OvercurrentCoordinationBasicsGenerators

Theinformationpresentedinthisapplicationguideisforreview,approval,interpretationandapplicationbyaregisteredprofessionalengineeronly.SKMdisclaimsany
responsibilityandliabilityresultingfromtheuseandinterpretationofthisinformation.

ReproductionofthismaterialispermittedprovidedproperacknowledgementisgiventoSKMSystemsAnalysisInc.

Purpose

Thepurposeofthisguideistoprovideabasicovercurrentprotectionphilosophyforgenerators.

GeneratorOvercurrentProtection
Timecurrentcurve(TCC)landmarks(figure1)


Fullloadamps(FLA)locatedintheupperdecade
Overloadcurvelocatedintheupper1or2decades
Shortcircuitwithstandcapabilitypointlocatedinthemiddledecade
Decrementcurvelocatedinthebottom3decades

TCCregions(figure2)

EquipmentoperatingregionlocatedatandtotheleftoftheFLAandthegeneratordecrementcurveintheinstantaneousregionofthelowestdecade
Equipmentdamageregionlocatedattotherightoftheoverloadcurveandshortcircuitwithstandpoint,andabovethedecrementcurve
Protectivedeviceoperatingregionlocatedbetweentheequipmentoperatinganddamageregions

Suggestedovercurrentprotection(figure3)

Setprotectionabovethefullloadampsandthedecrementcurveintheinstantaneousregionofthelowestdecade
Setprotectionbelowtheoverloadcurveandtheshortcircuitwithstandpoint
Setprotectiontointersectwiththedecrementcurveinthesecondlowestdecade

Comments

Ifcurrentpenetratesthelimitsoftheoverloadcurve,insulationlifeisreduced.
Ifprotectionissetabovethedecrementcurve,thedevicewillnevertrip.

http://www.skm.com/applicationguides11.html 1/3
8/4/2015 SKMSystemsAnalysis,Inc.PowerSystemSoftwareandArcFlashHazardAnalysisandDesignSolutions

Fig.1GeneratorTCClandmarks

Fig.2GeneratorTCCregions

http://www.skm.com/applicationguides11.html 2/3
8/4/2015 SKMSystemsAnalysis,Inc.PowerSystemSoftwareandArcFlashHazardAnalysisandDesignSolutions

Fig.3Generatorovercurrentprotection

References


OtherApplicationGuidesofferedbySKMSystemsAnalysisatwww.skm.com
ElectricalTransmissionandDistributionReferenceBook,ABBPowerT&DCompany,Raleigh,NorthCarolina,1997
ProtectiveRelayingTheoryandApplications,2ndEdition,MarcelDekker,NewYork,2004

Thelatestrevisionof:

IEEEStd242,IEEERecommendedPracticeforProtectionandCoordinationofIndustrialandCommercialPowerSystems(IEEEBuffBook)
IEEEStdC37.102,IEEEGuideforACGeneratorProtection
IEEEStdC37.101,IEEEGuideforGeneratorGroundProtection
ANSIC50.13,CylindricalRotorSynchronousGenerators
NEMAStdMG1,MotorsandGenerators