Beruflich Dokumente
Kultur Dokumente
In competitive power markets, the focus is on plant efficiency and cost control. This often means that developers
overlook devices that can reduce plant operation and maintenance costs as well as increase efficiency.
An overlooked asset
E nergy generation in todays market is
becoming more and more efficient,
with combined cycle power stations
on the rise with net efficiencies reaching
130
120
110
almost 60 per cent. While there is much 100
Throttle Control
focus on efficiency at full load, little or no 90
attention is paid to the impact of part-load
Power (%)
80
(cycling) operation on a plants efficiency.
This article tries to shed some light on the 70
design of the boiler feedwater system and 60 Power Savings Variable Speed
some common misconceptions or myths 50 Coupling
regarding the use of variable speed drives 40
for the high pressure boiler feed pumps. 30
20
Part-load vs base-load
10
Myth No. 1: Combined cycle power sta-
tions can be operated as base-load power 0
plants to best utilize the higher efficiencies 0 10 20 30 40 50 60 70 80 90 100 110
provided by this technology. Flow (%)
The idea of operating combined cycle Figure 1. Absorbed power of high-pressure boiler feed pumps (throttle vs. speed control)
power stations at base-load throughout
their service life is very appealing. In prac- mainly on the following factors: bined cycle plant in Singapore supports the
tice however, gas turbine powered stations Load pattern: The load pattern has a sig- above arguments fully. The study based
are much more suitable than e.g. coal-fired nificant impact on the potential savings in on exclusive base-load operation shows
plants to cover peak capacities. auxiliary energy as shown in Figure 1. a power saving of 180 kW per 50 per cent
Furthermore, there is no guarantee for Test point of heat recovery boiler: boiler feed pump. As a result an energy
base-load operation over the lifetime of 25 Depending on regulations, steam genera- saving of some 3 million kWh can be
years. Government regulations and PPAs tors have to withstand an excess steam achieved during one year. The theoretical
may change and electricity pool systems flow of up to 105 per cent, an excess feed- values have been verified and confirmed in
might be established obliging operators to water flow of up to 125 per cent and an real life operation. At 100 per cent MCR
bid for every kWh to sell. In times of reces- excess feedwater pressure of up to 110 per the pumps are running at 2580 r/min com-
sion, decreasing or stagnant electricity cent of design capacity. This leads to a pared to a design speed of 2877 r/min.
demand will ultimately result in excess design of a high-pressure boiler feed pump When related to the total plant output,
capacities installed thus forcing power
plants into part-load operation. If the plant has to go into part-load operation, the original
If after five or even ten years the plant has
to go into part-load operation, the original
design, i.e. as a base-load plant, may not be suitable for the more
design, i.e. as a base-load plant, may not be demanding requirements of a cycling plant
suitable for the more demanding require-
ments of a cycling plant. Assuming that no that largely exceeds the requirements of the plants net efficiency at full load can be
provisions were made to operate the high- the 100 per cent MCR (maximum contin- increased by 0.1 per cent compared to a
pressure boiler feed pumps at variable uous rating) operating point. In addition, design using fixed speed pumps. In view of
speed, the operator may face increasing contract guarantees from the boiler and the very moderate capital expenditure for
maintenance cost due to higher pressure the pump manufacturer further widen the the inclusion of variable speed couplings
levels and increased wear and tear. gap between design and nominal operating the cost for other efficiency enhancing
Frequent start-ups may cause problems conditions. The use of fixed speed pumps measures to achieve the same goal may be
with the minimum flow control valves inevitably results in high losses in the feed- far higher. The efficiency advantage
while the feedwater control valves have to water control valve even if the plant is remains throughout the plants lifetime
cope with higher differential pressures due exclusively operated at base-load. and can increase to as much as 0.5 per cent
to reduced plant output. Fixed pressure versus sliding pressure if the plant goes into cycling operation.
characteristic: If the boiler is operated in
Energy savings sliding pressure mode, the pressure differ- Operating experience
Myth No. 2: If combined cycle power sta- ence between pump characteristic and Myth No. 3: Additional installation of
tions are operated as base-load power boiler resistance line increases dramati- hydrodynamic variable speed couplings
plants the use of variable speed boiler feed cally towards lower flow rates and with it reduces reliability and increases mainte-
pumps has no economical advantage. the power losses of a fixed speed pump nance cost.
The potential of auxiliary energy savings compared to a variable speed pump. The operating experience of customers
in a combined cycle power station depends A study carried out for a 425 MW com- worldwide is in strong contrast to the
common opinion that an additional device Project cost control valves to balance any operational
will result in lower reliability or higher Myth No. 4: Hydrodynamic variable variation between two or three boilers.
maintenance cost of the overall system. To speed couplings increase the project cost The integrated oil system of the variable
understand the supposed contradiction, significantly. speed coupling can also supply lube oil to
one needs to look closer into the charac- The cost for hydrodynamic variable speed motor and pump bearings, whereas a sep-
teristic of a hydrodynamic coupling. couplings are not very high compared to the arate lube oil supply unit is needed in case
Contrary to a fixed gear box, the hydro- overall project cost. Typically, a coupling of fixed speed pumps.
dynamic variable speed coupling changes for a 500 MW combined cycle power sta-
the operating characteristic of the boiler tion costs some $50 000. At the contractors First choice
feed pump. Torque is transmitted by using side cost for modified foundations and Myth No. 5: Hydrodynamic variable speed
the kinetic energy of hydraulic oil flowing implementation into the control system has couplings are not cost-efficient.
from the primary wheel (pump impeller) to to be considered. Despite the tremendous development of
the secondary wheel (turbine). A mechani- On the other hand, some of the addi- frequency converters and improved filter
cally driven pump maintains the oil flow tional cost may be saved when designing systems to handle the harmonics feeding
needed to dissipate the hydraulic losses an optimized system making full use of the back into the mains, the demand for
while the moveable scoop tube adjusts the benefits of the latest design of hydrody- hydrodynamic variable speed drives has
oil level in the coupling according to the namic variable speed couplings. The con- not changed over the years. The absorbed
required output speed. A 4-20 mA signal ventional start-up and feedwater valves power of centrifugal machines decreases
from the control room is all that is needed
to control the speed. 160
The discharge pressure of a speed-con- 2 x 50%
140
trolled pump is lower than that of a fixed- 1 x 50%
speed pump. Thus the pump can be oper- Pump Characteristic Test Point
120
ated at its optimum operating point and
Pressure (bar)
2000
Motor Power (kW)
5000
considered a luxury. The concentration on
760 kW
1500
70% Flow
Throttle Control 1880 kW 4000 lowest capital expenditures for the power
Speed Control 1220 kW
Savings 2 x 380 = 760 kW
plant makes investors and contractors fail
3000 to notice a device which not only is able to
1000
increase the plants net efficiency by anoth-
2000
er 0.1-0.5 per cent, but also to protect
500 their capital investment by reducing main-
1000
tenance and wear and tear of the complete
0 0 feedwater system. When looking for alter-
0 10 20 30 40 50 60 70 80 90 100 110 120 130 natives at comparable price levels one will
Flow (%) easily find out that the hydrodynamic vari-
able speed coupling is an asset all too often
Figure 3. Load pattern and boiler feedwater pump power consumption
wrongly overlooked. PEi
Cr 598 e 08/ 2004 1.000 Pennwell Technial data and illustrations subject to change.