Beruflich Dokumente
Kultur Dokumente
Users Manual
Version 1.1
SENSAPHONE
1
WEB600 Users Manual
Every effort has been made to ensure that the information in this document is complete, accurate and up-
to-date. Sensaphone assumes no responsibility for the results of errors beyond its control. Sensaphone also
cannot guarantee that changes in equipment made by other manufacturers, and referred to in this manual,
will not affect the applicability of the information in this manual.
SENSAPHONE
901 Tryens Road
Aston, PA 19014
3
WEB600 Users Manual
1 YEAR LIMITED WARRANTY
THIS LIMITED WARRANTY CONTAINS SENSAPHONES STANDARD TERMS AND CONDITIONS. WHERE PERMITTED BY THE
APPLICABLE LAW, BY KEEPING YOUR SENSAPHONE PRODUCT BEYOND THIRTY (30) DAYS AFTER THE DATE OF DELIVERY, YOU
FULLY ACCEPT THE TERMS AND CONDITIONS SET FORTH IN THIS LIMITED WARRANTY.
IN ADDITION, WHERE PERMITTED BY THE APPLICABLE LAW, YOUR INSTALLATION AND/OR USE OF THE PRODUCT CONSTITUTES
FULL ACCEPTANCE OF THE TERMS AND CONDITIONS OF THIS LIMITED WARRANTY (HEREINAFTER REFERRED TO AS LIMITED
WARRANTY OR WARRANTY). IF YOU DO NOT AGREE TO THE TERMS AND CONDITIONS THIS WARRANTY, INCLUDING ANY
LIMITATIONS OF WARRANTY, INDEMNIFICATION TERMS OR LIMITATION OF LIABILITY, THEN YOU SHOULD NOT USE THE PRODUCT
AND SHOULD RETURN IT TO THE SELLER FOR A REFUND OF THE PURCHASE PRICE. THE LAW MAY VARY BY JURISDICTION AS TO
THE APPLICABILITY OF YOUR INSTALLATION OR USE ACTUALLY CONSTITUTING ACCEPTANCE OF THE TERMS AND CONDITIONS
HEREIN AND AS TO THE APPLICABILITY OF ANY LIMITATION OF WARRANTY, INDEMNIFICATION TERMS OR LIMITATIONS OF
LIABILITY.
1. WARRANTOR: IN THIS WARRANTY, WARRANTOR SHALL MEAN DEALER, DISTRIBUTOR, AND/OR MANUFACTURER.
2. ELEMENTS OF WARRANTY: THIS PRODUCT IS WARRANTED TO BE FREE FROM DEFECTS IN MATERIALS AND CRAFTSMANSHIP
WITH ONLY THE LIMITATIONS AND EXCLUSIONS SET OUT BELOW.
3. WARRANTY AND REMEDY: ONE-YEAR WARRANTY IN THE EVENT THAT THE PRODUCT DOES NOT CONFORM TO THIS
WARRANTY AT ANY TIME DURING THE TIME OF ONE YEAR FROM ORIGINAL PURCHASE, WARRANTOR WILL REPAIR THE DEFECT
AND RETURN IT TO YOU AT NO CHARGE.
THIS WARRANTY SHALL TERMINATE AND BE OF NO FURTHER EFFECT AT THE TIME THE PRODUCT IS: (1) DAMAGED BY
EXTRANEOUS CAUSE SUCH AS FIRE, WATER, LIGHTNING, ETC. OR NOT MAINTAINED AS REASONABLE AND NECESSARY; OR
(2) MODIFIED; OR (3) IMPROPERLY INSTALLED; OR (4) MISUSED; OR (5) REPAIRED OR SERVICED BY SOMEONE OTHER THAN
WARRANTORS AUTHORIZED PERSONNEL OR SOMEONE EXPRESSLY AUTHORIZED BY WARRANTORS TO MAKE SUCH SERVICE
OR REPAIRS; (6) USED IN A MANNER OR PURPOSE FOR WHICH THE PRODUCT WAS NOT INTENDED; OR (7) SOLD BY ORIGINAL
PURCHASER.
LIMITED WARRANTY, LIMITATION OF DAMAGES AND DISCLAIMER OF LIABILITY FOR DAMAGES: THE WARRANTORS OBLIGATION
UNDER THIS WARRANTY IS LIMITED TO REPAIR OR REPLACEMENT OF THE PRODUCT, AT THE WARRANTORS OPTION AS TO
REPAIR OR REPLACEMENT. IN NO EVENT SHALL WARRANTORS BE LIABLE OR RESPONSIBLE FOR PAYMENT OF ANY INCIDENTAL,
CONSEQUENTIAL, SPECIAL AND/OR PUNITIVE DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO ANY LABOR COSTS,
PRODUCT COSTS, LOST REVENUE, BUSINESS INTERRUPTION LOSSES, LOST PROFITS, LOSS OF BUSINESS, LOSS OF DATA OR
INFORMATION, OR FINANCIAL LOSS, FOR CLAIMS OF ANY NATURE, INCLUDING BUT NOT LIMITED TO CLAIMS IN CONTRACT,
BREACH OF WARRANTY OR TORT, AND WHETHER OR NOT CAUSED BY WARRANTORS NEGLIGENCE. IN THE EVENT THAT IT IS
DETERMINED IN ANY ADJUDICATION THAT THE LIMITED WARRANTIES OF REPAIR OR REPLACEMENT ARE INAPPLICABLE, THEN
THE PURCHASERS SOLE REMEDY SHALL BE PAYMENT TO THE PURCHASER OF THE ORIGINAL COST OF THE PRODUCT, AND IN
NO EVENT SHALL WARRANTORS BE LIABLE OR RESPONSIBLE FOR PAYMENT OF ANY INCIDENTAL, CONSEQUENTIAL, SPECIAL
AND/OR PUNITIVE DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO ANY LOST REVENUE, BUSINESS INTERRUPTION
LOSSES, LOST PROFITS, LOSS OF BUSINESS, LOSS OF DATA OR INFORMATION, OR FINANCIAL LOSS, FOR CLAIMS OF ANY NATURE,
INCLUDING BUT NOT LIMITED TO CLAIMS IN CONTRACT, BREACH OF WARRANTY OR TORT, AND WHETHER OR NOT CAUSED BY
WARRANTORS NEGLIGENCE.
WITHOUT WAIVING ANY PROVISION IN THIS LIMITED WARRANTY, IF A CIRCUMSTANCE ARISES WHERE WARRANTORS ARE FOUND
TO BE LIABLE FOR ANY LOSS OR DAMAGE ARISING OUT OF MISTAKES, NEGLIGENCE, OMISSIONS, INTERRUPTIONS, DELAYS,
ERRORS OR DEFECTS IN WARRANTORS PRODUCTS OR SERVICES, SUCH LIABILITY SHALL NOT EXCEED THE TOTAL AMOUNT PAID
BY THE CUSTOMER FOR WARRANTORS PRODUCT AND SERVICES OR $250.00, WHICHEVER IS GREATER. YOU HEREBY RELEASE
WARRANTORS FROM ANY AND ALL OBLIGATIONS, LIABILITIES AND CLAIMS IN EXCESS OF THIS LIMITATION.
INDEMNIFICATION AND COVENANT NOT TO SUE: YOU WILL INDEMNIFY, DEFEND AND HOLD HARMLESS WARRANTORS, THEIR
OWNERS, DIRECTORS, OFFICERS, EMPLOYEES, AGENTS, SUPPLIERS OR AFFILIATED COMPANIES, AGAINST ANY AND ALL CLAIMS,
DEMANDS OR ACTIONS BASED UPON ANY LOSSES, LIABILITIES, DAMAGES OR COSTS, INCLUDING BUT NOT LIMITED TO DAMAGES
THAT ARE DIRECT OR INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL, AND INCLUDING ATTORNEYS FEES AND LEGAL
COSTS, THAT MAY RESULT FROM THE INSTALLATION, OPERATION, USE OF, OR INABILITY TO USE WARRANTORS PRODUCTS AND
SERVICES, OR FROM THE FAILURE OF THE WARRANTORS SYSTEM TO REPORT A GIVEN EVENT OR CONDITION, WHETHER OR NOT
CAUSED BY WARRANTORS NEGLIGENCE.
YOU AGREE TO RELEASE, WAIVE, DISCHARGE AND COVENANT NOT TO SUE WARRANTORS, THEIR OWNERS, DIRECTORS, OFFICERS,
EMPLOYEES, AGENTS, SUPPLIERS OR AFFILIATED COMPANIES, FOR ANY AND ALL LIABILITIES POTENTIALLY ARISING FROM
ANY CLAIM, DEMAND OR ACTION BASED UPON ANY LOSSES, LIABILITIES, DAMAGES OR COSTS, INCLUDING BUT NOT LIMITED
TO DAMAGES THAT ARE DIRECT OR INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL, AND INCLUDING ATTORNEYS FEES
AND LEGAL COSTS, THAT MAY RESULT FROM THE INSTALLATION, OPERATION, USE OF, OR INABILITY TO USE WARRANTORS
PRODUCTS AND SERVICES, OR FROM THE FAILURE OF THE WARRANTORS SYSTEM TO REPORT A GIVEN EVENT OR CONDITION,
WHETHER OR NOT CAUSED BY WARRANTORS NEGLIGENCE, EXCEPT AS NECESSARY TO ENFORCE THE EXPRESS TERMS OF THIS
LIMITED WARRANTY.
EXCLUSIVE WARRANTY: THE LIMITED WARRANTY OR WARRANTIES DESCRIBED HEREIN CONSTITUTE THE SOLE WARRANTY
OR WARRANTIES TO THE PURCHASER. ALL IMPLIED WARRANTIES ARE EXPRESSLY DISCLAIMED, INCLUDING: THE WARRANTY
OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR USE AND THE WARRANTY OF FITNESS FOR A
4
PARTICULAR PURPOSE AND THE WARRANTY OF NON-INFRINGEMENT AND/OR ANY WARRANTY ARISING FROM A COURSE OF
DEALING, USAGE, OR TRADE PRACTICE.
IT MUST BE CLEAR THAT THE WARRANTORS ARE NOT INSURING YOUR PREMISES OR BUSINESS OR GUARANTEEING THAT THERE
WILL NOT BE DAMAGE TO YOUR PERSON OR PROPERTY OR BUSINESS IF YOU USE THIS PRODUCT. YOU SHOULD MAINTAIN
INSURANCE COVERAGE SUFFICIENT TO PROVIDE COMPENSATION FOR ANY LOSS, DAMAGE, OR EXPENSE THAT MAY ARISE IN
CONNECTION WITH THE USE OF PRODUCTS OR SERVICES, EVEN IF CAUSED BY WARRANTORS NEGLIGENCE. THE WARRANTORS
ASSUME NO LIABILITY FOR INSTALLATION OF THE PRODUCT AND/OR INTERRUPTIONS OF THE SERVICE DUE TO STRIKES, RIOTS,
FLOODS, FIRE, AND/OR ANY CAUSE BEYOND SELLERS CONTROL, FURTHER SUBJECT TO THE LIMITATIONS EXPRESSED IN ANY
LICENSE AGREEMENT OR OTHER AGREEMENT PROVIDED BY WARRANTORS TO PURCHASER.
THE AGREEMENT BETWEEN THE WARRANTORS AND THE PURCHASER, INCLUDING BUT NOT LIMITED TO THE TERMS AND
CONDITIONS HEREIN SHALL NOT BE GOVERNED BY THE CONVENTION FOR THE INTERNATIONAL SALE OF GOODS. WHERE
APPLICABLE, THE UNIFORM COMMERCIAL CODE AS ADOPTED BY THE STATE OF DELAWARE SHALL APPLY.
4. PROCEDURE FOR OBTAINING PERFORMANCE OF WARRANTY: IN THE EVENT THAT THE PRODUCT DOES NOT CONFORM
TO THIS WARRANTY, THE PRODUCT SHOULD BE SHIPPED OR DELIVERED FREIGHT PREPAID TO A WARRANTOR WITH EVIDENCE OF
ORIGINAL PURCHASE.
5. LEGAL REMEDIES AND DISCLAIMER: SOME JURISDICTIONS MAY NOT ALLOW, OR MAY PLACE LIMITS UPON, THE
EXCLUSION AND/OR LIMITATION OF IMPLIED WARRANTIES, INCIDENTAL DAMAGES AND/OR CONSEQUENTIAL DAMAGES
FOR SOME TYPES OF GOODS OR PRODUCTS SOLD TO CONSUMERS AND/OR THE USE OF INDEMNIFICATION TERMS. THUS, THE
EXCLUSIONS, INDEMNIFICATION TERMS AND LIMITATIONS SET OUT ABOVE MAY NOT APPLY, OR MAY BE LIMITED IN THEIR
APPLICATION, TO YOU. IF THE IMPLIED WARRANTIES CAN NOT BE EXCLUDED, AND THE APPLICABLE LAW PERMITS LIMITING
THE DURATION OF IMPLIED WARRANTIES, THEN THE IMPLIED WARRANTIES HEREIN ARE TO BE LIMITED TO THE SAME DURATION
AS THE APPLICABLE WRITTEN WARRANTY OR WARRANTIES HEREIN. THE WARRANTY OR WARRANTIES HEREIN MAY GIVE
YOU SPECIFIC LEGAL RIGHTS THAT WILL DEPEND UPON THE APPLICABLE LAW. YOU MAY ALSO HAVE OTHER LEGAL RIGHTS
DEPENDING UPON THE LAW IN YOUR JURISDICTION.
6. CHOICE OF FORUM AND CHOICE OF LAW: IN THE EVENT THAT A DISPUTE ARISES OUT OF OR IN CONNECTION WITH THIS
LIMITED WARRANTY, THEN ANY CLAIMS OR SUITS OF ANY KIND CONCERNING SUCH DISPUTES SHALL ONLY AND EXCLUSIVELY
BE BROUGHT IN EITHER THE COURT OF COMMON PLEAS OF DELAWARE COUNTY, PENNSYLVANIA OR THE UNITED STATES
DISTRICT COURT FOR THE EASTERN DISTRICT OF PENNSYLVANIA.
REGARDLESS OF THE PLACE OF CONTRACTING OR PERFORMANCE, THIS LIMITED WARRANTY AND ALL QUESTIONS RELATING TO
ITS VALIDITY, INTERPRETATION, PERFORMANCE AND ENFORCEMENT SHALL BE GOVERNED BY AND CONSTRUED IN ACCORDANCE
WITH THE LAWS OF THE STATE OF DELAWARE, WITHOUT REGARD TO THE PRINCIPLES OF CONFLICTS OF LAW.
Aston, PA 19014
Phone: 610.558.2700 Fax: 610.558.0222
www.sensaphone.com
5
WEB600 Users Manual
6
Table of Contents
Table of Contents
Chapter 1: Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
INSTALLATION and CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
RJ-45 10/100BASE-T Ethernet Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sensor Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
power On LED (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Alarm LED (red). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Parts Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wall Mount Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tabletop Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connecting Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
General Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Normally open / normally closed dry contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8K/10k Temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
420mA Current Loop Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Battery Backup (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Network Parameter Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Installing the Sensaphone Locator Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Using the Sensaphone Locator Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Resetting the WEB600 to Factory Default Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7
WEB600 Users Manual
Chapter 5: History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Event Log Query . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Datalog Query. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 6: Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Alarm Processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Return-to-Normal Alarm Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Network Service Disruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Appendix D: Specifications. . . . . . . . . . . . . . . . . . . . . . . 45
Alert Zones. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Data logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Physical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Appendix E: Thermistors . . . . . . . . . . . . . . . . . . . . . . . . 47
2.8K Thermistor Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
10K Thermistor Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8
Chapter 1: Installation
Chapter 1: Installation
Introduction
Congratulations on your purchase of the Sensaphone Web600 Monitoring System. The system is designed to
be an easy, costeffective, networkbased monitoring system to notify you when equipment or conditions go
awry. The internet browserbased programming makes the device easy to use from any computer on your
network. Monitored conditions can include temperature, humidity levels, line voltage, leak detection, UPS
systems, and more. The system allows multiple users to be notified immediately of any detected problems.
Notification can occur via email, SMS (text message) or SNMP trap. An optional battery backup system
(FGD-W610) insures that the unit will continue to run if main power fails.
Features
The Web600 includes the following key features:
n Six sensor inputs to monitor environmental conditions and/or alarm contacts from other computer
equipment such as UPS systems.
n 10/100BASE-T Ethernet port.
n Optional battery backup for uninterrupted performance.
n Compact design allows wall-mount or tabletop installation.
n Embedded web page to program and manage your Web600 system.
n Notification via email, SMS (text message) or SNMP trap.
Technical Support
If any questions arise upon installation or operation of the Web600, please contact the Sensaphone
Technical Service Department at 610.558.2700 and have the following information available:
Date of purchase __________________
Serial number __________________
Technical support is available from 8:00 AM to 5:00 PM, M-F, eastern time.
9
WEB600 Users Manual
Layout
The Web600 has connections for six sensor inputs, an ethernet port, battery backup, and 5VDC power.
See figure below:
1) 5V DC Power Jack
2) Battery Backup Connector
3) Ethernet Jack
4) Sensor Input Terminal Strip
5) Status LEDs
Sensor Inputs
The sensor inputs labeled zones 1-6 are designed to interface with normally open/normally closed devic-
es, 2.8K or 10K temperature sensors and 4-20mA transducers.
10
Chapter 1: Installation
Installation
This section provides information on:
Operating environment
Installation
Connecting sensors/Battery backup module
Network Configuration
Parts Required
Phillips Screwdriver
Cat 5 Patch Cable
Network Hub, Switch, or Router that supports 10 or 100 BASE-T
Computer w/Network Connection
Operating Environment
Before you install the Web600 be sure that your operating environment meets the physical requirements
of the equipment.
Operating Temperature: 32122 Fahrenheit (050 C)
Humidity: 590 %RH, non-condensing
Power: 115VAC 60 Hz outlet within 6
Tabletop Installation
The Web600 can be installed on a tabletop or shelf. Follow the steps below:
1) Attach the four self-adhesive rubber feet to the four corners on the bottom of the Web600.
2) Place the unit on a tabletop or shelf.
3) Attach sensors to the input terminals.
4) Plug the power adaptor into a 115VAC 60Hz outlet.
5) Connect a CAT5 cable to the Ethernet port and connect to a 10/100 network hub, switch or router.
11
WEB600 Users Manual
Connecting Sensors
The Web600 is compatible with a wide variety of sensors including normally open/normally closed con-
tacts, 2.8K and 10K temperature sensors, and 420mA current sources. Contact Sensaphone or your
Sensaphone reseller for assistance in selecting sensors for your monitoring requirements. A list of sen-
sors and accessories is shown in Appendix C. Follow the instructions below to properly wire and config-
ure the inputs for each type of electrical signal.
Warning: The inputs are designed to work with low voltage signals. DO NOT connect
voltages greater than 5V to the inputs. DO NOT connect 120VAC to the inputs.
12
Chapter 1: Installation
Normally open / normally closed dry contacts
Dry contact sources consist of alarm relays or switches that are isolated and have no external volt-
age applied. These devices can be connected directly to the zone terminals without regard for polarity.
Choose a zone and connect the wires to the corresponding screw terminals for that zone. The following
figure shows how to connect a dry contact sensor:
13
WEB600 Users Manual
420mA Current Loop Transducers
The inputs on the Web600 are compatible with transducers that produce an analog output current of 4
to 20mA. Such transducers are available to measure tank and well levels, extreme temperatures, air pres-
sure, water pressure, flow, voltage, current, rotational speed, etc. Contact our technical support depart-
ment for assistance regarding your monitoring requirements. Follow the wiring diagrams below for
connecting a 420mA device:
External
24V
Power
4-20 mA
Supply
FGD-0053 Transducer
14
Chapter 1: Installation
Network Configuration
The Web600 is designed for installation on an Ethernet network. This involves assigning it an IP
address. By default the Web600 will try to acquire an IP address automatically using DHCP. If it is suc-
cessful you can then use the Sensaphone Locator program to find the Web600 on your network and then
assign it a fixed IP address. The network configurations page can be found on the Network tab within
the Setup page. If no DHCP server is found the unit will fallback to a fixed IP address of 192.168.1.250.
Follow the instructions below depending on which scenario applies to your network:
Automatic Network Configuration Using DHCP:
If your network supports DHCP then simply plug the network jack into the Web600s Ethernet port and
turn it on. Allow the unit to finish booting up (1-2 minutes). Next, install the Sensaphone Locator pro-
gram on the included CDROM (or download it from www.sensaphone.com ). After installation, run the
Sensaphone Locator program and click the Search button. A list of detected Web600s will be displayed
showing their IP address and MAC address (Web600 serial number). Click on the Web600 in the list and
then click Connect and your browser will open to the WEB600 homepage. Click Setup, then Network to
view the Network Configuration page.
Configuration page
15
WEB600 Users Manual
After navigating to the network configuration page, you should now be able to access the network con-
figurations of your Web600, and set them accordingly.
NOTE: It is highly recommended that you consult all network configurations and settings changes with
your Network Administrator.
2) Using a network hub connect only your PC and the Web600 to the hub. Change the IP of your net-
work connection to something in 192.168.1.xxx that is not the same as the default IP of the Web600.
After navigating to the network configuration page, you should now be able to access the network con-
figurations of your Web600 and set them accordingly.
NOTE: It is highly recommended that you consult all network configurations and settings changes with
your Network Administrator.
3) Using a network router that is configured for DHCP server connect both your Web600 and your
computer to the router. Power cycle your Web600. Configure your computers network connection for
using DHCP. Once the Web600 has rebooted it should have acquired an IP from the routers DHCP
server. Log into your router and see what IP the router gave to the Web600. After navigating to the net-
work configuration page, you should now be able to access the network configurations of your Web600
and set them accordingly.
NOTE: It is highly recommended that you consult all network configurations and settings changes with
your Network Administrator.
Once you have access to the Network Configuration page change the DHCP Status to Disabled and enter
a permanent fixed IP address. Enter the other network settings also. Consult with your network admin-
istrator if your unsure of the proper settings. Click Save when done.
16
Chapter 1: Installation
Web Page Port Number: Allows selection of the port number that the webserver will use to host the
web page. Default is 80. If changed from the default you must include the port number in your browser
address (example: 192.168.1.250:85)
You will want to leave the Locator executable checked. To prevent the creation of a Start Menu or
Desktop shortcut, simply uncheck the box next to the option.
When you are satisfied with the installation options, press the Next button.
You are now presented with the following dialog:
This dialog allows you to specify the location where the executable will be installed. When you are satis-
fied with this value, press the Install button.
The installation will be performed and a progress bar will be displayed to inform you of the applications
progress. When the installation has been completed, you will see the following:
Press the OK button to continue. Then click Close. The Sensaphone Locator application is now installed.
17
WEB600 Users Manual
Using the Sensaphone Locator Software
Run the Sensaphone Locator application by double-clicking the Sensaphone Locator icon on your desk-
top, or selecting Start -> Programs -> Sensaphone Locator -> Sensaphone Locator. The Sensaphone
Locator application will display a screen similar to the one below:
Pressing the Search button will rescan your network for any Sensaphone devices that may be connected.
Your specific device can be identified by using the MAC Address field of the Sensaphone Locator, which
will be identical to your serial number. Click on your device within the Sensaphone Locator application
and click the Connect button. Your web browser will launch, taking you to the Web600s homepage.
Your Web 600 is now ready for use. Be sure to read the Network Configuration section of the manual
for further configuration options - such as configuring a static IP address.
18
Chapter 2: System Configuration
Summary Screen
Setup Menu
The Setup screen provides access to several menus dealing with the configuration of the device. They are
divided into the following areas: System, SMTP, SNMP, Modbus, Network & Administration. A descrip-
tion of each area and the associated programming parameters are described below.
System
The System settings are used to describe and configure general properties of the system. The informa-
tion entered into the Unit Name, Description, and Location fields will appear at the top of the webpage
and on e-mail alarm messages. The Unit Name will appear on SMS text messages. Use these to help
identify the facility and/or location so that when alarms occur youll know exactly where the trouble
occurred.
This screen also provides an entry for a Time Server. This can be used to periodically synchronize the
system clock to keep it accurate. Simply enter the address of a time server in this field and the WEB600
will automatically synchronize to it on a periodic basis. You can enter a host name or IP address in this
field. The system supports TP (Time Protocol on port 37). To set the time, click the Change System
Time box and enter the date and time, then click Save.
The Escalation Delay provides the ability to delay alarm delivery to selected users that may only be
interested in receiving alarms if they persist for a particular length of time. Each user can have a pro-
grammable Escalation Priority from 1 to 8. When an alarm occurs the WEB600 will deliver alarm
19
WEB600 Users Manual
messages to all users at priority level 1. Then it will wait the duration of the Escalation Delay and send
messages to priority level 2, as long as the alarm still exists, and so on with priority 3, 4, 5,. If the
alarm no longer exists, those users who have higher escalation levels will not be contacted.
The Summary Mode lets you choose the way in which the bar graph on the summary page appears.
There are two modes of operation: Arrow Mode and Bar Mode. The Arrow Mode displays an arrow next
to the bar graph which corresponds to the current value. White lines are used to mark the minimum
and maximum levels. The normal range will be displayed with a green background, alarm ranges will be
displayed in red. The Bar Mode differs in that the value is indicated by the top of the colored bar. The
bar will be green if the value is in the normal range. It will turn yellow if the value gets within 10% of the
alarm limits and it will turn red when the value is beyond the alarm limits. The range of the bar gauge
can be configured in the Zone programming screen.
Network
The Network Settings page allows you to view and configure all parameters associated with accessing the
device via the Ethernet port. (see Network Configuration in chapter 1 for details). This screen also dis-
plays the device MAC address and lets you configure the web page port number. Note that if you change
the port number to anything other than 80 (default) you will be required to enter the port number as
part of the device address in your browser (e.g xxx.xxx.xxx.xxx:### where xs represent the ip address
and #s represent the port number).
20
Chapter 2: System Configuration
SMTP
The SMTP (Simple Mail Transfer Protocol) section is where you must configure your e-mail server set-
tings. To have the unit send e-mail or SMS Text messages, you need to set the SMTP Server name and
the Return e-mail Address. If your SMTP server requires authentication then check the Security Enabled
box box and fill-in the Username and Password (if required). The WEB600 also allows you to change
the SMTP port number (25 is the default) in the event that your internet service provider is using a non-
standard port.
SNTP screen
SNMP
The WEB600 contains an SNMP (Simple Network Management Protocol) feature that allows the device
to be accessed from third party network management software. The unit supports versions v1 and v2c of
the protocol, over both UDP and TCP transports. Read and write access to most of the WEB600 param-
eters is provided along with the ability to send traps when alarms occur. A complete SNMPv1 MIB is
provided on the WEB600 CD.
SNMP screen
21
WEB600 Users Manual
Modbus
The WEB600 can be accessed via ModbusTCP protocol and function as a slave device. To use this fea-
ture select the desired Modbus Mode, Port number, and Bit Representation for your Modbus network.
Modbus screen
Admin
The Administration screen provides options to Save and Load your programming, update your WEB600
with new firmware and Reset to factory defaults. You can also choose to enable security for your
WEB600. A System Administrator password must be created before any of your User Profile logins will
become active. To create a System Administrator password check the Change Password box and enter a
password. The username for the Administrator account is admin. To delete the administrator account
(and disable user logins) simply delete the admin password and click Save.
The Programming Save function will create a file that includes all programming except the Network
settings and the Administration Password. Likewise when a file is loaded, the Network settings and the
Administration password will be preserved. Note that Uploading a programming file will erase the con-
tents of the Eventlog and Datalog.
Admin Screen
22
Chapter 3: Zone Programming
Zones page
The Zone Programming page displays a link for each of the six Zones, as well as a link for Battery and
Power monitoring. Note that the battery back-up option (FGD-W610) is required for power monitoring.
A description of each parameter is described below.
Enable/Disable: This setting determines if the Zone is being used (Enabled) or not (Disabled). Selecting
Disabled will remove the gauge from the Summary screen.
Name: Enter a name for the sensor you are monitoring which describes its purpose and/or location. The
name will appear on the Summary screen as well as on alarm messages.
Type: Choose the type of sensor you are connecting to the Zone input. For temperature sensors choose
either degrees F or C.
23
WEB600 Users Manual
Units: The units field is only used when the Zone Type is 4-20mA. Enter a description which corre-
sponds to the property youre monitoring (e.g. %RH, PSI, GPM, RPM,)
Calibration: This field can be used to offset the Zone value either positive or negative if there is some
error in the reading.
Recognition Time: This is the length of time that an alarm condition must be present before a valid
alarm exists and message delivery is started.
Table Low: The Table Low value is used to define the lower range (4mA) of your 4-20mA sensor.
Table High: The Table High value is used to define the upper range (20mA) of your 4-20mA sensor.
Alarm Delivery Enable/Disable: When Enabled, alarm messages will be delivered, if set to Disabled
alarm messages will not be delivered.
Alarm Low: This is used to determine the low level at which a temperature or 420mA Zone has
reached the alarm threshold. The value must fall below the Alarm Limit to trip an alarm.
Alarm High: This is used to determine the high level at which a temperature or 420mA Zone has
reached the alarm threshold. The value must exceed the Alarm Limit to trip an alarm.
Alarm Reset Enable/Disable: This setting enables or disables the Alarm Reset Feature. The Alarm Reset
feature is used to re-send alarm messages in the event that a fault condition is not corrected in a timely
fashion. If an alarm continues to exist for the duration of the programmed Reset Time (see below) the
alarm will reset (reactivate) and the alarm message delivery process will begin all over again. This is an
optional feature.
Alarm Reset Time: This is the time allowed for an alarms fault condition to be corrected before the
WEB600 resets (reactivates) the alarm and begins the message delivery process all over again. It is rec-
ommended that this be set to no lower than 30 minutes to prevent numerous messages from being sent.
Return to Normal Enable/Disable: This feature instructs the WEB600 to send a message when a zone
input has changed from an alarm condition back to a normal condition. Anyone who received the origi-
nal alarm message will also be sent the Return-to-Normal message.
Gauge Mode: The gauge mode has 2 settings: Auto and Manual. When set in the Auto mode the top
and bottom scale for the bar gauge on the Summary screen will be automatically computed based on the
minimum and maximum values. When set to Manual mode you can configure the scale yourself using
the Gauge Low and Gauge High settings below.
Gauge Low: This value sets the low scale on the bar gauge when configured for Manual mode.
Gauge High: This value sets the high scale on the bar gauge when configured for Manual mode.
Alarm Delivery Schedule: This weekly schedule sets the time period(s) when alarm delivery will be
active for the selected zone. The schedule is divided into half-hour increments over the seven weekdays.
A check mark indicates that alarm delivery is active for that time period.
Zone schedule
24
Chapter 3: Zone Programming
Datalogging Mode: The WEB600 has two modes of data logging for each zone: Continuous or While In
Alarm. In Continuous mode the unit will log the value of the input on a fixed time interval all the time.
The Normal Interval sets the logging rate while the value is within the normal range. The Alarm Interval
sets the logging rate while the value is an alarm condition. By choosing the While In Alarm mode you
can choose to have the unit only log values when it exceeds the alarm limits. This option minimizes the
amount of data collected and maximizes the storage capacity inside the WEB600.
Normal Datalog Interval: This is the interval that data will be logged while the input is within the pro-
grammed alarm limits. To maximize the available memory for datalogging, set the Datalog Interval for
each zone to multiples of each other. For example, Zone 1 can be set to 30 seconds, Zone 2 to 1 minute,
Zone 3 to 5 minutes, etc
Alarm Datalog Interval: This is the interval that data will be logged while the input is beyond the pro-
grammed alarm limits. (Note: this is regardless of the programmed Alarm Recognition Time).
25
WEB600 Users Manual
26
Chapter 4: User Programming
The WEB600 allows you to have up to 8 Users. Each User can have up to 4 contact (e-mail, SMS-
Text Message, or SNMP trap). You can choose to have a secure system with separate Usernames and
Passwords for each user, or you can choose to make the device accessible with no security (e.g. no login
required). Note that to have a secure system using Usernames & Passwords you must first create an
Admin password on the Admin Setup screen. Click on the Edit button next to each user to configure
their settings.
A description of each parameter is described below.
Enable/Disable: An Enabled User can login to the system and alarm messages will be delivered. A
Disabled User cannot login and no alarm messages will be delivered. This feature is useful to temporar-
ily suspend access or alarm delivery without deleting all of the Users programming.
Name: Enter the Users name in this field.
Username: Enter a Username for login purposes (optional)
Password: Enter a Password for login purposes (optional)
Access Level: If you are configuring a secure system then you must assign the User either Read Only
access or Read/Write access. Read Only access means that this user can only view the Summary page
and query the History logs. Read/Write access gives the user full programming privileges to the system
except for the Network and Admin screens.
Escalation Priority: This can be set to any number between 1 and 8. Users set to escalation level 1 will
immediately receive alarm messages. Those set to higher escalation levels will have their alarm messages
delayed by the time entered for the Escalation Delay on the System Setup screen. If the alarm condition
resets or corrects itself before the Escalation delay expires then no message(s) will be sent to those users
with a higher escalation setting. This feature is useful for staggering alarm message delivery based on the
duration of the alarm condition.
27
WEB600 Users Manual
Alarm Delivery Schedule: This weekly schedule sets the time period(s) when alarm delivery will be
active for the selected User. The schedule is divided into half-hour increments over the seven weekdays.
A check mark indicates that alarm delivery is active for that time period.
Pic of Schedule
Contact Programming
The WEB600 allows you to program up to 4 Contacts per User. The Contacts can be either: E-mail,
SMS-Text Message, or SNMP Trap. Each contact can have a programmable Schedule so that you only
receive messages when your Contact schedule is enabled. A Test button is also provided to check your
programming. When you click the Test button a test message will be sent to verify that everything is
working properly. Note: the Test button will not work until you have saved your programming.
E-Mail Programming
To configure an e-mail address choose E-mail from the drop-down list and enter your e-mail address in
the field below. Configure the Contact Schedule if desired.
28
Chapter 4: User Programming
SMS-Text Message Programming
To configure a SMS-Text Message choose SMS-Text Message from the drop-down list and enter your
telephone number in the field below. Choose your wireless provider from the drop-down list. Configure
the Contact Schedule if desired.
SNMP Trap
To configure an SNMP Trap choose SNMP Trap from the drop-down list and enter your SNMP Server
Name or IP address in the field below. Configure the Contact Schedule if desired.
29
WEB600 Users Manual
30
Chapter 5: History
Chapter 5: History
This chapter explains how to query the Event and Data Log History. The Event Log is a time-stamped
list of system events such as System Startup, Alarm Detection, Message Delivery, The Data Log con-
tains time stamped records of the input values. The logging rate is configured on the Zone programming
screen for each input. The query results can be viewed on screen within your browser or they can be
exported to other file formats (TXT, CSV, XML) for use within other programs, such as Excel. To begin,
click on History from the menu bar. The following screen will appear:
History Screen
Datalog Query
Select Data Log from the top of the screen. Select a particular Zone to narrow your query results to a
particular Zone or choose All to see samples from all Zones. Next, choose whether youd like to view All
samples, all Normal samples, or specifically samples that exceeded the alarm limits. You can narrow the
results from a particular time period by selecting the Mode drop-down. This gives you options to choose
events from the Previous 24 Hours, the Last 7 days, the Current Month or you can select a Custom time
period. When you choose Custom the Start Time and End Time fields will become active. Enter the start
and end times for your query. Next, choose the maximum number of records you want returned for
31
WEB600 Users Manual
your query, the choices are 25, 50, 100 and All. Finally, click the View Data button to display the results.
Alternatively you can Export the results to a file for viewing in another program. Choose the Export file
format from the drop-down list (XML, CSV, TXT) and click the Export button to create a file.
Datalog screen
32
Chapter 6: Operation
Chapter 6: Operation
Once you have finished installing and programming the WEB600 the unit is fully operational. Be sure to
test each sensor to make sure your alarm messages will be delivered as expected. Below is a description
of how the internal logic handles alarm message delivery for enabled inputs.
Alarm Processing
When a zone exceeds the programmed alarm limit (or if a contact changes state) the WEB600 will start
its alarm recognition timer and the Status on the Summary screen will change from OK to Waiting, to
indicate that the zone may become an alarm if the fault condition exceeds the programmed recognition
time. If Zone Alarm Delivery is disabled, the zone status will immediately change to Alarm. If the fault
becomes an alarm, the WEB600 will display the Status as either High, Low or Alarm, in red, to indicate
that an alarm exists and the Last Alarm time-stamp will update to reflect the time of the alarm. Note
that if Zone Alarm Delivery is disabled while an alarm condition exists, no messages will be delivered
and any existing alarm message processing will be cancelled.
Once an alarm meets the recognition time, the WEB600 will check to see if the Zone Alarm Delivery
Schedule is enabled. If it is, then alarm processing continues. If the Zone Alarm Delivery Schedule is or
becomes disabled, alarm processing will be cancelled.
Next, the unit will check the programmed Users and corresponding Contacts to see if alarm messages
should be delivered. First, the unit will locate all Users set to Escalation Priority 1. Then it will check to
see if the User is Enabled. Any Users that are not Enabled will immediately be discarded from receiv-
ing the alarm message. Next the unit will check the User Alarm Delivery Schedule. If the User Alarm
Delivery Schedule is enabled then alarm processing continues, if not, alarm processing to this User will
be suspended until either the Alarm Delivery Schedule becomes enabled or the alarm condition clears.
If the Alarm Delivery Schedule becomes enabled the Web600 will proceed to check the Contact pro-
gramming to see if alarm messages should be sent. Note that if a User is Disabled while the alarm condi-
tion still exists, then alarm message processing will be canceled for that User.
The Web600 will now check to see if any Contacts are enabled. Any Contacts that are not Enabled will
immediately be discarded from receiving the alarm message. Next, the unit will check the Contact
Alarm Delivery Schedule. If the Contact Alarm Delivery Schedule is enabled then the alarm message
will be sent, if not, alarm processing to this Contact will be suspended until either the Alarm Delivery
Schedule becomes enabled or the alarm condition clears. If the Contact Alarm Delivery Schedule
becomes enabled the Web600 will proceed to send the alarm message. Note that if a Contact is Disabled
while the alarm condition still exists, then alarm message processing will be canceled to that Contact.
Alarm delivery continues until there are no more users to contact or the alarm no longer exists.
Notes on Alarm Escalation
If no alarm message(s) can be delivered to an Escalation Priority 1 User due to a disabled status, the
WEB600 will proceed to Escalation Priority 2 Users, and so on, until it can immediately deliver its alarm
message. If any Users below the current Escalation Level become enabled at a later time as the result of a
schedule change, and the alarm still exists, then those Users/Contacts will receive the alarm message at
that time. Users with Escalation Priorities above the current Escalation level will not be sent the alarm
message until the Escalation Delay time activates their respective Escalation Priority level.
33
WEB600 Users Manual
Notes on Alarm Reset
If the alarm reset feature is enabled and an alarm is reset, then the previous alarm will be cancelled and
a new alarm will be processed from the beginning. Any users that were not yet contacted due to call
escalation delay, being unscheduled, or network error will not be contacted about the cancelled alarm.
The reset time must be set high enough to allow all enabled escalation levels to be notified about an
alarm before it is reset.
Sample Alarm Message (E-mail format):
From:
Sensaphone WEB600
ACME Widgets Monitoring System
Oak & Pine St - Hatfield, PA
34
Appendix A: Weekly Testing Procedure
Appendix A: Weekly
Testing Procedure
We recommend that you test your Sensaphone weekly to be sure it is functioning properly. This will
ensure that when a problem arises the Sensaphone will be ready to alert the appropriate personnel.
There are several tests that can be performed:
1.) Create an alarm on each zone by tripping all connected sensors.
Temperature sensors: Heat or cool the sensor.
Motion sensors: Have someone walk in front of the sensor.
Door/window sensors: open the door/window.
Water sensors: Apply a small amount of water beneath the sensor or use a wet towel and touch it to the
sensor probes.
Humidity sensors: Raise the humidity around the sensor by holding a cup of very hot water beneath the
sensor.
2.) Allow the unit to contact all programmed users. This will make sure that the Sensaphone is pro-
grammed properly. It will also prepare personnel to respond appropriately when they receive a message
from the Sensaphone.
3.) Test the battery (if installed) by unplugging the AC adapter and making sure that the Sensaphone
continues to function. Keep the AC adapter unplugged so that a Power Failure alarm occurs. Plug in the
AC adapter after the unit has finished.
4.) Keep a log of your tests, noting the date and whether the Web600 passed in each category tested. An
example of such a log is shown below. (See Test Log at the end of this manual.)
WEB600 Test Log
Date Inputs Alarm Battery
07/19/09
08/20/09
09/19/09
35
WEB600 Users Manual
36
Appendix B: Accessories
Appendix B: Accessories
The sensors listed below are available from Sensaphone, and represent the most commonly used zone
devices. Other dry contact sensors, designed for more specialized applications, may also be used.
Commercial or industrial electrical supply houses can provide devices to monitor virtually any condi-
tion. For further information, contact Sensaphone Customer Service at 610-558-2700.
37
WEB600 Users Manual
38
Appendix C: Modbus specifications
Arbitrary ordering number for this I/O point uint8 0x00 - 0xFF 4x10649
39
WEB600 Users Manual
40
Appendix C: Modbus specifications
Modbus Notes
Modbus Addresses
Address Ranges
The Modbus address ranges are laid out according to the following color-coded table.
The format below is TxDDDDD where T is the address type (bit/word, read-write/
read-only) and DDDDD is a 5 digit decimal base number from 0 to 65535.
The memory types map to the Modbus commands as shown in the following table.
The Web600 supports Modbus conformance classes 0 and 1.
Address Type Modbus Commands
0 1, 5, 15
1 2
3 4
4 3, 6, 16
Address Calculation
Modbus Address calculations are performed according to the following table:
Type Calculation Notes
Inputs BASE + (OFFSET * INPUT_NUMBER) The input number is as follows:
Zone 1 = 0
Zone 2 = 1
Zone 3 = 2
Zone 4 = 3
Zone 5 = 4
Zone 6 = 5
Power = 7
Battery = 8
Profiles BASE + (OFFSET * PROFILE_NUMBER) The profile number is as follows:
Profile 1 = 0
Profile 2 = 1
Profile 3 = 2
Profile 4 = 3
Profile 5 = 4
Profile 6 = 5
Profile 7 = 6
Profile 8 = 7
Contacts BASE + (OFFSET * ((PROFILE_NUMBER * 6) + The contact number is as follows:
CONTACT_NUMBER)) Contact 1 = 0
Contact 2 = 1
Contact 3 = 2
Contact 4 = 3
Network BASE
System BASE
41
WEB600 Users Manual
Quick Access Table
The following is a quick access table to retrieve the word-access, read-only current input values
as human-readable ASCII strings. Use the Modbus command 4 to access the data.
Address Description
3x01552 Zone 1
3x01594 Zone 2
3x01636 Zone 3
3x01678 Zone 4
3x01720 Zone 5
3x01762 Zone 6
3x01846 Power
3x01888 Battery
Modbus Data Formats
Bit-Representation
The Modbus interface supports a programmable bit ordering. Both the byte- and word-orders may be individually
programmed to either little- or big-endian formats. The default is big-endian byte-order and little-endian word-
order. This only applies to numeric values. Array, string and bit types are always given in the same format.
Bit
Bit values are boolean values where 1 is true and 0 is false.
uint8, sint16, uint32, sint32
These are integer data formats. The u stands for unsigned, the s stands for signed. The number
indicates the number of bits used to represent the data: 8, 16, or 32 corresponding to 1, 2, or 4 bytes
respectively. 1 and 2 byte integers are stored in one Modbus register while 4-byte integers are stored
in two consecutive Modbus registers. The byte- and word-orders are programmable.
The integer types may be either fixed-point format or the standard straight integer format. Fixed-
point integer formats are offset by 100, so divide the straight binary value by 100 to get the real
value. This provides 2 decimal places of precision for a maximum range of 80000.00.
Float
This is a standard IEEE 754 32-bit floating-point number. All floating-point numbers will be in this format
and span 2 consecutive Modbus registers according to the programmed byte- and word-orders.
String and array
Strings and arrays are strings of 0 or more characters/bytes. They are always returned first-byte first and last-byte
last. Strings are null-terminated with a binary 0 only if they are smaller than their maximum size. For example,
a name string may be up to 32-characters long. A value of John Doe would be terminated by a 0 because
it is less than 32-characters long, but not a name that is 32-characters long. Arrays are never terminated.
42
Appendix C: Modbus specifications
Non-generic data
Timestamps
Timestamps can be decoded using the following equations. div means integer division where the remainder
is dropped. mod means the modulus or remainder. All values start at 0. For example, Day 0 is the first
day of the month and Month 0 is January. The year is offset by -2000, so that a value of 9 indicates 2009.
Seconds = (Value div 1) mod 60
Minutes = (Value div 60) mod 60
Hours = (Value div 3600) mod 24
Day = (Value div 86400) mod 31
Month = (Value div 2678400) mod 12
Year = (Value div 32140800)
Timestamps are encoded in the reverse:
Timestamp = (Seconds * 1) +
(Minutes * 60) +
(Hours * 3600 +
(Day * 86400) +
(Month * 2678400) +
(Year * 32140800)
Access Level:
Access Level Description
0 Access Disabled
1 Read-Only
2 Read-Write
43
WEB600 Users Manual
Contact Types:
Contact Type Description
3 Email or SMS
9 SNMP Trap
Modbus Configuration:
Operating Mode Description
0 Modbus Disabled
1 Read-Only
2 Read-Write
44
Appendix D: Specifications
Appendix D: Specifications
Alert Zones
Number of Zones: 6
Zone Connector: terminal block
Zone Types: N.O./N.C. contact, 2.8K Thermistor ( -109 to 115F, -85 to 57C ) And 10K Thermistor
(-87 to 168F; -66 to 76C), and 4-20mA (-80,000.0 to 80,000.0
Zone Characteristics: 28.7K to 3.3V (temperature/contact) or 250 Ohms to ground (4-20mA)
A/D Converter Resolution: 12 bits 2 LSB
Zone Protection: 5.5VDC Metal Oxide Varistor with fast acting diode clamps.
Data logging
32,000 Samples (all samples include data date and time)
1 second to 1 month sampling rate
User programmable channel selection
Zones 1 6
Battery
Input Power
LED Indicators
Power On: On steady when the unit is powered on.
Alarm: Off when no alarm exists.
Ethernet Link and Activity LEDs
Communication types:
E-Mail SMTP
Text Messages
Web page Supported formats HTTP, PDA, WAP, and XML
SNMP MIB with Traps, GET, GETNEXT, and SET
MODBUS/TCP Slave Conformance Class 0 and 1
Power Supply
Power Supply: 120VAC/5VDC 50/60Hz 6W wall plug-in transformer w/6 cord.
Power Consumption: 2 Watts
Power Protection: Metal Oxide Varistor
Battery Backup: Optional 2hr battery backup module (Part #FGD-W610).
45
WEB600 Users Manual
Environmental
Operating Temperature: 32122 F (050 C)
Operating Humidity: 090% RH non-condensing
Storage Temperature: 32140 F (060 C)
Physical
Dimensions: 1.4h x 5.5w x 3.7d
Weight: 1.5 lbs.
Enclosure: Indoor-rated plastic housing suitable for wall or desktop installation.
46
Appendix E: Thermistors
Appendix E: Thermistors
2.8K Thermistor Data
Degrees Celsius Resistance (Ohms)
-50 187,625
-40 94,206
-30 49,549
-20 27,180
-10 15,491
0 9,142
10 5,572
20 3,498
30 2,256
40 1,491
50 1,009
60 697
70 490
80 351
47
WEB600 Users Manual
48
Appendix F: Returning the Unit for Repair
Appendix F: Returning
the Unit for Repair
In the event that the WEB600 does not function properly, we suggest that you do the following:
1) Record your observations regarding the WEB600s malfunction.
2) Call the Technical Service Department at 610-558-2700 prior to sending the unit to Sensaphone for
repair.
If the unit must be sent to Sensaphone for Servicing, please do the following:
1) Unplug the AC power supply from the wall outlet, remove the batteries, and disconnect all sensors
from the alert zones.
2) Carefully pack the unit to avoid damage in transit. Use the original container (if available) or a sturdy
shipping box.
3) You must include the following information to avoid shipping delays:
a) Your name, address and telephone number.
b) A note explaining the problem.
4) Ship your package to the address below:
SERVICE DEPARTMENT
SENSAPHONE
901 Tryens Road
Aston, PA 19014
5) Ship prepaid and insured via UPS or US Mail to ensure a traceable shipment with recourse for dam-
age or replacement.
49
WEB600 Users Manual
50
Appendix G: Test Log
51
WEB600 Users Manual
Alarms
52