SAUDI ARAMCO TEST REPORT
Area & Street Lighting (point to point) - Illumination Level SATR-P-3610
30-Apr-13 ELECT-
Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

A. Illumination Level Test Procedure and checklist

Lighting systems shall be designed for energy efficient operation and SAES-P-123
A1
installed in conformance with drawings and specifications. Sec. 4.1.3

Lighting levels stated in this specification refer to minimum maintained


SAES-P-123
A2 illuminance. Illuminance levels shall be maintained as per SAES-P-123
Sec. 4.1.7
Table 2.

Photocell switches shall be of the twist-lock type and perform test to


SAES-P-123
A3 check that it shall incorporate an inherent time delay to prevent spurious
Sec. 4.1.12
operations.

Street lighting design shall be in accordance with IESNA RP-8, as


SAES-P-123
A4 supplemented by this SAES. Check that as a minimum requirement,
Sec. 4.3.1
lighting are provided at all street intersections in plants.

Test that Outdoor non-plant Area and Street lighting fixtures are SAES-P-123
A5
individually controlled by a photocell mounted on the fixture. Sec. 4.1.11

Check that mounting method of lighting fixtures are based on the best
SAES-P-123
A6 arrangement for illuminance, as well as easy and safe access during
Sec. 4.1.15
installation and maintenance.

SAES-P-123
A7 Check the suitability of Lighting fixtures based on area and application.
Sec. 4.2.1

Illumination levels should be taken with " Weston" or similar light meter SAES-P-123
A8
calibrated in foot candles or similar. Sec. 5

During the illumination level check a note should be made of black spots
SAES-P-123
A9 (which could cause a safety hazard) and any additional task lighting that
Sec. 5
may be required.

SAES-P-123
A10 Light loss factors shall be used in computing illuminance levels.
Sec. 4.7

When illumination level checks are made on new installations allowance


should be made for lamp lumen depreciation and dirt depreciation,
dependent upon the amount of time that the installation has been in
service. A rough rule of thumb is the initial lighting level on a completely SAES-P-123
A11
new installation should be 50-40% above the installation level listed in Sec. 5
SAES-P-123. If however, the installation has been in service or installed
for some time before the illumination levels are checked this figure will
be considerably lower.

Page 1 of 5
SAES-P-123
A12 Check that Series street lighting connections have not been made.
Sec. 4.3.2

Page 2 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

Area & Street Lighting (point to point) - Illumination Level SATR-P-3610


30-Apr-13 ELECT-
Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Perform test that Outside area and street lighting are controlled by
photocells. Check that in plant areas photocell control of area and street SAES-P-123
A13
lighting shall be through a lighting contactor with a hand-off-automatic Sec. 4.3.7
switch and provisions for remote operation.

Loss Factors that shall be used in computing illuminance levels.


Table 1 Light Loss Factors
Lamp Lumen Depreciation Luminaire Dirt Depreciation
HPS 0.90 Outdoor Industrial 0.71
SAES-P-123
A14 MV 0.67 Outdoor Residential 0.77
Sec. 4.7
MH (above 400 W) 0.83 Indoor Non-Industrial 0.86
MH (400 W & below) 0.77 Indoor Industrial 0.79
Fluorescent (40 W) 0.86
Incandescent 0.90

The following minimum maintained (in service) illuminance levels in


Table 2 shall be used. The initial field measurement after installation SAES-P-123
A15
shall be no less than the specified illuminance divided by the light loss Sec. 5
factor (LLF) from Table 1 and other factors utilized in the design.

B. TEST EQUIPMENT AND MATERIALS CRITERIA

Illumination level measuring instrument- Lux Meter.


ILLUMINATION LEVEL TEST AREA LIGHTING AND STREET
ILLUMINANCE HEIGHT PLANE
LIGHTING LOCATION ACTUAL COMMENTS
LUX (fc) (mm) V/H

B1 Area Lighting General Area 10 (1) Ground H

B2 Area lighting under Pipe-Ways, Trestles and Walkways 30 (3) Ground H

B3 Area lighting - Piers 200 (20) Ground H

B4 Residential Street Lighting, Local Road 4 (0.4) Pavement H

B5 Residential Street Lighting, Parking Lots and Alleys 2 (0.2) Ground H [7]

2 (0.2)
Street Lighting for Side Walks, Residential ( Camps and Community Ground H
B6 5 (0.5)
Centers 1800 V [8]

5 (0.5) Ground H
B7 Street Lighting, Walkways distant from roadways, and Bikeways
5 (0.5) 1800 V [8]

NOTE:
H refers to the Horizontal Plane and V for the Vertical Plane. For [7]
&[8] refer to SAES-P-123 Table 2 under Notes. Refer to SAES-P-123
"Table 2" for illuminance levels in other locations.

Page 3 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

Area & Street Lighting (point to point) - Illumination Level SATR-P-3610


30-Apr-13 ELECT-
Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

C. TEST RESULTS

D. CONCLUSIONS

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.

Test results are acceptable and in accordance with Saudi Aramco


E1 N/A
Engineering Standards and contractual requirements.

REMARKS:

REFERENCE DOCUMENTS:
1. Schedule Q -- Quality Requirements (MP LSTK & LSPB Pro Forma, Revised 2/08)
2. Schedule G -- Materials, Tools and Equipment (MP LSTK & LSPB Pro Forma, Revised 3/06)
3. SAES-P-123 Lighting, 2 March 2011

NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer
indicates compliance with appropriate standards or performance in a specified manner.

Contractor / Third-Party Saudi Aramco


Technician Performing Test* PMT Representative
Name, Title, Department, Test Performed Successfully and Results are Acceptable: T&I Witnessed QC Record Reviewed Work Verified
Company, Initials and Name, Initials and Date:
Date:

QC Inspector PID Representative


Witnessed Test Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others

Page 4 of 5
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13

SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER

Area & Street Lighting (point to point) - Illumination Level SATR-P-3610


30-Apr-13 ELECT-
Testing
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED

Page 5 of 5