarefullyconsideredwhentheplotisarranged.
DimensionA,(seebelowfigures)isthetotallengthofpiperackandisgovernedbythenumberandsize
ofequipment,structuresandbuildingsarrangedalongbothsidesofthepiperack.Onaverage,3metersof
piperacklengtharerequiredperitemofprocessequipment,goodlayoutcanreducepiperacklength.
(Therebycosts).
Equipmentinpairs,stackedexchangerssupportedfromtowers,twovesselscombinedintoone,closely
locatedtowerswithcommonplatforms,processequipmentlocatedunderpiperackareexamples
whichhelpshortenpiperacklength.Inawellarrangedplant,averagelengthofpiperackperitemof
processequipmentcanbereducedto2.1metersto2.4meters.
CarefulselectionofdimensionsBandC,belowfigurewillminimizeinterconnectionequipmenton
oppositesidesofpiperack.Cisnormallynomorethan1.8metersto3meters.
DimensionsDandE,(seebelowfigure),minimize.Overgenerousdimensioningherewillincreasevertical
pipelengths.Maximizeuseofavailableplatformsforaccesstovalves.Whereairfinsarelocatedabove
thepiperack,useassociatedairfinmaintenanceplatforms,modifyingtheirextentifnecessary.This
methodwillbecheaperthanaddingspecialplatformsinthepiperack.
9.PiperackGeneralArrangementChecklist
Criticallyreviewpiperacklayoutagainstlatestinformation.Somelinesshouldrequirereroutingfor
maximumpipingeconomy.Checkloopsrequiredfornesting.Asmanyloopsaspossibleshouldbe
combinedinaloopbayhavingdueregardtostressrequirements.
9.1VibratingLines
Avoidchangesindirection
Avoidlongoverhangingbendswithoutsupport
Usebendswherepossible(checkwithjobspecification)
Teestobeavoidedasfaraspossible,flowshouldenteralongrunofteeandneverinthebranch.
Lowpointpocketstobeavoidedinthefollowinglines:
Steam(trapanypocketsanddeadends)
Slurry
Blowdown(theselinesmustbeselfdraining)
Caustic,acidandPhenol(alltheseservicestobeselfdraining)
R.V.sbothinletandoutlet
Vapourtoknockoutpots
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 92/136
4/26/2017 PlantLayout|ABCEngineering
Heavyproducts,bitumen,wax
Pumpsuctions
Lethalandtoxicsubstances
Highpointpocketstobeavoidedinthefollowinglines:
Pumpsuctions
Lightends
Vapour/liquidmixes(hottowerbottomsrefluxlines)
Crudelines
Onhotlines,checkshoerequirementsandclearancesatchangesofdirection(pipeexpansion).
Provideventsathighpoints.
Providedrainsatlowpoints.
Providesteamtrapsat:lowpoints,upstreamofloopsanddeadends,viacondensatedriplegs.
Onsteam,airandcondensateheaders,takeoffstobefromtopofheaders.RVheadershighorlow
elevation.BeforefinalizingelevationofRVheaderconsiderelevationofallRVdischargesandelevationof
knockoutdrumatflare.
Bends,ifused:(checkwithjobspecification).
Wherelineschangeelevationbendsmaybeusedprovidingdifferenceinelevationisadequateand
specificationpermits
Headertakeoffsinpiperacks,useelbows
Specialpiping:
Catalystlines5D(minimum).
Vibratingpiping5D.
Smallboreusuallybelow2(Clientpreferred).
Pipesetting:tobeavoidedinlargeborelines.Smallborelinestobesetonlywhereabsolutelynecessary.
PipeStressDepartmentwilladvisewhichpipingsystemsrequireformalstressanalysis.
Supports:avoidlongunsupportedoverhangs.
Steelworkclearances:checksteelworkclearancesforadditionoffireproofing(lowerelevationof
piperack),brackets,gussetsandthermalexpansionoflines.
Concretesupportclearances:checkforlocalthickeningofconcretecolumnsduetomethodoffabrication
adopted(i.e.corbels).
Valves:checkclearancesandaccessibility.Makefullofextendingplatformsforoperation(i.e.airfin
maintenanceplatforms).
Chainwheels:preferablydonotuse.However,ifnecessary,checkchainclearances.Spadingandvalving
atbatterylimit:checkforaccessibilityifnecessary,provideaccessplatform.
10.Pipetracks
Thistypeofpipewayisgenerallyassociatedwithoffsiteareaswhereequipmentiswellspacedout,and
landspaceisnotapremium.
10.1PipetrackWidth
Pipetrackwidthmaybeestimatedusingthemethoddetailedpreviouslyforpiperack.
10.2SpacingofPipetrackSleepers
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 93/136
4/26/2017 PlantLayout|ABCEngineering
Pipetracksleepersarerelativelycheapthuspipingeconomyisdictatedbytherecommendedspanofthe
smallestlineinthetrack.
Wheresmallborelinesarefew,sleeperspacingmaybedeterminedbythepipespanoflargeborelines
providedsmallborelinesaresupportedoffthelargerlinesatadequateintervals.AnanglewithUbolts
issufficient(checkwithPipeSupportSection).
Forrecommendedpipesupportspans,useCompanystandard.
Onanaverageminimumspan=3meters
maximumspan=6meters
dependingonlinesizeandsubstancecarriedinpipes,(i.e.gasorliquid).
Alllinesmustbesupported.Atchangesofdirectionduetolongoverhangs,fornarrowpipetracksa
diagonalcornersleeperisrecommended.Onwidepipetracks,usealternativemethodoftwoshort
sleeperslocatednearcorner.Seebelowfigures.
10.3PipetrackElevation
Pipetrackelevationissetbymaintenanceaccesstopipingitemslocatedunderneaththepipetrack,i.e.
drainsandsteamtraps.Aminimumof12/300mmclearancebetweenunderneathoflinesandgradeis
recommendedwherenecessary,thismaybeincreasedto18/450mm.
Aspipetracksaregenerallysingletier,nochangeinelevationisnecessaryatchangesofdirection.Thisis
effectedbyuseofaflatturn.Seebelowfigures.
Forindividuallineelevationabovesleeper,useCompanyjobspecificationno.C4elevationofhot
insulatedlines.
10.4LineLocation
Linelocationwithreferencetoboreandweightisunnecessary,asallpipesaresupportedonsleepers
whichrestdirectlyontheground.Lineroutingisallimportant.Alllinesinterconnectingprocess
equipmentand/orstoragetankslocatedonlefthandsideofpipetrackareplacedtothelefthandside.
Similarly,alllinesinterconnectingequipmentlocatedonrighthandsideofpipetrackareplacedtothe
rightofpipetrack.Linesinterconnectingequipmentlocatedoneithersideofpipetrackareplacednear
thecenterofpipetrack.
10.5LineSpacing
UseCompanyjobspecificationno.C100recommendedpipetrackspacing
10.6RoadCrossings
Thestandardmethodistoprovideculvertsunderaccessroads.Elevatingpipingonacrossoverrackis
expensiveandintroducesunnecessarypocketsinthelinesthusrouted.Whendeterminingwidthand
heightofculvert,caremustbetakentoallowsufficientroomroundthepipeworkformaintenance,
insulationandpainting.Whereonlyoneortwolinescrossaroad,crossingmaybebymeansofsleevesset
underroadway.
10.7AccessWays
Inareasneedingfrequentaccess,platformsmaybeprovidedacrosspipetrack.
10.8Valves
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 94/136
4/26/2017 PlantLayout|ABCEngineering
Wherepossible,theseshouldbegroupedattheedgeofanaccessplatformforeaseofoperation.Drain
valveswherepossibleshouldbebroughttooutsideofpipetrackforeaseofoperation.Thesameappliesto
steamtrapassemblies.
10.9ExpansionLoops
Horizontallyelevatedexpansionloopsabovepipetrackshouldbeprovidedwherenecessary.Groupallhot
linesrequiringexpansionloops,hottestandlargestlineontheoutside,ononesideofpipetrack.
(Generally,thesidechosenisthatsidewhichhasthehighestnumberoftakeoffsservingequipmenton
thatside).
11.TrenchedPiping(CivilDepartment)
Inmostplants,trenchesareavoidedduetoproblemsassociatedwiththistypeofpipeway:
Highinitialcost
Firehazard
Wheretrenchersareusedtoroutelinessuchas:
Pumpoutlines
Chemicalsewers
Chemicaldrains
Trenchersmustbeenoughtoallowsufficientclearancebetweentrenchwallandpiping.150mmbetween
outsideofpipeandinsideofwallistheminimumacceptableclearance.Thiswillallowforinstallationof
piping,paintingandfuturemaintenance.Seebelowfigures.Totalwidthoftrenchrequiredmaybe
determinedbyusingmethoddetailedabove.PipingDepartmentwilladviseCivilDepartmentof
requirements.
11.1LineSpacing
UseCompanyjobspecificationC100.recommendedpiperackspacing.
Linelocationinatrenchcarryinganumberoflinesshouldbecarefullychosenformaximumpiping
economyconsistentwithstressrequirements,ifany.
Opentrenchesrequiredrainstostopaccumulationofsurfacewater.Trenchbottomshouldbesloped
towardsdrainpoints.Inthiscase,pipesupportingisbymeansofanglesteelorIbeamssetintothewalls,
allowingbottomforfreedrainagetonearestdrainpoint.
Thismethodallowsdrainageofatrenchbyaminimumofdrainpointsbetweeneachpipesupportas
wouldbethecaseofsolidconcretepipesupportsbuiltupfromthetrench.Beforeproceedingontrench
drainagecheckwithcoordinationprocedureandCivilDepartmentforwatertablelevel.
11.2SafetyPrecautions
Mosttrencheshaveeitheracoverofconcreteslabsoragrating.
Whereflammableliquidsarecarriedintrenchedlines,afirebreakisprovidedatsuitableintervalsalong
atrenchandateachintersection.Thisgenerallyconsistsoftwoconcretewalls1M1.25Mapart,with
thespaceinbetweenfilledwithsand.Wherehighlyflammablegassesarecarried,thewholetrench,after
installationofpiping,isbackfilledwithsand.PipingwilladviseCivilDepartmentofrequirements.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 95/136
4/26/2017 PlantLayout|ABCEngineering
12.UndergroundPiping(byCivilDepartment)
Keepburiedpipingtoaminimum.Generallyonlysewerdrainlinesandfiremainsarelocatedbelow
ground.InsomecasesduetoClientorclimaterequirements,coolingwaterlinesarealsoburiedbelowthe
frostline.
Withfuturemaintenanceinmind,buriedlinesshouldbelocatedwellclearoffoundations,andifrunning
sidebyside,wellspacedout.Aminimumof300mmclearanceisnecessarybetweenfoundationsandlines
andbetweenthelinesthemselves.
Abovegroundsafedraintailswillenterbelowgrounddrainlineviaatundish(concentricreducer
normally)orifasealedsystemandcoolingwaterlinesbyaflangedstubraisedaboveground.
Flangedconnectionsshouldbeaminimumof300mmaboveprevalentgradelevel.Itisadvantageousto
setacommonlevelforallthesetakeoffsattheoutsetofthejob.Whenlocatingtieinconnectionsto
undergroundsystems,especiallyfromelevateddrainpoints,andadjacenttoequipmentplinths,ensure
adequateclearance.
Allburiedsteelpipesshouldhaveappliedacorrosionresistantcoatingandwrapping.
Deepvalveboxesforburiedlinesshouldbedesignedwithampleroominsidetheboxforamaintenance
mantobendoverandusewrenchesfortighteningflangesofrepackingvalves.Considerationshouldbe
giventotheuseofconcretepipeinlieuofsquareboxes.
Thecriteriaforagoodundergroundpipingdesignshouldbeeaseofmaintenance.Pipingshouldbeso
spacedastoalloweasydiggingoutandreplacementoffaultysectionsforthisreason,neverrun
undergroundpipingunderorthroughfoundations.
FiguresTable
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 96/136
4/26/2017 PlantLayout|ABCEngineering
TYPICALPIPERANKBENTS
TOTAL
AVAILABLE
TYPE PIPERACK CANTILEVER NUMBER
WIDTHWIN
mm
WITHOUT WITH
No. WIDTHA WIDTHB OFELEV.
CANTILEVER CANTILEVER
1 3000 3000 1
6000TO
2 6000TO7300 9150TO10400 1500 1
7300
8500TO
3 8500TO9750 11600TO12800 1500 1
9750
6100TO
4 11900TO14300 13700TO16150 900OR1200 2
7300
8500TO
5 16800TO19200 18600TO21000 900OR1200 2
9750
6100TO
6 8500TO10400 11000TO12800 900OR1500 1.5
7300
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 97/136
4/26/2017 PlantLayout|ABCEngineering
TYPICALPIPERANKINTERSECTION
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 98/136
4/26/2017 PlantLayout|ABCEngineering
SINGLETIERRACKTURNINGTHROUGH90
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 99/136
4/26/2017 PlantLayout|ABCEngineering
CROSSSECTIONOFSINGLELEVELPIPERACK
EXPANSIONLOOPS
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 100/136
4/26/2017 PlantLayout|ABCEngineering
PIPERACKLAYOUTS
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 101/136
4/26/2017 PlantLayout|ABCEngineering
PIPERACKLAYOUTS
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 102/136
4/26/2017 PlantLayout|ABCEngineering
SPACINGPIPETRACKSLEEPERS
TRENCHEDPIPING
Categories:PlantLayoutTags:designguide,pipeway,plantlayout
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 103/136
4/26/2017 PlantLayout|ABCEngineering
PROCESSDESIGNBASISSULFURDEGASSINGSECTION
March15,2012qdzungLeaveacomment
1.0INTRODUCTION
1.1SulfurRecoveryComplex
1.2SulfurDegassing
2.0PROCESSDESCRIPTION
2.1ProcessOverview
3.0SCOPEOFGAALICENSEPACKAGE
4.0FEEDSTOCK
5.0PRODUCTSTREAMS
6.0DESIGNCONSIDERATIONS
7.0PROCESSCONTROLPHILOSOPHIES
7.1ControlPhilosophyOverview
7.2DetailedControlPhilosophyDescription
8.0UTILITIES
9.0BATTERYLIMITCONDITIONS
1.0INTRODUCTION
1.1SulfurRecoveryComplex
DuetothehighersulfurcontentinCanadianextraheavycrude,theOperationCanadianCrude(OCC)Project
willincludeanexpansionofsulfurrecoveryprocesses,includingamineregeneration,sourwaterstripping,
elementalsulfurproduction,andtailgassulfurremoval.Revisedsulfurremovalcapacitywillbe1,220LTD.
TomeetpostOCCsulfurrecoveryrequirementsof1,220LTD,threeexistingsulfurrecoveryunit(SRU)trains
A,B,andCtrainswilloperatewithtwonewtrainsDandE.Undernormaloperation,SRUCwilloperateon
40%oxygenenrichmentwhileSRUAandSRUBwilloperateonaironlyandnewSRUDandSRUEwill
operatewithalight(22%)oxygenenrichment.Duringupsetconditions(SRUtrainortailgasunit(TGU)is
tripped),theunitwilloperateinmaximumoxygenenrichmentmodewithtrainCat40%O2andnewtrainsat
30%O2.
1.2SulfurDegassing
Theexisting600LTDDGAASSsulfurdegassingfacilitywillberelocatedandexpandedwithtwonew
identical575LTDtrainstodegastheproductsulfurpriortostorageandtransportation.Thedegassingsection
includesonedegassingcontactorandsupportingequipmentforeachnewSRUtrain.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 104/136
4/26/2017 PlantLayout|ABCEngineering
Therelocationoftheexistingdegassingtrainisnotpartofthedesignofthenewdegassingunits.Inthis
documentthenewunitsaredescribed.Refurbishingtheexistingdegassingunitandintegratingthethree
degassingunitswillalsobepartoftheoverallOCCscopebutisnottheresponsibilityofGoar,Allison&
Associates(GAA).
2.0PROCESSDESCRIPTION
2.1ProcessOverview
TomeetpostOCCsulfurrecoveryrequirementsof1,220LTD,theexistingSulfurDegassinghastobe
expandedwithtwonew575LTPDtrains,whichwilloperateinparalleltotheexistingoneandfedwithsulfur
fromSRUA,SRUB,andSRUCandthenewSRUDandSRUE.Undernormaloperation,alltrainsexcept
SRUCwilloperateasaironlywithaminimumoxygenflowtothenewunits.
Thenewdegassingtrainsincludeadegassingcontactorandsupportingequipment.
ExistingdegassingcontactorT394andsulfurcoolerE394willberelocatedadjacenttonewsulfurdegassing
contactorsT395andT396.Undegassedsulfurfromexistingandnewsulfurrecoveryunitswillbemanifolded
toallowdistributionofsulfurtothethreedegassingcontactors.Productsulfurfromdegassingcontactorswill
rundowntonewsulfurloadingtanks.DegassingventwillreturntoSRUD&SRUEtobeusedas
supplementalcombustionair.
ApreliminaryProcessFlowDiagramhasbeenincludedbelow.
2.2DetailedProcessDescription
Theliquidsulfurfromthesulfurlocksisdrainedviaacollectingheadertothesulfurcollectingdrumineach
SRU.Thevesselbreathesagainstthetailgasheader.Fromthisdrum,thesulfurispumpedtoasulfurcollection
header,feedingboththeexistingandthenewdegassingcolumns.BeforeenteringtheDGAASScolumn,the
sulfuriscooledusinghighpressurecondensate.
ThesulfurproducedintheClausunitscontainsnormallyabout250300ppmwtH2Swithamaximumof400
ppmwt.DegasificationreducestheH2Scontenttolessthan10ppmwt.Theprincipleofdegasificationis
injectionofpressurizedairintotheliquidsulfur,therebystrippingthedissolvedH2Sfromthesulfurand
convertingtheH2Sx(polysulfide)toH2SandSulfur.
Theactualsulfurstrippingtakesplaceinthecolumnpackingwherethesulfurisvigorouslyagitatedbybubbling
ofairthroughtheliquidsulfur.Thestrippingair,containingthereleasedH2Sisremovedfromthecolumnand
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 105/136
4/26/2017 PlantLayout|ABCEngineering
reroutedviasulfurdegassingventknockoutdrum(thefeedvesseloftheexistingsulfurdegassingtrain),
operatedat25psig,tothefrontofoneofthenewSRUs.
ThesulfurlevelinthepumpingcompartmentsoftheSRUsulfurcollectingdrumsarekeptconstantbymeansof
levelcontrolleractingonacontrolvalveinthedischargeofthesulfurpump.Thesulfurfromeachstripping
columnisdischargedtosulfurbulkstorageonlevelcontrol.
AminimumflowrecyclelinefromthesulfurbulkstoragetankswillberoutedbacktoSRUA/B/C/D/Esulfur
pits.ThissulfurshallbereprocessedthroughthedegassingsystemalongwiththeundegassedSRUsulfurto
keepthesulfurintheliquidsulfurheadersflowing.Thislineisoutsidethescopeofthenewunits.
3.0SCOPEOFGAALICENSEPACKAGE
RequirementsforpostOCCSulfurDegassingwillbemetwithoneexistingtrainandtwonewidentical575
LTDtrains.
Therequiredstrippingairwillbedeliveredbycompressorsandairdryersthatwillfeedalldegassingtrains.
GAAwillindicatetheairrequirementsforthenewtrains.
TherelocationandupgradeoftheexistingtrainisnotpartoftheGAAlicensepackage.
4.0FEEDSTOCK
Designbasisforthesulfurfeedstreamtoeachdegassingtrainissummarizedbelow.
SRUSulfurfeedrate 575LTD
H2SandH2Sx(asH2S)inthesulfur
400ppmwt.max.
feed
Sulfurfeedpressure ByGAA
Sulfurfeedtemperature 342F
DryPurity,weight%minimum 99.5
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 106/136
4/26/2017 PlantLayout|ABCEngineering
OrganicMaterial,weightppm 1,000
maximum
MineralAsh,weightppmmaximum 100
Acidity,weightppmmaximum 40
5.0PRODUCTSTREAMS
BrightYellow(at
Color ambient
temperatures)
Sulfurfeedpressure ByGAA
Sulfurtemperature ByGAA
DryPurity,weight%minimum 99.5
OrganicMaterial,weightppm
1,000
maximum
HydrogenSulfide,weightppm
10
maximum
MineralAsh,weightppmmaximum 100
Acidity,weightppmmaximum 40
6.0DESIGNCONSIDERATIONS
Objectiveistomakeprocessconfigurationofallthreedegassingunitsidentical.SulfurDegassingB(SDB)and
SDCshouldalsobeidenticalinequipment,instrument,andpipesizes.
NewsulfurcoolerswillhavesimilarconfigurationasexistingsulfurcoolerE394.Recycledsteamcondensate
willbeused.Incasecondensateistoocool,directsteaminjectionwillbeusedfortemperaturecontrol.Hot
waterreturnfromsulfurcoolerwillbereturnedtocondensateflashdrumD361togenerate10psigsteam.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 107/136
4/26/2017 PlantLayout|ABCEngineering
Thetotalventgasstreamfromthethreedegassingtrainswillbecombinedinoneheaderandhavethecapability
tobesenttoeitherSRUDorSRUE.
Protectiveinstrumentationwillbeprovidedtopreventliquidsulfurcarryoverinsulfurdegassingvent.An
additionalsafeguardistobeadded:ConvertexistingsulfurfeeddrumD394tosulfurdegassingventknockout
drum.ThedrumwillnolongerbeusedincurrentserviceasfeeddrumforT394.Withthisconfiguration,each
degassingcontactorwillhaveindividualbackpressurecontrol.VentfromD394willhaveabackpressure
controller,setat25psigtoensureadequatepressuretodrainsulfurcarryovertosulfurcollectingdrumsD278
orD288.
Mostclientsrequirepressurereliefdeviceforthedegassingcontactorevenalthoughtherearenoviable
contingenciestocauseoverpressure.Typicalsizingbasisistoratepressurereliefdevicefordesignsulfurflow
rate.ExistingsulfurdegassingcontactorT394usesarupturedisk.
ThenecessityofreliefdeviceshastobeevaluatedbyGAA.GAAisrequestedtoproposedalternativesolutions,
ifany.
7.0PROCESSCONTROLPHILOSOPHIES
7.1ControlPhilosophyOverview
SulfurDegassingUnitwillconsistoftwonewsulfurdegassingsections.Thefollowingisabriefprocess
overviewofeachnewequipmenttrain:
TheliquidsulfurfromtheSRUispumpedtothedegassingcolumnaftercoolingwithhighpressurecondensate.
ThesulfurproducedintheClausunitscontains250400ppmwtH2S.Degasificationbymeansofthe
degassingprocessreducestheH2Scontenttolessthan10ppmwt.Thestrippingair,containingthereleased
H2SisremovedfromthecolumnandreroutedtothemainSRUreactorburnerviaasulfurdegassingventknock
outdrum.Theliquidsulfurfromthestrippingcolumnisdischargedtoexistingstoragetanksonlevelcontrol.
MaincontrolobjectivesforeachnewSulfurDegassingUnitincludes:
Controlofthesulfurfeedflowtoeachdegassingunit.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 108/136
4/26/2017 PlantLayout|ABCEngineering
ControltemperatureoftheliquidsulfurbyadjustingtheflowrateHPcondensate.
ControlthetemperatureoftheHPcondensatebyadjustingthe(reduced)400#steamflowtothecondensate
steammixvalve.
Controltheflowofairtothedegassingcontactor.
Controlthelevelofliquidsulfurinthedegassingcontactorbyadjustingtheamountofsulfurtothestorage
tanks.
Backpressurecontroltheventgasoffthedegassingcontactor.
Backpressurecontroloftheventgasfromthesulfurdegassingventknockoutdrumatapressurehighenough
tofeedbacktotheSRUreactorburner.Similarly,thepressuremustbehighenoughsuchthatanysulfur
collectedinD394candrainbacktoeitherSRUDorEpits.
7.2DetailedControlPhilosophyDescription
TheliquidsulfurfromtheSRUispumpedtothedegassingcolumnaftercoolingHPcondensate.The
temperatureoftheliquidsulfurismaintainedattheoptimumtemperaturebyadjustingtheHPcondensateflow
rateattheoutletsideofthesulfurcooler.TheHPcondensateistemperaturecontrolledbyadjustingthe400#
steamflowtoensureproperheattransferbetweentheHPcondensateandliquidsulfur.
Toensureproperdegasification,air,whichisflowcontrolled,isinjectedintotheliquidsulfur,therebystripping
thedissolvedH2Sfromthesulfur.
TheactualH2Sstrippingtakesplaceinthecolumnwherethesulfurisvigorouslyagitatedbybubblingofair
throughtheliquidsulfur.Thestrippingair,containingthereleasedH2S,isremovedfromthecolumnbymeans
ofbackpressurecontrolandreroutedtothesulfurdegassingventknockoutdrum.Thedrumisalsokept
pressurizedbymeansofpressurecontrolhighenoughtobeabletodischargetheventgastomainreactorburner
intheSRUDorSRUE.ThisventgasstreamwillbemeasuredandviaaratiostationincorporatedintheSRU
burnercontrolsystem.
8.0UTILITIES
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 109/136
4/26/2017 PlantLayout|ABCEngineering
Pressure
Pressure Pressure Temperature Temperature Temperature
Min
Utility Normal Design MinMax Normal Design
Max
PSIG PSIG F F F
PSIG
SteamLowPressure
921 17 46 240245 242 300
(10psig)
SteamLowPressure
4565 55 90 276296 287 308
(55psig)
SteamMedium
80121 98 146 340530 420 580
Pressure(100psig)
SteamHighPressure
340460 360 510 420505 440 555
(400psig)
85
CoolingWaterSupply 105125 120 150 6085 125
(ForHX
Design)
105110
CoolingWaterReturn 5570 60 95 120Max. 170
(ForHX
Design)
UtilityWater(Service
2732 30 57 3575 55 125
Water)
Oxygen
58142 118 167 20110 65 160
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 110/136
4/26/2017 PlantLayout|ABCEngineering
9.0BATTERYLIMITCONDITIONS
SulfurRecovery
LiquidSulfur ByGAA* 334342 ByGAA ByGAA
Units
SulfurRecoveryUnit
SulfurDegassingVent ByGAA ByGAA ByGAA ByGAA
D/E
*GAAtoconfirmsupplypressureforexistingrelocatedsulfurdegassingcontactor.
Categories:PlantLayoutTags:DESIGNBASIS,designguide,PROCESS
PlantLayoutGeneralRequirements
March15,2012qdzungLeaveacomment
TableofContents
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 111/136
4/26/2017 PlantLayout|ABCEngineering
1.Process
2.HazardousandToxicAreas
3.EconomicConsiderations
4.AestheticConsiderations
5.Access
6.Safety
7.SiteConsiderations
8.ExternalInfluences
9.Clearances
10.Paving
11.Elevations
12.Insulation
13.ColumnsandDrums(Vertical/Horizontal)
14.Exchangers
15.FurnacesandFiredEquipment
16.Pumps
17.Compressors
18.Piping
19.AccesstoValvesandInstruments
20.ReliefValveSystems
21.MaintenanceandEquipmentHandling
1.Process
Equipmentshouldbelaidoutinasequencetosuittheprocessflow.Fluidflowrequirements,forexample
gravityflowsystems,pumpsuctionheadsandthermosyphonsystem,oftendictaterelativeelevationsand
provoketheneedforstructures.Limitationsofpressureortemperaturedropintransferlinesdecide
proximityoffurnaces,reactors,etc.
2.HazardousandToxicAreas
Equipmentitemsconsideredapossiblesourceofhazardshouldpreferablybegroupedandlocated
separately,ifpossibleandeconomic.
Examplesare:
Furnaces,flarestacks,orotherdirectfiredequipmentcontaininganopenflamerotatingormechanical
equipmenthandlingflammableorvolatileliquidswhichcouldeasilyleakorspill.
Equipmenthandlingacidsorothertoxicmaterialswhichcouldcausedamageordangerbyspillage,
shouldbegroupedandcontainedwithinabundedarea.
2.1LocateControlRooms
15metersormorefromequipmentwhichinoperationorduringmaintenancecancreateahazard.(Ifnot
practicable,pressurize).Ensuremaximumcableruntoanyinstrumentisnotmorethan90meters.
2.2LocateBuildings
Exampleoffices,firstaidrooms,cafeterias,garages,firestation,warehouses,gasholdersandworkshops
aminimumof30metersfromanyhazard.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 112/136
4/26/2017 PlantLayout|ABCEngineering
Unpressurisedsubstationandswitchroomsaminimumof15metersfromanyhazard.
DefinitionofdangerousareasandtheirsafetyrequirementsshallbeinaccordancewiththeInstituteof
PetroleumSafetyCodes,orwherethisisnotrecognized,totheapplicableNationalCode(s).
LocalbyelawsandFireOfficewhoserequirementsmaybemorestringentorspecificthantheabove
codesshalltakeprecedence.
3.EconomicConsiderations
Apartfromprocessrestrictions,positionequipmentformaximumeconomyofpipeworkandsupporting
steel.Ascompactalayoutaspossiblewithallequipmentatgradeisthefirstobjective,consistentwith
standardclearances,constructionandsafetyrequirements.
Minimizerunsofalloypipeworkandlargeborepipewithouttheintroductionofexpensiveexpansion
devices.
Optimizeuseofsupportingstructuresinconcreteorsteelbyduplicatingtheirapplicationtomorethan
oneitemofequipmentandensuringthataccessways,platforms,etc.,havemorethanonefunction.Space
savingcanbeachievedbylocatingequipmentoverthepiperack.Pumpsshouldingeneralbelocatedwith
theirmotorsunderneaththemainpiperack.
4.AestheticConsiderations
Attentionshouldbepaidtothegeneralappearanceoftheplant.Anattractivelylaidoutplantwith
equipmentinstraightlinesisusuallyeconomical.Preferenceshouldbegiventouseofasinglecentral
pipewaywithaminimumnumberofsidebranches,withequipmentlaidoutinrowsoneitherside.
Buildings,structuresandgroupsofequipmentshouldformneat,symmetrical,balancedlayout,consistent
withkeepingpiperunstoaminimum.
Towersandlargeverticalvesselswillbearrangedinrowswithacommoncenterlineifofsimilarsize,but
lineupwithacommonfaceifdiametersvarygreatly.Ifadjacenttoastructure,commonfacewillbeon
thestructureside.
Centerlinesofexchangerchannelnozzlesandcenterlinesofpumpdischargenozzlesshouldbelinedup.
Pipingaroundpumps,exchangersandsimilargroundlevelequipmentshouldberunatsetelevations,
onefornorthsouthandanotherforeastwestelevationswhereverpossible.(Similarforrackpipework).
Theseelevationsbeingtobottomofpipeorundersideofshoeforinsulatedlines.Thisshouldalsohelpto
achieveacommonelevationforofftakesfrompipeways.
Ifpossible,duplicatedstreamsshouldbemadeidentical.Handedarrangementsshouldbeavoided.Follow
thisprincipleforthissimilarequipmentsequenceswithintheprocessstream,forexample,fractionator
towerwithoverheadcondensers,refluxdrumpumpsandreboiler,etc.,isasystemwhichcouldbe
repeatedalmostidenticallyfordifferenttowershavingadifferentprocessduty.Advantagesaredesign
andconstructioneconomy,improvedmaintenanceandoperatingefficiency.
5.Access
Overallplantarrangementmustbereviewedforconstructions,operation,safetyandmaintenance.
Considerlargeitemsofequipmentortowersforwhichspecialliftinggearwillberequired.Provide
adequateaccesstolifttheseintoplace.Largeequipmentpositionedclosetoboundarylimitsmayrequire
erectionfromoutside.
Checktoascertainwhethersufficientspacewillbeavailableattheconstructionphase.
Operationandmaintenanceshouldbereviewedbytheeventualoperatingcompany.Giveconsiderationto
maintenanceaccesstoairfins,etc.,abovepipetracks.
Considerlocationofequipmentrequiringfrequentattendancebyoperatingpersonnelandrelative
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 113/136
4/26/2017 PlantLayout|ABCEngineering
positionofcontrolroomtoobtainshortestandmostdirectroutesforoperatorswhenonroutine
operation.
6.Safety
Provide:Sufficientclearareabetweencriticalorhightemperatureitemsofequipment.Clearroutesfor
operatorswithtwoormoreescapeladdersorexitsatextremities.Clearroutesforaccessbyfirefighting
equipment.
DonotAllow:Areasclassifiedashazardoustooverlaptheplotlimitsorextendoverrailwayswhereopen
fireboxenginesarelikelytobeemployed.
7.SiteConsiderations
Ascertainsoilloadingconsiderationsandsitecontoursbeforefixingfinallayout.Considerablevariations
occurinallowablesoilloadsthroughoutsiteareas.Itmaybeadvantageoustolocateheavyequipmentin
thebestsoilloadingarea.Useexistingcontours,sothatthequantityofearthmovementduetocutandfill
maybesubstantiallyreducedbyintelligentpositioningoftheequipment.
8.ExternalInfluences
Stacksshouldpreferentiallybelocatedsothatprevailingwindsdonotblowsmokeovertheplant.Trynot
tolocatetheplantwhereitwillreceivedust,smoke,sprayoreffluentfromaneighboringplant.
Avoidusinglocationspollutedbycontinuousdriftofdust,smoke,etc.
Iftheplantistobelocatedinanexistingrefineryorfactorysite,lineupwithexistingroads,columns,
stacks.
Locationofexternalrailways,pipeways,cableways,sewersanddrains,etc.,mayalsoinfluencethefinal
orientationoftheplant.
Whenrailwayfacilitiesarerequired,avoidboxingintheplantbybranchlines.
Hazardousareasfromotherexistingplantsorequipmentmayextendovertheplantlimit.Thiscould
effectivelyreduceplotsizeandthusinfluencetheplantlayoutphilosophy.
9.Clearances
(SeeTableA)Clearancesbetweenadjacentplantsshouldatleastequalthoseforprimaryaccessroads.
Thespacebetweenedgeofanyroadandnearestequipmentmustnotbelessthan1.5meters.
Adequateroadaccesswithproperlyformedroadsmustbeprovidedforknownmaintenancepurposes:
e.g.,compressorhouse,largemachineryareas,reactorsorconverterswherecatalystremovaland
replacementmustbeeffected.
Equipmentrequiringinfrequentmaintenancesuchasexchangertubebundles,towerinternals,etc.,need
adequatelevelclearspaceforaccess/removalpurposes.Thegroundneednotbespecificallybuiltupto
takeloadsotherthanasurfacingofgranitechipsorsimilar,asduckboards,gratings,orothertemporary
materialcanbelaidatthetimewhentheplantisundermaintenance.
10.Paving
Withintheprocessareaminimalconcretepavingshouldbesuppliedforwalkwaysinterconnectingmajor
itemsofequipment,platforms,stairwaysandbuildings.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 114/136
4/26/2017 PlantLayout|ABCEngineering
Pavingshouldbesuppliedaroundpumpsorothermachinerylocatedintheopen,underneathfurnaces,
andanyotherareaswherespillageislikelytooccurduringnormaloperation.
Areascontainingalkalisacids,orotherchemicalsortoxicmaterialsshouldbepavedandbundedto
preventspillagespreading.Otherareasoftheplantaretobegradedandsurfacedwithgranitechipsor
similarmaterial.
11.Elevations
(SeeTableA)Allelevationsrefertoanominal100meters.Thepoint100elevationistakenasthehigh
pointofpavinginthepavedareas.Thisshouldbecommonthroughouttheplant.Equipmentelevations
referringtogradeelevationsof100metersareasshownintableA.
12.Insulation
Insulationmaybeappliedtovesselsupportsorstanchionsofstructuresforfireprotectionpurposes,thus
decreasingavailablefreespaceforaccess,sitingofpipework,instrumentsorelectricalequipment.
Inparticular,notethicknessofinsulationofveryhightemperatureorlowtemperaturepiping,whichmay
considerablyincreaseeffectiveo/dofpipetoberouted.Forlowtemperatureinsulation,additional
clearancemustbeprovidedaroundcontrolvalves,instrumentation,etc.Consideradditionalweightof
insulationandreducedcentersofsupportsnecessarytosupportheavilyinsulatedpipe.
13.ColumnsandDrums(Vertical/Horizontal)
Columnsareusuallyselfsupportingwithoutexternalstructures.Circularorsegmentalplatformswith
laddersaresupportedfromtheshell.Maximumallowablestraightrunofladderbeforeabreakplatform
shouldnotexceed9meters.
Factorsinfluencingcolumnelevationareprovisionofgravityflowsystemandinstallationoftherm
syphonreboilers.Dependingonplantarrangementcolumnsmayhavetobeelevatedtoaheightinexcess
ofthenormalrequirementstoallowforheadroomclearancefromlowlevelpipingofftakes.
Skirtheightofallcolumnsorvesselsprovidingsuctiontopumps,particularlyifhandlinghotorboiling
liquids,shouldbeadequateforpumpNPSHrequirements.
Provideplatformsoncolumnsforallvalves3andabove,instrumentcontrollersandtransmitters,relief
valves,manholesandblindsorspades.Otherwise,accesstosmallvalves,indicatinginstruments,etc.,is
acceptablebyladder.
Platformsforaccesstolevelgaugesandcontrollersshouldnotbeprovidedifundersideofsupporting
steelworkislessthannormalheadroomclearancefromgrade.Adjacentcolumnsshouldbechecked,so
thatplatformsdonotoverlap.Forlayout,2.0to2.5metersbetweenshells,dependinguponinsulation,
shouldsuffice.Allow900metersminimumclearancebetweencolumnfoundationandadjacentplinth.
Provideclearanceforremovalofinternalsandattachments,andfordavitsattopofcolumnifrelevant.
Centerlineofmanholeswillbe900mmaboveanyplatform.
Horizontalvesselsshouldbelocatedatgrade,withlongitudinalaxisatrightanglestothepipewayif
possible.Considersavingplotspacebychangingvesselsfromthehorizontalandbycombiningvessels
togetherwithaninternalhead.(Subjecttoprojectapproval).Sizeandnumberofaccessplatformson
horizontalvesselsshallbekepttoaminimumandarenottobeprovidedonhorizontalvesselsordrum
whenthetopofthevesselis2.5metersorlessfromgrade.
Channelendofvesselsprovidedwithinternaltubularheaterswillfacetowardsopenspace.Withdrawal
areamusttobeindicatedonstudies,GAsandPlotPlants.Internalagitatorsormixersaretobeprovided
withadequateclearanceforremoval.RemovalareamustbeindicatedonStudies,GAsandPlotPlants.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 115/136
4/26/2017 PlantLayout|ABCEngineering
14.Exchangers
Tubularexchangersusuallyhavestandardlengthtubesof2.5,4,5,and6meters.
Wheneverpossiblelocateexchangersatgradetofacilitatemaintenanceandtubewithdrawal.Twoor
moreshellsformingoneunitwillbestacked,orotherwisearrangedasindicatedontheexchanger
specificationsheet.
Exchangersondissimilarservicemaybestackedbutnevermorethanthreehigh,exceptforfintubetype
units.Horizontalclearanceofatleast900mmwillbeleftbetweenexchangersorexchangersandpiping.
Wherespaceislimited,clearancemaybereducedbetweenalternateexchangers,providingsufficient
spaceisleftformaintenanceandinspectionaccess.
Tubebundleremovaldistancewillbeminimumtubelengthplus900mm.Minimumremovaldistance
plus600mmwillbeleftbehindtherearshellcoveroffloatingheadexchangers.Whererearshellcoveris
providedwithadavit,allowclearanceforfullswingofthehead.Setoverheadvaporexchangersor
condensersatsuchelevationthatexchangerisselfdraining.
Arrangeoutletstoaliquidholdpotortrap,sothatundersideofexchangertubesisabovetheliquidlevel
inthetrap.Arrangeexchangerssothatfixedendisatthechannelend.Verticalexchangersshouldbeset
toallowliftingorloweringoftubebundle.ConsultVesselSectionastofeasibilityofsupportingvertical
exchangersfromassociatedtowers.
Spacefortubeorbundlewithdrawalshouldbeleftfree,exchangerchannelspreferablypointingtowards
accessareaorroad.Ifexchangerissituatedwellwithintheplot,leaveafreeareaandapproachfor
mobileliftingequipment.Preferablyairfinexchangersshouldbelocatedinaseparaterowoutsidethe
mainequipmentrow,remotefromthecentralpipeway.Considerlocationofairfinexchangersoverthe
centralpipewayifplotspaceifverylimited.
15.FurnacesandFiredEquipment
Locateatleast15metersawayfromotherequipmentwhichcouldbeasourceofspillageorleakageof
gas.
Nopitsortrenchespermittedtoextendunderfurnacesoranyfiredequipmentandifpossibletobe
avoidedinfurnaceareas.
Ensureampleroomatfiringfrontforoperationandremovaloftheburnersandforburnercontrolpanel
ifrequired.
Bottomfloorfiredfurnacesrequireadequateheadroomunderneaththefurnace.Wallfiredfurnaces
requireanadequateplatformwidthwithescaperoutesateachendofthefurnace.
Apartfromadequateplatformingandaccesstothefiringfront,otherstructuralattachmentsand
platformingaroundfurnacesshouldbekepttoaminimum.Peepholesshouldonlybeprovidedwhere
absolutelynecessary.Accessbymeansofstepladderissufficient.
Arrangeheatersoncommoncenterlinewhereverpossible.Provideunobstructedspaceforwithdrawal.
Operationandmaintenanceplatformsshouldbewideenoughtopermita1.0meterclearwalkway.
Escapeladdersshouldbeprovidedonlargeheaters.Verticalheatersareusuallysuppliedwithstub
supportingfeet,ensuredrawingsshowadequatesupportselevatedtorequiredheight.Headroom
elevationfromfloorleveltoundersideofheatershouldbe2.3meters,toprovidegoodfiringcontrol
operation.
16.Pumps
Locatepumpsclosetotheequipmentfromwhichtheytakesuctionpossiblyunderstructuresorwith
motorendsunderapiperackallowinganaccessaisleformobilehandlingequipment.Suctionlinesare
generallylargerthandischargelines,toavoidproblemsarisingfromlowNPSH.
Endsuction,topdischargeispreferableforpumpstakingsuctiondirectlyfromtanksorvesselslocatedat
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 116/136
4/26/2017 PlantLayout|ABCEngineering
grade.Pumpsshouldbearrangedinrowswithcenterlineofdischargesonacommonline.Clearances
betweenpumpsorpumpsandpipingshallbeaminimumof900mm.
17.Compressors
Locatereciprocatingcompressors,anchorsandrestrainsforpipesinthecompressorsystemon
foundationsindependentofanybuilding,structureorpipetrestle.
Spacingvarieswithtypeandduty,payparticularattentionto:Withdrawalofengineandcompressor
pistons,camshaft,crankshaftandlubeoilcoolerbundlecylindervalvemaintenanceclearancewith
leastpossibleobstructionfrompipingsupports.
Compressorsaregenerallyprovidedwithadegreeofshelter,i.e.,asheetsbuilding.Keepthesidesupto8
feetabovegrade,openandventtheridgetoallowforescapeofflammablegaswhichmightleakfromthe
machines.Certaintypesofcompressors,owingtotheheightofthemassfoundationabovegradelevel,
requireamezzaninefloorofthegridconstructiontoavoidtrappinganygas,foroperationand
maintenance.
18.Piping
Allpipingwithinaprocessareashouldusuallyberunabovegrade.Trenchedpipingtobeavoided.
Piperacksandsupportstobeofthesimplestform.
Piperacksmaycontaintwolayersofpipework.Avoidtriplelayerofpipewaysexceptforveryshortruns.
Runpipingexternaltotheprocessareaatgradeonsleepers(300mmhigh).(Pipingatgradeischeaper
butliabletointerferewithaccess).
Locatelargeborepipingasclosetostanchionsaspossible.Linesrequiringaconstantfall(reliefheaders)
canberunoncantileversfrompiperackstanchionsoronverticalextensionstopipetrackstanchions.
Runhotlinerequiringexpansionloopsontheoutsideedgeofpipewaytopermitloopstohavegreatest
widthoverthepipewayandfacilitatenesting.Takeoffelevationsfrompipewaysshouldbeataconstant
elevationconsistentwiththerangeofpipesizesinvolved.
Changeelevationwheneverbanksofpipes,eithertogradeoronpiperackschangedirection.Elevationsto
theundersideofpiperackswillbeminimumforoperationandmobilemaintenanceequipmentand
consistentwithclearances.
Openpipetrenchesmaybeusedbetweenplantswherethereisnoriskofflammablevaporscollecting.It
issometimesconvenienttorunopentrenchesalongsideroadways.(Soilfromthetrenchcanbeusedto
builduptheroad).Whereapipewayorroadchangesdirection,thepipeisrunbeneaththeroad.
Occasionallyitispermissibletorunpipesintrenchestoovercomeadifficultpipingproblem.Such
trenchesshouldbeconcreted,drainedandcovered.Althoughtrenchedpipingistobeavoidedduetothe
expenseandhazardsassociatedwithopentrenches,undergroundburiedpipingisacceptableprovided
pipeisadequatelyprotectedandbelowthefrostline.
Sizingandarrangementofundergroundpipingshouldbefixedearlytoensurethatinstallationis
simultaneouswithfoundationwork.(Manydrains,sewersandcableways,whichdonotrequireattention,
arerunundergroundbelowthefrostline).Leavespacefordrawboxesoncableways,anchorson
undergroundcoolingwaterpipesandmanholesonsewers.Firemainsshouldbelocatedbetweenthe
perimeterroadandtheplant.
19.AccesstoValvesandInstruments
(SeeTableA)
Alloperatingvalves3andlargeraretobeaccessibleeitherfromgradeorsuitableplatformwith
maximum2.0metersaboveworkingleveltocenterofhandwheel.Smalloperatingvalvescanbereached
fromaladder.Valvesinstalledformaintenanceandshutdownpurposes(otherthanoperating)canbe
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 117/136
4/26/2017 PlantLayout|ABCEngineering
reachedbyportableladder.Otherwiseextensionspindlesorsuitableremoteoperatinggearshouldbe
provided,butnotonvalves11/2andbelow.TheminimumaccesstobeprovidedisasshownonTableA.
20.ReliefValveSystems
Closedreliefvalvesystemsshouldbearrangedtobeselfdrainingandshouldnotcontainpocketswhere
liquidsmaycondenseandcollecttoprovideanybackpressure.
21.MaintenanceandEquipmentHandling
Handlingfacilitiesarelimitedtothehandlingofworkingpartsofequipmentwhichrequirefrequentor
routineserviceandwhichareinaccessibletomobilehandlingfacilitiesassumedtobeavailableatthe
plant.Thesefacilitiesarenotdesignedtohandleheavypartssuchasbedplatesofrotatingmachines,
rotatingequipment,compressorsbodies,machineryframes,etc.Thehandlingfacilitiesprovidedare
limitedasshownontableA
Thedesignandinstallationoftrolleybeams,overheadtravellingcranesandhoisttrestlesisbasedon
liftingthepartstobehandledandtransportingorloweringthemtospecifiedmaintenanceareasorto
grade.Fromthesepointstheyareexpectedtoberemovedbyskidsorhandtruckstootherareasmore
suitableformaintenance.
TablesA
ACCESSCLEARANCES
DESCRIPTION MINIMUM
ClearHeadroom ClearWidth OtherClearance
PrimaryAccessRoads
10.5Minsidecorner
(carryingmajor 6M 6M
radius
equipment)
4.5Minsidecorner
Secondary 5.1M 4.8M
radius
MinorAccessRoads 5.1M 3.6M
YardPiping 3M
Platform,walkways,
1Mworking
passageways,working 2.1M
platforms
areas,stairways
Manholecentre
Clearancefromfaceof
2.1M 1M Approx.1Mabove
manhole
platform
Railways Tosuitlocalcodes
ELEVATION
OpenAirPavedAreaHighPointofPaving 100.000M
Undersideofbaseplatesforstructuralsteel 100.150M
Stairandladderspads 100.075M
Undersideofbaseplatesvesselandcolumnplinths 100.300M
Topofpumpplinths 100.230M
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 118/136
4/26/2017 PlantLayout|ABCEngineering
VALVEACCESS
MINIMUM
LOCATE
ITEM ACCESS
OVER
FROM
FIXED EDGEOF PLATFORM
SIZE
LADDERS PLATFORM ORGRADE
EXCHANGERHEADS ALL X
OPERATIONAL 2and
X
VALVES under
OPERATIONAL
over2 X
VALVES
MOTOROPERATED
all X
VALVES
CONTROLVALVES all X
R.V.s(Process) 2andover X
Accessibleby
BLOCKVALVES portable
ladder.
Edgeof
platform
accesswhere
BATTERYLIMIT
ALL ClientsSpec.
VALVESETC.
requests.
Otherwiseno
access.
PRESSURE
ALL X
INSTRUMENTS
TEMP.INSTRUMENTS ALL X
SAMPLEPOINTS ALL X
TRYCOCKS ALL X
GAUGEGLASSES ALL X
LEVEL
ALL X
CONTROLLERS
PROCESSBLINDS
ALL X
ANDSPADES
MANWAYS ALL X
HANDHOLES ALL X
Noaccess
NOZZLES ALL
Provided.
VESSELVENTS ALL X
LINEDRAINSAND Noaccess
VENTS Provided.
MAINTENANCEFACILITIES
Internalrequiringregular
Trolleybeamsordavitsfor
removalorservicing.
loweringfromholesto
grade.
Thesewillbeprovidedas
Fixedbedreactors,catalyst speciallyspecifiedtoenable
change,etc. catalysttobeoffloadedand
loaded.
Allsuchexchangersare
providedwithjackboltsto
FloatingHeadExchangers. TubeBundles. breakjoints.Itisassumed
bundleswillbehandledby
mobileequipment.
ExchangerHeads,Channel
Nospecialprovision.
Cover,Bonnets.
Overheadtrolleybeamor
VerticalExchangers. RemovableTubeBundles.
davit.
Pump. Anypart. None.
Overheadtrolleybeamsor
CentrifugalCompressors. Rotatingparts.
cranes.
ReliefValves,2nominal Hitchingpointordavitfor
Piping.
boreandlarger. loweringtograde.
Overheadhitchingpointor
Blanks,blankflangesand
davitonlywhensubjectto
swingelbowweighing
frequentremovalfor
morethan300lbs(125kg).
maintenance.
ListingofInstrumentationWhichMayAssistInitialLayout
LikelyDevicesandProbableNumberFittedtoVariousTypesofEquipment.DevicesandDesignPoints
Affected.
LIST1)
DEVICESANDPROBABLENUMBEROF
EQUIPMENT
ITEMSFITTED
PSV(1)(PressureSafetyValve)
PIC(1)(PressureIndicatingController)
FRC(3)(FlowRecordingController)
TR(1)(Multipoint6channel)(Temperature
Recorder)TI(6)(TemperatureIndicator)
DISTILLATIONTOWER
PI(6)(PressureIndicator)
Analyser(1)(SingleStream)
LG(2)(LevelGauge)
LI(1)(LevelIndicator)
LIC(1)(LevelIndicatingController)
LG(3)(LevelGauge)
REFLUXDRUMSURGE LIT(1)(LevelIndicatingTransmitter)
DRUMBUFFERSTORAGE PI(1)(PressureIndicator)
FEEDTANKPRODUCT TI(1)(TemperatureIndicator)
TANK PSV(1)(PressureSafetyValve)
PIC(1)(PressureIndicatingController)
REACTOR PI(6)(PressureIndicator)
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 120/136
4/26/2017 PlantLayout|ABCEngineering
REACTOR PI(6)(PressureIndicator)
TI(6)(TemperatureIndicator)
PSV(1)(PressureSafetyValve)
TR(1)(Multipoint50Channels)(Temperature
Recorder)
FIC(2)(FlowIndicatingController)
LIC(1)(LevelIndicatingController)
Analyser(1)
PIC(1)(PressureIndicatingController)
TIC(1)(TemperatureIndicatingController)
LIST1)
DEVICESANDPROBABLENUMBEROF
EQUIPMENT
ITEMSFITTED
PI(4)(PressureIndicator)
DPC(1)(DifferentialPressureController)
PIC(1)(PressureIndicatingController)
FR(1)(FlowRecorder)
COMPRESSOR(Axialflow) TI(1)(Multipoint12channel)(Temperature
Indicator)Vibration(2)
NRV(Dampedtopreventreverseflow)
ProgrammerandLogicSystem(1)
ShutdownSystem(1)
PI(4)(PressureIndicator)
COMPRESSORDRIVER FRC(1)(FlowRecordingController)
(Steamturbine) TI(4)(TemperatureIndicator)
ShutdownValve(1)
TRC(1)(TemperatureRecordingController)
TI(6)(TemperatureIndicator)
EXCHANGER PI(2)(PressureIndicator)
LG(1)(LevelGauge)
PSV(PressureSafetyValve)
FRC(4)(FlowRecordingController)
TRC(TemperatureRecordingController)
PIC(PressureIndicatingController)
FURNACES
FlameDetector(2)
LocalPanel
PI(12)(PressureIndicator)
LIST1)
DEVICESANDPROBABLENUMBEROF
EQUIPMENT
ITEMSFITTED
FURNACES(contd) TI(6)(TemperatureIndicator)
MultichannelTemperature(1)
O2Analyser(1)(OnlywhereBFWorsteamis
circulating)
pHAnalyser(1)
Conductivity
LG(3)(LevelGauge)
LIC(1)(LevelIndicatingController)
PSV(3)(PressureSafetyValve)
PCV(3)(PressureControlValve)
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 121/136
4/26/2017 PlantLayout|ABCEngineering
PCV(3)(PressureControlValve)
Inlineinstrumentelements:FlowElements(Orifice,Plates,Venturi,Turbine,P/D,etc.).ControlValves
(Globe,Butterfly,Ball,etc.).ReliefValves.Thermowells.LIST2)
LIST2)
Be Photo Locationofinstrumentandwindow.
Electrical/Colour
ANALYSER
Usuallywithbypasslinetodrainonback
DiverseMethods
toprocessonlyoccasionallyinline
An includingSGand
sometimescoaxialspoolpiece.Faceto
density
face/Flanges.
LEVEL
MEASUREMENT
An Capacitance SimilartotemperatureTe1.
Probe Conductivity Sometimescoaxialinspoolpiece.
PROXIMITY Feromagnetic) Nonintrusive
SWITCH Magnetic) Locationandmounting
a)Noninstrusive
Inductive)
b)Instrusive,typeTe1.
PRESSURE
BourdonTubes
Smalltapping/location/connections/size
DifferentialPressure CapsulesStrain
andtype
Gauge
LIST2)
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 123/136
4/26/2017 PlantLayout|ABCEngineering
GENERALNOTE:Instrusiveelementsand/orspooltypeinstallationmaycallforflowlinesizedueto
changeduetoforcesonwettedparts,erosion,noise,depositionofsolidsincavitiesorviscosity.
Categories:PlantLayoutTags:designguide,plantlayout
PlantLayoutDesignguidescheckingPlotPlansandPlantLayout
March15,2012qdzung8comments
Designguides,CheckingofPlotplansandPlantlayouts.
Tableofcontent
1.Purpose
2.CheckingofPlotplans
3.RecordingofChanges
4.References
5.Attachments
1.Purpose
Thisprocedure,bytheapplicationofchecklists,describesthesafeguardingofqualityaspectsof
engineeringworkinthedevelopmentofplotplansandplantlayouts.Itcoverstherequirementstoensure
thattheapplicablespecifieddesignbasis,regulatoryrequirements,codesandstandardsarecorrectly
translatedintheirdevelopmentwithintheEngineeringDepartment.
2.CheckingofPlotplans
Theplotplansandplantlayoutsshallbeverifiedasaminimumagainstfourlists,asfollows:
2.1ChecklistforAdministration
Allchangesontheplotplansshallberecordedproperlyontherevisionlistsandthemarkedupissues
filed.Attachment1containschecklistthatcoverstheadministrativeaspectsofplotplancontrol.
2.2SafetyChecklistsforPlotplans
Allquestionsofthesafetychecklistshallbeverifiedagainsttheplotplan,seeAttachment2.
2.3ChecklistforTechnicalContentofPlotplans
Allquestionsofthechecklistwillbeverifiedagainsttheplotplandrawing,seeAttachment3.
2.4EquipmentClearanceGuidelineGenerally,clientshavetheirguidelinesonclearancesbetween
equipmentandorlocalregulationsexist.Inabsenceofthisdata,thefiguresmentionedinAttachment4
shallbeusedasaguide.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 124/136
4/26/2017 PlantLayout|ABCEngineering
3.RecordingofChanges
Therecordingofchangesandthefilingoftheassociateddocumentsshallbeinaccordancewiththe
relevantsectionsofref.4.4,4.3and4.4.Thesefilesshallbemaintainedaspartoftheprojectfile.Toeach
documentaListofRevisionsshallbeattached(ref.4.7).
4.References
Document
Title Level
Number
CMMA
4.1 101
TheNumberingofDocuments 2
CMMA
4.2 102
DocumentIssueCodeandChangeIdentification 2
BNS
4.6 UK004
ChecklistDesignReviewTechnicalDisciplines(later) 5
BN
4.7 UE(I)10
ListofRevisions 4
5.Attachments
1.ChecklistforAdministration
2.SafetyChecklistforPlotplans
3.ChecklistforTechnicalContentofPlotplans
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 125/136
4/26/2017 PlantLayout|ABCEngineering
4.EquipmentClearanceGuideline
1.CHECKLISTFORADMINISTRATION
1.Wasalistingpreparedofregulationstobefollowed?
2.Doesalistoftheplotplansexist?
3.Isthislistkeptuptodatewithnumberofdrawingsandissues?
4.Doanyalternativelistsexist?
5.Whatisthetypeoflist(Manual,Printout)?
6.Whatisfrequencyofupdatingofplotplan?
7.Dolargedeviationsexistinupdatingperiodsofeachunit?
8.Wasclientapproval
obtainedformally?
properlyrecorded?
9.Doesamarketupmastercopyexist?Isitkeptuptodate/
10.Arechanges
recordedonrevisionlists?
arerevisionlistsorderlyfiled?
properlyreferencedtoplotplan
referencedtopotentialchangeorder?
11.Aretheserevisionlistsorderlyfiled?
12.Isoriginofchangeandimpactproperlyindicatedonrevisionlist?
13.Aremarketupmastercopiesproperlyfiledinnumericalorder?
14.Arerevisionsproperlyindicatedonplotplan?
15.Authorizedsignatures?(Refertorelevantprocedure,ref.4.3).Locationforcertifiedsignature.
2.SAFETYCHECKLISTFORPLOTPLANS
CHECKLISTQUERIES
1.IdentifyCodesofPractice,StatutoryLegislationorClientsrequirementsdetermining.
1.1Overallplantlayout,proximitytopublicaccess,parkingplacesatsafelocations.
1.2Minimumspacingbetweenadjacentplants,interrelatedplantsandonplotequipment.
1.3Spacingandbundingofstorageareasandunits.
1.4Minimumspacingbetweenbuildingsandhazardousareas.
1.5LocationanddesignofControlBuilding.
1.6Atmosphericconditions,e.g.winddirection.
1.7Soilconditionsandtopography.Highpoints,slopes.
2.Identifypotentialhazardsfromhighlyflammableortoxic,orcorrosivematerials.Dotheseaffectlayout
orimposerestrictions?Identifyrequirements.
2.1Highorlowtemperatures.
2.2Highorlowpressures.
2.3Chemicalreactions.
2.4Flammableexplosivesubstances.
2.5Riskofdustexplosions.
2.6Toxiccorrosivesubstances.
2.7Radiationemission.
2.8Startupsituations(coveredinprocedures?).
2.9Shutdownsituations(coveredinprocedures?).
3.IdentifyCodesdeterminingFlareLocation(ifincluded).
4.Identifyfirefightingandprotectionrequirementstogetherwithapplicablecodesandlaws/reviewwith
localspecialistsrequired?
4.1Firewater,foam,drypowderlocation.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 126/136
4/26/2017 PlantLayout|ABCEngineering
4.2Fireandgasdetection,locationofequipment.
4.3Locationofutilitystations.
4.4Fireprotectionofstructuresandequipment.
5.Identifymeansofaccessandegress.
5.1Overallroadaccessrequirements.
5.2Fireaccessrequirements.
5.3Meansofescapefromareasatgradeandbunds.
5.4Meansofescapefromelevatedareas.
5.5Havealternativemeansofaccessandegressbeendevelopedwhereverpracticable?
6.Establishsafelocationofventsanddrains.
6.1Atmosphericreliefvalvedischarges.
6.2Steamandgasvents/drains.
6.3Continuousprocessvents/drains.
7.Noiseprofiles.
8.Constructionaspects.
9.Samplingandanalyzerpoints.
10.Drainage/collectinginsewer.Accessibilityofsamplepoint.
11.Plantsecurity.
12.Checksuitabilityofsafetyshowerlocation.Verifythatwatersupplycannotfreeze.
13.Specialplantsituations,e.g.offshore.
14.HasProcessDepartmentidentifiedandlistedallequipmentandlinessubjecttolethalortoxicrulesor
requiringspecialattentionforsafetyreasons?Emergencyshowersandeyewashersforeseen?
15.HasProcessDepartmentidentifiedandlistedallequipmentandlinesinvolvedinextremedesign
conditions?
16.Rulesforguardingofmovingmachinery?
17.Anyhazardstothepublic.(Releaseoftoxicgasesorwastes,fire,explosionundermisoperation,
malfunction,equipmentfailure?).
18.Areallopenpits,flooropeningsetc.fencedorprovidedwithguardrails?
3.CHECKLISTFORTECHNICALCONTENTOFPLOTPLANS
GENERAL
Nearestgeodeticstartingpointnoted?
Arebatterylimitsindicated?Blockvalvesforeseen?
Areaccessroadssuitable?Headroomclearance?Whatrules?
Accessroadtodischargeandloadingpointswalkwaysegregatedfromroadtraffic?
Supplypointsforchemicals,catalysts?Accessroadsforhazardouschemicals?
Isplotbrokenupinunits?Flowpatternbetweenunits?
Locationofinterconnectingpiperacks?Roomforfutureextension?
Havelocationsoffutureequipmentbeenindicated?
Whatrulesforequipmentclearance(refertoguideline)?
Locationofmaintenanceshop/accessroadsormaintenanceandequipmentreplacement?
Closewatchequipmentdefinedandlisted?
NOTE:
FollowingitemshavebeenlistedinsequenceoftheCompanyCostCode.
A.TOWERS.
1.Wasgroupingofdistillationtowersforeseen?
2.Overheadcondensersandreboilersgroupedoncommonstructure?
3.Verifysectionaldrawingsforelevation.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 127/136
4/26/2017 PlantLayout|ABCEngineering
4.Lightningprotection?
B.BUILDINGS
1.Useofsafetyglass(forwindows)?
2.Firestopsinpipepassagesthroughconcretewalls?Idemforcables?
3.Buildingscodeswrittenandlisted?
4.Protectionoflunchheatingdevices?
5.Typeofheating/airconditioning?
6.Ventilationandairintakepoints?
7.Sanitaryfacilities/firstaidfacilities?
8.Lightningprotection?
9.Exitsidentified/integratedinemergencylighting
10.Orientationofbuildings/sunshadesforeseen?
C.PIPING
Emergencyshutdownandisolationblockvalvestobecheckedforalllinesandplantlimits.Verifyuseof
ROVandaccessibility.Useofotherisolatingdevices?
Wherearespectacleblindstobeforeseen?
Locationofanchors/pipesupportstobeadequateforallowablestressandnozzleload/
Lockingdeviceoncriticalvalves?
Insulationforpersonnelprotection?
Protectionagainststaticelectricity?
Vibrationbracingforeseen/installed?
Locationofisolationpushbuttons?
Expensivealloypipinglayoutforminimumlength?
Firestopsforpipingpassingthroughconcretefloorsandwalls?
SafetyRelievingDevices
Layoutofflareheader/slope
Atmosphericrelease(steametc.)awayfromplatform.
D.STRUCTURES
Useofconcreteorsteel/fireproofing?
Useoffiredecks?
Rulesforstackingofequipment?
Standardsforstairs,platforms,laddersandhandrailings?Grating?
Lightningprotection?
Norexposedtoprocessequipment?
Stairs,platforms,laddersforaccesstooperatingvalves?
Useofnonslipsurfacesonstairs,platforms,accessways.
E.ELECTRICAL
1.Hazardousarea
classification Identificationofsourceofhazards.
Identificationofsubstancesreleased.
Establishmentofriskzones.
Establishmentoftemperatureclassandgasgroups.
Selectionofcertifiedequipment.
Criticalequipment Powersupply(transformers,switchgear)locatedseparately
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 128/136
4/26/2017 PlantLayout|ABCEngineering
andprotected.Oilcontainmentdikesaroundtransformers.
2.Earthing Protectionagainstlightning
Dischargeofstaticelectricity.
Dispersaloffaultcurrents.
Limitingstepandtouchpotentialstosafelevels.
Protectionofearthingconductorsagainstcorrosion.
3.Cathodic
Protectionofburiedmetals.
protection
Interferencewithearthingsystem.
4.Fireprotection Firealarmcallpoints.
Firealarmbells/sirens.
Sprinkler/cloudsystems.
Fireresistanceofmaterials.
5.Area&road
Adequateillumination.
lighting
Lightscorrectlypositioned.
Avoidanceoftoomuchglareorreflection.
Adequateemergencylighting.
Possibilityofmaintenancelighting.
6.Cabling Compliancewithregulations.
Correctconductorsizing.
Adequateprotectionforcables.
7.Equipment Accessibility.
Easeofmaintenance
Emergencypower Isemergencygeneratorforeseen/locatedinsafearea?
Useofdieseldrives/turbines?
Powerconnections Distances.
Failureofelectricalcontrolstobeconsideredin
8.Controlfailure
design.Foreseefail/safeequipment
9.Switchgears Arelockoutfacilitiesforeseen?
F.FIREFIGHTING(seealsoK,item3)
Checksuitabilityoffirefightingequipment,locationofhydrantsandadequacyofwatersupply.
Checktoensurethatadequateaccessforfiretenderhasbeenprovidedtoallrelevantplantlocations.
Checkthatclearescaperoutesatgradehavebeenprovided.
Checkthatladdersandstairsarepositionedatgradeleadingtoclearescaperoutes.
Waterflooding/sprinklingforspheres.
Stairwaysmustbetheprimaryaccesstomainoperatingorserviceplatforms.
Auxiliaryexitsbyladderstobeprovided.
Nodeadendplatformtobelongerthan8meters.
Horizontalwalkingdistancetoprimaryorauxiliaryexitmustnotexceed25meters.
Checkonflametraprequirementsforventpipes.
Checkonventrequirementsforundergrounddrainagesystems.
Checkthatallventpipesandreliefvalvemanifoldsdischargingtoatmosphereareatleast3metersabove
anyplatformwithinaradiusof15meters.
Checkthatsuitableinterlockinghasbeencalledforatmultiplereliefvalveassemblies.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 129/136
4/26/2017 PlantLayout|ABCEngineering
Havesmokingregulationsbeendetermined?
DesignEngineeringSupervisorinconjunctionwithProcessandProjectshallchecksuitabilityofallrelief
systemarrangements.Particularattentionshallbegiventopossibilityofpockets/vaporlocksand
dischargerequirementsanduseand/orneedofclosedsystems.
Checklocationsofsniffersifprovidedontheplant.
Monitorsandhydrantsguardedagainstvehicledamage?
Reliabilityoffirewaterpumpincaseofpowerfailure.Auxiliarydrive.
G.GENERAL
Handlingdevicesrequiredforhandlingweightsover.kg.
Spaceformaterialstorage.
Haveweightandsizeofcontainersbeenconsidered/listed?Equipmentfoehandlingofcontainers,bins.
Loadingpiers:accessibilitytoemergencyshutoffvalves.
Communicationsbetweenshippingpumpandloadingpoint.
Flarewellsegregated?Areaprotectedagainstradiation.Extentofradiationzone.
Distancebetweenutilitystations.
Accessibilityofutilitystationsandcomposition.
H.HEATERS/BOILERS
Locatedinseparatearea.Wellsegregated.
Distancetoprocessunits:minimum15meterstohydrocarbonbearingequipment.
Sufficientinspectionopeningstoverifytheinternalsvisually.
Anchoringofinletandoutletlines.
Locatedupwindofoperatingunits.
Airintakelocations.
Remotelyoperated/accessibleshutdownvalvesonfuelsupplylines.
Whatincaseoftubeburst?
Accessforemergencyequipment?
Diversionwallsforeseen?
J.CIVIL
Haveundergroundservicesbeenmarked?
Markingalsoincaseofexcavation(warningstrips)?
Standardforroadways?
Considerriskofsettlementsoffoundations.
Areallopenpits,flooropeningsetc.fencedorprovidedwithguardrails?
K.CONTROLSYSTEMS
SpecificreferenceshallbemadetoChecklistDesignReviewTechnicalDisciplines,section9(ref.4.6)
andshallinclude:
1.Hazardousareas: Designphilosophy.
Selectionofcertifiedequipment.
Compliancewithareaclassificationdrawing
Installationtocodeandspecificcertificaterequirements
2.Earthing. Limitingtouchpotentialtosafelevels.
Protectionofearthingconductorsagainstcorrosion.
3.Fireprotection Firealarmbells/sirens.
Smoke/firedetection.(Instrumentequipment)
Shutdown,interlockandalarms.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 130/136
4/26/2017 PlantLayout|ABCEngineering
Fireresistanceofmaterials.
Operationalimplicationsofafire.
Firefightingsystem.(Instrumentequipment).
Highfireriskareas.
4.Fail/safedesign Shutdownsystems/emergencydepressurizingsystem.
Failsafefeaturesaffectingplantsafety.
Effectoffailureorlossofelectricity,andallutilities.
Burnermanagementsystems.
5.Safetyrelieving
Sizingcriteria.
devices
Safetyfactors.
Calculationsapproval.
6.Equipment
Maintenance
location
Accessibility
7.Cabling Compliancewithregulations.
Correctconductorsizing.
Adequateprotectionforcables
Segregations.
8.Electricalsupply
Correcttypeandsizingoffusesandcircuitbreakers.
system
Extentofequipmentofuninterruptablepowersupplysystem.
Alarms.
Overallpowerconsumption.
9.Airsupply Instrumentairconsumption.
Securityofsupply.
Operationalanddesignconditions.
Isanaudiblealarmincludedtowarnforreleaseofflammable
10.Alarming
vapors?Releaseoflethalgas.Firedheaterflamefailure.
M.VESSELS(TANKS)
Protectionincaseofleakage(bundwalls).
Lightningprotection.
Distancesbetweentanks/dikedareas.Whatrulestobefollowed?
Protectionagainststaticelectricity.
Specialrulesforcoldstoragedefined.
Accessibilityoftankgaugingdevice/suitableforpressureandtemperature.
Minimumflangedconnectionswithindikedareas.
Useofflowlimitingdevices.
Tankfarmsatlowerlevelthanprocessunits.
SitingoftanksingroupsconsiderAPIrules.
Icingprotectionforrefrigeratedstorageprotectionforspontaneouswarming.
Protectionofgasstoragetanksagainstsunradiation.
N.INSULATION
Resistanceofinsulationagainstfire.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 131/136
4/26/2017 PlantLayout|ABCEngineering
Personnelprotectioninsulationforeseen(verifyalongaccessroads).
Ifinsulationfoepersonnelprotectionisnotforeseen,protectbyopenguards,shields,railings.
P.PUMPS/COMPRESSORS
Locationseparatelyfornoiselimitation.Compressorsupwindfromfiredequipment.
Groupedunderpiperack(separaterows).Separatehighpressurepumps.
Possibilityofsprinklerinstallation/commonloops.
Accessibilityofrotatingequipmentforoperationandmaintenance(equipmentreplacement).
Allrotatingequipmentadequatelyguarded.
Noiseprotectioninrotatingequipment.Whatrulesimposed?
Airintakelocationforcompressors.
Whatisriskincaseofsealleakage?Whatprotectionforeseen?
Equipmentclearance/removalpossibilityofdefectiveequipment.
Installationofliftingequipment.
Lubricationpointsdefined.Accessibleforoperatingandmaintenancepersonnel?
Highpressurechargepumpstobeisolated.
Locationofsealoilunits.
Q.SEWERS
Checkareaclassificationforpitsandothercatchmentdevices.
Howissealingandventingofcatchbasinsdone?
Verifyremovalofreleasesanddripsfromunderequipment.
Consideruseofseparatesewerandtoxicsewer.Oilysewerrequired?
Pollutionrisk.Wastewatercollectionandtreatment.Locationofdischargepoint.
Specialprecautionsforhighlytoxichighlyflammableproducts.
T.EXCHANGERS
Accessibilityforcleaningrodding.
Spaceforbundlepullingdevice.
Locationofairfincoolers(nopumpsunderneath).
Arefiredecksforeseen?
4.EQUIPMENTCLEARANCEGUIDELINES
ITEMS
OverheadclearanceMeters
Equipment,structures,platforms,pipingandpipesupportsshallprovidethe
followingclearanceoverhead:
Railroads,topofrailtobottomofanyobstruction 7
Plantroadsformajormobileequipment 6
Secondaryroadsandaccesswaysformobileequipment 5
Gradesatpumprowaccesswayinsidebatterylimits 3
Walkways,passways,platformsandinsidebuildings
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 132/136
4/26/2017 PlantLayout|ABCEngineering
Exchangersatgrade,shellcoverchannelend 1.5
Horizontalclearances
Betweenexchangers(aislesbetweenpiping) 0.9
Aroundpumps(aislesbetweenpiping) 0.9
Firedheaterstopumpshandlingflammablestocks 15
Firedheaterstootherflammablecontainingequipmentnotclosely
8
associatedwithheaters
Driverendofpumpswheretruckaccessisrequired 3
Driverendofpumpswheretruckaccessisnotrequired 1.8
Shellcoverendofexchangersatgradeforaccess 1.3
Betweenshellsofadjacenthorizontalvessels 1.2
Pipeberths
Underground,minimumcleargapbetweenpipes(300mm) 0.3
Aboveground,normal,betweenflangesandbarepipeorsurface
0.025
ofinsulationandplugs(25mm)
Equipmentspacing
Smallpumps,3.75kWorsmaller,mountedoncommonfoundations,center
suitable
tocenterdistance
Mediumpumps,22.5kWorsmaller,clearaisle 0.9
Largepumps,largerthan22.5kW,clearaisle
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 133/136
4/26/2017 PlantLayout|ABCEngineering
0.9
Exchangersandotherequipmentonstructures,minimumclearaisle 0.9
Platforms
Vessels(verticalandhorizontal)andtowers
Sideplatformdistancebelowcenterlineofmanholeflange 0.91.05
Sideplatformwidthfrommanholecovertooutsideedgeofplatform 0.9
Sideplatformextensionbeyondcenterlineofmanhole 0.9
Headplatformdistancebelowundersideofflange 0.175
Headplatformwidthfromthreesidesofmanhole 0.75
Exchangers(horizontal)
Clearanceinfrontofchannelorbonnetflange 1.2
Exchangertubebundleremovalspace bundlelength
Minimumclearancefromedgeofflanges 0.3
Exchangers(vertical)
Distanceofplatformbelowtopflangeofchannelorbonnet 1.5
Furnaces
Widthofplatformatsidesofhorizontalandverticaltube
0.75
furnaces,minimum
Widthofplatformatendsofhorizontaltubefurnaces,minimum 1.0
Controlroom
Distanceofcontrolroomtoprocessequipment
25
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 134/136
4/26/2017 PlantLayout|ABCEngineering
SUGGESTEDSPACINGSFORLPGSTORAGE
Minimum
distances
Vessel From Between
capacity buildings vessels
imp. cubic
feet meters feet meters
gallons meters
upto100 upto0.45
101500 0.452.3 10 3 3 1
5012,000 2.39.1 25 7.5 3 1
over2,000 over9.1 50 15 5 1.5
Categories:PlantLayoutTags:designguide,plantlayout,plotplans
RSSfeed
RecentPosts
PDMSVIDEOTUTORIAL05.CreatePointsets
PDMSVIDEOTUTORIAL04.CreateComponentsp9
PDMSVIDEOTUTORIAL04.CreateComponentsp8
PDMSVIDEOTUTORIAL04.CreateComponentsp7
PDMSVIDEOTUTORIAL04.CreateComponentsp6
Search
columnCompressorsDESIGNBASISdesignguidedrumExchangersFiredHeatersgeneralinstrumentInternationalEngineeringStandards
NDT NonDestructiveTestingPDMSpipewaypipingplantlayoutplotplansPROCESSpumpsquestionquestionnaire
PipingQuestionnaire01
PlantLayoutReliefSystem
PDMSTrainningSampleProjectmodeleditor
PlantLayoutDesignguidescheckingPlotPlansandPlantLayout
PROCESSDESIGNBASISSULFURDEGASSINGSECTION
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 135/136
4/26/2017 PlantLayout|ABCEngineering
PDMSVIDEOTUTORIAL02.CreateCatalogue&Sections
Categories
Instrument
PDMSVideotutorial
PlantLayout
Uncategorized
Top
BlogatWordPress.com.
https://abcengineering.wordpress.com/category/plantlayout2/page/2/ 136/136