Introduction
Voltage Regulator theory
Voltage Regulator application considerations
Installation and proper bypassing
Wrap-up/questions
VLD
Voltage
Distance
2013 Eaton. All rights reserved.
3
Regulator Theory Purpose
Why is voltage regulation needed?
Power quality criteria requires a constant voltage
despite variations in load current
Load current variations are due to:
New loads
Load profiles Daily and Seasonal
LOAD CURRENT VS TIME OF DAY
CURRENT
R1
OLTC
L1 L4 L2 L5 L3 L6 L7
+5%
Nominal
Voltage
--5%
Non-OLTC
3 - 1f SVRs
N.C.
OLTC #1 (B) Bus Regulation
N.O.
3 - 1 f SVRs
N.C.
OLTC #2
3 - 1 f SVRs
(A) Regulation with Non-OLTC
Footprint
REVERSING
SWITCH
1.25%
SERIES WINDING
S L
N 1 2 3 4 5 6 7 8
CURRENT
X-FORMER
SHUNT CONTROL
WINDING
POTENTIAL
SL TRANSFORMER
2013 Eaton. All rights reserved.
13
Type A Design Straight
REVERSING
SWITCH
1.25%
SERIES WINDING
S L
N 1 2 3 4 5 6 7 8
CURRENT
X-FORMER
SHUNT
WINDING CONTROL
CONTROL
WINDING
SL
2013 Eaton. All rights reserved.
15
Type B Design Inverted
128
SET POINT
126
124
BANDWIDTH
VOLTAGE
122
120
118
116
114 30 SECONDS
112 Given: TD = 30
TIME
SVR SVR
TD = 45 SEC TD = 60 SEC
128
Maximum
voltage
124
Min. load
VOLTAGE
120
128
124
R C
VOLTAGE
On Line
120
116
112
FEEDER DISTANCE
2013 Eaton. All rights reserved.
32
Coordination w/Capacitors
Load Side DG
Substation
DG
Customer
Load
Direction of
P, Q
Voltage Regulation P, Q
Substation Substation
Circuit Voltage Open
Breaker Regulator DG DG Closed
Tie Recloser
P, Q N.O. P, Q
Substation Substation
Circuit
Breaker
When one source is lost, power flow will change and some
VRs should change direction of the voltage regulation
Source 1
P Q
CB1
Closed Tie
Recloser
DG
Open
Source 2
CB2
Closed
Source 1
P Q
CB1
Open Tie
Recloser
DG
Closed
Source 2
CB2
Closed
Response to Undervoltage
130
125
120
115 Voltage setting
Voltage
Time (s)
2013 Eaton. All rights reserved.
41
Voltage Limiting
High Limit
Low Limit
C
N
10% regulation
Series
Lightning L L L
Arrester
S SL S SL S SL
Bypass Switch
3 Wire open delta:
Phase A
Phase B
Phase C
S SL S SL
15% regulation L
SL
L
SL
L
SL
S S S
2 situations to consider :
Continuous Parallel operation (in substation)
Tying Feeders through N.O. point (or with Bus Tie switch)
R R
N.O.
! Warning!
Installing or removing the regulator with the tap changer
off neutral will short circuit part of the series winding!
Before bypassing, the regulator must be in neutral.
Tap Position
At Limit
0
Verify the tap position of the control indicates Neutral
P.I. ADD-AMP -16, 16
Base Voltage
voltage per step
120 .75
2400 15
4800 30
7200 45
7620 48
12000 75
14400 90
19920 125
Source Load
Phase A Bypass
Disconnect Disconnect
S L
SL
Neutral
Source Load
Phase A B
S-DIS L-DIS
S L
Start 1 2 3
SL
B O C C C
S-Dis C C C O
L-Dis C C O O
Neutral
Step 1 is Critical Operation.
Source Load
Phase A Bypass
Disconnect Disconnect
S L
SL
Disconnect
Phase B
Source Load
Phase A B
L-DIS
S-DIS
S L
Start 1 2 3 4
SL B O C C C C
SL-Dis C C C C O
S-Dis C C C O O
SL-DIS
L-Dis C C O O O
Phase B
Step 1 is Critical Operation.
Questions??