BEAM
A beam is a structural member subject to bending.
(Flexural member)
Its function carrying gravity load in the direction
normal to its axis, which results in bending moment
and shear force.
Bending occurs in member when a component
of load is applied perpendicular to member axis, and
some distance from a support.
Most beams span between two or more fixed
points (support).
Three types of beams:-
Secondary Beam
- Beam that
supporting by
another beam at
the end
Types of beam
A B C
2m
1a
2m
4m 4m
L L
x
x
One-way Two-way
slab slab
kN/m
1
Floor thickness : 150 a
mm
2.5
m
2.5 m
Panel A-B/1-2
LY/LX = 5 / 2 = 2.5 >2
1
a :- one way slab
2.5
m
Panel B-C/1-1a
2
LY/LX = 5.5 / 2.5 = 2.2 >2
:- one way slab
2.0 5.5
m m
ANSWER
Concrete density : 24 kN/m3
Dead load characteristic: 1.0 kN/m (excluding the slab
self-weight)
Live load characteristic: 2.5 kN/m
Floor thickness : 150 mm
b - width
h d d depth
h high
b 0.45fcu
Fcc = 0.405fcuAcc
0.9 x
x
d z= (d-
As Fst = 0.87 fy As 0.9x/2)
a
0.87fy M
section stress force
Equation Where:
Ma = 0 f cu - Characteristic of concrete strength
Fcc (d-0.9x/2) M = 0 (30N/mm2)
Fcc = Fst f y - Characteristic of reinforcement
strength
0.9x F cc 125mm
0.9x
d
Fst Acc
Fcc
Fst
0.87fy
Steel tension
6m
BEAM DESIGN
6 mm
h = 300mm
b = 125mm
STEP 1 : Calculation of
Moment
Moment at centre (max)
gk = 2kN/m
=WL2/ 8
= 2 x 62 /8
= 9kNm 6 mm
9kNm
STEP 2 : Calculation of d
d = h - cover link rebar
= 300 25 10 12/2
= 259 mm
d= mm h = 300mm
b = 125mm
STEP 3 : Force Diagram
Fcc F cc
d = 259mm
z=(d-0.9x/2)
As
Fst
Fst
a
b = 125mm
Ma = 0
Fcc x ( d - 0.9x / 2) M = 0
0.45fcu x Acc x (d - 0.9x / 2) M = 0
STEP 3 : Force Diagram
0.405 x 30 x 125 x x ( 259 0.9x / 2 ) 9x106 = 0
1518.8x x (259 - 0.45x) 9 x 106 = 0
393369.2x - 683.46x2 - 9 x106 = 0
683.46x2 393369.2x + 9x106 = 0
x = -b + b2-4ac
2a
x = 551.7mm @ 23.9mm
Fcc = 0.405 x 30 x 23.9 x 125
= 36298N
= 36.3kN
Fcc= Fst
36298N = 0.87fy x As
As= 36298 / 0.87(460)
h = 300mm
= 90.70 mm 2
As = 90.70 mm2
So size rebar
A = j2= D2 / 4 = 90.70mm2 b = 125mm
A = 90.70 /2 = 45.35mm
D = 45.35 x 4 / D = 8mm
D = 7.6 mm for 2 bar
So size rebar for the beam is 8mm.
:. size rebar to be provided is 2 T 8
COLUMN
COLUMN
Vertical elements which are normally
loaded in compression.(compression member)
2 types :-
i) Strut small member in a framed structure
ii) Column larger member as a main support for a
beam in a building
Axial loaded compression members can fail in two principal
ways:
i) short fat member fail by crushing or splitting of the
material. ( strength criterion)
ii) long thin members fail by sideways buckling. (stiffness
criterion)
DESIGN COLUMN
Ultimate compressive load capacity,
N = sum of the strengths of both the concrete and steel
components.
Table 1
Diameters and areas of reinforcing bars
Bar dia.(mm) 6 8 10 12 16 20 25 32 40
C/s area (mm2) 28 50 79 113 201 314 491 804 1256
Design Column
A short reinforced concrete Design load = 1.4 Gk + 1.6 Qk
column is to support the = 1.4 (758) + 1.6 (630)
following axial loads : = 2069 KN
reinforcing bars.
FOUNDATION DESIGN