Sie sind auf Seite 1von 1

140

LTL Transformers (Pvt) Limited


154/11,Railway Station Road,Angulana,Moratuwa,Sri Lanka.
Telephone:+94 11 2605101-3 Telefax:+94 11 2607312
Email: transformer@ltl.lk

OIL IMMERSED TRANSFORMER


kVA 160 PHASES 3 FREQUENCY 50Hz

NATURE OF WINDING RATED VOLTAGES RATED CURRENT

PRIMARY 33000 V 2.8 A

SECONDARY 400 V 231 A

INSULATION LEVELS LI 170 , AC 70 / AC 3 IEC 60076:2000

TRANSFORMER OIL : UNINHIBITED, FREE OF PCB IEC 60296:2003

TEMPERATURE RISE: WINDING: 55 OIL: 50

IMPEDANCE VOLTAGE % EXCITATION CURRENT %

COOLING ONAN RATING CONTINUOUS

TAP POS. VOLTAGE


200

1 34650
2 33825
3 33000
4 32175
5 31350
6 30525
7 29700
B Y R
CONNECTION " Dyn11 "
b y r n
R
11

r
n y
b
B Y

TOTAL MASS kg OIL kg

SERIAL NO: YEAR OF MFG.

A subsidiary of Ceylon Electricity Board


A Licensee of ABB AS of Norway

MATERIAL : 1.0 mm TH.STAINLESS STEEL

LTL Transformers (Pvt) Limited


DETAIL OF RATING PLATE
02 TAP POSSITION CHANGED TO 7 EE2 22/01/11
160kVA 33kV/400V TRANSFORMERS
01 AS PER COMMENTS BY LTLP EE2 14/01/11
REV DESCRIPTION OF REVISION INITIALS DATE DESIGN SCALE N.T.S DRAWING NO DRW/CT1048B/23
DATE 11/01/11 DESIGN NO 1603340AUX
Note; APPROVED
All Dimensions are in Millimeters DRAWN Nadil REV. 02

Das könnte Ihnen auch gefallen