Beruflich Dokumente
Kultur Dokumente
Outline Specification
03/31/2017
SECTION 260573
1.1 SUMMARY
1. Arcing faults.
2. Simultaneous faults.
3. Explicit negative sequence.
4. Mutual coupling in zero sequence.
1.3 EXECUTION
A. Begin analysis at the service, extending down to the system overcurrent protective
devices as follows:
B. Study electrical distribution system from normal and alternate power sources.
E. Motor-starting study.
F. Field Adjusting: Adjust relay and protective device settings to the settings provided by
the coordination study.
SECTION 260574
PART 1 - products
1.1 SUMMARY
A. Computer-based, arc-flash study to determine the arc-flash hazard distance and the
incident energy to which personnel could be exposed during work on or near electrical
equipment.
B. Produce 3.5-by-5-inch labels for each work location included in the analysis.
1.3 EXECUTION
A. Calculate the arc-flash protection boundary and incident energy at locations in the
electrical distribution system where personnel could perform work on energized parts.
B. Include medium- and low-voltage equipment locations, except 240-V ac and 208-V ac
systems fed from transformers less than 125 kVA.
C. Specify safe working distances based on the calculated arc-flash boundary at incident
energy of 1.2 cal/sq.cm.
D. Base arc-flash calculations on actual overcurrent protective device clearing time. Cap
maximum clearing time at two seconds based on IEEE 1584, Section B.1.2.