Sie sind auf Seite 1von 56

www.usa.siemens.

com/mvswitchgear

Instruction manual
Types 3AH3 and 3AHc vacuum circuit breaker operator modules
4.16 kV to 38 kV
Installation operation maintenance E50001-F710-A251-V1-4A00

Answers for infrastructure and cities.


Hazardous voltages and high-speed moving parts.

Will cause death, serious injury or property damage.

Always de-energize and ground the equipment before maintenance. Read


and understand this instruction manual before using equipment.
Maintenance should be performed only by qualified personnel. The use of
unauthorized parts in the repair of the equipment or tampering by
unqualified personnel will result in dangerous conditions which will cause
death, severe injury or equipment damage. Follow all safety instructions
contained herein.

Important Further, a qualified person shall also be


The information contained herein is general familiar with the proper use of special
in nature and not intended for specific precautionary techniques, personal
application purposes. It does not relieve the protective equipment, insulation and
user of responsibility to use sound practices shielding materials, and insulated tools and
in application, installation, operation and test equipment. Such persons are permitted
maintenance of the equipment purchased. to work within limited approach of exposed
Siemens reserves the right to make changes live parts operating at 50 volts or more, and
in the specifications shown herein or to shall, at a minimum, be additionally trained
make improvements at any time without in all of the following:
notice or obligation. Should a conflict arise
 he skills and techniques necessary to
T
between the general information contained
distinguish exposed energized parts from
in this publication and the contents of
other parts of electric equipment
drawings or supplementary material or
both, the latter shall take precedence.  he skills and techniques necessary to
T
determine the nominal voltage of
Qualified person
exposed live parts
For the purpose of this instruction manual a
qualified person is one who is familiar with  he approach distances specified in NFPA
T
the installation, construction or operation of 70E and the corresponding voltages to
the equipment and the hazards involved. In which the qualified person will be
addition, this person has the following exposed
qualifications:
 he decision-making process necessary
T
I s trained and authorized to to determine the degree and extent of
de-energize, clear, ground and tag the hazard and the personal protective
circuits and equipment in accordance equipment and job planning necessary to
with established safety procedures. perform the task safely.
I s trained in the proper care and use of
protective equipment, such as: rubber
gloves, hard hat, safety glasses or face
shields, flash clothing, etc., in
accordance with established safety
practices.
Is trained in rendering first aid.
Note: Table of contents
These instructions do not purport to cover all
details or variations in equipment, nor to Introduction 04 05
provide for every possible contingency to be
met in connection with installation, operation Receiving, handling and storage 06 08
or maintenance. Should further information be
Installation checks and functional tests 09 10
desired or should particular problems arise
that are not covered sufficiently for the Vacuum interrupter/operator 11 27
purchasers purposes, the matter should be
referred to the local sales office. Maintenance 28 41

The contents of this instruction manual shall Overhaul 42 46


not become part of or modify any prior or
Technical data and troubleshooting 47 55
existing agreement, commitment or
relationship. The sales contract contains the
entire obligation of Siemens Industry, Inc. The
warranty contained in the contract between
the parties is the sole warranty of Siemens
Industry, Inc. Any statements contained herein
do not create new warranties or modify the
existing warranty.
Introduction

Hazardous voltages and high speed moving parts.


Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before maintenance.
Read and understand this instruction manual before using equipment.
Maintenance should be performed only by qualified personnel. The use
of unauthorized parts in the repair of the equipment or tampering by
unqualified personnel will result in dangerous conditions which will
cause death, severe injury or equipment damage. Follow all safety
instructions contained herein.

Introduction Signal words


The type 3AH3 and type 3AH-compact The signal words danger, warning and
(3AHc) families of vacuum circuit breaker caution used in this manual indicate the
operator modules are designed to meet all degree of hazard that may be encountered
applicable ANSI, NEMA and IEEE standards. by the user. These words are defined as:
Successful application and operation of this
Danger - Indicates an imminently hazardous
equipment depends as much upon proper
situation that, if not avoided, will result in
installation and maintenance by the user as
death or serious injury.
it does upon the proper design and
fabrication by Siemens. Warning - Indicates a potentially hazardous
situation that, if not avoided, could result in
The purpose of this instruction manual is to
death or serious injury.
assist the user in developing safe and
efficient procedures for the installation, Caution - Indicates a potentially hazardous
maintenance and use of the equipment. situation that, if not avoided, may result in
minor or moderate injury.
Contact the nearest Siemens representative
if any additional information is desired. Caution (without safety alert symbol) -
Indicates a potentially hazardous situation
In this instruction manual, reference to type
that, if not avoided, may result in property
3AH includes both type 3AH3 and type 3AHc
damage.
operator modules. When information
specific to the type 3AH-compact (3AHc)
design is involved, the text will so designate.

4
Hazardous Procedures Field service operation and warranty
In addition to other procedures described in issues
this instruction manual as dangerous, user Siemens can provide competent, well-
personnel must adhere to the following: trained field service representatives to
provide technical guidance and advisory
1. A
 lways work only on a de-energized
assistance for the installation, overhaul,
circuit breaker. The circuit breaker should
repair and maintenance of Siemens
be isolated, grounded and have all
equipment, processes and systems. Contact
control power removed before
regional service centers, sales offices or the
performing any tests, maintenance or
factory for details, or telephone Siemens
repair.
field service at 1-800-347-6659 or 1-919-
2. A
 lways perform maintenance on the 365-2200 outside the U.S.
circuit breaker after the spring-charged
For medium voltage customer service
mechanisms are discharged (except for
issues, contact Siemens at 1-800-347-6659
test of the charging mechanisms). Check
or 1-919-365-2200 outside the U.S.
to be certain that the indicator flags read
OPEN and DISCHARGED.
3. Always let an interlock device or safety
mechanism perform its function without
forcing or defeating the device.

5
Receiving, handling
and storage

Heavy weight.
Improper lifting or hoisting can result in death, serious injury or
property damage.
Obtain the services of a qualified rigger prior to hoisting the circuit
breaker to assure adequate safety margins in the hoisting equipment
and procedures to avoid damage.

Introduction Shipping damage claims


This portion of the instruction manual Important: The manner in which visible
covers the receiving, handling and storage shipping damage is identified by consignee
instructions for a type 3AH3 vacuum circuit prior to signing the delivery receipt can
breaker operator module. This section of the determine the outcome of any damage
instruction manual is intended to help the claim to be filed.
user identify, inspect and protect the circuit
Notification to carrier within 15 days for
breaker operator module prior to its
concealed damage is essential if loss
installation.
resulting from unsettled claims is to be
Receiving procedure eliminated or minimized.
Make a physical inspection of the shipping
1. W
 hen the shipment arrives, note
container before removing or unpacking the
whether the equipment is properly
circuit breaker operator module.
protected from the elements. Note the
Check for shipment damage or indications trailer number the equipment arrived on.
of rough handling by the carrier. Check each Note also any blocking of equipment.
item against the manifest to identify any During unloading, check the actual
shortages. equipment delivered to verify it agrees
with the delivery receipt.
Accessories such as the manual charging
crank, the racking crank (if applicable) and 2. M
 ake immediate inspection for visible
the split plug jumper (if applicable) are damage upon arrival and prior to
shipped separately. disturbing or removing packaging or
wrapping material. This should be done
prior to unloading when possible. When
total inspection cannot be made on
vehicle prior to unloading, close
inspection during unloading must be
performed and visible damage noted on
6 the delivery receipt. Take pictures if
possible.
3. A
 ny visible damage must be noted on the Note: Shipments are not released from the
delivery receipt and acknowledged with factory without a clear bill of lading.
the drivers signature. The damage should Approved methods are employed for
be detailed as much as possible. It is preparation, loading, blocking and tarping
essential that a notation "possible of the equipment before it leaves the
internal damage, subject to inspection" Siemens factory. Any determination as to
be included on the delivery receipt. If the whether the equipment was properly loaded
driver will not sign the delivery receipt or properly prepared by shipper for over-the-
with the damage noted, the shipment road travel cannot be made at the
should not be signed for by the destination. If the equipment is received in a
consignee or their agent. damaged condition, this damage to the
equipment has to have occurred while en
4. N
 otify Siemens medium-voltage
route due to conditions beyond Siemens
customer service immediately of any
control. If the procedure outlined above is
damage, at 1-800-347-6659 or 1-919-
not followed by the consignee, purchaser or
365-2200 outside the U.S.
their agent, Siemens cannot be held liable
5. Arrange for a carrier inspection of the for repairs. Siemens will not be held liable
damage immediately. for repairs in any case where repair work
was performed prior to authorization from
Important: Do not move the equipment
Siemens.
from the place it was set when unloading.
Also, do not remove or disturb packaging or Handling procedure
wrapping material prior to carrier damage 1. C
 arefully remove the shipping carton
inspection. Equipment must be inspected by from the circuit breaker. Keep the
carrier prior to handling after receipt. This shipping pallet for later use if the circuit
eliminates loss due to claims by carrier that breaker is to be stored prior to its
the equipment was damaged or further installation.
damaged on site after unloading.
2. Inspect for concealed damage.
6. Be sure the equipment is properly Notification to carrier must take place
protected from any further damage by within 15 days to assure prompt
covering it properly after unloading. claim resolution.
7. If practical, make further inspection for 3. E
 ach circuit breaker should be lifted
possible concealed damage while the appropriately to avoid crushing the side
carriers inspector is on site. If inspection panels of the circuit breaker, or
for concealed damage is not practical at damaging the primary disconnect
the time the carriers inspector is assemblies.
present, it must be done within 15 days
Type 3AH3 vacuum circuit breaker
of receipt of the equipment. If concealed
operator modules weigh between 165
damage is found, the carrier must again
and 408 lbs (75-185 kg), plus an
be notified and inspection made prior to
additional 100 lbs (45 kg) for packaging
taking any corrective action to repair.
and pallet. Refer to Table 13 for more
Also notify Siemens immediately at
information.
1-800-347-6659 or 1-919-365-2200
outside the U.S. Type 3AHc vacuum circuit breaker
operator modules are not furnished
8. O
 btain the original carrier inspection
separately, but are supplied as a
report and forward it with a copy of the
component of a complete drawout
noted delivery receipt to Siemens.
circuit breaker. Weights and lifting
Approval must be obtained by Siemens
details are provided in the circuit breaker
from the carrier before any repair work
manuals.
can be performed.
4. T
 he palleted circuit breaker can be
B
 efore approval can be obtained, Siemens
moved using a properly rated fork-lift
must have the documents referenced in
vehicle. The pallets are designed for
the paragraph above. The carrier
movement by a standard fork-lift vehicle.
inspection report and/or drivers signature
on the delivery receipt does not constitute
approval to repair.
7
Storage procedure
1. Whenever possible, install the circuit
breaker operator module in its assigned
switchgear enclosure or end location for
storage.
2. When the circuit breaker operator
module needs to be placed on its pallet
for storage, be sure the unit is securely
A E bolted to the pallet and covered with
polyethylene film at least 10 mils thick.
Indoor storage
Whenever possible, store the circuit breaker
B
F
operator module indoors. The storage
environment must be clean, dry and free of
such items as construction dust, corrosive
C
atmosphere, mechanical abuse and rapid
temperature variations.
D
Outdoor storage
Outdoor storage is not recommended. When
no other option is available, the circuit
breaker operator module must be
completely covered and protected from rain,
snow, dirt and all other contaminants.
Space heating
Space heating must be used for both indoor
and outdoor storage to prevent
condensation and corrosion. When the
circuit breaker operator module is stored
Item Description Item Description outdoors, 250 watts per circuit breaker of
A Manual spring-charging port E Manual close pushbutton space heating is recommended. If the circuit
B CHARGED/DISCHARGED indicator F Manual open pushbutton breaker operator module is stored inside the
switchgear enclosure, and the switchgear is
C OPEN/CLOSED indicator
G Rating plate equipped with space heaters, energize the
D Operation counter
space heaters.

Figure 1: Front panel controls of circuit breaker and manual charging of closing spring

8
Installation checks
and functional tests

Hazardous voltage and high-speed moving parts.

Will cause death, serious injury and property damage.

Read instruction manuals, observe safety instructions and use qualified


personnel.

Introduction De-energizing control power in


This section provides a description of the switchgear
inspections, checks and tests to be When the circuit breaker is mounted in
performed on the circuit breaker operator switchgear, open the control-power
module only. disconnect device in the metal-clad
switchgear cubicle, outdoor circuit breaker
Inspections, checks and tests without
housing or other location.
control power
Vacuum circuit breakers are normally In metal-clad switchgear, the control-power
shipped with their primary contacts OPEN disconnect device is normally located on the
and their springs DISCHARGED. However, it secondary-device panel in the upper cell of
is critical to first verify the DISCHARGED the vertical section. The normal control-
condition of the spring-loaded mechanisms power disconnect device is a pullout-type
after de-energizing control power. fuse holder. Removal of the fuse holder
de-energizes control power to the circuit
breaker in the associated switchgear cell.
In some switchgear assemblies, a molded-
case circuit breaker or knife switch is used in
lieu of the pullout-type fuse holder. Opening
this circuit breaker or switch accomplishes
the same result: control power is
disconnected. Opening this circuit breaker
or switch accomplishes the same result:
control power is disconnected.

9
Spring-discharge check (refer to Figure 1) Automatic spring-charging check
Perform the spring-discharge check before The automatic spring-charging features of
removing the circuit breaker or operator the circuit breaker must be checked. Control
module from the pallet or removing it from power is required for automatic spring-
the switchgear. charging to take place.
The spring-discharge check should be Note: A temporary source of control power
performed after de-energizing control and test leads may be required if the
power. This check assures both the tripping control-power source has not been
and closing springs are fully discharged. connected to the switchgear or circuit
breaker. Refer to specific wiring information
Note: Do not perform the spring-discharge
and rating label for your circuit breaker to
check if the circuit breaker is in the
determine the voltage required and where
CONNECT position. Open the circuit breaker
the control-voltage signal should be applied.
and rack to the DISCONNECT position, and
When control power is connected to the
then perform the spring-discharge check.
circuit breaker, the closing spring should
For fixed-mounted circuit breaker
automatically charge.
applications, open the isolator switches on
the line side and on the load side of the 1. Open control-power circuit by opening
circuit breaker before performing the spring- the control-power disconnect device.
discharge check.
2. Energize (close) the control power-circuit
1. P
 ress red trip pushbutton. disconnect.
2. P
 ress black close pushbutton. 3. Use the close and open controls (refer to
Figure 1) to first close and then open the
3. P
 ress red trip pushbutton again.
circuit breaker contacts. Verify contact
4. V
 erify spring-condition indicator shows positions visually by observing the OPEN/
DISCHARGED. CLOSED indicator on the circuit breaker.
5. V
 erify main contact status indicator 4. De-energize (close) the control-power by
shows OPEN. repeating Step 1. If a split-plug jumper
was used for temporary control-power
Manual-spring charging check
connections, disconnect the split-plug
1. Insert the manual-spring charging crank
jumper from the switchgear first and
into the manual-charge handle socket as
next from the circuit breaker.
shown in Figure 1. Turn the crank
clockwise (about 48 revolutions) until 5. P
 erform the spring discharge check
the spring condition indicator shows the again. Verify the closing springs are
closing spring is CHARGED. DISCHARGED and the primary contacts of
the circuit breaker are OPEN.
2. R
 epeat the spring-discharge check.
Final mechanical inspections without
3. V
 erify the springs are DISCHARGED and
control power
the circuit-breaker primary contacts are
1. Make a final mechanical inspection of
OPEN by indicator positions.
the circuit breaker. Verify the contacts
As-found and vacuum-integrity check are in the OPEN position, and the closing
tests springs are DISCHARGED.
Perform and record the results of both the
2. Verify mechanical condition of springs.
as-found insulation test and the vacuum-
integrity check (dielectric) test. Procedures 3. Check for loose hardware.
for these tests are described in the
Maintenance section of this instruction
manual beginning on page 28.

10
Vacuum interrupter/
operator

Figure 2: Vacuum circuit breaker operator module

3AH vacuum circuit breaker operator 3AHc vacuum


circuit breaker
B A
operator

M
N N
T
C

D R

E S
Q P
H
K
B G M
R J
F
O S
F D
C V
E
Q
G
H U
P
L O
I A
J
K J

Item Description Item Description


A Pole head L Guide link
B Upper connection pad M Upper post insulator
Introduction
C Strut N Operator housing
The type 3AH vacuum circuit-breaker
operator is intended for application in a D Vacuum interrupter O Lower post insulator
drawout truck for use in medium-voltage E Moving contact P Insulating coupler (48.0)
metal-clad switchgear and for stationary F Centering piece Q Contact pressure spring (49.0)
applications, such as the type SDV6 outdoor G Terminal clamp R Lever
distribution circuit breaker. The type 3AH
H Flexible connector S Jack shaft
circuit breaker conforms to the requirements
of ANSI/IEEE standards, including C37.20.2, I Eye bolt T Pole plate
C37.04, C37.06, C37.09 and C37.010. J Pole bottom (lower pole head) U Lower connector
K Angled lever V Vehicle frame

11
This section describes the operation of each
1
major subassembly as an aid in the
operation, installation, maintenance and
repair of the circuit breaker.
2
Vacuum interrupters
The operating principle of the vacuum
interrupter is simple. Figure 3 is a section
4
3 view of a typical vacuum interrupter. The
5 entire assembly is sealed after a vacuum is
established.
3AH3 operator mechanism
The vacuum interrupter stationary contact is
3AH vacuum circuit breaker operator
6 connected to the upper pole head of the
circuit breaker. The vacuum interrupter
7
movable contact is connected to the pole
8 bottom and driving mechanism of the circuit
breaker.
9
3AHc operator mechanism
The vacuum interrupter stationary contact is
Item Description
connected to the lower pole head of the
circuit breaker. The vacuum interrupter
Fixed contact-current
1 movable contact is connected to the upper
connection
pole head (pole bottom) and drive
2 Ceramic insulator mechanism of the circuit breaker.
3 Arc shield
The metal bellows provide a secure seal
4 Fixed contact
around the movable contact, preventing loss
5 Moving contact of vacuum while permitting vertical motion
6 Ceramic insulator of the movable contact.
7 Metal bellows When the two contacts separate, an arc is
8 Guide initiated that continues conduction up to
Moving contact- the following current zero. At current zero,
9
current connection the arc extinguishes and any conductive
metal vapor that has been created by and
Figure 3: Vacuum interrupter cut-
supported the arc condenses on the
away view contacts and on the surrounding arc shield.
Contact materials and configuration are
3AHc vacuum circuit breaker operator optimized to achieve arc motion and to
minimize switching disturbances.
Figure 4: Vacuum circuit breaker operator module Primary connections (refer to Figure 2)
Figure 2 illustrates the pad provision to
accept the primary connections. Each circuit
breaker has three upper and three lower
primary disconnect pad provisions, to allow
The circuit breaker includes three vacuum connection to the switchgear.
interrupters, a stored-energy operating
For stationary circuit breaker applications,
mechanism, necessary electrical controls
bus conductors connect directly to these
and interlock devices, disconnect devices to
pads. Bolting hardware is M12 x 1.75 grade
connect the circuit breaker to both primary
8. Torque M12 bolts to 52 ft-lb (70 Nm).
and control power (for drawout
applications) and an operator housing.
In a typical installation in a drawout truck,
insulating barriers may be located between
the vacuum interrupters and along the
sides.
12
Phase barriers (if applicable) The energy-storing mechanism and all the
Plates of glass-polyester insulating material control and actuating devices are installed
are attached to the circuit breaker and in the operator housing. The mechanism is
provide suitable electrical insulation of the spring stored-energy type and is
between the vacuum interrupter and mechanically and electrically trip-free.
primary conductors and the cubicle.
The close-open indicator, closing spring-
Stored-energy operating mechanism charge indicator and the operation counter
The stored-energy operating mechanism of are located on the front of the operator
the circuit breaker is an integrated housing.
arrangement of springs, coils and
The control connector for the control and
mechanical devices designed to provide a
signalling cables is a multi-contact plug in
number of critical functions. The energy
most designs, although direct connection to
necessary to close and open the contacts of
the switchgear is used for certain products.
the vacuum interrupters is stored in
powerful opening and closing springs. The Circuit breaker pole (refer to Figure 2)
closing springs are normally charged The vacuum interrupter is bolted to the
automatically, but there are provisions for upper pole head and the upper pole head is
manual charging. The operating mechanism rigidly connected to the operator housing by
that controls charging, closing and tripping the post insulator. The moving contact end
functions is fully trip-free. Trip-free of the vacuum interrupter is stabilized
requires that the tripping function prevail against lateral forces by a centering ring on
over the closing function as specified in the pole bottom. The external forces due to
ANSI/IEEE C37.04-1999, clause 6.9. switching operations and the contact
pressure are absorbed by the struts.
Vacuum interrupter/operator module
The vacuum interrupter/operator module Current-path assembly (refer to Figure 2)
consists of the three poles, each with its The current-path assembly consists of the
vacuum interrupters and primary insulators, pole head, the stationary contact and the
mounted on the common operating moving contact, that is connected to the
mechanism housing. This module is shown pole bottom by a terminal clamp and a
in Figure 4. flexible connector.
Construction (Refer to Figures 1, 2, 5 and Vacuum interrupter (refer to Figure 2)
6) (3AH only) The moving-contact motion is aligned and
This description covers the type 3AH stabilized by a guide bushing. The metal
operator. The type 3AHc differs in bellows follows the travel of the contact and
arrangement but the fundamental seals the vacuum interrupter against the
discussion of operation applies. surrounding atmosphere.
Each of the circuit breaker poles are fixed to Switching operation (refer to Figures 2
the rear of the operating mechanism and 5)
housing by two cast-resin insulators. The When a closing command is initiated, the
insulators also connect to the upper and closing spring (62.0), that was previously
lower pole supports that in turn support the charged by hand or by the motor, actuates
ends of the vacuum interrupter. the moving contact through the jack shaft
(63.0), lever, contact pressure spring (49.0),
The pole supports are aluminum castings
insulating coupler (48.0) and angled lever.
(most 1,200 A, all 2,000 A and some
3,000 A), copper castings (some 3,000 A) or The forces that occur when the action of the
sheet steel (some 1,200 A). For type 3AH insulating coupler (48.0) is converted into
operators, primary disconnect stud the vertical action of the moving contact are
extensions may be attached directly to the absorbed by the guide link, that pivots on
upper and lower pole connection pads. the pole bottom and the eye bolt.

13
During closing, the opening spring (64.0) Motor-operating mechanism (refer to
(refer to Figure 6) and the contact pressure Figure 5)
springs (49.0) are charged and latched by The spring-charging motor (50.4) is bolted
pawl (64.2) (refer to Figure 6). The closing to the charging mechanism (50.2) gear box
spring (62.0) (refer to Figure 5) of the installed in the operator housing. Neither
motor-operated circuit breaker is recharged the charging mechanism nor the motor
immediately after closing. require any maintenance.
In the closed state, the necessary contact Mode of operation
pressure is maintained by the contact The operating mechanism is of the stored-
pressure springs (49.0) and the atmospheric energy trip-free type. For example, the
pressure. The contact pressure spring charging of the closing spring is not
automatically compensates for arc erosion, automatically followed by the contacts
which is very small. changing position, and tripping function
prevails over the closing function.
When a opening command is given, the
energy stored in the opening and contact When the stored-energy mechanism has
pressure springs (49.0) is released by pawl been charged, the mechanism is ready for a
(64.2) (refer to Figure 6). closing operation at any time.
The opening sequence is similar to the The mechanical energy for carrying out an
closing sequence. The residual force of the Open-Close-Open sequence for auto-
opening spring maintains the moving reclosing duty is stored in the closing and
contacts in the open position. opening springs.
Operating mechanism Charging
The operating mechanism is comprised of The details of the closing spring charging
the mechanical and electrical components mechanism are shown in Figure 5. The
required to: charging shaft is supported in the charging
mechanism gear box (50.2), but is not
1. Charge the closing spring with sufficient
coupled mechanically with the charging
potential energy to close the circuit
mechanism. Fitted to it are the crank (62.2)
breaker and to store opening energy in
at one end, and the cam (62.3), together
the opening and contact pressure
with lever (62.5), at the other.
springs.
2. Mechanisms to release closing and
opening actions.
3. Means of transmitting force and motion
to each of the three vacuum
interrupters.
4. Operate all these functions
automatically through an electrical
charging motor, cutout switches, an
anti-pump relay, a close coil, an open
coil and an auxiliary switch.
5. Provide indication of the circuit breaker
status (OPEN/CLOSED), spring condition
(CHARGED/DISCHARGED) and number of
operations.
Construction
The essential parts of the operating
mechanism are shown in Figures 5 and 6.
The control and sequence of operation of
the mechanism is described in Figure 7.

14
Figure 5: Stored-energy operating mechanism (circuit breaker shown in OPEN position) (straight linkage shown)

62.5
55.2 62.3

62.1 50.3
62.5.2
62.2
68.0
53.0
50.5 62.6
50.2

55.1
53.1

62.0 54.1
50.4.1

55.0 54.0

50.4
64.0
68.1

58.0

63.0 63.1

63.5
61.8
59.0
60.0
Item Description Item Description Footnote:
50.2 Charging mechanism gear box 62.1 Charging shaft
1.
For certain applications, the
straight trip coupling rod (62.8) is
50.3 Charging flange 62.2 Crank replaced by a collapsible trip-free
50.3.1 Driver (not visible) 62.3 Cam disc coupling system, illustrated in
Figures 6-10.
50.4 Spring charging motor 88.0 62.5 Lever
50.4.1 Limit switches 62.5.1 Pawl roller (not visible)
50.5 Manual spring-charging port 62.5.2 Close latch pawl
53.0 Close pushbutton 62.6 Driver lever
53.1 Close coil 52SRC 62.8 Straight coupling rod1
54.0 Open pushbutton 62.8.1 Spring return latch (not shown)1
54.1 Trip coil 52T 62.8.3 Trip-free coupling lever1
55.0 Closing spring-charge indicator 63.0 Jack shaft
55.1 Linkage 63.1 Lever phase C
55.2 Control lever 63.5 Lever phase B
58.0 CLOSED/OPEN indicator 63.7 Lever phase A
59.0 Operations counter 64.0 Opening spring
60.0 Operator housing 68.0 Auxiliary switch
61.8 Shock absorber
68.1 Auxiliary switch link
62.0 Closing spring

15
Item Description Closing (refer to Figures 5, 7-10)
54.0 Open pushbutton If the circuit breaker is to be closed
62.8 Trip-free coupling rod1 62.8.1 manually, the closing spring is released by
pressing the Close button (53.0). In the case
62.8.1 Spring-return latch 1
of remote electrical control, the close coil
Trip-free coupling link 62.8.2 52SRC (53.1) unlatches the closing spring
62.8.2
(draw bar)1
64.0
62.8 (62.0).
64.0 Opening spring 54.0
As the closing spring discharges, the
64.2 Trip-latch pawl (not visible)
charging shaft (62.1) is turned by crank
64.3 Lever (62.2).
64.3.1 Pawl roller 64.3.1
The cam disc (62.3) at the other end of the
64.3 charging shaft actuates the drive lever
(62.6), with the result that jack shaft (63.0)
is turned by lever (63.5) via the coupling rod
Footnote: (62.8). At the same time, the levers (63.1),
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is (63.5) and (63.7) fixed on the jack shaft
replaced with a straight coupling rod, and other parts associated with drawout operate the three insulated couplers (48.0)
interlocking are eliminated. (refer to Figure 2) for the circuit breaker
poles. Lever (63.7) changes the OPEN/CLOSE
Figure 6: Stored-energy operating mechanism (circuit breaker shown in CLOSED position) indicator (58.0) over to CLOSED. Lever
(Drawout trip-free linkage shown) (63.5) charges the opening spring (64.0)
during closing, and the circuit breaker is
When the charging mechanism is actuated latched in the closed position by lever (64.3)
by hand with a hand crank (refer to Figures with pawl roller (64.3.1) and by pawl (64.2).
12 and 13) or by a motor (50.4), the flange Lever (63.1) actuates the auxiliary switch
(50.3) turns until the driver (50.3.1) locates (68.0) through the linkage (68.1).
itself in the cutaway part of the cam disc
The crank (62.2) on the charging shaft
(62.3), thus causing the charging shaft to
(62.1) moves the linkage (55.1) by acting
follow. The crank (62.2) charges the closing
on the control lever (55.2). The closing
spring (62.0). When the closing spring has
spring charged indication is thus canceled,
been fully charged, the crank actuates the
and the limit switches (50.4.1) switch in the
linkage (55.1) via the control lever (55.2)
control supply to cause the closing spring to
for the closing spring CHARGED indicator
recharge immediately.
(55.0), and actuates the limit switches
(50.4.1) for interrupting the motor supply. Trip-free operation
At the same time, the lever (62.5) at the (refer to Figures 5 and 6)
other end of the charging shaft is securely Trip-free for all drawout circuit breakers
locked by the close latch pawl (62.5.2). and some fixed-mounted circuit breakers
When the closing spring is being charged, The trip coupling rod (62.8 together with
the cam disc (62.3) follows along, and it is 62.8.1 and 62.8.2) permits the immediate
brought into position for closing when the de-coupling of the drive lever (62.6) and the
closing spring is fully charged. jack shaft (63.0) to override closing action
by trip command or by means of the racking
interlocks.
The trip-free coupling rod (62.8) forms a
link between the drive lever (62.6) and the
jack shaft (63.0). The rigidity of this link
depends upon a spring-return latch (62.8.1)
carried within the coupling rod. The latch
pivots within the coupling rod and is
normally positioned to maintain the rigidity
of the coupling rod.

16
Trip-free coupling link (62.8.2) and trip-free Manual operation
coupling lever (62.8.3) cause the spring- Electrically operated vacuum circuit breakers
return latch position to be dependent upon can be operated manually if the control
the normal tripping components and the supply should fail.
racking interlock (if applicable). Thus,
Manually charging the closing spring
whenever a trip command is applied or the
(refer to Figures 13 and 14)
circuit breaker is not in the fully CONNECT
Insert the hand crank (50.0) with the over
or TEST position (for drawout applications),
running coupling pushed forward (50.6)
the trip-free coupling rod is no longer rigid,
through the opening (50.1) onto hand crank
effectively decoupling the drive lever and
coupling (50.5) and turn it clockwise (about
jack shaft. Under these conditions the
48 revolutions) until the closing-spring
vacuum interrupter contacts cannot be
indicator (55.0) shows CHARGED. The hand
closed.
crank is coupled with the charging
Trip-free for the type SDV6 outdoor distri- mechanism via an over-running coupling;
bution circuit breaker and some fixed- thus the operator is not exposed to any risk
mounted circuit breakers should the control supply be restored during
For the type SDV6 outdoor distribution manual charging.
circuit breaker and some other fixed-
mounted circuit breakers, the drawout trip-
free linkage (refer to Figures 7-10) is
replaced with simplified linkage. The trip-
free coupling rod (62.8) is replaced with a
straight coupling rod (refer to Figure 5), and
other parts associated with drawout The special hand crank automatically disengages
interlocking are eliminated. if the spring-charging motor operates. In order to
avoid injuries as a result of the motor suddenly
The parts modified or eliminated are noted
starting up, the circuit breaker spring must only
in the relevant figures. In these circuit be charged manually with the special hand crank
breakers, the trip-free function is (50.0).
accomplished by blocking the movement of
the close latch pawl (62.5.2) when the
manual trip pushbutton is actuated.
Opening (refer to Figure 5)
If the circuit breaker is to be opened
manually, the opening spring (64.0) is
released by pressing the OPEN pushbutton
(54.0). In the case of an electrical command
being given, the trip coil 52T (54.1)
Manual closing (refer to Figure 6)
unlatches the opening spring (64.0).
Press the close button (53.0). The CLOSE/
The opening spring (64.0) turns the jack OPEN indicator (58.0) will then display
shaft (63.0) via lever (63.5); the sequence CLOSED and the closing spring condition
being similar to that for closing. indicator (55.0) will now read DISCHARGED.
Rapid auto-reclosing Manual opening (refer to Figure 6)
Since the closing spring is automatically The opening spring (64.0) is charged during
recharged by the motor operating closing. To open the circuit breaker, press
mechanism when the circuit breaker has the Open pushbutton (54.0) and OPEN will
closed, the operating mechanism is capable be displayed by indicator (58.0).
of an Open-Close-Open duty cycle as
required for rapid auto-reclosing.
The circuit breaker is suitable for use in
applications with a rated reclosing-time
interval of 0.3 seconds, per ANSI/IEEE
C37.06-2009.

17
Figure 7: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED

Item Description
48.0 Insulating coupler
50.3 Charging flange
50.3.1 Driver
53.0 Close pushbutton
62.5.1
62.5 53.1 Close coil 52SRC
62.1 54.0 Open pushbutton
62.3 50.3
54.1 Trip coil 52T
62.2
50.3.1 62.1 Charging shaft
62.2 Crank
62.5.2
53.0 62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1 Pawl roller
64.5* 62.6
53.1 62.2.2 62.5.2 Close latch pawl

64.2.2 62.6 Drive lever

64.0* 62.8 Trip-free coupling rod


62.8.1
62.8.1 Spring-return latch
64.2.1 62.8.2 Trip-free coupling link (draw bar)

62.8.3 54.0 62.8.3 Trip-free coupling lever


62.8.5 Push rod and cam assembly
62.8.2 62.8.6 Interlock lever push rod
62.8* 62.8.7 Interlock lever actuator
64.2* 62.8.8 Trip-free actuator
64.3.1*
63.5* 63.0 Jack shaft
62.8.5
63.1 Lever - phase C
63.5 Lever - phase B
64.5*
63.7 Lever - phase A
63.0*
64.0 Opening spring
63.7 62.8.7
48.0* 63.5* 64.2 Trip-latch pawl
63.5 62.8.6
63.1 64.2.1 Trip-latch pin

62.8.8 64.2.2 Latching pawl-release lever


64.3 Lever
64.3.1 Jack-shaft pawl
64.5 Opening-spring shaft

Footnotes:
* Items moved from position shown in Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
CLOSED, closing spring DISCHARGED on trip operation.
Items moved from position shown in Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN,
closing spring DISCHARGED on closed spring discharge operation.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other
parts associated with drawout interlocking are eliminated.

18
Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
.

Item Description
48.0 Insulating coupler
50.3 Charging flange
50.3.1 Driver
53.0 Close pushbutton
53.1 Close coil 52SRC
54.0 Open pushbutton 62.2
50.3.1
54.1 Trip coil 52T
62.1 62.3
62.1 Charging shaft 50.3

62.2 Crank 62.5


62.5.1
62.2.2 Closing-spring mounting 62.2.2
62.3 Cam disc
62.5 Lever
62.5.1 Pawl roller
62.5.2 Close latch pawl
62.6 Drive lever 64.5*
62.8 Trip-free coupling rod
62.8.1 Spring-return latch
62.8.2 Trip-free coupling link (draw bar)
62.8.3 Trip-free coupling lever 54.1*
62.8.5 Push rod and cam assembly
62.8.6 Interlock lever push rod
62.8.7 Interlock lever actuator
62.8.8 Trip-free actuator 62.8*
63.0 Jack shaft 64.2*
64.3*
63.1 Lever - phase C
63.5*
63.5 Lever - phase B
63.7 Lever - phase A
64.0 Opening spring
63.0*
64.2 Trip-latch pawl
64.2.1 Trip-latch pin 64.5* 63.7*
63.5* 63.5*
64.2.2 Latching pawl-release lever 48.0*
63.1*
64.3 Lever
64.3.1 Jack-shaft pawl
64.5 Opening-spring shaft

Footnotes:
* Items moved from position shown in Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
CLOSED, closing spring CHARGED on trip operation.
Items moved from position shown in Figure 7: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
OPEN, closing spring DISCHARGED on closed spring discharge operation.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other
parts associated with drawout interlocking are eliminated.

19
Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring DISCHARGED

Item Description
48.0 Insulating coupler
53.0 Close pushbutton
53.1 Close coil 52SRC
62.1 Charging shaft
62.2 Crank
62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1
62.5.1 Pawl roller
62.5 62.5.2 Close latch pawl
62.1 62.6 Driver lever

62.2 62.8 Trip-free coupling rod


63.0 Jack shaft
62.5.2 62.3
63.1 Lever - phase C
53.0
63.5 Lever - phase B
63.7 Lever - phase A
64.5 Opening-spring shaft
64.5 62.6
53.1
62.2.2

62.8
64.5

63.7
63.5
63.1

63.0
48.0
63.5

Footnotes:
* Numbered items moved from position shown in Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown)
mechanism OPEN, closing spring DISCHARGED.
1.
 or type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other
F
parts associated with drawout interlocking are eliminated.

20
Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring CHARGED

Item Description
50.3 Charging flange
50.3.1 Driver
62.1 Charging shaft
62.2 Crank
62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1 Pawl roller

62.2
50.3.1
62.3
62.1
62.5 50.3
62.5.1
62.2.2

Footnotes:
*N
 umbered items moved from position shown in Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown)
mechanism CLOSED, closing spring DISCHARGED.
1.
 or type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other
F
parts associated with drawout interlocking are eliminated.

21
Figure 11: Operator sequential operation diagram

Closing Closed
voltage applied. Anti-pumping feature (52Y) assures a continuously applied closing command does not cause
the circuit breaker to reclose automatically after it has tripped out on a fault.

Undervoltage device Spring-charge motor Continuous


27 picks up. (88.0) energized. closing command.

Closing spring is
fully charged.
Close coil (52SRC)
unlatches the closing
LS21 and LS22 LS9 closes close
L3 opens in series LS41 closes to spring and the circuit
operate to circuit only when
with anti-pump signal closing spring breaker closes.
de-energize spring- closing spring is
relay (52Y). is charged.
charging motor. fully charged.
Motor cutoff switches
LS21, LS22 and LS3 are
Circuit Circuit closed because the
breaker breaker closing spring is
is closed. Close coil is
No action! Open is open. discharged.
Closing actuated through
52b in series with
command the closed 52b
close coil (52SRC)
when contacts and the Before the spring-
blocks closing
two normally closed charge motor has
spring-release.
Closing contacts of the anti- recharged the closing
spring is pump relay (52Y). spring and opened LS3,
not charged. anti-pump relay (52Y)
No action! Anti- picks up and seals in.
pump relay (52Y)
The closing spring is The opening spring
picks up through
unlatched. is charged. The anti-pump relay
the closed LS3
contact and opens. (52Y) opens two
contacts in series with
the close coil (52SRC).
LS21 and LS22 close
52a contacts in
Circuit breaker to energize motor
series with the trip
auxiliary contacts The circuit breaker (88). LS3 closes and
coil (52T) close to
52a and 52b change closes. LS9 opens to cancel The close coil (52SRC)
enable a trip
state. closing spring is now blocked and
operation.
signal. cannot be activated
until springs are fully-
Rapid auto-reclosing. The closing spring is automatically recharged as described above. charged and close
Therefore, when the circuit breaker is closed both of its springs are charged. The closing command is removed.
spring charges the opening spring during closing. As a result, the circuit breaker is capable of
an O-0.3s-CO-3 min-CO operating cycle. The dashed line shows the operating sequence
Footnote:
initiated by the closing command. 1.
Optional items.
Tripping
Trip
command.

Undervoltage device (27) is Secondary shunt-


Trip coil (52T) can Undervoltage device (27) is
activated by closing NO contact, release (dual-trip)
only be activated activated by opening a NC
shorting the 27 coil. The NO function activated
when in series contact in series with 27 or by
contact is only effective with the by remote trip
connected 52a loss or reduction of tripping
circuit breaker closed. Resistor command contact
contact is closed. voltage.1
required.1 NO.1

Trip coil (52T) Undervoltage device Secondary release


unlatches the 27 unlatches the unlatches the
opening spring. opening spring.1 opening spring.1

Circuit breaker trips.

22
The schematic shown in Figure 14 is
intended to aid in understanding the
mechanism operation discussed in this 50.0 50.5 53.0
instruction manual. It shows a drawout
circuit breaker as an example. Refer to the
schematic diagram furnished with your
circuit breaker for specific information.
Close coil (52SRC)
The close coil (3AY1510) is a standard 55.0
54.0
component of the circuit breaker that is
used to unlatch the stored energy of the
closing spring and thus close the circuit
breaker electrically. It is available for either
ac or dc operation. After completion of a
closing operation, the close coil is
de-energized internally. If operated with ac
voltage, a rectifier is installed in the circuit
breaker. Item Description

Trip coil (52T) 50.0 Hand crank


The trip coil (3AY1510) is a standard 50.5 Manual spring-charging port
component of the circuit breaker. The 53.0 Manual CLOSE pushbutton
electrically supplied tripping signal is passed 54.0 Manual OPEN (TRIP)) pushbutton
on to the trip-latching mechanism by means
55.0 CHARGED/DISCHARGED indicator
of a direct action solenoid armature and the
circuit breaker is thus opened. It is available
for either ac or dc operation. After Figure 12: Use of manual spring-operation crank
completion of an opening operation, the
trip coil is de-energized internally. If
operated with ac voltage, a rectifier is
installed in the circuit breaker.
50.5

50.6

50.0

Item Description
50.0 Hand crank
50.5 Manual spring-charging port
50.6 Over-running coupling

Figure 13: Use of manual spring-charging crank

23
Figure 14: Typical elementary diagram

(+)
01
01 T
C

SD16 SD13

W 21 G R
LS21 41
22 52b
42
SD3 SD4 SD1
22 21 14
Motor 88 52Y LS3 52Y
21 22 13
13 31 24
LS41 31 52b 52a
DC supply 14 52Y 32 23
21 32
LS22
22 A1 A1 A1
52SRC 52Y 52T
22 22 A2 A2 SD14 A2
MI1 MI2 34
13 52a
21 21 LS9 33
TB 14
1 SD2
2
3
4
5
SD15 6

(-)

SD11 SD9 SD7 SD5

54 64 91 101 74 84 111 121


52a 52a 52b 52b 52a 52a 52b 52b
53 63 92 102 73 83 112 122
SD12 SD10 SD8 SD6

Standard:
Fuses in close circuit. Slugs in trip circuit (fuses optional).

Shown with springs discharged, trip-latch reset, circuit breaker open, connect or withdrawn position.

Item Description Item Description


88.0 Spring-charging motor LS Spring-charged switch
52a Auxiliary switch is open when circuit breaker is open MI1, M12 Mechanical interlock
52b Auxiliary switch is closed when circuit breaker is open 01/C Control switch (CLOSE)
52SRC Spring-release coil (CLOSE) 01/T Control switch (TRIP)
52T Shunt-trip coil G Green indicating light (TRIP)
R Red indicating light (CLOSED)
52Y Closing relay (anti-pump)
W White indicating light (spring-charged)

24
Indirect releases - secondary shunt
release (dual trip) (52T1) or undervoltage
(27.0)
33.0
The indirect release provides for the 23.0
conversion of modest control signals into 31.0
25.0 27.0
powerful mechanical-energy impulses. It is 21.0
primarily used to open medium-voltage 11.0
13.0 7.0
circuit breakers while functioning as a
9.0 1.0
secondary shunt-release (dual trip) or
15.0
undervoltage device.
These releases are mechanical energy-
6.0
storage devices. Their internal springs are
charged as a consequence of the circuit 3.0
breaker mechanism operation. This energy
is released upon application or removal (as
Item Description Item Description
appropriate) of applicable control voltages
(refer to Figures 15, 16 and 17). 1.0 Magnet core 15.0 Tripping pin
3.0 Housing 21.0 Locking pin
The secondary shunt-release and
undervoltage release mounts to the 6.0 Mounting holes 23.0 Striker pin
immediate right of the trip coil (54.1). 7.0 Magnet coil 25.0 Latch

Secondary shunt-release (52T1) (refer to 9.0 Magnet armature 27.0 Spring


Figure 15) 11.0 Tension spring 31.0 Striker-pin spring
A secondary shunt-release (extra-trip coil) 13.0 Adjusting screw (factory set) for 11.0 33.0 Terminal block
(3AX1101) is used for electrical opening of
the circuit breaker by protective relays or Figure 15: Construction of secondary shunt release (shown charged)
manual control devices when more than
one trip coil is required. The second trip coil
is generally connected to a separate
auxiliary supply (dc or ac) from the control
supply used for the normal trip coil.
29.0
Undervoltage release (27.0) (refer to
Figures 16 and 17)
The undervoltage release (3AX1103) is used
for continuous monitoring of the tripping 23.0
supply voltage. If this supply voltage falls
excessively, the undervoltage release will
provide for automatic tripping of the circuit
breaker.
25.0 27.0
The undervoltage device may be used for
manual or relay tripping by employing a
contact in series with undervoltage device 21.0
holding coil. Relay tripping may also be
achieved by employing a normally open
contact in parallel with the holding coil. If
this scheme is used, a resistor must be
provided to limit current when the normally
Item Description Item Description
open contact is closed.
21.0 Locking pin 25.0 Latch
Secondary shunt and undervoltage releases
23.0 Striker pin Undervoltage enable/disable set-
are available for all standard ANSI/IEEE 29.0
25.0 Latch ting screw (undervoltage only)
control voltages.
Figure 16: Latch details (shown charged)

25
Construction and mode of operation of
secondary shunt-release and
Position A: locked (disabled)
undervoltage release (refer to Figures 15,
16 and 17)
The release consists of a spring-power
stored-energy mechanism, a latching device
A 29.0
23.0 and an electromagnet.
B These elements are accommodated side by
side in a housing (3.0), with a detachable
cover and three through-holes (5.0) for
Position B: unlocked (enabled) (operating position) fastening screws. The supply leads for the
trip coil are connected to a terminal block
Item Description
(33.0).

23.0 Striker pin The energy-storing mechanism consists of


Undervoltage A the striker pin (23.0) and its operating
enable/ 23.0 spring (31.0), which is mostly located inside
29.0 B 29.0
disable the striker pin (23.0). When the spring is
setting screw compressed, the striker pin is held by a latch
(25.0), whose sloping face is forced against
the appropriately shaped striker pin (23.0)
Cancel the lock for the undervoltage release by shifting the locking screw (29.0)
from A (disable) to B (enable). by spring (27.0). The other end of the latch
(25.0) is supported by a partly milled
locking pin (21.0), pivoted in the cover
sheets of the magnet armature (9.0). The
armature (9.0) is pivoted in front of the
Figure 17: Undervoltage lock/operate selection
poles of the U-shaped magnet core, (1.0)
and is pulled away from it by the tension
spring (11.0).
If the magnet coil (7.0) of the secondary
01
T
shunt release 3AX1101 is energized by a trip
signal, or if the tripping pin (15.0) is
mechanically actuated, magnet armature
SD5 (9.0) is swung against the pole faces. When
this happens, the latch (25.0) loses its
support and releases the striker pin (23.0)
24
52a
that is forced out by the spring (31.0).
23
On the undervoltage release 3AX1103, the
120 or 240 Vac Capacitor latch (25.0) is held by the locking pin (21.0)
A1 (+)
supply as long as the armature (9.0) is energized. If
52T 1
(-) the circuit of the magnet coil (7.0) is
A2 Resistor interrupted, the armature (9.0) drops off,
34
2 thus causing the latch (25.0) to lose its
52a
(+)
33 support and release the striker pin (23.0).
Rectifier
(-)
Following every tripping operation, the
striker pin (23.0) must be reset to its normal
Capacitor trip
position by loading the spring (31.0). This
takes place automatically via the operating
mechanism of the circuit breaker.

Figure 18: Capacitor-trip device

26
Since the striker pin of the undervoltage Shock absorber
release 3AX1103 is latched only when the Circuit breakers are equipped with a
armature is energized, the undervoltage hydraulic shock absorber (61.8) (refer to
release is provided with a screw (29.0), for Figure 5). The purpose of this shock
locking the striker pin (23.0) in the normal absorber is to limit overtravel and rebound
position for adjusting purposes or for of the vacuum interrupter movable contacts
carrying out trial operations during circuit during the conclusion of an opening
breaker servicing. Position A (locked) operation. The shock absorber action affects
disables the undervoltage release. Position B only the end of an opening operation.
(unlocked) is the normal operating position.
Auxiliary switch (52a/b)
Capacitor trip device Figure 6 shows the circuit breaker mounted
The capacitor trip device is an auxiliary auxiliary switch (68.0). This switch provides
tripping option providing a short-term auxiliary contacts for control of circuit
means of storing adequate electrical energy breaker closing and opening functions.
to ensure circuit breaker tripping. If Contacts are available for use in relaying
provided, a capacitor trip device must be and external logic circuits. This switch is
located on the drawout truck or in the driven by linkage (68.1) connected to the
stationary circuit breaker enclosure, as jack shaft (63.0). The auxiliary switch
space is not available inside the type 3AH contains both b (normally Closed) and a
operator housing. (normally Open) contacts. When the circuit
breaker is open, the b contacts are closed
This device is applied in circuit breaker
and the a contacts are open.
installations lacking independent auxiliary
control power or station battery. In such Spring-charging motor (88.0)
installations, control power is usually Spring-charging motors (50.4) (refer to
derived from the primary source. In the Figure 5) are available for either ac or dc
event of a primary ac source fault or operation. If operated with ac voltage, a
disturbance the capacitor trip device will rectifier is installed in the circuit breaker.
provide short-term tripping energy for
circuit breaker opening due to protective
relay operation or operation of a circuit
breaker control switch.
The capacitor trip converts 120 or 240 Vac
control voltage to a dc full-wave voltage
that is used to charge a large capacitor to
the peak of the converted wave (refer to
Figure 18).

27
Maintenance

Hazardous voltage and high-speed moving parts.

Will cause death, serious injury and property damage.

De-energize before working on this equipment.

Read instruction manuals, observe safety instructions and use qualified


personnel.

Introduction and maintenance intervals Regardless of the length of the maintenance


Periodic inspections and maintenance are and lubrication interval, Siemens
essential to safe and reliable operation of recommends that circuit breakers should be
the circuit breaker operator module. inspected and exercised annually.
When circuit breakers are operated under For the safety of maintenance personnel as
usual service conditions, maintenance and well as others who might be exposed to
lubrication are recommended at ten-year hazards associated with maintenance
intervals (five-year intervals for the type activities, the safety related work practices
SDV6 outdoor distribution circuit breaker) or of NFPA 70E, chapters 1 and 2, should
at the number of operations indicated in always be followed when working on
Table 2. Usual and unusual service electrical equipment.
conditions for medium-voltage metal-clad
Maintenance personnel should be trained in
switchgear (includes circuit breaker module)
the safety practices, procedures and
are defined in ANSI/IEEE C37.20.2, sections
requirements that pertain to their respective
4 and 8.1, ANSI/IEEE C37.04, section 4 and
job assignments.
ANSI/IEEE C37.010, section 4. Generally,
usual service conditions are defined as an This instruction manual should be reviewed
environment where the equipment is not and retained in a location readily accessible
exposed to excessive dust, acid fumes, for reference during maintenance of this
damaging chemicals, salt air, rapid or equipment.
frequent changes in temperature, vibration,
The user must establish a periodic
high humidity and extreme temperatures.
maintenance program to ensure trouble-free
The definition of usual service conditions and safe operation. The frequency of
is subject to a variety of interpretations. inspection, periodic cleaning and a
Because of this, you are best served by preventive maintenance schedule will
adjusting maintenance and lubrication depend upon the operation conditions.
intervals based on your experience with the NFPA publication 70B, Electrical equipment
equipment in the actual service maintenance may be used as a guide to
environment. establish such a program.

28
Failure to maintain the equipment can result in death, serious injury, property damage or product
failure, and can prevent successful functioning of connected apparatus.

The instructions contained herein should be carefully reviewed, understood and followed.

The maintenance tasks in Table 1 must be performed regularly.

Note: A preventive maintenance program is Recommended maintenance and


not intended to cover reconditioning or lubrication
major repair, but should be designed to Periodic maintenance and lubrication should
reveal, if possible, the need for such actions include all the tasks shown in Table 1.
in time to prevent malfunctions during Recommended procedures for each of the
operation. listed tasks are provided in this section of
the instruction manual.
Recommended hand tools
Metric hardware is used on these circuit The list of tasks in Table 1 does not
breakers. represent an exhaustive survey of
maintenance steps necessary to ensure safe
The following list of hand tools describes
operation of the equipment. Particular
those normally used in disassembly and
applications may require further procedures.
re-assembly procedures:
Should further information be desired or
Open-end wrenches: 7, 8, 10, 13, 17, 19 should particular problems arise that are not
and 24 mm covered sufficiently for the Users purposes,
the matter should be referred to the local
Open-end wrench: 55 mm used to
Siemens sales office.
exchange shock absorber (Quantity: two
pieces are required for the task) Checks of the primary power path
The primary power path consists of the
Sockets: 7, 8, 10, 13 and 17 mm
three vacuum interrupters, the three upper
Socket: 36 mm (used for replacing post and the three lower primary disconnects
insulators) (drawout only) or bus connections
(stationary only). These components are
Deep sockets: 19 and 24 mm
checked for cleanliness and condition. The
Hex keys: 5, 6, 8 and 10 mm vacuum interrupters are also checked for
vacuum integrity.
Torque wrench: 0-150 Nm
(0-100 ft-lbs) Some test engineers prefer to perform the
contact-erosion check during the manual
Screwdrivers: 0.032 x 1/4 in wide and
spring-charging check of the operator, since
0.055 x 7/16 in wide
charging of the springs is necessary to place
Pliers the contacts in the CLOSED position.
Light hammer Also, the vacuum-integrity check is usually
performed in conjunction with the high-
Dental mirror
potential tests.
Flashlight
These instructions assume these tests
Drift pins: 1/8, 3/16 and 1/4 in (contact-erosion/manual spring-charging
check and vacuum-integrity/high-potential
Retaining ring plier (external type, tip
tests) will be combined as described.
diameter 0.038 in).
29
The use of unauthorized parts in the repair of the equipment, or tampering by unqualified personnel
can result in hazardous conditions, that can result in death, serious injury or property damage.

Follow all safety instructions contained herein.

Inspection items and tests Cleanliness check


Primary-power path checks Figure 2 is a side view of the circuit breaker
with the insulating barriers removed (if
 leanliness check
C
furnished) to show the vacuum interrupter,
Inspection of flexible connectors and the upper and lower connection pads.
Stored-energy operator-mechanism checks
All of these components must be clean and
Maintenance and lubrication free of dirt or any foreign objects. Use a dry
 astener check
F lint-free cloth. For stubborn dirt, use a clean
cloth dipped in isopropyl alcohol (except for
Manual spring-charging check the vacuum interrupters). For stubborn dirt
Contact-erosion check on a vacuum interrupter use a cloth and
Electrical-control checks warm water and a small amount of mild
liquid-household detergent as a cleaning
Wiring and terminals checks
agent. Dry thoroughly using a dry lint-free
Secondary-disconnect check (drawout only) cloth.
Automatic spring-charging check Inspection of flexible connectors
Electrical close and trip check Inspect the flexible connectors that connect
the bottom movable contacts of the vacuum
Vacuum-integrity check
interrupters to the lower connection pad for
High-potential test tightness and absence of mechanical
Insulation test damage, burning or pitting.
Contact-resistance test
Checks of the stored-energy operator
Inspection and cleaning of circuit-breaker mechanism
insulation The stored-energy operator checks are
Functional tests divided into mechanical and electrical
checks for simplicity and better
Table 1: Maintenance tasks organization. This first series of checks
determine if the basic mechanism is clean,
lubricated and operates smoothly without
control power. The contact-erosion check of
the vacuum interrupter is also performed
during these tasks.

30
Maintenance and lubrication Lubricants composed of ester oils and
Table 2 gives the recommended lithium thickeners will generally be
maintenance intervals for circuit breakers. compatible.
These intervals assume that the circuit
 or all lubrication (except electrical
F
breaker is operated under usual service
moving or sliding surfaces), use one of
conditions as discussed in ANSI/IEEE
the following:
C37.20.2, section 4 (for drawout circuit
breakers) or ANSI/IEEE C37.04, section 4 and  lber Isoflex Topas L32
 K
elaborated in ANSI/IEEE C37.010, section 4 (part 3AX11333H)
(for outdoor distribution circuit breakers).
 Klber Isoflex Topas L32N (spray)
The maintenance and lubrication interval is
(part 15-172-879-201).
the lesser of the number of closing
operations or the time interval since last Source:
maintenance.
 lber Isoflex Topas L32 or L32N:
K
Klber Lubrication North America L.P.
www.klueber.com.
Number of years/closing Fastener check
Circuit
operations (whichever comes Inspect all fasteners for tightness. Both
breaker type
first) locknuts and retaining rings are used.
SDV6 5 years/10,000 operations Replace any fasteners that appear to have
been frequently removed and replaced.
All others 10 years/10,000 operations
Manual spring-charging and contact-
Table 2: Maintenance and lubrication schedule
erosion checks
Perform the manual spring-charging check
contained in the section describing the
installation check and initial functional tests
(refer to pages 9-10). The key steps of this
The vacuum interrupter operator
procedure are repeated here:
mechanism is shown in Figure 19, with the
front cover removed to show construction 1. Insert the hand-charging crank into the
details. Both the opening spring and the manual-charge socket at the front of the
closing spring are shown. The movable end operator control panel. Turn the crank
of the closing spring is connected to a crank clockwise (about 48 revolutions) to
arm. The movable end of the opening spring charge the closing spring. Continue
is connected to the jack shaft by a pull rod. cranking until the CHARGED flag appears
in the window of the spring indicator.
Clean the entire stored-energy operator
mechanism with a dry, lint-free cloth. 2. P
 ress the Close (black) pushbutton. The
contact-position indicator on the
Check all components for evidence of
operator control-panel should indicate
excessive wear. Place special attention upon
that the circuit breaker contacts are
the closing spring-crank and the insulating
CLOSED.
couplers and linkages.
3. Perform the contact-erosion check.
Lubricate all non-electrical moving or sliding
Contact erosion occurs when high fault-
surfaces with a light coat of synthetic grease
currents are interrupted. Determination
or oil.
of acceptable contact condition is
checked by the visibility of the white
contact-erosion mark shown in Figure
20. The white contact-erosion mark is
located on the movable stem of the
vacuum interrupter, near the plastic
guide-bushing.

31
Figure 19: Operator mechanism lubrication

Klber L32 or Klber L32N

Typical for all three-phases

32
High-speed moving parts.

Can result in serious injury.

Tripping spring is charged. If trip latch is moved, the stored-energy springs


will discharge rapidly.

Stay clear of circuit breaker components that are subject to sudden, high-
speed movement.

The contact-erosion check procedure is:


a) Be sure the circuit breaker primary
contacts are CLOSED.
b) Observe the white contact-erosion
mark (refer to Figure 20) of each pole.
When any part of the white contact-
erosion mark is visible, contact wear
is within acceptable limits.
4. Press the red Open pushbutton after
completing the contact-erosion check.
Visually verify the Discharged condition
of the closing spring and that the circuit
breaker contacts are OPEN.
5. Press the black Close pushbutton.
Nothing should happen. The manual-
spring check should demonstrate
smooth operation of the operating
Figure 20: Contact-erosion check mark dot circled in mechanism.
orange (shown with circuit breaker OPEN)
Electrical control checks
The electrical controls of the circuit breaker
should be checked during inspections to
verify absence of any mechanical damage,
and proper operation of the automatic
spring-charging and Close and Trip circuits.
Unless otherwise noted, all of these tests
are performed without any control power
applied to the circuit breaker.

33
Hazardous voltage and high-speed moving parts.

Will cause death, serious injury and property damage.

De-energize before working on this equipment.

Read instruction manuals, observe safety instructions and use qualified


personnel.

Check of the wiring and terminals Electrical close and trip check (control
1. Physically check all of the circuit breaker power required)
wiring for evidence of abrasion, cuts, A check of the circuit breaker control circuits
burning or mechanical damage. shall be performed. This check is made with
the circuit breaker energized by control
2. Check all terminals to be certain they are
power either from the switchgear or an
solidly attached to their respective
external control-power source.
device.
1. O
 nce the circuit breaker springs are
Automatic spring-charging check (control
charged, move the switchgear-mounted
power required)
Close/Trip switch to the Close position.
Repeat the automatic spring-charging check
Verify by both the sound of the circuit
described in the section describing the
breaker closing and by the main contact
installation check and initial functional tests
status indicator that the circuit breaker
(refer to pages 9-10).
contacts are CLOSED.
Primary tasks of this check are:
2. As soon as the circuit breaker has closed,
1. The circuit breaker must be energized the automatic spring-charging process is
with control power for this check. repeated.
2. Energize the control-power source. 3. A
 fter a satisfactory close operation is
verified, move the switchgear-mounted
3. When control power is connected to the
Close/Trip switch to the Trip position.
circuit breaker, the closing spring should
Verify by both the sound of the circuit
automatically charge. Visually verify that
breaker opening and by the main
the closing spring is charged.
contact status indicator that the circuit
Note: A temporary source of control power breaker contacts are OPEN.
and test leads may be required if the
4. A
 fter a satisfactory open operation is
control-power source has not been
verified, hold the circuit breaker manual
connected to the switchgear or circuit
Trip button and apply and maintain an
breaker. When control power is connected
electrical close signal. The circuit breaker
to the circuit breaker, the closing spring
should close, immediately trip, the close
should automatically charge.
spring should charge, and the circuit
breaker should not attempt to close
again.
Completion of these checks demonstrates
satisfactory operation of auxiliary switches,
internal relays and open and close coils.

34
Table 3: Typical vacuum interrupter contact life expectancy

Right hand limit


Rated maximum Interrupting class Vacuum
Rated short-circuit current Graph of curve (refer to
voltage kV MVA interrupter type
Figure 21)1
VS-17006 A 36
4.76 250 29 kA @ 4.76 kV; 36 kA @ 3.85 kV
VS-17040 E 36
4.76 350 41 kA @ 4.76 kV; 49 kA @ 4.0 kV VS-15052 B 49
8.25 500 33 kA @ 8.25 kV; 41 kA @ 6.6 kV VS-15052 B 41
15.0 500 18 kA @ 15.0 kV; 23 kA @ 11.5 kV VS-17006 A 23
VS-15052 B 36
15.0 750 28 kA @ 15.0 kV; 36 kA @ 11.5 kV
VS-17040 E 36
15.0 1,000 37 kA @ 15.0 kV; 48 kA @ 11.5 kV VS-15052 B 48
38.0 1,500 21 kA @ 38.0 kV; 35 kA @ 23.0 kV VS-30030 D 35
Right hand limit
Rated maximum Interrupting class Vacuum
Rated short-circuit current Graph of curve (refer to
voltage kV kA interrupter type
Figure 21)1
VS-17006 A 31.5
4.76 31.5 31.5
VS-17040 E 31.5
VS-15052 B 40
4.76 40 40
VS-17040 E 40
4.76 50 50 VS-15052 B 50
4.76 63 63 VS-17085 F 63
VS-15052 B 40
8.25 40 40
VS-17040 E 40
15.0 20 20 VS-17006 A 20
15.0 25 25 VS-17006 A 25
VS-17006 A 31.5
15.0 31.5 31.5
VS-17040 E 31.5
VS-15052 B 40
15.0 40 40
VS-17040 E 40
15.0 50 50 VS-15052 B 50
15.0 63 63 VS-17085 F 63
15.5 20 20 VS-25008 C 20
15.5 25 25 VS-25008 C 25
15.5 31.5 31.5 VS-15052 B 31.5
15.5 40 40 VS-15052 B 40
27.6 20 20 VS-25008 C 20
27.6 25 25 VS-25008 C 25
38.0 20 20 VS-30030 D 20
38.0 25 25 VS-30030 D 25
38.0 31.5 31.5 VS-30041 D 31.5
38.0 40 40 VS-30041 D 40

Footnote:
1.
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).

35
Figure 21: Typical vacuum interrupter contact life curves

Load graph "A" vacuum interrupter type VS-17006


Load graph "C" vacuum interrupter type VS-25008
Load graph "E" vacuum interrupter type VS-17040

Permissible operating cycles

100,000

50,000

20,000

10,000

5,000

2,000

1,000

500

200

100

50

20
C A E
10
1 2 5 10 20 25 31.5 40 50 100

Breaking current (symmetrical value)

Note: Right-hand vertical segment of curve is located at the maximum


symmetrical interrupting current rating of the circuit breaker, as indicated in
Table 3.

36
Figure 21: Typical vacuum interrupter contact life curves (continued)

Load graph "B" vacuum interrupter type VS-15052


Load graph "D" vacuum interrupter types VS-30030 and VS-30041
Load graph "F" vacuum interrupter type VS-17085

Permissible operating cycles

100,000

50,000

20,000

10,000

5,000

2,000

1,000

500

200

100

50

20
D B F
10
1 2 5 10 20 40 50 63 100

Breaking current (symmetrical value)

Note: Right-hand vertical segment of curve is located at the maximum


symmetrical interrupting current rating of the circuit breaker, as indicated in
Table 3.

37
Checks of the spring-charging motor Vacuum-integrity check (using
(88.0) mechanical test) (refer to Figure 22)
No additional checks of the spring-charging Before putting the circuit breaker into
motor are necessary. If it is necessary to service, or if a vacuum interrupter is
remove or replace the spring-charging suspected of leaking as a result of
motor, torque motor-mounting hardware to mechanical damage, check the vacuum
7.3-8 ft-lb (10-11 Nm). integrity either mechanically as described in
this section, or alternatively, electrically
Anti-pump relay
using a high-potential test set as described
If it is necessary to remove the connections
in the next section.
to the anti-pump relay, use care to avoid
damaging the relay. Replace the relay if the Open and isolate the circuit breaker and
relay terminals are damaged or loose in the detach the insulating coupler (48.0) from
relay body. lever (48.6) (refer to Figure 22).
Vacuum interrupters The atmospheric pressure will force the
The life expectancy of vacuum interrupters moving contact of a hermetically sealed
is a function of the numbers of interruptions vacuum interrupter into the Closed
and magnitude of current interrupted (refer position, causing lever (48.6) to move into
to Table 3 and Figure 21). the position shown in Figure 21.
The vacuum interrupters must be replaced A vacuum interrupter may be assumed to be
before the number of mechanical operations intact if it shows the following
(listed in Table 2) are reached, or when the characteristics:
contacts have been eroded beyond allowed
1. An appreciable closing force has to be
limits. Vacuum interrupter replacement
overcome when lever (48.6) is moved to
procedures are detailed in the following
the Open position by hand (refer to
maintenance instructions.
Figure 22);
The vacuum interrupter contact life curves
2. When the lever is released, it must
(refer to Figure 21) are offered as a guide to
automatically return to the Closed
expected life.
position with an audible sound as the
contacts touch.
After checking the vacuum, reconnect the
lever (48.6) to the insulating coupler (48.0)
(refer to Figure 22).

High-potential tests employ hazardous voltages.

Will cause death and serious injury.

Follow safe procedures, exclude unnecessary personnel and use safety


barriers. Keep away from the circuit breaker during application of test
voltages. Disconnect the split plug jumper from between the circuit breaker
and switchgear before conducting high-potential tests.

38
Vacuum interrupters may emit X-ray radiation.

Can result in serious injury.

Keep personnel more than six feet away from a circuit breaker under test.

High-potential tests High-potential test voltages


The next series of tests (vacuum-integrity The voltages for high-potential tests are
test and insulation tests) involve use of shown in Table 4.
high-voltage test equipment. The circuit
Note: This test includes not only the
breaker under test should be inside a
vacuum interrupter, but also the other
suitable test barrier equipped with warning
insulation components in parallel with the
lights.
vacuum interrupter. These include the post
Vacuum-integrity check (using dielectric insulators and the insulating coupler, as well
test) as the insulating (tension) struts between
A high-potential test is used to verify the the upper and lower vacuum interrupter
vacuum integrity of the circuit breaker. The supports. If these insulation components are
test is conducted on the circuit breaker with contaminated or defective, the test voltage
its primary contacts in the Open position. will not be sustained. If so, clean replace the
affected components, and retest.
Vacuum integrity test procedure
1. Observe safety precautions listed in the
danger and warning advisories. Table 4: High-potential test voltages
Construct the proper barrier and
warning light system. Equipment Equipment rated
Maximum ac rms Maximum dc
maximum voltage power-frequency
2. G
 round the frame of the circuit breaker, test voltage kV average test voltage
rating kV withstand kV (rms)
and ground each pole not under test.
4.76 19 14 20
3. A
 pply test voltage (refer to Table 4)
across each pole for one minute (circuit 8.25 36 27 38
breaker Open).
4. If the pole sustains the test voltage for 15.0 36 27 38
that period, its vacuum integrity has
been verified. 15.5 50 38 53

Note: Do not use dc high-potential testers 27.6 60 45 64


incorporating half-wave rectification. These
devices produce high peak voltages. 38 80 60 85
High peak voltages will produce X-ray
radiation. DC testers producing excessive
peak voltages also show erroneous readings
of leakage current when testing vacuum
circuit breakers.

39
Item Description
48.0 Insulating coupler
48.6 Lever
Detach lever (48.6) and insulated
Step 1
48.0 coupler (48.0)
Primary contact CLOSED position and
Step 2 Step 2
insulated coupler disconnected
48.6
Primary contact OPEN position (forced 48.0
Step 3 Operating
open by manual pressure) 48.0
48.6 position
Step 2 Step 1
Step 3
48.0
Upper connector pad

Primary contact
48.6 resistance test

Lower connector pad


48.0

3AH vacuum circuit breaker operator 3AHc vacuum circuit breaker operator

Figure 22: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance test

As-found insulation and contact Insulation and contact-resistance test


resistance tests equipment
As-found tests verify the integrity of the In addition to the high-potential test
circuit breaker insulation system. Megger* equipment capable of test voltages as listed
or insulation resistance tests and contact- in Table 4, the following equipment is also
resistance tests conducted on equipment required:
prior to installation provide a basis of future
 C high-potential tester with test voltage
A
comparison to detect changes in the
of 1,500 volts, 60 Hz
protection afforded by the insulation
system. A permanent record of periodic  est equipment for contact-resistance
T
as-found tests enables the maintenance tests.
organization to determine when corrective
actions are required by watching for
significant deterioration in insulation
resistance, or increases in contact
resistance.
* Megger is a registered trademark of
Megger Group, Ltd.

40
Insulation and contact-resistance test Inspection and cleaning of circuit breaker Current rating
Contact
procedure insulation resistance
A
Micro-Ohms
1. Observe safety precaution listed in the 1. Perform the spring-discharge check
danger and warning advisories for the (refer to page 9) on the circuit breaker 1,200 35
vacuum integrity check tests (refer to after all control power is removed. The
2,000 30
pages 38-39). spring-discharge check consists of:
3,000 30
2. Close the circuit breaker. Ground the a) P
 ressing the red Open pushbutton
frame of the circuit breaker, and ground
b) Pressing the black Close pushbutton Table 5: Maximum contact-resistance
each pole not under test. Use manual
charging, closing and tripping c) Pressing again the red Open
procedures. pushbutton.
3. Apply the proper ac or dc (refer to Table All of these controls are on the circuit
4) high-potential test voltage between a breaker front panel (refer to Figure 1).
primary conductor of the pole and Visually verify the Discharged condition
ground for one minute. of the springs.
4. If no disruptive discharge occurs, the 2. Remove any inter-phase and outer-phase
insulation system is satisfactory. barriers if furnished (applicable for
certain types only).
5. After test, ground both ends and the
middle of each vacuum interrupter to 3. Clean barriers and post insulators using
dissipate any static charge. clean cloth dipped in isopropyl alcohol.
6. For drawout applications, connect all 4. Replace all barriers. Check all visible
points of the secondary disconnect with fasteners again for condition and
a shorting wire. For stationary tightness.
applications, disconnect secondary
Note: Do not use any cleaning compounds
circuits for the operating mechanism by
containing chlorinated hydrocarbons, such
disconnecting the multiple pin-plug at
as: trichlorethylene, perchlorethylene or
the upper right corner of the operator,
carbon tetrachloride.
and connect all pins on the operator side
with a shorting wire. Connect the These compounds will damage the
shorting wire to the high-potential lead phenylene ether copolymer material used in
of the high-voltage tester, and ground the barriers and other insulation on the
the circuit breaker housing. Starting circuit breaker.
with zero voltage, gradually increase the
Functional tests
test voltage to 1,500 volts rms, 60 Hz.
Refer to the installation checklist in the
Maintain test voltage for one minute.
installation checks and initial functional
Alternatively, the test may be conducted
tests section of this instruction manual
at 1,800 volts rms for one second.
(refer to pages 9-10). Functional tests
7. If no disruptive discharge occurs, the consist of performing at least three manual
secondary control insulation level is spring-charging checks and three automatic
satisfactory. spring-charging checks. After these tests are
complete, and the springs are fully
8. Disconnect the shorting wire, and
discharged, all fasteners and connections
reattach the multiple pin-plug (if
are checked again for tightness and
applicable).
condition.
9. Perform
 contact-resistance tests of the
primary contacts. The resistance should
be read between the lower and upper
connection pads (refer to Figure 22).
Contact resistance should not exceed
the values listed in Table 5.

41
Overhaul
Circuit Closing Introduction c) Install replacement coils with new M4
breaker type operations The following procedures along with the x 10 hex-head screws (Siemens part #
troubleshooting charts in this instruction 00-000-443-820) and new lock
10,000 manual (refer to pages 47-51), provide washers for M4 (Siemens part #
SDV6
operations maintenance personnel with a guide to 00-000-288-316).
All others
10,000 identifying and correcting possible
operations d) The coil-mounting screws must be
malfunctions of the circuit breaker.
installed using thread locking
Table 6: Overhaul schedule
Circuit breaker overhaul adhesive (Loctite #222, Siemens part
Table 6 gives the recommended overhaul 15-133-281-007) and primer (Loctite
schedule type 3AH operating mechanisms. primer T (#7471), Siemens part
These intervals assume that the circuit 15-133-281-005).
breaker is operated under usual service
e) C
 onnect wires to coils with new wire
conditions as discussed in ANSI/IEEE
terminals (Siemens part #
C37.20.2 section 4 (for drawout circuit
15-171-600-002).
breakers) or ANSI/IEEE C37.04 section 4 and
elaborated in C37.010 section 4 (for 3. L ubricate operating mechanism
outdoor distribution circuit breakers). If the according to maintenance and
circuit breaker is operated frequently, the lubrication information (refer to page
overhaul interval in Table 6 may coincide 32).
with the maintenance interval in Table 2.
4. W
 hen work is finished, operate circuit
Replacement at overhaul breaker and close and open several
The following components are replaced times, and check that all screw
during an overhaul of the circuit breaker, connections are tight.
when required:
Replacement of vacuum interrupters
Vacuum interrupters as determined by It is recommended that vacuum interrupters
vacuum integrity test, contact erosion or be replaced only by a qualified Siemens field
according to overhaul schedule (refer to service representative. The information in
Table 6) the following sections is provided to aid in
understanding the replacement procedures.
Close coil, 52SRC
Vacuum interrupters for type 3AH rated
Trip coil, 52T
63 kA interrupting or rated 3,000 A
 rip-free drive bar mechanism (if
T continuous current and all type 3AHc
applicable). operators require special expertise for
replacement and must be replaced only by a
When these parts are changed, locking
qualified Siemens field service
devices must also be removed and replaced.
representative. Accordingly, detailed
These include lock washers, retaining rings,
instructions for replacement vacuum
retaining clips, spring pins, cotter pins, etc.
interrupters for these ratings are not
1. R
 eplace vacuum interrupter; instructions provided in this instruction manual.
follow.
Replacement vacuum interrupters are
2. Close coil (52SRC) and trip coil (52T). furnished as a complete assembly. They
have been completely tested and
a) Remove two push on terminal
dielectrically and mechanically conditioned.
connections
It is recommended that one vacuum
b) Remove two M4 hex-head screws and
interrupter be removed and replaced
remove solenoid.
completely rather than removing two or
more vacuum interrupters at a time.
42
The following procedure in check list format 1.5 F
 ree struts (28.0) from the pole head
describes the procedure for removing and (20.0). Loosen the strut hardware on
replacing a vacuum interrupter. Components the pole bottom (40.0) and swing the
may be identified by reference to Figures 23 struts forward and downward.
and 24.
1.6 L oosen screws fastening the centering
Instructions herein apply for replacement of ring (28.1).
all vacuum interrupters except type
1.7 R
 emove bolt (31.2), lock washer and
VS-17085 vacuum interrupters, and
large washer at the stationary contact
interrupters on 3,000 A circuit breakers
of the vacuum interrupter (18 mm or
having the flexible connector (refer to 29.1
24 mm socket with extension).
in Figure 23) electron-beam welded to the
moving terminal (refer to 36.1 in Figure 23) 1.8 U
 sing a 24 mm socket with an
of the vacuum interrupter. These extension, loosen and remove hex-cap
interrupters must be replaced by factory- screw fastening the pole head to the
trained personnel. Contact Siemens post insulator. Completely remove the
medium-voltage customer service at 1-800- pole head and set aside.
347-6659 or 1-919-365-2200 outside the
1.9 G
 rasp the vacuum interrupter (30.0)
U.S.
and withdraw vertically. Assistance
1. Removing the vacuum interrupter may be required to work the terminal
clamp off the movable stem of the
Note: Special care needs to be exercised in
vacuum interrupter. DO NOT USE
removal or installation of hardware around
UNDUE FORCE OR TWISTING
the bottom, or movable contact end, of the
MOTION. If the terminal clamp (29.2)
vacuum interrupter.
cannot be easily removed, STOP!, check
The movable contact uses a metal bellows to be certain hardware is loose, and
to maintain the vacuum seal while still that the terminal clamp (29.2) is not
permitting up and down motion of the binding.
contact. The bellows is rugged and reliable,
2. Installing a vacuum interrupter
and is designed to withstand years of
vertical movement. However, care should be Note: Replacement vacuum interrupter
exercised to avoid subjecting the bellows to (30.0) will be received from the factory with
excessive torque during removal and an eye bolt (36.3) in place, adjusted and
replacement. Twisting the bellows through torqued to specific requirements. DO NOT
careless bolt removal or tightening may ALTER THE ADAPTER (EYE-BOLT)SETTING.
damage the vacuum interrupter, resulting in
2.1 Inspect all silver-plated connection
loss of vacuum integrity.
surfaces for cleanliness. Clean only
1.1 B
 efore starting work, the circuit with a cloth and solvent. Do not
breaker should be isolated from all abrade, as this will damage the silver
primary and control-power sources and plating.
all stored energy discharged by
2.2 Insert vacuum interrupter (30.0) into
opening, closing and opening the
the lower pole-support (40.0). Slip
circuit breaker by hand. Discharge any
terminal clamp (29.2) into position on
static charge by grounding both ends
the movable stem.
and the middle of each vacuum
interrupter. Carefully remove outer- 2.3 A
 lign vacuum interrupter and fasten
phase and inter-phase barriers. finger tight using heavy flat washer,
lock washer and bolt (31.2).
1.2 L oosen the lateral bolt(s) on terminal
clamp (29.2). Employ the illustrated 2.4 F
 asten the pole head to the post
procedure to loosen clamp hardware insulator (16.1) finger tight using
(refer to Figure 25). hex-head bolt, lock washer and flat
washer.
1.3 W
 ithdraw pin (48.5) from insulating
coupler (48.0) and levers (48.6).
1.4 R
 emove coupling pin from the eye bolt
(36.3).
43
Figure 23: Vacuum interrupter replacement illustration - type 3AH

Item Description
20.0 Upper pole-support (pole head)
28.0 Strut
28.1 Centering ring
20.0
29.1 Flexible connector
31.2 29.2 Terminal clamp
29.3 Spacer (or shoulder)
30.0 Vacuum interrupter
31.2 Upper terminal bolt
36.1 Moving terminal
36.3 Eye bolt (or adapter)
40.0 Lower pole-support
48.0 Insulating coupler
48.5 Pin
28.0
48.6 Angled lever
48.9 Drive link

30.0

28.1
29.3
36.1

29.1 29.2

36.3

48.0
40.0 48.9
48.6
48.5

44
Figure 24: Illustration showing required technique for fastening terminal-clamp hardware

Item Description
A Moving contact (36.1)
B Spacer (shoulder) (29.3)
C Torque wrench
D Direction of force (P)
E Terminal clamp (29.2)
F Holding wrench
G
G Vacuum interrupter

F
A
B

Position of torque wrench to avoid undue stressing of moving contact (36.1)

2.5 A
 ttach struts (28.0) to the upper pole- 2.7 R
 aise the terminal clamp (29.2) against
support (20.0), replace hardware the step or the spacer (if applicable) of
(M10), but do not tighten at this time. the moving contact (36.1) of the
vacuum interrupter (30.0) so that the
2.6 C
 ouple levers (48.6) and drive link
radius of the movable contact faces the
(48.9) to the eye bolt (36.3), using the
connecting surface of the flexible
pin supplied. Apply retaining clips.
connector (29.1). Employ technique
Appropriate pin is modestly chamfered,
illustrated to fasten terminal clamp
not to be confused with pin for the
(refer to Figure 25). Note opposing
insulating coupler.
wrenches. Tighten the bolt(s) of the
terminal clamp to a torque of 40 Nm
(30 ft-lb), taking care to see that the
terminal of the vacuum interrupter is
not subjected to excessive bending
movement.
Note: Excessive bending movement exerted
while fastening the terminal clamp will
damage the vacuum interrupter.

45
2.8 A
 lign pole head (20.0) correctly and 3.5 R
 epeat the measurement described in
tighten bolt fastening it to the post step 3.3 again with care to maximize
insulator. Torque M16 bolt to 130 Nm accuracy. Record your result.
(96 ft-lb). Fasten securely all bolts
3.6 D
 etermine difference between the
associated with struts (28.0).
measurements made under steps 3.3
2.9 Tighten vacuum interrupter fastening and 3.5. Your results should be per
bolt (31.2) on the pole head (20.0) Table 7.
holding the vacuum interrupter firmly
3.7 If you fail to achieve the listed results,
by its upper insulator and operate
carefully repeat the entire procedure
levers (48.6), by hand, to see whether
making certain of your measurements.
the movable contact moves freely. If
any binding or lack of freedom is 3.8 L oosen eye bolt locking nut on
noted, loosen bolt (31.2) and adjust insulating coupler (48.0), and retain
the vacuum interrupter in pole head by position of the eye. Make adjustments
turning and moving it slightly. Torque in one-half turn increments. After
M12 bolt to 60 Nm (44 ft-lb) and M16 adjustment is completed, tighten eye
bolt to 130 Nm (96 ft-lb). bolt locking nut to 26-34 ft-lb. (35-45
Nm).
2.10 The centering ring (28.1) has been
loose and floating during installation 4. After eye bolt is tightened to proper
of the vacuum interrupter. Check that torque, repeat all measurement
the movable contact is free to move procedures, making certain they are in
vertically without binding, and then agreement with values indicated in
tighten the hardware which secures step 3.6.
the centering ring. Recheck that the
5. Complete all other maintenance
movable contact is free to move
procedures. Completely reassembled
vertically without binding.
circuit breaker should pass the high-
2.11 Attach insulating coupler (48.0) and potential test before it is ready for
lever (48.6) together, using pin (48.5). service.
Apply retaining clips. Correct pin has
Hydraulic shock absorber
ends that have been generously
The mechanism is equipped with a hydraulic
chamfered.
shock-absorber that functions when the
2.12 Open and close circuit breaker several circuit breaker opens (refer to item 61.8 in
times and then check to see that all Figure 6). The shock absorber should require
bolted joints and devices are tight. no adjustment. However, at maintenance
checks, the shock absorber should be
3. Checking the contact stroke
examined for evidence of leaking. If
3.1 Open the circuit breaker. evidence of fluid leakage is found, the shock
absorber must be replaced to prevent
3.2 F
 ree insulating coupler (48.0) by
damage to the vacuum interrupter bellows.
removing pin (48.5). The vacuum
interrupter contacts must now close
automatically as a consequence of
atmospheric pressure.
3.3 Observe the terminal clamp (29.2)
through the openings on each side of
the pole bottom (40.0). Using vernier
calipers, measure the distance from the
bottom surface of the terminal clamp
to the bottom edge of the cutout
opening. Measure carefully and record
your result.
3.4 C
 onnect the insulating coupler (48.0)
using pin (48.5) and the retaining clips
provided.

46
Technical data and
troubleshooting
Rated maximum Interrupting Rated short- Vacuum Table 7: Vacuum interrupter stroke
Continuous current Stroke2
voltage class circuit current interrupter
kV MVA kA Type A mm
Footnotes:
29 kA@4.76 kV; VS-17006 1,200, 2,000 7-9 (3AH)/ 1.
The vacuum interrupter type des-
36 kA@3.85 kV VS-17006 1,200, 2,000 5-7 (3AHc) ignation is labeled on the vac-
4.76 250
29 kA@4.76 kV; uum interrupter. If the vacuum
VS-17040 1,200, 2,000 7-9 interrupter installed does not
36 kA@3.85 kV
match that indicated in this
41 kA@4.76 kV;
4.76 350 VS-15052 1,200, 2,000, 3,000 8.5-9.5 table, contact the nearest Sie-
49 kA@4.0 kV
mens representative.
33 kA@8.25 kV; 2.
If you need assistance achieving
8.25 500 VS-15052 1,200, 2,000, 3,000 8.5-9.5
41 kA@6.6 kV the indicated stroke setting, con-
tact the nearest Siemens
18 kA@15.0 kV;
15.0 500 VS-17006 1,200, 2,000 7-9 representative.
23 kA@11.5 kV
28 kA@15.0 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.0 750
36 kA@11.5 kV VS-17040 1,200, 2,000 7-9
37 kA@15.0 kV;
15.0 1,000 VS-15052 1,200, 2,000, 3,000 8.5-9.5
48 kA@11.5 kV
21 kA@38.0 kV;
38.0 1,500 VS-30030 1,200, 2,000, 3,000 18-22
35 kA@23.0 kV
Rated maximum Interrupting Rated short- Vacuum
Continuous current Stroke2
voltage class circuit current interrupter
kV kA kA Type A mm
VS-17006 1,200, 2,000 7-9 (3AH)/
4.76 31.5 31.5 kA@4.76 kV VS-17006 1,200, 2,000 5-7 (3AHc)
VS-17040 1,200, 2,000 7-9
VS-15052 1,200, 2,000, 3,000 8.5-9.5
4.76 40 40 kA@4.76 kV
VS-17040 1,200, 2,000 7-9
4.76 50 50 kA@4.76 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-15052 1,200, 2,000, 3,000 8.5-9.5
8.25 40 40 kA@8.25 kV
VS-17040 1,200, 2,000 7-9
15.0 20 20 kA@15.0 kV VS-17006 1,200, 2,000 7-9
15.0 25 25 kA@15.0 kV VS-17006 1,200, 2,000 7-9
VS-17006 1,200, 2,000 7-9
15.0 31.5 31.5 kA@15.0 kV
VS-17040 1,200, 2,000 7-9
VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.0 40 40 kA@15.0 kV
VS-17040 1,200, 2,000 7-9
15.0 50 50 kA@15.0 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.0 63 63 kA@15.0 kV VS-17085 1,200, 2,000, 3,000 10-11
15.5 20 20 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 25 25 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 31.5 31.5 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.5 40 40 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
27.6 20 20 kA@27.6 kV VS-25008 1,200, 2,000 15-16
27.6 25 25 kA@27.6 kV VS-25008 1,200, 2,000 15-16
38.0 20 20 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 25 25 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 31.5 31.5 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22
47
38.0 40 40 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22
Table 8: Troubleshooting

Problem Symptoms Possible causes and remedies


1. Secondary control circuit is de-energized or control
circuit fuses are blown. Check and energize or replace
if necessary.

2. Secondary multi-pin plug contacts A1 or D16 are not


engaging. Check and replace if required.

3. Damage to wiring, terminals or connectors. Check


Closing spring will not automatically charge. and repair as necessary.

4. Failure of charging motor (88.0). Replace if required.

5. Motor cut-off switch LS21 or LS22 fails to operate.


Replace if necessary.

6. Mechanical failure of operating mechanism. Check


and contact the factory or Siemens field service at
1-800-347-6659 or 1-919-365-2200 outside the U.S.
 econdary control circuit de-energized or control
1. S
circuit fuses blown. Correct as indicated.

Circuit breaker fails to close. 2. No closing signal to secondary disconnect pin A2.
Check for continuity and correct protective relay
logic.

Closing coil or solenoid 3. Secondary disconnect contacts 13 or 15 are not


(52SRC) fails to energize. engaging. Check and correct as required.
No sound of circuit 4. Failure of anti-pump relay (52Y) contacts 21 to 22, 31
breaker closing. to 32 or 13 to 14. Check and replace as required.
Closing springs charge
but circuit breaker does 5. F
 ailure of close coil (solenoid) (52SRC). Check and
not close. replace as required.

6. Auxiliary switch NC contacts 41 to 42 are open when


circuit breaker contacts are open. Check linkage and
switch. Replace or adjust as necessary.

Closing coil energizes.


Sound of circuit breaker 1. M
 echanical failure of operating mechanism. Check
closing is heard, but and contact the factory or Siemens field service at
circuit breaker contacts 1-800-347-6659 or 1-919-365-2200 outside the U.S.
do not close.

1. N
 uisance or false closing signal to secondary
disconnect multi-pin plug contact. Check protective
relay logic. Correct as required.
Electrical problem
2. C
 losing coil (52SRC) terminal A2 is shorted-to-
Nuisance or false close ground. Check to determine if problems are in wiring
or coil. Correct as required.
1. M
 echanical failure of operating mechanism. Check
Mechanical problem and contact the factory or Siemens field service at
1-800-347-6659 or 1-919-365-2200 outside the U.S.

48
Table 8: Troubleshooting (continued)

Problem Symptoms Possible causes and remedies


1. Secondary control power is de-energized or
control power fuses are blown. Correct as
indicated.

2. Damage to wiring, terminals or connectors.


Check and repair as necessary.

3. No tripping signal to secondary disconnect


contact C2. Check for continuity and correct
protective relay logic.
Tripping coil or solenoid (52T) does not
energize. There is no tripping sound. 4. Secondary multi-pin plug contacts C1 or D2
are not engaging. Check and replace if
required.

5. Failure of trip coil (52T). Check and replace


Circuit breaker will not trip. if necessary.

6. Auxiliary switch 52a NO contacts 23 to 24


or 33 to 34 are open when circuit breaker is
closed. Check linkage and switch. Replace
or adjust as necessary.
Tripping coil (52T) energizes. No tripping
1. Failure of tripping spring or its mechanical
sound is heard, and circuit breaker contacts do
linkage. Check and replace if required.
not open. In other words, they remain closed.
1. M
 echanical failure of operating mechanism.
Check and contact the factory or Siemens
Tripping coil (52T) energizes. Tripping sound is field service at 1-800-347-6659 or 1-919-
heard, but circuit breaker contacts do not 365-2200 outside the U.S.
open.
2. One or more of the vacuum interrupters are
held closed. Check and replace as necessary.
1. T
 ripping signal remains energized on
Electrical problem secondary multi-pin plug contact C2.

2. Check for improper protective relay logic.


Nuisance or false trip
1. Mechanical failure of operating mechanism.
Check and contact the factory or Siemens
Mechanical problem
field service at 1-800-347-6659 or 1-919-
365-2200 outside the U.S.

49
Table 9: Circuit breaker control data

ANSI/IEEE C37.06 control voltages Spring charging motor


Close
Trip coil
coil Run Inrush
Range Charging
(Average)1 (Peak)
Nominal
Close Trip A1 A1 A A Seconds

24 Vdc 19-28 14-28 5.7 15/---- ---- ---- ----

48 Vdc 36-56 28-56 11.4 11.4/303 8 25 10

125 Vdc 100-140 70-140 2.1 4.8/7.43 4 18 10

250 Vdc 200-280 140-280 2.1 4.2/9.63 2 10 10

120 Vac 104-127 104-127 2.0 ----2 6 ---- 10

240 Vac 208-254 208-254 2.0 ----2 3 ---- 10

Footnotes:
1.
Current at nominal voltage
2.
Capacitor trip
3.
Value preceding slash (/) is the current for the standard trip coil with standard rating interrupting time.
Value following (/) is current for optional trip coil with three-cycle interrupting time.
4.
---- means this selection is not available at this voltage.

Table 10: Interrupting capacity auxiliary switch contacts2

Continuous Control circuit voltage


Type of
current
circuit
amperes 120 Vac 240 Vac 48 Vdc 125 Vdc 250 Vdc

Non-
10 10 5 10/301 9.6 4.8
inductive

Inductive 10 6 3 10 6 3

Footnotes:
1.
 wo contacts in series.
T
2.
 ll switches are non-convertible.
A

50
Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis)

Maximum
Withstand voltage Continuous Short-circuit These ratings are in
design accordance with:
Voltage levels current7 (I)3,4
voltage (V)1
Circuit breaker range  NSI/IEEE C37.04-1999
A
type factor Lightning
Power Standard Rating Structure
(K)2 impulse
kV rms frequency A rms kA rms sym for AC High-Voltage Circuit
(BIL)
kV rms
kV crest Breakers

5-3AH-31.5 4.76 1.0 19 60 1,200, 2,000 31.5  NSI/IEEE C37.06-2009 AC


A
High-Voltage Circuit
1,200, 2,000, Breakers Rated on a
5-3AH-40 4.76 1.0 19 60 40
3,000
Symmetrical Current Basis -
5-3AH-50 4.76 1.0 19 60
1,200, 2,000,
50 Preferred Ratings and
3,000 Related Required
1,200, 2,000, Capabilities for Voltages
5-3AH-63 4.76 1.0 19 60 63
3,000 Above 1,000 Volts
1,200, 2,000,
7-3AH-40 8.25 1.0 36 95 40  NSI/IEEE C37.09-1999
A
3,000
Standard Test Procedure
15-3AH-20 15.0 1.0 36 95 1,200, 2,000 20 for AC High-Voltage Circuit
Breakers Rated on a
15-3AH-25 15.0 1.0 36 95 1,200, 2,000 25 Symmetrical Current Basis

1,200, 2,000,  NSI/IEEE C37.010-1999


A
15-3AH-31.5 15.0 1.0 36 95 31.5
3,000 Application Guide for AC
1,200, 2,000, High-Voltage Circuit
15-3AH-40 15.0 1.0 36 95 40
3,000 Breakers Rated on a
1,200, 2,000, Symmetrical Current Basis.
15-3AH-50 15.0 1.0 36 95 50
3,000 Footnotes:
1,200, 2,000,
1.
Maximum design voltage for
15-3AH-63 15.0 1.0 36 95 63 which the circuit breaker is
3,000
designed and the upper limit for
15.5-3AH-20 15.5 1.0 50 110 1,200, 2,000 20 operation.
2.
K is listed for information
purposes only. For circuit
15.5-3AH-25 15.5 1.0 50 110 1,200, 2,000 25
breakers rated on a "constant kA"
ratings basis, the voltage range
15.5-3AH-31.5 15.5 1.0 50 110 1,200, 2,000 31.5 factor is 1.0.
3.
All values apply to polyphase and
1,200, 2,000, line-to-line faults.
15.5-3AH-40 15.5 1.0 50 110 40
3,000 4.
Standard duty cycle is O - 0.3 s -
CO - 3 min. - CO.
27-3AH-20 27.6 1.0 60 150 1,200, 2,000 20 5.
Standard rating interrupting time
is five-cycles (83 ms). Optional
27-3AH-25 27.6 1.0 60 150 1,200, 2,000 25 rated interrupting time of three-
cycles (50 ms) is available
(except with 24 Vdc tripping).
38-3AH-20 38.0 1.0 80 150/2006 1,200, 2,000 20 6.
150 kV BIL is for drawout
applications. 200 kV BIL is for
38-3AH-25 38.0 1.0 80 150/2006 1,200, 2,000 25 type SDV6 with appropriate
construction.
1,200, 2,000, 7.
Continuous current capability
38-3AH-31.5 38.0 1.0 80 150/2006 31.5
3,000 may be increased by the use of
forced-cooling (fan-cooling) in
1,200, 2,000,
38-3AH-40 38.0 1.0 80 150/2006 40 the switchgear together with
3,000
increased bus bar capacity.

51
Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis) (continued)

Permissible
Interrupting Max. sym. % dc Short-time
tripping delay Closing and latching (momentary)
time5 interrupting (I) component current (I) (3 s)
Circuit breaker (y)
type Asymmetrical Peak
ms/cycles s kA rms sym % kA rms (1.55 x I) (2.6 x I)
kA rms kA peak

5-3AH-31.5 83/5 2 31.5 47 31.5 49 82

5-3AH-40 83/5 2 40 47 40 62 104

5-3AH-50 83/5 2 50 47 50 78 130

5-3AH-63 83/5 2 63 47 63 98 164

7-3AH-40 83/5 2 40 47 40 62 104

15-3AH-20 83/5 2 20 47 20 31 52

15-3AH-25 83/5 2 25 47 25 39 65

15-3AH-31.5 83/5 2 31.5 47 31.5 49 82

15-3AH-40 83/5 2 40 47 40 62 104

15-3AH-50 83/5 2 50 47 50 78 130

15-3AH-63 83/5 2 63 47 63 98 164

15.5-3AH-20 83/5 2 20 47 20 31 52

15.5-3AH-25 83/5 2 25 47 25 39 65

15.5-3AH-31.5 83/5 2 31.5 47 31.5 49 82

15.5-3AH-40 83/5 2 40 47 40 62 104

27-3AH-20 83/5 2 20 47 20 31 52

27-3AH-25 83/5 2 25 47 25 39 65

38-3AH-20 83/5 2 20 47 20 31 52

38-3AH-25 83/5 2 25 47 25 39 65

38-3AH-31.5 83/5 2 31.5 47 31.5 49 82

38-3AH-40 83/5 2 40 47 40 62 104

52
Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis)

Nominal These ratings are in


Maximum Voltage accordance with:
Nominal three-
design Continuous range Withstand voltage
voltage phase
voltage current11 factor levels ANSI/IEEE C37.04-1979
class MVA
Circuit (V)1 (K)2 Standard Rating Structure
class7
breaker type for AC High-Voltage Circuit
Lightning Breakers Rated on a
Power
impulse Symmetrical Current Basis
kV MVA kV rms A rms ---- frequency
(BIL)
kV rms
kV crest  NSI C37.06-1987 AC
A
High-Voltage Circuit
5-3AH-250, Breakers Rated on a
4.16 250 4.76 1,200, 2,000 1.24 19 60
5-3AHc-250 Symmetrical Current Basis -
Preferred Ratings and
5-3AH-350, 1,200, Related Required
4.16 350 4.76 1.19 19 60
5-3AHc-350 2,000, 3,000 Capabilities
 NSI/IEEE C37.09-1979
A
1,200,
7-3AH-500 7.2 500 8.25 1.25 36 95 Standard Test Procedure for
2,000, 3,000
AC High-Voltage Circuit
Breakers Rated on a
1,200, Symmetrical Current Basis
15-3AH-500 13.8 500 15.0 1.30 36 95
2,000, 3,000
 NSI/IEEE C37.010-1979
A
Application Guide for AC
1,200,
15-3AH-750 13.8 750 15.0
2,000, 3,000
1.30 36 95 High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis.
1,200,
15-3AH-1000 13.8 1000 15.0 1.30 36 95
2,000, 3,000

38-3AH-1500 38.0 1,500 38.0 1,200, 2,000 1.65 80 150

Footnotes: 4.
Within the limitations stated in 10.
 igh close and latch
H
1.
Maximum design voltage for which the circuit ANSI/IEEE C37.04-1979, all values apply to (momentary) rating available for
breaker is designed and the upper limit for polyphase and line-to-line faults. For single special application.
operation. phase-to-ground faults, the specific conditions 11.
 ontinuous current may be
C
2.
K is the ratio of the rated maximum design stated in clause 5.10.2.3 of increased by the use of forced-
voltage to the lower limit of the range of ANSI/IEEE C37.04-1979 apply. cooling (fan-cooling) in the
operating voltage in which the required 5.
Current values in this row are not to be exceeded switchgear, together with
symmetrical and asymmetrical interrupting even for operating voltage below 1/K times rated increased bus bar capacity.
capabilities vary in inverse proportion to the maximum design voltage. For operating voltages
operating voltage. between rated maximum design voltage and 1/K
3.
To obtain the required symmetrical interrupting times rated maximum design voltage, follow
capability of a circuit breaker at an operating Footnote 5.
voltage between 1/K times rated maximum 6.
Current values in this row are independent of
design voltage and rated maximum design operating voltage up to and including rated
voltage, the following formula shall be used: maximum voltage.
Required symmetrical interrupting capability = 7.
"Nominal three-phase MVA class" is included for
rated short-circuit current (I) x [(rated maximum reference only. This information is not listed in
design voltage)/(operating voltage)]. For ANSI C37.06-1987.
operating voltages below 1/K times maximum 8.
Standard duty cycle is O - 15 s - CO.
design voltage, the required symmetrical 9.
Standard rating interrupting time is five-cycles
interrupting capability of the circuit breaker shall (83 ms). Optional rated interrupting time of
be equal to K times rated short-circuit current. three-cycles (50 ms) is available (except with
24 Vdc tripping).

53
Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis) (continued)

Short-circuit Rated
(at rated maximum Maximum Short-time
Permissible
maximum Interrupting design symmetrical current (I) Closing and latching
tripping delay
design time9 voltage (V) interrupting (three (momentary)
(y)
Circuit breaker voltage) divided by K (K x I)5 seconds)
type (I)3, 4, 8 (= V/K)
Asymmetrical Peak
(1.6 x (2.7 x
kA rms sym ms / cycles Sec kA rms kA rms sym kA rms
K x I)6 K x I)6
kA rms kA peak

5-3AH-250,
29 83 / 5 2 3.85 36 36 58/7810 97/13210
5-3AHc-250

5-3AH-350,
41 83 / 5 2 4.0 49 49 78 132
5-3AHc-350

7-3AH-500 33 83 / 5 2 6.6 41 41 66/7710 111/13010

15-3AH-500 18 83 / 5 2 11.5 23 23 37/5810 62/9710

15-3AH-750 28 83 / 5 2 11.5 36 36 58/7710 97/13010

15-3AH-1000 37 83 / 5 2 11.5 48 48 77 130

38-3AH-1500 21 83/5 2 23.0 35 35 56 95

54
Table 13: Type 3AH3 vacuum circuit breaker weight in lbs (kg) (circuit breaker operator only)2

Circuit breaker type Weight in lbs (kg)1 Footnote:


1.
Add 100 lbs (45 kg) for
Interrupting Continuous current packaging.
Maximum voltage capability kA
2.
For weights of circuit breakers
kV (MVA) with the type 3AHc operator,
1,200 A 2,000 A 3,000 A refer to the instruction manual
symmetrical)
for the circuit breaker.
4.76 31.5 (250) 242 (110) 264 (120) ----
4.76 40 246 (112) 268 (122) 390 (177)
4.76 50 (350) 330 (150) 363 (165) 396 (180)
4.76 63 432 (196) 441 (200) 463 (210)
8.25 40 (500) 246 (112) 268 (122) 390 (177)
15.0 20 (500) 165 (75) 257 (117) ----
15.0 25 165 (75) 257 (117) ----
15.0 31.5 (750) 242 (110) 264 (120) ----
15.0 40 246 (112) 268 (122) 390 (177)
15.0 50 (1,000) 330 (150) 363 (165) 396 (180)
15.0 63 436 (198) 445 (202) 467 (212)
15.5 20 262 (119) 278 (126) ----
15.5 25 273 (124) 298 (131) ----
15.5 31.5 298 (135) 313 (142) 385 (175)
15.5 40 309 (140) 324 (147) 390 (177)
27.6 20 276 (125) 291 (132) ----
27.6 25 287 (130) 302 (137) ----
38.0 20 353 (160) 375 (170) 386 (175)
38.0 25 353 (160) 375 (170) 386 (175)
38.0 31.5 363 (165) 385 (175) ----
38.0 40 375 (170) 397 (180) 408 (185)

Table 14: Circuit breaker operating times (type 3AH3 operator)

Spring charging time 10 s

Up to 15.5 kV 55 ms
Close time from energizing close coil at rated
Over 15.5 kV up to 27.6 kV 65 ms
control voltage to contact touch (last pole)
Over 27.6 kV up to 38 kV 70 ms

Up to 15.5 kV 56 ms
5-cycle interrupting time
Over 15.5 kV up to 27.6 kV 56 ms
(83 ms)
Over 27.6 kV up to 38 kV 56 ms
Opening time from
Up to 15.5 kV 43 ms
energization trip coil at
3.5-cycle interrupting time
rated control voltage to Over 15.5 kV up to 27.6 kV 43 ms
(58 ms)
contact part (last pole),
Over 27.6 kV up to 38 kV 43 ms
not including arcing time
Up to 15.5 kV 38 ms
3-cycle interrupting time
Over 15.5 kV up to 27.6 kV 38 ms
(50 ms)
Over 27.6 kV up to 38 kV 38 ms

55
The information provided in this
document contains merely general
descriptions or characteristics of
performance which in case of actual use
do not always apply as described or which
may change as a result of further
development of the products. An
obligation to provide the respective
characteristics shall only exist if expressly
agreed in the terms of contract.

All product designations may be


trademarks or product names of Siemens
AG or supplier companies whose use by
third parties for their own purposes could
violate the rights of the owners.

Siemens Industry, Inc. For more information, contact: Subject to change without
7000 Siemens Road 1-800-347-6659 prior notice.
Wendell, NC 27591 Order No.:
www.usa.siemens.com/mvswitchgear
E50001-F710-A251-V1-4A00
All rights reserved.
Printed in USA
2013 Siemens Industry, Inc.

Das könnte Ihnen auch gefallen