All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.
Project: Kegalle Substation ETAP Page: 2
Location: Sri Lanka 16.0.0C Date: 05-19-2017
Contract: 123456 SN: 4359168
Engineer: Revision: Base
Study Case: SC
Filename: KEGALLE Config.: Normal
Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
SS1-E00-W11 132.000 1.35744 19.00414 19.05256 1.35744 19.00414 19.05256 0.37111 6.15380 6.16498 0.00000 0.00000 0.00000
SS1-E00-W12 132.000 1.35744 19.00414 19.05256 1.35744 19.00414 19.05256 0.37111 6.15380 6.16498 0.00000 0.00000 0.00000
SS1-H00-W11 33.000 0.12277 2.89469 2.89729 0.12277 2.89469 2.89729 31.65758 110.80150 115.23530 0.00000 0.00000 0.00000
SS1-H00-W12 33.000 0.12277 2.89469 2.89729 0.12277 2.89469 2.89729 31.65758 110.80150 115.23530 0.00000 0.00000 0.00000
SS1-H02-W11 33.000 0.23591 14.20842 14.21038 0.23591 14.20842 14.21038 31.66135 110.91460 115.34510 0.00000 0.00000 0.00000
SS1-H02-W12 33.000 0.16915 6.83651 6.83861 0.16915 6.83651 6.83861 31.65943 110.84090 115.27370 0.00000 0.00000 0.00000
SS1-H13-W11 33.000 0.23591 14.20842 14.21038 0.23591 14.20842 14.21038 31.66135 110.91460 115.34510 0.00000 0.00000 0.00000
SS1-H13-W12 33.000 0.16915 6.83651 6.83861 0.16915 6.83651 6.83861 31.65943 110.84090 115.27370 0.00000 0.00000 0.00000
SS2-E00-W11 132.000 2.21244 23.35789 23.46244 2.21244 23.35789 23.46244 4.15123 19.52522 19.96163 0.00000 0.00000 0.00000
SS2-E00-W12 132.000 2.21244 23.35789 23.46244 2.21244 23.35789 23.46244 4.15123 19.52522 19.96163 0.00000 0.00000 0.00000