dseGenset

dse6110/20
ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2

AUTO START & AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
CONTROL MODULES EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE6110 is an Auto Start Both modules offer electronic TEMPERATURE


Control Module and the DSE6120 (CAN) and non-electronic (magnetic BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
is an Auto Mains (Utility) Failure pick-up/alternator sensing) engine BS EN 60068-2-2
Control Module suitable for a wide versions and offer a number of Bb/Be Dry Heat +70 oC
variety of single gen-set flexible inputs, outputs and engine VIBRATION
applications. protections so the system can be BS EN 60068-2-6
easily adapted to suit a wide range Ten sweeps in each of three
major axes
Monitoring speed, frequency, of application demands. 5 Hz to 8 Hz @ +/-7.5 mm,
voltage, current, oil pressure, 8 Hz to 500 Hz @ 2 gn
coolant temperature and fuel level, The modules can be easily HUMIDITY
the modules will display warnings, configured using the DSE BS EN 60068-2-30
shutdown and engine status Configuration Suite PC software. Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
information on the back-lit LCD Selected front panel editing is also BS EN 60068-2-78
screen and illuminated LED. available. Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

6 4 3

USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE6110/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) DC OUTPUTS GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING ALTERNATOR OUTPUTS ENGINES OR
DSE6120 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
+ + W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N

ISSUE 2

DSEGenset

DSE6110/20
SPECIFICATION

DC SUPPLY
CONTINUOUS VOLTAGE RATING

AUTO START & AUTO MAINS FAILURE 8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


DSE6120 178 mA at 12 V, 95 mA at 24 V

MAXIMUM STANDBY CURRENT


88 mA at 12 V, 50 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V
DSE6110 MAINS (UTILITY) DSE6120 ONLY
VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
2 A DC at supply voltage

OUTPUT B (START)
2 A DC at supply voltage

AUXILIARY OUTPUTS C,D,E & F


2 A DC at supply voltage

GENERATOR
VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

KEY FEATURES Current Monitoring and protection Multiple engine parameters are MAGNETIC PICK UP
Back-lit text LCD display 3 Phase Mains (Utility) monitored simultaneously VOLTAGE RANGE
+/- 0.5 V to 70 V
Front panel editing monitoring (DSE6120 only) Module can be configured to
LED and LCD alarm indication Test button (DSE6120 only) suit individual applications FREQUENCY RANGE
Power Save mode Battery voltage monitoring Compatible with a wide range 10,000 Hz (max)
CAN and Magnetic Pick-up/Alt. Engine pre-heat of CAN engines DIMENSIONS
versions available (specify on Hours counter Tier 4 engine support OVERALL
ordering) Comprehensive shutdown or Uses DSE Configuration Suite 215 mm x 158 mm x 42 mm
8.5 x 6.2 x 1.6
PC and front panel warning on fault condition PC software for simplified
configuration configuration PANEL CUT-OUT
6 Digital inputs KEY BENEFITS IP65 rating (with optional 182 mm x 137 mm
7.2 x 5.4
3 Analogue inputs Automatically transfers between gasket) offers increased
6 Outputs (4 configurable on mains (utility) and generator resistance to water ingress MAXIMUM PANEL THICKNESS
Magnetic Pick-up/Alt., 6 power (DSE6120 only) Licence-free PC software 8 mm
0.3
configurable on CAN version) Hours counter provides accurate
Configurable timers and alarms information for monitoring and STORAGE TEMPERATURE RANGE
Alternative configuration maintenance periods -40 oC to +85 oC
Event Log (10) User-friendly set-up and button
Remote Start input layout
3 Phase generator monitoring

RELATED MATERIALS
TITLE PART NOS
DSE6110 Installation Instructions 053-059
DSE6120 Installation Instructions 053-060
DSE6100 Quick Start Guide 057-102
DSE6100 Operator Manual 057-095
DSE6100 Configuration Suite PC Manual 057-096

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708