Control Fundamentals
and Energy Conservation
for
HVAC Equipment-Part 1
1-1
Disclaimer
This presentation was prepared specifically for use as
college training material
material. It shall not be modified
without the consent of the authors.
PNWD-SA-8834
1-2
DDC Controls and Energy Conservation for
HVAC Equipment
Eq ipment - Agenda
1. Introduction of DDC Controls Project
2
2. HVAC C Control
t lP Principles
i i l
3. Communication Standards and Networks
4
4. Vendor Examples of DDC Software Programming and
Operator Interfacing
5. Typical Rooftop and Central AHU HVAC Control
Systems and Applications
6. System Maintenance and Service of DDC Controls
7. Avoiding
g Common Control Problems and Fixing g the
Problems
8. Calibrating and Verifying Energy Savings of the DDC
Controls
PNWD-SA-8834
1-3
Part 1
HVAC Control Principles
1. Intent of Battelle Pacific NW Division involvement
2. Purpose of Controls
3. Keyy Components
p of Control Systems
y
4. Control Loops, Open vs. Closed Loops
5 Terminology
5.
6. The Control Cycle and Control Actions
7 The
7. Th Energy
E Sources
S for
f Control
C t lSSystems
t
8. DDC Point Types
PNWD-SA-8834
1-4
Part 2
Control Applications, Networks,
Programming, Maintenance, and
Energy Savings
1. DDC Control Applications
2. DDC Networks and Architecture
3. Communication Standards and Networks
4. Vendor Examples of DDC Software Programming
and Operator Interfacing
5. System maintenance and service of DDC controls
g DDC controls to save energy
6. Using gy
PNWD-SA-8834
1-5
Section 1
Introduction of DDC Controls Project
Purpose of this project is to provide HVAC
educational
d ti l materials
t i l tto WWashington
hi t St State
t
community colleges to educate students who have
chosen or may chose career paths related to HVAC
servicing and building energy management fields
PNWD-SA-8834
1-6
Section 2
HVAC Control Principles
The Purpose of Temperature Controls
Control systems are the brains of HVAC equipment to
maintain
i t i h human comfort.
f t Pi
Pictured
t db below
l iis an AHU th thatt
serves only one zone. This type of AHU is called a single
zone AHU. In the example, a temperature sensor (stat) sends
a signal
i l tto a control
t l panel,
l which
hi h sends
d a signal
i l tto a valve.
l
PNWD-SA-8834
1-12
1000 (Ohms) Balco PTC
Electronic Temperature Sensors
The resistance outputs of a electronic Balco temperature
sensor follow the diagrams below:
DDC
Controls
PNWD-SA-8834
1-16
Electronic Control System
y
Damper
Controller Operator
Filter
Main or Supply
pp y
Pressure
Pressure
Compressor Regulator
Valve
Actuator Thermostat
Valve
Control Valves
two-way Control Valves
Used with differential pressure (DP) sensors and VSD pump
systems on primary and secondary loops
three-way (mixing or diverting)
Pressure
Press re independent control valves
al es
Automatic dampers
Damper operators
VSDs: variable speed drives
Courtesy Belimo
PNWD-SA-8834
1-25
Controlled Devices
Valves
Diverting Valve
Mixing
g Valve
PNWD-SA-8834
1-30
Economizer Damper Actuators
will have either direct connect actuators bolted
directly to the damper or they will be installed with a
shaft and linkage arrangement (more prone to fail)
PNWD-SA-8834
1-35
DDC control systems have variable
f
frequency drives ((VFDs)) as
standard equipment on:
Cooling
C li towers
AHUs and VAV fans
Pumps
Chillers
PNWD-SA-8834
1-36
Variable Speed Drives
PNWD-SA-8834
1-38
Review of the Key
y Control
Components
Exercise-connect the sensor, controller, and
controlled device in the proper order.
order
___________Acting
_________________ _________________
l
closed
d or open
LLoop
Closes
Cl loops
l provide
id ffeedback-good
db k d controll
Open loops have no feedback-poor control
PNWD-SA-8834
1-45
Basic Closed-Loop-Example
The sensor feeds back to the controller
PNWD-SA-8834
1-49
Setpoint
Setpoint is the desired condition of a variable that is to be
maintained, such as temperature. In the example below,
75 degrees F F. is the room temperature setpoint that the
building occupant desires.
Two
T position
iti
Floating action
Proportional action
PI
PI
PID
Courtesy PECI
PNWD-SA-8834
1-53
Control Cycle Graph
PNWD-SA-8834
1-56
Floating Action Control
PNWD-SA-8834
1-61
Review of Control Cycles
Exercise; study the drawings and identify
the control loop types as either:
2-position, proportional, or PI Control
_________________
_________________
PNWD-SA-8834
1-69
Conventional Pneumatic
Control Systems
Requirements:
Clean and dry air supply
Pressure reducing valve
Utilizes pneumatic controllers
Pneumatic devices
PNWD-SA-8834
1-70
Pneumatic Controls Include:
Pneumatic relays:
Reversing relay
High/low pressure selector
Air motion
Pneumatic Switch
Signal repeating EP-Electric to Pressure Switch
Minimum position
PNWD-SA-8834
EPs and PEs PE-Pressure to Electric Switch
1-73
B i Pneumatic
Basic P ti Control
C t lS System
t
PNWD-SA-8834
1-74
Example of Pneumatic Controls
PNWD-SA-8834
1-78
Example of Electronic Control for
Basic AHU Economizer Control
PNWD-SA-8834
1-80
Section 8-DDC Point Types
Input
p and Output
p Point Types
yp Chart
Input Output
Two state information from the building Two state information from DDC field
into the DDC field panel panel to the building
Di it l
Digital
Switches: On/Off - fans, pumps, lights
Differential press/proof Open/Close, two position damper
PNWD-SA-8834
1-83
DDC Control System
Digital Input (DI) Pulsed Signal
Illustration
Flow Switch
PNWD-SA-8834
1-84
DDC Control System
Digital Output (DO) Illustration
Triac Type Digital Output with External Relay Transistor with Pilot Relay
Courtesy Belimo
PNWD-SA-8834
1-89
Example
p of DDC AHU Control
Application with Point Types Identified